Or Design2
Or Design2
Fig. 1. Layout of the operating suite. OP, Operating room. The broken line indi-
cates the position of the zonal ventilation; A, anaesthetic room; E, exit area.
Perforated ceiling
Slits r ---
Filtered clean air
Bacteriological experiments
Airborne bacteria-carrying particles were sampled using a Casella slit sampler
sampling 700 I/min. Blood agar plates were used. The plates were incubated at
37 0C for 48 h before being examined. The total count of c.f.u. of bacteria was
estimated and presumptive Staph. aureus c.f.u. were tested for deoxyribonuclease
activity.
RESULTS
Gas tracer experiments
In more than three-quarters of the experiments with balanced ventilation there
was no detectable transfer of air from adjacent rooms into the operating theatre
and only once did the concentration in this room exceed 3 % of that in the
(adjacent) room in which the gas was being liberated.
When there was a forced exhaust of the air in the operating theatre transfer of
air into the operating room was detected in half these experiments and the con-
centration in the operating room was between 2 and 20% of that in the room
where the gas was liberated.
When tracer gas was liberated in the operating room transfer from the operating
room to adjacent rooms was detected in half the experiments with the ventilation
in the balanced conditions and in as many as one-third of the experiments when
there was increased extraction of air from the operating room. On no occasion
did the concentration found in any room exceed 10 % of that in the operating room.
per hour. Air samples were taken at the source for 1 min periods at 2 min intervals.
In the receiving rooms samples were taken continuously for 10 min during the
period of no activity and for 4 min every 5 min during the period of activity. The
transfer of airborne particles from one place to another will be presented as the
ratio of the particle concentration at the source site to that at the receiving site.
The results of the experiments are shown in Table 1. When there is no activity
there is a detectable transfer of particles only from the operating room to the
anaesthetic room. During activity the lowest ratio 9-6 x 10 is found for transfer
from the operating theatre to the anaesthetic room. Transfers to the exit area and
the staff corridor were of the same order with ratios of 4-8 x 102 and 7*9 x 102
respectively. The transfer into the operating room is much the same for the two
doors tested, ratios being 2-1 x 103 and 1-3 x 103, mean value 1-7 x 103. As the third
door was of the same size, particle transfer through this door was not measured.
In some experiments the concentration of particles was measured simultaneously
just outside the source room and about 4 m along the corridor. As can be seen the
concentration fell to between i and J between these two points.
The risk of transfer from one operating room to the adjacent one of a pair, under
the experimental conditions, can be calculated as follows. For transfer via the
exit area:
S/R = S/E x E/R = 4-8 x 102 X 1*7 x 103 = 8-2 x 105,
where S represents the particle concentration in the operating room, acting as the
source room, R that in the receiving operating room and E that in the exit area.
For this calculation the mean of the two experimental values for transfer into an
126 A. HAMBRAEUS, S. BENGTSSON AND G. LAURELL
Table 2. Transfer of tracer particles within an operating room; see Fig. 3
(Ratio of concentration to that close by source, 1.)
Conventional Zonal
Expt. ventilation ventilation
At periphery near source, 2 1 0-30 0-83
2 0-53 0-45
3 2-50 0-11
Mean* 0-74 0-34
At centre, 3 1 0-27 0-18
2 0-31 0-14
3 1-25 0-05
Mean 0-47 0-11
At periphery opposite source, 4 1 0-24 1-43
2 0-32 0.91
3 1-67 0-21
Mean 0-51 0-65
* Means are geometric.
operating room through a door has been taken as the value of EIR. For transfer
via the staff corridor:
SIR = SICR x CR/IR = 2*4 x 103 x 1-3 x 103 = 3-1 x 106,
where CR represents the particle concentration in the staff corridor outside the
receiving operating room door, i.e. 4 m from the source room door.
The overall transfer ratio between the two operating theatres is then
1/(1/(8-2 x 105) + 1/(3-1 x 106)) = 6-5 x 106.
Particle transfer within the operating room
Transfer of potassium iodide particles
Experiments were made in rooms with and without zonal ventilation. The
arrangement of the tests can be seen from Fig. 3 and the results in Table 2. In
order to create a normal turbulence in the operating rooms one person was moving
around in the periphery during the experiments.
As might be expected there is considerable variation in the distribution of par-
ticles from experiment to experiment. In rooms with conventional ventilation the
ratios between the particle concentration at the different sampling sites to that
at the source site varied between 2-5 and 0-24. In rooms with zonal ventilation
the corresponding range was from 1-43 to 0-06. However, the mean peripheral
concentration ratios were similar for both types of ventilation, 0-74 and 0'51 with
conventional ventilation compared with 0-34 and 0-65 with zonal ventilation. The
mean concentration ratio at the centre was, however, much less with zonal ven-
tilation, 0.11 compared with 0-47.
