Schneider Electric_Logic-Controller-Modicon-M221_TM221C24R
Schneider Electric_Logic-Controller-Modicon-M221_TM221C24R
Specifications
Main
Range Of Product Modicon M221
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
[Us] Rated Supply Voltage 100...240 V AC
Discrete Input Number 14, discrete input conforming to IEC 61131-2 Type 1
Complementary
Discrete I/O Number 24
Inrush Current 40 A
Maximum Power Consumption In 55 VA at 100...240 V with max number of I/O expansion module
Va 32 VA at 100...240 V without I/O expansion module
Lsb Value 10 mV
Conversion Time 1 ms per channel + 1 controller cycle time for analogue input analog input
Permitted Overload On Inputs +/- 30 V DC for 5 min (maximum) for analog input
+/- 13 V DC (permanent) for analog input
11-Jun-2024 1
Input Impedance 3.4 kOhm for discrete input
100 kOhm for analog input
4.9 kOhm for fast input
Reset Time 1s
Memory Capacity 256 kB for user application and data RAM with 10000 instructions
256 kB for internal variables RAM
Data Backed Up 256 kB built-in flash memory for backup of application and data
Execution Time For 1 Kinstruction 0.3 ms for event and periodic task
2 11-Jun-2024
Counting Input Number 4 fast input (HSC mode) at 100 kHz 32 bits
Integrated Connection Type USB port with mini B USB 2.0 connector
Non isolated serial link serial 1 with RJ45 connector and RS485 interface
Non isolated serial link serial 2 with RJ45 connector and RS232/RS485 interface
Transmission Rate 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232
480 Mbit/s for USB
Marking CE
Mounting Support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
Height 90 mm
Depth 70 mm
Width 110 mm
Environment
Standards IEC 61131-2
UL 508
CAN/CSA C22.2 No. 213
IACS E10
ANSI/ISA 12-12-01
11-Jun-2024 3
Product Certifications LR
ABS
DNV-GL
RCM
cULus
EAC
CE
UKCA
cULus HazLoc
Surge Withstand 2 kV power lines (AC) common mode conforming to IEC 61000-4-5
2 kV relay output common mode conforming to IEC 61000-4-5
1 kV I/O common mode conforming to IEC 61000-4-5
1 kV shielded cable common mode conforming to IEC 61000-4-5
0.5 kV power lines (DC) differential mode conforming to IEC 61000-4-5
1 kV power lines (AC) differential mode conforming to IEC 61000-4-5
1 kV relay output differential mode conforming to IEC 61000-4-5
0.5 kV power lines (DC) common mode conforming to IEC 61000-4-5
Electromagnetic Emission Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC))
at 0.15…0.5 MHz conforming to IEC 55011
Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC))
at 0.5…300 MHz conforming to IEC 55011
Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz
conforming to IEC 55011
Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz
conforming to IEC 55011
Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz
conforming to IEC 55011
Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500
kHz conforming to IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz
conforming to IEC 55011
Immunity To Microbreaks 10 ms
4 11-Jun-2024
Shock Resistance 98 m/s² for 11 ms
Packing Units
Unit Type Of Package 1 PCE
11-Jun-2024 5
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right
Transparency RoHS/REACh
Well-being performance
Mercury Free
Pvc Free
Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins
6 11-Jun-2024
Product datasheet TM221C24R
Dimensions Drawings
Dimensions
11-Jun-2024 7
Product datasheet TM221C24R
Mounting on a Rail
8 11-Jun-2024
Product datasheet TM221C24R
11-Jun-2024 9
Product datasheet TM221C24R
Mounting
10 11-Jun-2024
Product datasheet TM221C24R
Clearance
11-Jun-2024 11
Product datasheet TM221C24R
Digital Inputs
12 11-Jun-2024
Product datasheet TM221C24R
Relay Outputs
(1) The COM0, COM1 and COM2 terminals are not connected internally.
(2) To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a
free wheeling diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load
(1) The COM0, COM1 and COM2 terminals are not connected internally.
(2) To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a
free wheeling diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load
11-Jun-2024 13
Product datasheet TM221C24R
Analog Inputs
0V Black
AN1 Red
0V Black
AN0 Red
14 11-Jun-2024
Product datasheet TM221C24R
11-Jun-2024 15
Product datasheet TM221C24R
SL1 Connection
SL1
N° RS 232 RS 485
1 RxD N.C.
2 TxD N.C.
3 RTS N.C.
4 N.C. D1
5 N.C. D0
6 CTS N.C.
7 N.C*. 5 Vdc
8 Common Common
16 11-Jun-2024
Product datasheet TM221C24R
SL2 Connection
N° RS 485
1 N.C.
2 N.C.
3 N.C.
4 D1
5 D0
6 N.C.
7 N.C.
8 Common
11-Jun-2024 17
Product datasheet TM221C24R
Performance Curves
Derating Curves
X: Ambient temperature
X: Ambient temperature
18 11-Jun-2024