SCSP105part2
SCSP105part2
TABLE OF CONTENTS
2
SCSP10503/MAI/ZAK PAGE 2 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
3
SCSP10503/MAI/ZAK PAGE 3 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
4
SCSP10503/MAI/ZAK PAGE 4 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
5
SCSP10503/MAI/ZAK PAGE 5 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
32.0 ANNUNCIATORS
6
SCSP10503/MAI/ZAK PAGE 6 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
1.1.1 Inspect the grounding system(s) for conformance with approved design
drawings and specifications.
1.1.2 Inspect the mechanical integrity and quality of all bolted and/or thermite
welded grounding joints and connections.
1.1.3 Inspect and verify the size and type of conductors to conform with the
standard requirements.
1.2.1 Measure the ground grid system resistance by the “fall of potential”
method according to IEEE Standard 81.
1.2.2 Measure the contact resistance at 100Adc of all bolted and/or thermite-
welded joints at the grounding conductor between the equipment to be
grounded and the grounding mesh.
2.1.3 Check intercell and inter-tier connection link bolts tightness (torque
wrench method).
7
SCSP10503/MAI/ZAK PAGE 7 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
2.1.7 Check that all battery maintenance tools and accessories (hydrometer,
wall mounted thermometer, insulated torque wrench, rubber gloves,
apron, face shield, etc.) have been provided per specifications. Ensure
that all maintenance equipment is stored in a wall mounted lockable
cabinet.
2.1.8 Check that room ventilation, exhaust fan, etc., are to specification.
2.1.10 For flooded Lead Acid batteries, check for correct specific gravity and
liquid level.
2.1.12 Check that the battery bank is provided with an isolation disconnect
switch.
2.1.13 Check that for VRLA battery bank, an ammeter is provided for
monitoring the float charge current.
2.2.1 For Valve Regulated Lead Acid Batteries, check the open circuit voltage
of each cell.
2.2.2 Perform initial charging of the battery (equalize voltage, charging rate
and charging time according to the manufacturer’s instructions).
2.2.3 Record individual cell voltage, electrolyte specific gravity and cell
temperatures at the end of the charge cycle.
8
SCSP10503/MAI/ZAK PAGE 8 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
2.2.6 Place battery on charge at the specified float voltage. For VRLA battery
bank, measure and record the float current.
3.1.4 Verify all panel mounted devices (meters, switches, push buttons,
indicator lamps, etc.) are supplied and installed according to approved
drawings.
3.2.1 Megger all wiring and input/output power cables at 500 V DC. For 480V
rated wiring the megger voltage should be 1000VDC.
3.2.2 Check the adjustment range of output float and equalize voltages. Note
that the adjustment of float and equalize voltages should be independent
of each other.
9
SCSP10503/MAI/ZAK PAGE 9 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
● Soft start
● Impedance monitors (if applicable)
● Silicone droppers (if applicable)
3.2.6 Measure AC input and DC output voltages and currents and calculate
efficiency at 50% and 100% of rated output current.
3.2.8 If applicable measure the following and verify that they are compatible
with and meet the requirements of the communications equipment:
3.2.10 Ensure that settings of adjusted control, shutdown, alarm voltage, etc.,
have been reset to the final operational values as specified by SCECO-
East.
4.1.1 Check impact recorder records for any abnormal impacts during transit.
10
SCSP10503/MAI/ZAK PAGE 10 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
4.1.7 Check that all grounding is securely connected (including star neutral
points).
a) Cooling fans/pumps
b) Tap changer
c) Oil level gauges
d) Winding temperature gauges
e) Top oil temperature gauges
f) Buchholz relay
g) OLTC oil/Gas surge (Pressure) Relay
h) Pressure relief devices
j) Push buttons and indicators
k) Oil sampling port(main tank and OLTC)
l) Upper and lower main tank valves
4.1.12 Check liquid in the tank, conservator and bushing for proper level.
4.1.13 Bleed trapped air at the bushing turrets and tank top.
4.1.14 Check that the valves between the tank and the radiators are open.
4.1.16 Check HV, LV and TV (if applicable) bushings for damages and
completeness of accessories.
4.1.17 Check condition (color and quantity) of Silica gel in breathers and oil in
bath level.
