Project: ETAP Page: 1

19.0.1C
Location: Date: 10-10-2024
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: LINE HUB Config.: Normal

Momentary Duty Summary Report

3-Phase Fault Currents: (Prefault Voltage = 100 % of the Bus Nominal Voltage)

Momentary Device
Bus Device Duty Capability
Symm. X/R Asymm. Asymm. Symm. Asymm. Asymm.
ID kV ID Type kA rms Ratio M.F. kA rms kA Peak kA rms kA rms kA Peak

Bus_AC-1B 0.400 Bus_AC-1B Bus 3.121 0.7 1.000 3.121 4.452

Bus_AC-2B 0.400 Bus_AC-2B Bus 3.048 0.7 1.000 3.049 4.375

Bus_AC-5B 0.400 Bus_AC-5B Bus 3.015 0.5 1.000 3.015 4.278

Bus_AC-6B 0.400 Bus_AC-6B Bus 3.389 0.5 1.000 3.389 4.808

Bus_AC-EXE 0.400 Bus_AC-EXE Bus 1.098 0.2 1.000 1.098 1.552

Bus_AC-LOC 0.400 Bus_AC-LOC Bus 2.886 0.6 1.000 2.886 4.099

Bus_BOOSTER 0.400 Bus_BOOSTER Bus 1.171 0.3 1.000 1.171 1.657

Bus_DB - GU 0.400 Bus_DB - GU Bus 0.565 0.1 1.000 0.565 0.800

Bus_DB- GU 0.400 Bus_DB- GU Bus 0.559 0.1 1.000 0.559 0.790

Bus_DB-CL-EXE 0.400 Bus_DB-CL-EXE Bus 1.930 0.4 1.000 1.930 2.732

Bus_DB-GU 0.400 Bus_DB-GU Bus 0.785 0.1 1.000 0.785 1.110

Bus_DB-STO 0.400 Bus_DB-STO Bus 1.050 0.2 1.000 1.050 1.485

Bus_GEN1 0.400 Bus_GEN1 Bus 11.895 13.4 1.500 17.844 30.124

Bus_JOCKEY 0.400 Bus_JOCKEY Bus 0.521 0.1 1.000 0.521 0.737

Bus_LP-1B 0.400 Bus_LP-1B Bus 2.662 0.5 1.000 2.662 3.774

Bus_LP-2B 0.400 Bus_LP-2B Bus 2.620 0.6 1.000 2.620 3.725

Bus_LP-5B 0.400 Bus_LP-5B Bus 2.570 0.4 1.000 2.570 3.637

Bus_LP-6B 0.400 Bus_LP-6B Bus 2.834 0.4 1.000 2.834 4.012

Bus_LP-EXE 0.400 Bus_LP-EXE Bus 0.863 0.2 1.000 0.863 1.221

Bus_LP-LOC 0.400 Bus_LP-LOC Bus 1.235 0.2 1.000 1.235 1.746

Bus_MCC-1B 0.400 Bus_MCC-1B Bus 3.751 1.1 1.003 3.761 5.578

Bus_MCC-2B 0.400 Bus_MCC-2B Bus 3.612 1.2 1.005 3.630 5.471

Bus_MCC-5B 0.400 Bus_MCC-5B Bus 3.659 0.9 1.001 3.662 5.313

Bus_MCC-6B 0.400 Bus_MCC-6B Bus 4.195 0.9 1.001 4.199 6.117

Bus_MCC-EXE 0.400 Bus_MCC-EXE Bus 3.009 0.8 1.000 3.011 4.342

Bus_MCC-LOC 0.400 Bus_MCC-LOC Bus 3.233 0.7 1.000 3.233 4.631

Bus_PP-1B 0.400 Bus_PP-1B Bus 4.177 1.1 1.004 4.192 6.263

Bus_PP-2B 0.400 Bus_PP-2B Bus 3.981 1.3 1.007 4.009 6.102

Bus_PP-5B 0.400 Bus_PP-5B Bus 4.089 0.9 1.001 4.092 5.950

Bus_PP-6B 0.400 Bus_PP-6B Bus 4.787 1.0 1.001 4.793 7.019

Bus_PP-EXE 0.400 Bus_PP-EXE Bus 2.116 0.5 1.000 2.116 2.995

Bus_PP-LOC 0.400 Bus_PP-LOC Bus 2.128 0.4 1.000 2.128 3.012


Project: ETAP Page: 2
19.0.1C
Location: Date: 10-10-2024
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: LINE HUB Config.: Normal

3-Phase Fault Currents: (Prefault Voltage = 100 % of the Bus Nominal Voltage)

Momentary Device
Bus Device Duty Capability
Symm. X/R Asymm. Asymm. Symm. Asymm. Asymm.
ID kV ID Type kA rms Ratio M.F. kA rms kA Peak kA rms kA rms kA Peak

