Product datasheet

Specifications

logic controller, Modicon M221, 24


IO, relay
TM221C24R

Main
Range Of Product Modicon M221

Product Or Component Type Logic controller

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
[Us] Rated Supply Voltage 100...240 V AC

Discrete Input Number 14, discrete input conforming to IEC 61131-2 Type 1

Analogue Input Number 2 at 0...10 V

Discrete Output Type Relay normally open

Discrete Output Number 10 relay

Discrete Output Voltage 5...125 V DC


5...250 V AC

Discrete Output Current 2A

Complementary
Discrete I/O Number 24

Maximum Number Of I/O 7 (local I/O-Architecture)


Expansion Module 14 (remote I/O-Architecture)

Supply Voltage Limits 85…264 V

Network Frequency 50/60 Hz

Inrush Current 40 A

Maximum Power Consumption In 55 VA at 100...240 V with max number of I/O expansion module
Va 32 VA at 100...240 V without I/O expansion module

Power Supply Output Current 0.52 A 5 V for expansion bus


0.16 A 24 V for expansion bus

Discrete Input Logic Sink or source (positive/negative)

Discrete Input Voltage 24 V

Discrete Input Voltage Type DC

Analogue Input Resolution 10 bits

Lsb Value 10 mV

Conversion Time 1 ms per channel + 1 controller cycle time for analogue input analog input

Permitted Overload On Inputs +/- 30 V DC for 5 min (maximum) for analog input
+/- 13 V DC (permanent) for analog input

Voltage State 1 Guaranteed >= 15 V for input

Voltage State 0 Guaranteed <= 5 V for input

Discrete Input Current 7 mA for discrete input


5 mA for fast input

11-Jun-2024 1
Input Impedance 3.4 kOhm for discrete input
100 kOhm for analog input
4.9 kOhm for fast input

Response Time 35 µs turn-off, I2...I5 terminal(s) for input


10 ms turn-on for output
10 ms turn-off for output
5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input
35 µs turn-on, other terminals terminal(s) for input
5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input
100 µs turn-off, other terminals terminal(s) for input

Configurable Filtering Time 0 ms for input


3 ms for input
12 ms for input

Output Voltage Limits 125 V DC


277 V AC

Maximum Current Per Output 4 A at COM 2


Common 7 A at COM 0
7 A at COM 1

Absolute Accuracy Error +/- 1 % of full scale for analog input

Electrical Durability 100000 cycles AC-12, 120 V, 240 VA, resistive


100000 cycles AC-12, 240 V, 480 VA, resistive
300000 cycles AC-12, 120 V, 80 VA, resistive
300000 cycles AC-12, 240 V, 160 VA, resistive
100000 cycles AC-15, cos phi = 0.35, 120 V, 60 VA, inductive
100000 cycles AC-15, cos phi = 0.35, 240 V, 120 VA, inductive
300000 cycles AC-15, cos phi = 0.35, 120 V, 18 VA, inductive
300000 cycles AC-15, cos phi = 0.35, 240 V, 36 VA, inductive
100000 cycles AC-14, cos phi = 0.7, 120 V, 120 VA, inductive
100000 cycles AC-14, cos phi = 0.7, 240 V, 240 VA, inductive
300000 cycles AC-14, cos phi = 0.7, 120 V, 36 VA, inductive
300000 cycles AC-14, cos phi = 0.7, 240 V, 72 VA, inductive
100000 cycles DC-12, 24 V, 48 W, resistive
300000 cycles DC-12, 24 V, 16 W, resistive
100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms)
300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms)

Switching Frequency 20 switching operations/minute with maximum load

Mechanical Durability 20000000 cycles for relay output

Minimum Load 1 mA at 5 V DC for relay output

Protection Type Without protection at 5 A

Reset Time 1s

Memory Capacity 256 kB for user application and data RAM with 10000 instructions
256 kB for internal variables RAM

Data Backed Up 256 kB built-in flash memory for backup of application and data

Data Storage Equipment 2 GB SD card (optional)

Battery Type BR2032 or CR2032X lithium non-rechargeable

Backup Time 1 year at 25 °C (by interruption of power supply)