11
SCSP10503/MAI/ZAK PAGE 11 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
4.2.9 Winding temperature indicator (WTI) device check (by current injection
at the heater element).
12
SCSP10503/MAI/ZAK PAGE 12 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
Except for the dielectric breakdown and power factor tests all other tests
must be performed at a SCECO East approved laboratory and the results
are to be submitted for SCECO East review and approval.
a) Dielectric strength:
i) ASTM D 877 (with 2.5 mm gap) for unprocessed oil & for oil in
OLTC
ii) ASTM D 1816 (with 1.0 mm gap) for oil in Transformer Main
Tank
b) Neutralization Number (ASTM D 974)
c) Interfacial tension (ASTM D 971)
d) Color (ASTM D 1500)
e) Moisture content (ASTM D 1533A)
f) Power factor test (ASTM D 924)
g) Dissolved gas in oil analysis (ASTM D 3612)
a) Polarity
b) Insulation resistance
c) Secondary winding resistance (all windings and taps)
d) Current ratio (by current injection)
e) Magnetization characteristics (minimum of 5 points below and 2
points above the knee point of the magnetization curve)
f) Verify secondary circuits, terminal to terminal
13
SCSP10503/MAI/ZAK PAGE 13 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
g) Burden test
h) Demagnetize CT cores after all tests
j) Ensure that there are no open circuited secondaries
4.2.17 Check each transformer trip device has an individual trip cutout located
at the transformer protection panel via FT switches.
4.2.19 Check CT wiring for correctness, tightness and for ring type terminal
lugs.(no spade lugs permitted).
4.2.21 A main tank insulating oil sample for Dissolved Gas Analysis shall be
taken immediately prior to first energizing a power transformer and
another sample three days after continuous energization.
5.1.1 Inspect for physical damage and defects (cracks, chips, etc., of the cast
resin.).
5.1.4 Check that all grounding is securely connected, including star point
neutral.
14
SCSP10503/MAI/ZAK PAGE 14 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
5.2.7 Check the off load tap changer is set at the rated voltage tap.
6.1.5 Check that all grounding cables are securely connected (including star
neutral points).
15
SCSP10503/MAI/ZAK PAGE 15 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
6.2.7 Check that the off load tap changer is set at the nominal voltage tap.
a) Dielectric strength
i) ASTM D 877 (with 2.5 mm gap) - For unprocessed oil
ii) ASTM D 1816 (with 1.0 mm gap) - For processed oil
b) Neutralization Number (ASTM D 974)
c) Interfacial tension (ASTM D 971)
d) Color (ASTM D 1500)
e) Moisture content (ASTM D 1533A)
f) Power factor test (ASTM D 924)
16
SCSP10503/MAI/ZAK PAGE 16 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
17
SCSP10503/MAI/ZAK PAGE 17 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
7.2.9 Insulation power factor (Doble) test (live tank CT’s - 115 kV and above).
8.1.4 Check that the HV connection does not transfer stress to the VT HV
terminal.
8.1.6 Check mechanical clearances and proper operation of all isolation and
grounding devices (as applicable).
18
SCSP10503/MAI/ZAK PAGE 18 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
8.2.8 Check electrical operation of all isolating and grounding devices (if
applicable).
9.1.4 Check that all grounding cables are securely connected including the star
point neutral.
9.1.5 Check mechanical clearances and proper operation of all isolating and
grounding devices (as applicable).
9.1.6 Check electromagnetic unit spark gaps for correct setting (if applicable).
19
SCSP10503/MAI/ZAK PAGE 19 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
9.2.8 Check electrical operation of all isolating and grounding devices (if
applicable).
10.1.4 Check that all grounding cables are securely connected including star
point neutral.
10.1.6 Check electromagnetic unit spark gaps for correct setting (if applicable).
10.1.7 Check drain coil unit spark gaps for correct setting (if applicable).
20
SCSP10503/MAI/ZAK PAGE 20 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
10.2.8 Check electrical operation of all isolating, grounding and shorting devices
(if applicable).
11.1.4 Inspect all covers, panels sections and doors for paint work and proper fit.
21
SCSP10503/MAI/ZAK PAGE 21 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
11.1.5 Check for smooth and proper movement of racking mechanisms, shutters,
rollers, rails and guides.
