T 372 PrimeLINE and PrimeLINE ONE Units. Operation and Service Manual. Models 69NT40 571 000 To 199 575 000 To 199
T 372 PrimeLINE and PrimeLINE ONE Units. Operation and Service Manual. Models 69NT40 571 000 To 199 575 000 To 199
T-372 Rev B
OPERATIONS AND SERVICE
MANUAL
For
PrimeLINE
69NT40-571-000 to 199
PrimeLINE ONE
69NT40-575-000 to 199
i T-372
3.1.4 Compressor Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–3
3.1.5 Air-Cooled Condenser Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–3
3.1.6 Water-Cooled Condenser Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–5
3.1.7 Control Box Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–6
3.2 REFRIGERATION SYSTEM DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–7
3.3 ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–7
3.4 SAFETY AND PROTECTIVE DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–9
3.5 REFRIGERATION CIRCUIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–10
3.5.1 Standard Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–10
3.5.2 Economized Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–10
3.5.3 Electronic Expansion Valve (EEV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–10
MICROPROCESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–1
4.1 TEMPERATURE CONTROL MICROPROCESSOR SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–1
4.1.1 Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–1
4.1.2 Display Module and Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–1
4.2 CONTROLLER SOFTWARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–3
4.2.1 Configuration Software (CnF Variables) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–3
4.2.2 Operational Software (Cd Function Codes) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–3
4.3 MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–3
4.3.1 Start Up - Compressor Phase Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–3
4.3.2 Start Up - Compressor Bump Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–4
4.3.3 Perishable Mode (Temperature Control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–4
4.3.4 Perishable Pulldown Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–4
4.3.5 Perishable Steady State Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–4
4.3.6 Perishable Idle Mode (Air Circulation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–4
4.3.7 Perishable Heating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–4
4.3.8 Perishable Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–5
4.3.9 Perishable Dehumidification - Bulb Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–6
4.3.10 Perishable Economy Fan Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–6
4.3.11 Perishable Mode Cooling - Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–7
4.3.12 Perishable Mode Heating - Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–8
4.3.13 Perishable Mode - Trim Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–8
4.3.14 Frozen Mode (Temperature Control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–8
4.3.15 Frozen Steady State Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–8
4.3.16 Frozen Idle Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–9
4.3.17 Frozen “Heat” Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–9
4.3.18 Frozen Economy Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–9
4.3.19 Frozen Mode Cooling - Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–9
4.3.20 Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–10
4.3.21 Defrost Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–10
4.3.22 Defrost Related Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–12
4.3.23 Protection Mode - Evaporator Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–12
4.3.24 Protection Mode - Failure Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–12
4.3.25 Protection Mode - Generator Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–12
4.3.26 Protection Mode - Compressor High Temperature Protection . . . . . . . . . . . . . . . . . . . . . . 4–12
4.3.27 Protection Mode - Compressor Low Pressure Protection . . . . . . . . . . . . . . . . . . . . . . . . . . 4–12
4.3.28 Protection Mode - Perishable Mode System Pressure Regulation . . . . . . . . . . . . . . . . . . . 4–12
4.3.29 Protection Mode - Condenser Fan Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–13
T-372 ii
4.3.30 Quest . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–13
4.4 CONTROLLER ALARMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–13
4.5 PRE-TRIP DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–15
4.6 DATACORDER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–15
4.6.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–15
4.6.2 DataCORDER Operational Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–16
4.6.3 DataCORDER Configuration Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–17
4.6.4 Sensor Configuration (dCF02) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–17
4.6.5 Logging Interval (dCF03) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–18
4.6.6 Thermistor Format (dCF04) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–19
4.6.7 Sampling Type (dCF05 & dCF06) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–19
4.6.8 Alarm Configuration (dCF07 - dCF10) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–19
4.6.9 Stored Temperature Display (Scrollback) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–19
4.6.10 DataCORDER Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–19
4.6.11 Pre-Trip Data Recording . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–20
4.6.12 USDA Cold Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–20
4.6.13 USDA Cold Treatment Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–20
4.6.14 ISO Trip Header . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–22
4.6.15 DataCORDER Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–22
4.7 CONTROLLER COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–23
4.7.1 Controller Wired Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–23
4.7.2 Controller Wireless Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–23
4.8 CONTROLLER CONFIGURATION VARIABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–25
4.9 CONTROLLER FUNCTION CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–26
4.10 CONTROLLER ALARM INDICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–37
4.11 CONTROLLER PRE-TRIP TEST CODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–53
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–1
5.1 INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–1
5.2 CONNECT POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–1
5.2.1 Connecting to 380/460 VAC Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–1
5.2.2 Connecting to 190/230 VAC Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–1
5.3 ADJUST FRESH AIR MAKEUP VENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–2
5.3.1 Upper Fresh Air Makeup Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–2
5.3.2 Vent Position Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–3
5.4 EVERFRESH OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–3
5.5 CONNECT WATER-COOLED CONDENSER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–3
5.5.1 Water-Cooled Condenser with Water Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
