Fiu 3700
Fiu 3700
PLC’s &
SCADA Systems
Legal Metrology and Custody Transfer Compliant with API Standards and OIML as outlined in the
certification from notified bodies.
FUNCTIONAL SPECIFICATION
Tank Database 200 Tanks without compromise.
Supported Gauge Model All MTG gauges, legacy and new. Any transmitter with support for
Modbus, HART® 7 and lower, or Foundation Fieldbus H1 Interfaces
and Protocols.
Tank Scanning 8 Field ports in parallel, rate dependant on protocol and hardware
interface.
Support API Product Calculations API MPMS Ch. 11.1 Tables, 5, 6, 23, 24, 53, 54, 59, 60 and 59, 60
Product groups A, B, C, D
API MPMS Ch. 11.2.4 Tables, 5, 6, 23, 24, 53, 54, 59, 60 and 59, 60
Product group E
OPERATING SYSTEM
OS Linux
CONNECTIVITY
Expansion Ports 8x Series 3700 Expansion Ports for use with Field Interface Option
Cards.
USB 2 Optional Rear USB 2.0 Ports, 1 Front Optional USB Port.
RS232 1 RS232 Port for PLC integration, and operation as a Modbus Slave
Device.
ENVIROMENT
Operational Temperature 0 oC to 60 oC (32oF to 140oF)
Storage Temperature -20 oC to 85 oC (-4oF to 185oF)
MECHANICAL
Form Factor 19” 2U Rackmount, Desktop or Wall mount.
ORDERING CODE
Supply
AC 110-240 VAC
DC 24VDC
3700 Range
BU 3700 FIU: Base Unit (Process Variables Only)
AD 3700 FIU Advanced: Base Unit with API Volume/Weight Correction
A57 3700 FIU Advanced: Base Unit with API Volume/Weight Correction with Integrated 5700 Server
Form Factor
2U 2U 19” Rack Mount
WM Wall Mount
Redundancy
XX None
01 With
Port 0
XX No Interface
01 Modbus RS232
02 Modbus RS485
03 Modbus TCP/IP
04 OPC Server
Port 1
XX No Interface
01 MTG Bus RS485
02 Modbus RS485
03 ENRAF BPM
04 ENRAF GPU RS485
05 SAAB TRL/2
Port 2
XX No Interface
01 MTG Bus RS485
02 Modbus RS485
03 ENRAF BPM
04 ENRAF GPU RS485
05 SAAB TRL/2
Port 3
XX No Interface
01 MTG Bus RS485
02 Modbus RS485
03 ENRAF BPM
04 ENRAF GPU RS485
05 SAAB TRL/2
Port 4
XX No Interface
01 MTG Bus RS485
02 Modbus RS485
03 ENRAF BPM
04 ENRAF GPU RS485
05 SAAB TRL/2
Port 5
XX No Interface
01 MTG Bus RS485
02 Modbus RS485
03 ENRAF BPM
04 ENRAF GPU RS485
05 SAAB TRL/2
Port 6
XX No Interface
01 MTG Bus RS485
02 Modbus RS485
03 ENRAF BPM
04 ENRAF GPU RS485
05 SAAB TRL/2
Port 7
XX No Interface
01 MTG Bus RS485
02 Modbus RS485
03 ENRAF BPM
04 ENRAF GPU RS485
05 SAAB TRL/2
Port 8
XX No Interface
01 MTG Bus RS485
02 Modbus RS485
03 ENRAF BPM
04 ENRAF GPU RS485
05 SAAB TRL/2
37