11.1.6 Check for proper alignment of the breaker primary and secondary
contacts.
11.1.9 Check bus and supports for defects such as cracked welds, chipped
porcelain, cracked insulation, etc., and free of dust accumulation.
11.1.10 Check main and riser buses for correct phasing connections.
11.1.11 Verify that all front panel mounted devices (meters, push buttons,
switches, indicator lamps, etc. )are installed per drawings.
11.1.12 Perform mechanical checks and visual inspections on all circuit breakers
per section 12.
11.1.15 Perform mechanical checks and visual inspection on all disconnect and
grounding switches per section 18.
11.2.1 Insulation resistance test of all wiring and cabling (megger at 500 V DC).
22
SCSP10503/MAI/ZAK PAGE 22 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
11.2.6 Check that all phase markings have been installed per specifications.
11.2.8 Check that all special tools, devices, etc., as per specification have been
provided.
23
SCSP10503/MAI/ZAK PAGE 23 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
12.1.9 For air magnetic breakers, check the arc chutes for damage and correct
positioning above the interrupter contacts.
12.1.10 For minimum oil breakers, check correct oil level in each pole.
12.1.11 For SF6 breakers, check the correct gas pressure, quality and leakage.
12.1.12 For SF6 breakers, check the operation of the gas density switch (alarm
and lockout functions).
12.1.13 Perform all specific checks on the breaker and spring operating
mechanism according to the manufacturer’s instructions.
12.1.14 Check that all control wiring is correct according to the approved
drawings and terminal connections are secure.
12.2.10 Check spring charge time and motor currents at rated control voltage.
24
SCSP10503/MAI/ZAK PAGE 24 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
12.2.11 Functional check of thermostat and space heaters; measure heater current.
12.2.14 For SF6 breakers, verify electrically the low gas pressure alarm and
lockout functions.
12.2.15 For minimum oil breakers, test insulating oil for dielectric strength.
ASTM D-877 (with 2.5 mm gap)
12.2.16 Check correct operation of all auxiliary “a” and “b” contacts (for breaker
open/closed position).
a) For vacuum breakers, test across open contacts and live parts to
ground. Precautions should be taken against emission of X-rays.
b) For all other breakers, test in conjunction with section 11 with
breakers racked in the switchgear and in the closed position.
13.1.4 Check all wiring is correct according to approved drawings and terminal
connections are secure.
25
SCSP10503/MAI/ZAK PAGE 25 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
13.1.7 Check breaker, truck, rails, etc., for proper alignment and smooth
movement.
13.1.10 For minimum oil circuit breakers, check for correct oil level in each pole.
a) Check the compressor, air piping, valves, pressure gauges, air filter,
water trap and switches for damage/defects/blockage.
b) Calibrate the air pressure gauges.
c) Check the setting of air pressure switches (compressor start/stop,
alarm, lockout).
d) Perform all specific checks on the compressed air system according
to the manufacturer’s instructions.
e) Check for correct direction of compressor rotation.
f) Check air charging time.
g) Check safety relief valve operating pressure and resetting pressure.
h) Measure air consumption for C, O, CO and OCO operations.
26
SCSP10503/MAI/ZAK PAGE 26 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
13.2.3 Insulation resistance test of all low voltage wiring and cabling.
27
SCSP10503/MAI/ZAK PAGE 27 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
13.2.12 Check correct operation of all auxiliary “a” and “b” contacts (for breaker
open/closed positions).
13.2.14 For SF6 breakers, verify electrically the low gas pressure alarm and
lockout functions.
13.2.15 For minimum oil circuit breakers, test insulating oil for dielectric
strength.
ASTM D 877 (with 2.5 mm gap)
13.2.16 For motor/spring operating mechanisms, measure spring charge time and
motor current.
13.2.18 Verify the electrical operation of the breaker racking truck. Check the
correct functioning of interlocks and limit switches.
28
SCSP10503/MAI/ZAK PAGE 28 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
14.1.4 Check all wiring is correct according to approved drawings and terminal
connections are secure.