Ventilation and airborne transfer 127
I
N\\O\ 2
'O 4
N
I I I I
0 1 2 3
m
in rooms with conventional ventilation. When sampling in the centre the slit
sampler was placed as close to the patient as possible. The level of airborne con-
tamination in rooms with zonal ventilation was about half that found in rooms
with conventional ventilation. In the centre of the rooms the mean values per
operation were 31-5 c.f.u./m3 and 73-2 c.f.u./m3 for rooms with zonal and con-
ventional ventilation respectively. The corresponding values for samples from
the periphery were 53'9 and 89-0 c.f.u./m3. The mean ratio between bacterial
concentration in the centre and the periphery for rooms with zonal ventilation
was 0-6 (range 0.5-0.8), for rooms with conventional ventilation it was 0*8 (range
0.7-1). The difference, although small, is significant (P < 0-01 > 0.005).
DISCUSSION
The aim of the investigation was mainly to study transfer of airborne particles
and airborne contamination in a modern operating unit with positive pressure
ventilation. The initial experiments with tracer gas showed that the ventilation
system functioned in agreement with the plans drawn up for this unit. The transfer
of inert particles from one space to another was very low when there was no
activity. When particles were generated in the operating room the highest con-
centration outside it was found in the anaesthetic room. During activity the ratio
of particle concentration between the two rooms was about 100. This was due to
the fact that the anaesthetic room is a small closed area from which particles
disappear more slowly than from the large open corridors.
The transfer from the outside into the operating room was assumed to be the
same for all three doors and therefore only transfer through two of the doors was
tested. The mean value of the two ratios found was 1-7 x 103 and this was used in
calculations including the third door, i.e. transport from exit area to operating
room. As two operating rooms share the same exit area, the transfer of particles
from one operating room to the other via the exit area was calculated. Under
experimental conditions the ratio of particle concentration between the source and
the receiving operating rooms was 8-2 x 105 for transfer via the exit area only, and
1/(l/(8.2 x 105) + 1/(3.1 x 106)) = 6-5 x 105 if transfer via the staff corridor with
the same rate of door opening, 60/h, is included.
The ratio between source room and receiving room is inversely proportionate
to the frequency of movement through the door (Lidwell, 1972). It is therefore
possible to recalculate the experimentally found value into one that would cor-
respond to particle transfer during actual activity according to the following
simplified formulae:
60
am = a0 x q7g
= aD 60
m
am= X
'IO
a' denoteconcentration in source room
concentration in exit area
a' denotes concentration in exit area
concentration in receiving room
m number of movements through the door in each direction
=
amI and c4 are the ratios at m movements
a40 and aL4 are the ratios at 60 door openings per hour (= experimental
activity).
9 HYG 79
130 A. HAMBRAEUS, S. BENGTSSON AND G. LAuIRELL
The frequency of door openings between the operating rooms and the exit area
was 12 times per hour. For this activity the ratio of particle concentration between
source and receiving operating rooms would be 8'2 x 105 (60/12)2 = 2-1 x 107. It
would seem that this should provide good protection against airborne transfer of
bacteria from one room to the other, since a value of 1 particle/l in the source
room would give rise to only 5 x 1o-8 particles per litre in the receiving room. The
risk of airborne transfer from one operating room to the other through the staff
corridor was more than ten times less.
The potassium iodide particle method has earlier proved to be a useful method
for estimating transfer of airborne particles in different kinds of patient wards
(Hambraeus & Sanderson, 1972; Foord & Lidwell, 1975). It has proved possible
to use this technique in a highly ventilated area such as an operating room. A
comparison between room to room transfer found in an isolation ward (Hambraeus
& Sanderson, 1972) with plenum ventilated rooms with air-locks and that found
in the operating suite showed that the airborne isolation provided for the patient
in an operating room was more than 1000 times better than that provided for the
patient in the isolation ward. Since airborne transfer of bacteria in the isolation
ward was found to be far less important than transfer of bacteria by other means
such as clothes (Hambraeus, 1973), the airborne room-to-room transfer of bacteria
in the operating suite is probably negligible compared with other routes of trans-
mission. The distribution of particles within the operating room itself is therefore
more interesting. In this study operating rooms with zonal ventilation were com-
pared with operating rooms with conventional ventilation.
In operating rooms with zonal ventilation experiments with tracer particles as
well as bacteria-carrying particles showed that the contamination in the centre
was lower than in the periphery. In operating rooms with conventional ventilation
both tracer particles and bacteria-carrying particles were almost evenly distri-
buted within the room.
In operating rooms with zonal ventilation only about one-tenth of tracer par-
ticles were transferred from the periphery into the centre compared with one half
when conventional ventilation was employed. The air currents from the ceiling
are too slow to create a completely effective air curtain over the operating table
and in experiments with bacteria-carrying particles the difference between centre
and periphery and vice versa was substantially less being only about one half.
This may be due to the fact that in both these sets of investigations there were
people in the centre during the measurements. In the series of experimental
activity one person had to attend to the slit sampler in the centre and during
operations the entire operating team was in the centre. Since they generate
bacteria-carrying particles themselves it is natural that the differences will be
smaller than when tracer particles are used.