Execution Time For 1 Kinstruction 0.3 ms for event and periodic task

Execution Time Per Instruction 0.2 µs Boolean

Exct Time For Event Task 60 µs response time

Maximum Size Of Object Areas 255 %C counters


8000 %MW memory words
512 %M memory bits
512 %KW constant words
255 %TM timers

Realtime Clock With

Clock Drift <= 30 s/month at 25 °C

Regulation Loop Adjustable PID regulator up to 14 simultaneous loops

2 11-Jun-2024
Counting Input Number 4 fast input (HSC mode) at 100 kHz 32 bits

Counter Function A/B


Single phase
Pulse/direction

Integrated Connection Type USB port with mini B USB 2.0 connector
Non isolated serial link serial 1 with RJ45 connector and RS485 interface
Non isolated serial link serial 2 with RJ45 connector and RS232/RS485 interface

Supply (serial)serial link supply: 5 V, <200 mA

Transmission Rate 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232
480 Mbit/s for USB

Communication Port Protocol USB port: USB - SoMachine-Network


Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network

Local Signalling 1 LED (green) for PWR


1 LED (green) for RUN
1 LED (red) for module error (ERR)
1 LED (green) for SD card access (SD)
1 LED (red) for BAT
1 LED (green) for SL1
1 LED (green) for SL2
1 LED per channel (green) for I/O state

Electrical Connection removable screw terminal block for inputs


removable screw terminal block for outputs
terminal block, 3 terminal(s) for connecting the 24 V DC power supply
connector, 4 terminal(s) for analogue inputs
Mini B USB 2.0 connector for a programming terminal

Maximum Cable Distance Shielded cable: <10 m for fast input


Between Devices Unshielded cable: <30 m for output
Unshielded cable: <30 m for digital input
Unshielded cable: <1 m for analog input

Insulation Between input and internal logic at 500 V AC


Non-insulated between analogue input and internal logic
Non-insulated between analogue inputs
Between supply and ground at 1500 V AC
Between sensor power supply and ground at 500 V AC
Between input and ground at 500 V AC
Between output and ground at 1500 V AC
Between supply and internal logic at 2300 V AC
Between sensor power supply and internal logic at 500 V AC
Between output and internal logic at 2300 V AC
Between Ethernet terminal and internal logic at 500 V AC
Between supply and sensor power supply at 2300 V AC

Marking CE

Sensor Power Supply 24 V DC at 250 mA supplied by the controller

Mounting Support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit

Height 90 mm

Depth 70 mm

Width 110 mm

Net Weight 0.395 kg

Environment
Standards IEC 61131-2
UL 508
CAN/CSA C22.2 No. 213
IACS E10
ANSI/ISA 12-12-01

11-Jun-2024 3
Product Certifications LR
ABS
DNV-GL
RCM
cULus
EAC
CE
UKCA
cULus HazLoc

Environmental Characteristic Ordinary and hazardous location

Resistance To Electrostatic 8 kV in air conforming to IEC 61000-4-2


Discharge 4 kV on contact conforming to IEC 61000-4-2

Resistance To Electromagnetic 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3


Fields 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3
1 V/m 2...2.7 GHz conforming to IEC 61000-4-3

Resistance To Magnetic Fields 30 A/m 50/60 Hz conforming to IEC 61000-4-8

Resistance To Fast Transients 2 kV (power lines) conforming to IEC 61000-4-4


2 kV (relay output) conforming to IEC 61000-4-4
1 kV (I/O) conforming to IEC 61000-4-4
1 kV (Ethernet line) conforming to IEC 61000-4-4
1 kV (serial link) conforming to IEC 61000-4-4

Surge Withstand 2 kV power lines (AC) common mode conforming to IEC 61000-4-5
2 kV relay output common mode conforming to IEC 61000-4-5
1 kV I/O common mode conforming to IEC 61000-4-5
1 kV shielded cable common mode conforming to IEC 61000-4-5
0.5 kV power lines (DC) differential mode conforming to IEC 61000-4-5
1 kV power lines (AC) differential mode conforming to IEC 61000-4-5
1 kV relay output differential mode conforming to IEC 61000-4-5
0.5 kV power lines (DC) common mode conforming to IEC 61000-4-5

Resistance To Conducted 10 V 0.15...80 MHz conforming to IEC 61000-4-6


Disturbances 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL)
10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to
Marine specification (LR, ABS, DNV, GL)

Electromagnetic Emission Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC))
at 0.15…0.5 MHz conforming to IEC 55011
Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC))
at 0.5…300 MHz conforming to IEC 55011
Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz
conforming to IEC 55011
Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz
conforming to IEC 55011
Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz
conforming to IEC 55011
Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500
kHz conforming to IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz
conforming to IEC 55011