29
SCSP10503/MAI/ZAK PAGE 29 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
a) Check the compressor, air piping, valves, pressure gauges, air filter,
water trap and switches for damage/defects.
b) Calibrate the air pressure gauges.
c) Check the setting of air pressure switches (compressor start/stop,
alarm, lockout).
d) Perform all specific checks on the compressed air system according
to the manufacturer’s instructions.
e) Check for correct direction of compressor rotation.
f) Check air charging time.
g) Check safety relief valve operating pressure and resetting pressure.
h) Measure air consumption for C, O, CO and OCO operations.
i) Air storage test, perform as specified, the following without
replenishment:
5 X CO, or O + CO + 3 min. + CO
j) Air leakage test (pressure drop method over 24 hours, CB closed and
open).
30
SCSP10503/MAI/ZAK PAGE 30 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
14.2.3 Insulation resistance test of all low voltage wiring and cabling.
31
SCSP10503/MAI/ZAK PAGE 31 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
14.2.12 Check correct operation of all auxiliary “a” and “b” contacts (for breaker
open/closed positions).
14.2.14 For SF6 breakers, verify electrically the low gas pressure alarm and
lockout functions.
14.2.15 For minimum oil circuit breakers, test insulating oil for dielectric
strength.
ASTM D 877 (with 2.5 mm gap)
14.2.17 For motor/spring operating mechanisms, measure spring charge time and
motor current.
14.2.19 A.C. Hipot test (applicable to SF6 breakers, if the tank is opened at site,
e.g., to install bushings.
32
SCSP10503/MAI/ZAK PAGE 32 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
a) Polarity
b) Insulation resistance
c) Secondary winding resistance (all windings and taps)
d) Current ratio (by current injection)
e) Magnetization characteristics (minimum 5 points below knee point
voltage and 2 above)
f) Verify secondary circuits, terminal to terminal
g) Burden test
h) Demagnetize CT cores after all tests
i) Ensure no open circuited secondaries
15.1.5 Ensure that all special tools and equipment are provided as specified and
that proper storage is provided.
15.1.6 Ensure that gas handling cart (if provided) operates correctly and that
special filling and degassing fittings are provided and have proper
storage.
15.1.7 Verify that all lifting devices are correctly labeled for lifting.
15.1.8 Ensure that adequate ladders and walkways are provided for access to
meters, filling ports, cranes, lights, etc.
15.1.9 Check that all grounding is securely connected per layout drawings.
33
SCSP10503/MAI/ZAK PAGE 33 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
15.1.10 Check that all specified grounding switches are insulated, with removable
grounding links.
15.1.13 Check SF6 gas at each gas section for air and moisture content.
15.1.15 Gas leak test of all flanges and joints after erection and filling.
15.1.17 Check operation of all gas density switches (alarm and lockout
functions). Confirm correct set points.
15.1.19 Verify that all front panel mounted devices (meters, push buttons,
switches, indicator lamps, mimic buses, etc.) are installed as per drawings
and are correctly labeled.
15.1.22 Check that all phase markings have been installed per specifications.
15.1.23 Ensure that all disconnects are provided with viewing windows for
verification of contact positions and that all grounding switch positions
can be safely verified visually.
34
SCSP10503/MAI/ZAK PAGE 34 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
15.2.1 Insulation resistance test of all low voltage wiring and cabling.
15.2.8 Check that all cubicle space heaters and thermostats are functional.
Measure the heater currents at rated voltage.
15.2.11 AC hipot test of the complete switchgear main circuit to ground at 80%
of the factory routine test voltage for 1 minute (DC test is not acceptable).
35
SCSP10503/MAI/ZAK PAGE 35 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
16.1.5 Inspect internal compartments for cleanliness (free from dust and
moisture).
16.1.6 Check for water tight seals at all joints including expanding interface
points.
16.1.7 Check bus conductor support insulators for cracked insulation, chipped
porcelain, etc.
16.1.9 Check that ventilation openings are not blocked, and screened against
ingress of insects and rain.
36
SCSP10503/MAI/ZAK PAGE 36 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
16.2.6 Heaters and thermostats functional test. Measure the heater currents.
17.1.3 Check bus connections for correct phasing and marking of phases.
17.1.5 Check for proper phase to phase to ground clearances (for indoor
buswork.)
17.1.6 Ensure that PT, etc., connections are flexible, to prevent transferring
expansion stress from the bus.
