SCHEDULE OF LOAD
BRANCH CKT NO. LOAD WATTS (W) VOLTAGE (V) LOAD CURRENT (A) AMPERE PROTECTION SIZE OF WIRE & CONDUIT
1 LIGHTING OUTLET (9) 900 230 3.91 15 A No. 14 AWG in 2.0 mm diameter PVC
2 CONVENIENCE (10) 1800 230 7.82 15 A No. 14 AWG in 2.0 mm diameter PVC
3 SPEACIAL POWER (4) 1900 230 8.26 20A No. 10 AWG in 5.5 mm diameter PVC
4 AIRCON UNIT 1.5HP (3) 3600 230 15.65 20 A No. 12 AWG in 3.5 mm diameter PVC
SOLUTIONS:
W= Refrigerator = 100W
Circuit 3:
Washing Machine = 900W
=1900W
W = 1900W/230 V
L= 8.26 Ampers
Wire = 8.26 / 80% = 10.32 Amperes
Use #10 AWG
Use 20 A Circuit Breaker
Use 5.5 mm diameter PVC