Airborne contamination was, however, low especially in operating rooms with
zonal ventilation. The contamination in these operating rooms was not con-
siderably higher than has been reported in investigations where ultra clean air
ventilation systems have been used (McDade, Whitcomb, Whitfield & Franklin,
1968; Scott, 1970; Cook & Boyd, 1971).
Ventilation and airborne transfer 131
This operating unit is planned with two corridors, one for the patients and the
other for the staff. The operating and service rooms are situated in the centre.
One of the reasons for this arrangement is to minimize the traffic to and from the
operating rooms during operations. It was therefore surprising to find that the
activity was high during operations, a door being opened almost every minute.
According to several workers an intensive traffic in operating rooms is considered
to increase the risk of acquiring infections during operations. From observations
during operations it was not possible to calculate how much the entrance of one
or two more people contributed to air contamination. The variations in activity
during the operations were too rapid and frequent. From the experiments in which
bacteria-carrying particles were generated by standard activity it is possible to
calculate the influence of people and ventilation rate on the amount of airborne
contamination. With five people present in a room with a ventilation rate of 20
turnovers per hour the average airborne contamination was 41 c.f.u./m3.
The die-away rate due to sedimentation can be taken as approximately 5.5/h,
assuming a particle settling-rate of 0 3 m/min in a room 3'3 m high. The equili-
brium concentration in the room is given by Ne = (nB)/(R x S) (Bourdillon,
Lidwell & Lovelock, 1948), with n the number of persons, B the rate of dispersal
per person, B the ventilation rate and S the rate of loss due to sedimentation. For
the above conditions B = 41(20 + 5.5)/5 = 209. It is then possible to calculate
the equilibrium concentration for any number of persons present and for any
ventilation rate assuming the same rates of sedimentation and dispersal per person.
Although the mean number present at the operations was 13-15 probably not
more than 10 were active. According to this calculation the number of airborne
bacteria would then be 82/m3 in the conventionally ventilated room, the observed
mean value was 71.
In a following paper the frequency of infections during a three-year period
among patients operated on in this unit will be presented. Attempts will be made
to explain the importance of airborne infection and whether routines involving as
much movement as those described above may contribute to an increased rate
of infection.
REFERENCES
ABEL, E. & ALLANDER, C. (1966). Undersokning av nytt inbiAsnings system for rena rum.
V VS No. 8.
BOuEDILON, R. B., LIDwELL, O. M. & LOVELOCK, J. E. (1948). Studies in air hygiene.
Medical Re8earch Council Special Report Serie8 No. 262. London: H.M.S.O.
CHARNLEY, J. (1964). A clean air operating enclosure. Brii8h Journal of Surgery 51, 202.
CiHNLY, J. (1972). Postoperative infection after total hip replacement with special refer-
ence to air contamination in the operating room. Clinical Orthopaedic8 87, 167.
CHARNLEY, J. & EFTEKHAR, N. S. (1969). Postoperative infection in total prosthetic replace-
ment arthroplasty of the hip joint, with special reference to the bacterial content of the
air of the operating room. Briti8h Journal of Surgery 56, 641.
CooK, R. & BomD, N. A. (1971). Reduction of the microbial contamination of surgical wound
areas by sterile laminar air-flow. British Journal of Surgery 58, 48.
EFTXHAR, N. S. (1973). The surgeon and clean air in the operating room. Clinical Ortho-
paedics 96, 188.
FOORD, N. & LIDWELL, 0. M. (1972). An airbome particle tracer for crossinfection studies.
Journal of Hygiene 70, 279.
9-2
132 A. HAMBRAEus, S. BENGTSSON AND G. LAURELL
FooRD, N. & LIDWELL, 0. M. (1975). Airborne infection in a fully air-conditioned hospital.
II. Transfer of airborne particles between rooms resulting from the movement of air from
one room to another. Journal of Hygiene 75, 31.
HAMBRAEuS, A. (1973). Transfer of Staphylococcue aureus via nurses' uniforms. Journal of
Hygiene 71, 799.
HBAMRAEuS, A. & SANDEmON, H. F. (t972). Studies with an airborne particle tracer in an
isolation ward for burned patients. Journal of Hygiene 70, 299.
LEADING ARTICLE (1975). Risks and uses of total hip replacement. Briti8h Medical Journal i,
296.
LIDWELL, 0. M. (1960). The evaluation of ventilation. Journal of Hygiene 58, 297.
LDWELL, 0. M. (1972). Ventilation in subdivlided isolation units. Joural of Hygiene 67, 649.
M1DADE, J. J., WmTco1m, J. G., WHmTFmI, W. J. & FRANXLI, C. R. (1968). Microbio-
logical studies conducted in a vertical lamina airflow surgery. Journal of the American
Medical A88ociation 203, 125.
SCoTT, C. C. (1970). Laminar/linear flow system of ventilation. Lancet i, 989.
WILiAMs, R. E. O., BLOWERS, R., GARROD, L. P. & SHOOTER, R. A. (1966). Ho8pital Infec-
tion8, Cau8e8 and Prevention. 2nd ed. London: Lloyd-Luke Ltd.