17.2.3 Hi-pot test (indoor buswork including PT’s where applicable, 69 kV and
below).
37
SCSP10503/MAI/ZAK PAGE 37 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
18.1.5 Check smoothness and ease of operation (both closing and opening).
18.1.7 Check for proper contact, fingers spread and contact pressure in fully
closed position.
18.1.8 Check that end of travel stops are correctly adjusted, set and locked in
position.
18.1.9 Check open gap and minimum clearances between phases and to ground.
18.1.10 Check switch opens more than 90° (for horizontally mounted vertical
open disconnects).
18.1.11 Check switch drive linkage toggled in both the closed and opened
positions.
18.1.12 Check that switch can be pad locked in both the closed and opened
positions.
18.1.16 Check that the operator’s platform is of adequate size and is properly
grounded.
38
SCSP10503/MAI/ZAK PAGE 38 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
39
SCSP10503/MAI/ZAK PAGE 39 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
20.1.5 Check impact recorder records for any abnormal impacts during transit.
40
SCSP10503/MAI/ZAK PAGE 40 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
20.1.6 Check that all grounding cables are securely connected (including star
neutral points).
20.1.9 Check liquid in the tank, conservator and bushings for proper level
20.1.11 Check that valves between the tank and radiators are open
a) Cooling fans/pumps
b) Oil level gauges
c) Winding temperature gauges
d) Top oil temperature gauges
e) Buchholz relay
f) Pressure relief device
g) Push buttons and indicators
h) Silica gel breathers
i) Oil sampling port
j) Upper and lower main tank valves
41
SCSP10503/MAI/ZAK PAGE 41 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
20.2.5 Winding temperature indicator (WTI) device check (by current injection
at the heater element).
a) Dielectric strength
i) ASTM D 877 (with 2.5 mm gap) - for unprocessed oil
ii) ASTM D 1816 (with 1.0 mm gap) - for processed oil
b) Neutralization Number (ASTM D 974)
c) Interfacial tension (ASTM D 971)
d) Color (ASTM D 1500)
e) Moisture content (ASTM D 1533A)
f) Power factor test (ASTM D 924)
g) Dissolved gas in oil analysis (ASTM D 3612)
a) Polarity
b) Insulation resistance
c) Secondary winding resistance (all windings and taps)
d) Current ratio (by current injection)
e) Magnetization characteristics (minimum of 5 points below and 2
points above the knee point of the magnetization curve)
f) Verify secondary circuits, terminal to terminal
42
SCSP10503/MAI/ZAK PAGE 42 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
g) Burden test
h) Demagnetize CT cores after all tests
i) Ensure that there are no open secondaries
21.1.1 Inspect capacitor units for physical damage and sign of fluid leaks.
21.1.7 Check external protective fuse of each capacitor unit for correct rating per
nameplate.
21.1.8 Check installation of bird proof terminal caps at each capacitor bushing
(if applicable).
21.1.9 Inspect mounting racks and support insulators, and structures for defects
such as cracked welds, chipped porcelains, etc.
21.1.10 Check that the support structures of each phase are grounded at two
diagonally opposite legs.
43
SCSP10503/MAI/ZAK PAGE 43 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
21.2.1 Short time voltage withstand test per ANSI/IEEE No. 18, (performed on
10% of installed capacitor units).
21.2.2 Insulation power factor (Doble) test, performed on 10% of the installed
capacitor units.
21.2.4 Terminal to terminal (or terminal to casing for single bushing type)
resistance measurement (on all capacitor units).
22.1.2 Verify circuits layout for conformance with breaker’s directory drawing.
22.1.3 Verify correct rating of each circuit breaker per design drawings.
22.1.5 Verify that all front panel mounted devices (meters, selector switches,
push buttons, timers, indication lights) are installed per layout drawing
and are correctly labeled.
44
SCSP10503/MAI/ZAK PAGE 44 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
22.2.6 Functional check of all auxiliary devices, including individual, group and
main circuit breaker alarms.
23.1.2 Verify circuits layout for conformance with breaker’s directory drawing.
23.1.3 Verify correct rating of each circuit breaker per design drawing.
23.1.5 Verify that all front panel mounted devices are installed per layout
drawing and are correctly labeled.