EMDB-PH01 0.400 EMDB-PH01 Bus 11.780 9.4 1.423 16.765 28.589

MDB-01 0.400 MDB-01 Bus 11.667 8.2 1.388 16.195 27.732

SMDB - 1B 0.400 SMDB - 1B Bus 4.528 1.3 1.008 4.564 6.972

SMDB - 2B 0.400 SMDB - 2B Bus 4.278 1.5 1.014 4.339 6.773

SMDB - 5B 0.400 SMDB - 5B Bus 4.461 1.0 1.002 4.470 6.586

SMDB - 6B 0.400 SMDB - 6B Bus 5.289 1.1 1.004 5.308 7.925

SMDB - EXE 0.400 SMDB - EXE Bus 3.951 1.0 1.002 3.961 5.867

SMDB - LOC 0.400 SMDB - LOC Bus 3.564 0.8 1.000 3.565 5.130

- Method: IEEE - X/R is calculated from separate R & X networks.


- Generator protective device duty is calculated based on maximum through fault current. Other protective device duty is calculated based on total fault current.

- The multiplication factors for high voltage circuit-breaker and high voltage bus momentary duty (asymmetrical and crest values) are calculated based on system X/R.

* Indicates a device with momentary duty exceeding the device capability.


Project: ETAP Page: 3
19.0.1C
Location: Date: 10-10-2024
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: LINE HUB Config.: Normal

Interrupting Duty Summary Report

3-Phase Fault Currents: (Prefault Voltage = 100 % of the Bus Nominal Voltage)

Bus Device Interrupting Duty Device Capability

CPT Symm. X/R Adj. Sym. Test Rated Adjusted


ID kV ID Type (Cy) kA rms Ratio M.F. kA rms kV PF Int. Int.

Bus_AC-1B 0.400 3.121 0.7

Bus_AC-2B 0.400 3.048 0.7

Bus_AC-5B 0.400 3.015 0.5

Bus_AC-6B 0.400 3.389 0.5

Bus_AC-EXE 0.400 1.098 0.2

Bus_AC-LOC 0.400 2.886 0.6

Bus_BOOSTER 0.400 1.171 0.3

Bus_DB - GU 0.400 0.565 0.1

Bus_DB- GU 0.400 0.559 0.1

Bus_DB-CL-EXE 0.400 1.930 0.4

Bus_DB-GU 0.400 0.785 0.1

Bus_DB-STO 0.400 1.050 0.2

Bus_GEN1 0.400 11.895 13.4

Bus_JOCKEY 0.400 0.521 0.1

Bus_LP-1B 0.400 2.662 0.5

Bus_LP-2B 0.400 2.620 0.6

Bus_LP-5B 0.400 2.570 0.4

Bus_LP-6B 0.400 2.834 0.4

Bus_LP-EXE 0.400 0.863 0.2

Bus_LP-LOC 0.400 1.235 0.2

Bus_MCC-1B 0.400 3.751 1.1

Bus_MCC-2B 0.400 3.612 1.2

Bus_MCC-5B 0.400 3.659 0.9

Bus_MCC-6B 0.400 4.195 0.9

Bus_MCC-EXE 0.400 3.009 0.8

Bus_MCC-LOC 0.400 3.233 0.7

Bus_PP-1B 0.400 4.177 1.1

Bus_PP-2B 0.400 3.981 1.3

Bus_PP-5B 0.400 4.089 0.9

Bus_PP-6B 0.400 4.787 1.0

Bus_PP-EXE 0.400 2.116 0.5

Bus_PP-LOC 0.400 2.128 0.4


Project: ETAP Page: 4
19.0.1C
Location: Date: 10-10-2024
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: LINE HUB Config.: Normal

3-Phase Fault Currents: (Prefault Voltage = 100 % of the Bus Nominal Voltage)

Bus Device Interrupting Duty Device Capability

CPT Symm. X/R Adj. Sym. Test Rated Adjusted


ID kV ID Type (Cy) kA rms Ratio M.F. kA rms kV PF Int. Int.

EMDB-PH01 0.400 11.780 9.4

MDB-01 0.400 11.667 8.2

SMDB - 1B 0.400 4.528 1.3

SMDB - 2B 0.400 4.278 1.5

SMDB - 5B 0.400 4.461 1.0

SMDB - 6B 0.400 5.289 1.1

SMDB - EXE 0.400 3.951 1.0

SMDB - LOC 0.400 3.564 0.8

- Method: IEEE - X/R is calculated from separate R & X networks.


- HV CB interrupting capability is adjusted based on bus nominal voltage.
- Short-circuit multiplying factor for LV Molded Case and Insulated Case Circuit Breakers is calculated based on asymmetrical current.
- Generator protective device duty is calculated based on maximum through fault current. Other protective device duty is calculated based on total fault current.

* Indicates a device with interrupting duty exceeding the device capability


** Indicates that the circuit breaker has been flagged as a generator circuit breaker. However, ETAP could not detect a single path, without a transformer, to the specified generator.
Therefore, this circuit breaker is treated as a regular circuit breaker in short-circuit calculations.
+ The prefault voltage exceeds the rated maximum kV limit of the circuit breaker - The rated interrupting kA must be derated.