Immunity To Microbreaks 10 ms

Ambient Air Temperature For -10…55 °C (horizontal installation)


Operation -10…35 °C (vertical installation)

Ambient Air Temperature For -25…70 °C


Storage
Relative Humidity 10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)

Ip Degree Of Protection IP20 with protective cover in place

Pollution Degree <= 2

Operating Altitude 0...2000 m

Storage Altitude 0…3000 m

Vibration Resistance 3.5 mm at 5…8.4 Hz on symmetrical rail


3.5 mm at 5…8.4 Hz on panel mounting
1 gn at 8.4…150 Hz on symmetrical rail
1 gn at 8.4…150 Hz on panel mounting

4 11-Jun-2024
Shock Resistance 98 m/s² for 11 ms

Packing Units
Unit Type Of Package 1 PCE

Number Of Units In Package 1 1

Package 1 Height 11.116 cm

Package 1 Width 14.219 cm

Package 1 Length 15.643 cm

Package 1 Weight 640.0 g

Unit Type Of Package 2 CAR

Number Of Units In Package 2 20

Package 2 Height 29.1 cm

Package 2 Width 39.5 cm

Package 2 Length 56.3 cm

Package 2 Weight 13.87 kg

Unit Type Of Package 3 P12

Number Of Units In Package 3 240

Package 3 Height 120.0 cm

Package 3 Width 105.0 cm

Package 3 Length 80.0 cm

Package 3 Weight 164 kg

11-Jun-2024 5
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Mercury Free

 Rohs Exemption Information Yes

 Pvc Free

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)

China Rohs Regulation China RoHS declaration

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile End of Life Information

6 11-Jun-2024
Product datasheet TM221C24R

Dimensions Drawings

Dimensions

11-Jun-2024 7
Product datasheet TM221C24R

Mounting and Clearance

Mounting on a Rail

8 11-Jun-2024
Product datasheet TM221C24R

Direct Mounting on a Panel Surface

(1) Install a mounting strip

Mounting Hole Layout

11-Jun-2024 9
Product datasheet TM221C24R

Mounting

Correct Mounting Position

Acceptable Mounting Position

Incorrect Mounting Position

10 11-Jun-2024
Product datasheet TM221C24R

Clearance

11-Jun-2024 11
Product datasheet TM221C24R

Connections and Schema

Digital Inputs

Wiring Diagram (Positive Logic)

(*) Type T fuse

Wiring Diagram (Negative Logic)

(*) Type T fuse

Connection of the Fast Inputs

I0, I1, I6, I7

12 11-Jun-2024
Product datasheet TM221C24R

Relay Outputs

Negative Logic (Sink)

(*) Type T fuse

(1) The COM0, COM1 and COM2 terminals are not connected internally.

(2) To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a
free wheeling diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load

B Sink wiring (negative logic)

Positive Logic (Source)

(*) Type T fuse

(1) The COM0, COM1 and COM2 terminals are not connected internally.

(2) To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a
free wheeling diode in parallel to each inductive DC load or an RC snubber in parallel of each inductive AC load

A Source wiring (positive logic)

11-Jun-2024 13
Product datasheet TM221C24R

Analog Inputs

The (-) poles are connected internally.

Pin Wire Color

0V Black

AN1 Red

0V Black

AN0 Red

14 11-Jun-2024
Product datasheet TM221C24R

USB Mini-B Connection

11-Jun-2024 15
Product datasheet TM221C24R

SL1 Connection

SL1
N° RS 232 RS 485

1 RxD N.C.

2 TxD N.C.

3 RTS N.C.

4 N.C. D1

5 N.C. D0

6 CTS N.C.

7 N.C*. 5 Vdc

8 Common Common

N.C.: not connected


* : 5 Vdc delivered by the controller. Do not connect.

16 11-Jun-2024
Product datasheet TM221C24R

SL2 Connection

N° RS 485

1 N.C.

2 N.C.

3 N.C.

4 D1

5 D0

6 N.C.

7 N.C.

8 Common

N.C.: not connected

11-Jun-2024 17
Product datasheet TM221C24R

Performance Curves

Derating Curves

Embedded Digital Inputs (No Cartridge)

X: Ambient temperature

Y: Input simultaneous ON ratio

Embedded Digital Inputs (with Cartridge)

X: Ambient temperature

Y: Input simultaneous ON ratio

18 11-Jun-2024