45
SCSP10503/MAI/ZAK PAGE 45 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
23.2.7 Functional check of all auxiliary devices, including individual, group and
main circuit breaker alarms.
24.1.2 Check that all front panel mounted devices are supplied and arranged
according to approved drawings.
24.1.3 Check that all devices and cables are properly identified and labeled.
24.1.5 Check that all grounding is correct and securely connected (including
neutral bus).
46
SCSP10503/MAI/ZAK PAGE 46 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
24.2.8 Functional check of transfer operation (simulate loss of one source) and
retransfer on re-establishment of preferred source voltage. Check with
each source as the preferred source.
24.2.10 Set undervoltage relay and time delay per manufacturer’s instructions.
25.1.3 For multi-unit stacks, check that the physical arrangement of the units are
erected according to the manufacturer’s specifications.
25.1.4 Check that all grounding cables are correctly and securely connected.
47
SCSP10503/MAI/ZAK PAGE 47 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
26.1.5 Check that relay mounting is secure and protected against misoperation
due to vibration, shock, etc.
26.2.3 Verify that all auxiliary relays and timers are tested by pick up and drop
out
26.2.4 By secondary injection, verify relay operation over the setting range (3
points check at minimum, specified setting and maximum of range)
48
SCSP10503/MAI/ZAK PAGE 48 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
26.2.6 Verify circuits, terminal to terminal (as testing is completed, yellow line
the drawing section to reflect completion)
26.2.7 Check proper operation of current shorting links, voltage links, trip
isolating and signal isolating devices, etc.
26.2.8 Ensure that the relays and relay covers are properly identified and that the
identification does not obscure relay information displays.
26.2.9 Remove all relays from the cases and check for tightness and that all
shorting terminals are making proper contact
26.2.10 Check that all test switches operate properly and all are properly labeled
by device number and individual functions
26.2.12 Perform Primary injection tests on CT & PT circuits. Verify ratio and
Polarity throughout entire circuit. In case Primary Injection Tests are not
practicable then Secondary Injection Tests shall be performed.
26.2.13 Perform trip tests to verify all of the trip functions. Trip relays must have
a timing test. If applicable, verify that sufficient target current is
available to simultaneously drop all three phase target indicators.
26.2.14 Perform a reduced voltage trip test for all trip relays.
26.2.15 Perform insulation tests - megger each circuit terminal to relay frame on
all DC and AC circuits and wiring at 500 VDC or recommendations of
Manufacturer. Caution: Do not megger any circuits to which static or
solid state devices are connected
26.2.16 Verify that only designated grounds exist in current and potential
transformers secondary circuits.
26.2.17 Measure the loop resistance of all current transformer secondary circuits
with all relays and associated devices in place
49
SCSP10503/MAI/ZAK PAGE 49 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
26.2.19 With all final settings applied perform a secondary injection test that will
operate each relay element and trip each device (HV breaker, motor
operated switch etc.)
26.2.20 Perform In-service readings to verify the CT, PT ratios and polarities
27.1.4 Check that all mounting bolts and wiring terminations are tight and
secured.
27.1.5 Check that all instrument scaling factors are according to design
specifications.
27.2.3 Calibrate and verify accuracy of all transducers, shunts, etc. with the
associated meters.
50
SCSP10503/MAI/ZAK PAGE 50 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
28.1.3 Check for proper cable support, clamping and blocking, etc.
28.1.4 Check cable bends to ensure that the bending radius is equal to or greater
than the minimum bending radius specified.
28.1.5 Verify that shields are terminated as specified (through link box or
directly grounded).
28.1.6 Check that all grounding points are securely connected to ground grid as
specified.
51
SCSP10503/MAI/ZAK PAGE 51 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
28.2.2 Insulation resistance between cable conductor and sheath (at 5000 V DC).
28.2.5 Test on corrosion resistant coverings at 10 kV, 1(one) minute, (per IEC
60141-1).
29.1.3 Check for proper cable support, clamping and blocking, etc.
29.1.4 Check cable bends to ensure that the bending radius is equal to or greater
than the minimum bending radius specified.
52
SCSP10503/MAI/ZAK PAGE 52 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
29.1.5 Verify shield grounding as per design ( single point, both ends, via
voltage limiters, etc.
29.2.3 Test on corrosion resistant coverings at 10 kV, 1(one) minute, (per IEC
60141-1).
29.2.5 AC high voltage withstand test at specified test voltage per SCS-P-
104.08.
30.1.1 Inspect that the access roads and structure pads are to specification
(locations, widths, depth of base, cover material properly compacted,
etc.).
30.1.2 Check that sand stabilization has been done per specification (if
applicable).
30.1.3 Check the right of way to ensure that there is no building or tree
encroachment.
53
SCSP10503/MAI/ZAK PAGE 53 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
30.1.4 Check that grounding connection is made properly with steel structure
and protective coating is applied on the concrete cap (if specified). There
shall be no cracks, and the concrete cap shall slope away from the stub
angle.
30.1.5 Check that the ground profile allows water to runoff away from the
structures.
30.1.6 Ensure that the structure footing resistance is as specified (see section
1.0).
30.1.7 For wood pole structures, ensure that poles are the correct specification
and have been installed correctly (depth and plumb). Ensure that the
depth indication tags are on each pole.
30.1.8 Check that all wood structures have been identified correctly and that the
identification plates are to specification. For double circuit structures,
ensure that each circuit is correctly identified.
30.1.9 Check the quality of paint work. Ensure that the coatings are to
specification and that touch up painting is applied as required (no rust).
30.1.12 Check insulators for chips, cracks, etc. (for porcelain insulators). Ensure
correct number of insulators have been installed in each string. Ensure
that cotter keys have been properly installed.
30.1.13 Check that all line hardware (insulator, vibration dampers, spacers,
conductor clamps, armor rods, etc.) are to specification, installed
correctly and in correct locations.
30.1.15 Check that all splices are correct and are installed in correct span
locations.
54
SCSP10503/MAI/ZAK PAGE 54 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
30.1.17 Check that overhead ground conductors are grounded securely to towers
as specified.
30.1.18 Ensure that sags for phase and overhead ground conductors are to
specification.
30.1.19 Ensure that the site has been properly cleaned up and all earthwork
profiles are correct before acceptance.
30.1.20 Check phase identification plates have been correctly installed at each
structure.
31.1.3 Verify that all cables and cores are labeled correctly.
31.1.5 Check that all cable trays are secure and correctly grounded.
31.1.7 Check that conductor sheaths conform with SCECO East color code.
55
SCSP10503/MAI/ZAK PAGE 55 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
32.0 ANNUNCIATORS
32.1.2 Check wiring for correct connections according to the approved drawing.
32.1.3 Check that all alarm/annunciation points are provided and arranged
according to the approved drawing. Ensure that all are clearly labeled.
32.1.5 Verify that all window labels clearly and adequately describe the
annunciated condition.
a) Alarm acknowledge
b) Alarm reset
c) Audible alarm (buzzer/bell)
d) Lamp test
32.2.2 Functional check of each alarm point by simulating the alarm condition at
each alarm source. Verify that all applicable alarms are correctly
received at PCC.
56
SCSP10503/MAI/ZAK PAGE 56 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
33.1.2 Check that the DTR and interface cabinet have been mounted in
accordance with the manufacturer’s instructions.
33.1.5 Check that all input wiring is in accordance with approved drawings, and
meets ESPD requirements.
33.2.1 Check that the communications connection is made and that the
communications channel is functional.
33.2.2 Power up the DTR and check power supplies for correct output, and that
120 V AC supply is present at DTR AC outlets.
33.2.5 Calibrate all voltage and current channels in accordance with ESPD
specifications.
33.2.7 Check operation of all digital inputs by simulating contact closure using a
jumper wire.
33.2.8 Check operation of all analog channels by simulating current and voltage
inputs from the interface panel.
57
SCSP10503/MAI/ZAK PAGE 57 of 58
5/14/00
Saudi Consolidated Electric Company ≠B_IZ¢y{{ ©X_R•}{A ™¶X•__la{A ™yZ_c{A
in the Eastern Province
™__¶_vZ_c{A ™___wi }{A ßs
33.2.11 Verify that master station software is setup to accept remote DTR inputs.
58
SCSP10503/MAI/ZAK PAGE 58 of 58