5.5.2 Water-Cooled Condenser with Condenser Fan Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
5.6 STARTING AND STOPPING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
5.6.1 Starting the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
5.6.2 Stopping the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
5.7 START-UP INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
5.7.1 Physical Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
5.7.2 Check Controller Function Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–4
5.7.3 Start Temperature Recorder in DataCORDER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–5
5.7.4 Complete Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–5
5.8 PRE-TRIP DIAGNOSIS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–5
5.8.1 Starting a Pre-Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–6
iii T-372
5.8.2 Displaying Pre-Trip Test Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–7
5.9 PROBE DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–7
5.10 TRIPWISE (OPTION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–8
5.10.1 Checking TripWise Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–8
5.10.2 Enabling or Disabling TripWise Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–8
5.10.3 TripWise Status Event . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–9
5.11 AUTOMATIC COLD TREATMENT (OPTION) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–11
5.12 AUTOMATIC SETPOINT CHANGE (ASC) CD53 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–13
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–1
6.1 UNIT WILL NOT START OR STARTS THEN STOPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–1
6.2 UNIT OPERATES LONG OR CONTINUOUSLY IN COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . 6–1
6.3 UNIT RUNS BUT HAS INSUFFICIENT COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–2
6.4 UNIT WILL NOT HEAT OR HAS INSUFFICIENT HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–2
6.5 UNIT WILL NOT TERMINATE HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–2
6.6 UNIT WILL NOT DEFROST PROPERLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–2
6.7 ABNORMAL PRESSURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–3
6.8 ABNORMAL NOISE OR VIBRATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–3
6.9 MICROPROCESSOR MALFUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–4
6.10 NO EVAPORATOR AIR FLOW OR RESTRICTED AIR FLOW . . . . . . . . . . . . . . . . . . . . . . . . . . 6–4
6.11 ELECTRONIC EXPANSION VALVE MALFUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–4
6.12 AUTOTRANSFORMER MALFUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–4
6.13 WATER-COOLED CONDENSER OR WATER PRESSURE SWITCH . . . . . . . . . . . . . . . . . . . . . 6–5
6.14 COMPRESSOR OPERATING IN REVERSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–5
6.15 ABNORMAL TEMPERATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–5
6.16 ABNORMAL CURRENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6–5
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–1
7.1 SECTION LAYOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–1
7.2 MANIFOLD GAUGE SET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–1
7.2.1 Evacuating the Manifold Gauge Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–2
7.3 SERVICE CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–2
7.3.1 Connecting the Manifold Gauge Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–3
7.3.2 Removing the Manifold Gauge Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–3
7.4 PUMP DOWN THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–3
7.4.1 Automatic Pump Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–4
7.4.2 Manual Pump Down: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–4
7.5 REFRIGERANT LEAK CHECKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–4
7.6 EVACUATION AND DEHYDRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–5
7.6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–5
7.6.2 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–5
7.6.3 Evacuate and Dehydrate - Complete System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–5
7.6.4 Evacuate and Dehydrate - Partial System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–6
7.7 REFRIGERANT CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–6
7.7.1 Checking the Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–6
7.7.2 Adding Refrigerant to System - Full Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–7
7.7.3 Adding Refrigerant to System - Partial Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–7
7.8 CONVERTING TO R-513A REFRIGERANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–7
7.9 COMPRESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–8
7.9.1 Removal and Replacement of Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–8
7.10 HIGH PRESSURE SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–10
T-372 iv
7.10.1 Checking High Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–10
7.10.2 Replacing High Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–11
7.11 CONDENSER COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–11
7.11.1 Condenser Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–11
7.11.2 Condenser Coil Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–11
7.11.3 Condenser Coil Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–12
7.11.4 Condenser Coil Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–12
7.12 CONDENSER FAN AND FAN MOTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–13
7.12.1 Condenser Fan Motor Remove and Replace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–13
7.13 WATER-COOLED CONDENSER CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–14
7.13.1 Cleaning Supplies Needed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–14
7.13.2 Cleaning Procedure Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–14
7.13.3 Cleaning Procedure Detailed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–15
7.14 FILTER DRIER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–16
7.14.1 Checking the Filter Drier: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–16
7.14.2 Replacing the Filter Drier: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–17
7.15 EVAPORATOR COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–17
7.15.1 Evaporator Coil Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–17
7.16 EVAPORATOR HEATERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–17
7.16.1 Megger Testing the Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–18
7.17 EVAPORATOR FAN AND MOTOR ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–19
7.17.1 Replacing the Evaporator Fan Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–19
7.17.2 Disassemble the Evaporator Fan Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–20
7.17.3 Assemble the Evaporator Fan Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–20
7.18 EVAPORATOR SECTION CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–21
7.18.1 Cleaning Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–21
7.18.2 Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–22
7.19 ELECTRONIC EXPANSION VALVE (EEV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–22
7.19.1 Removing an EEV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–22
7.19.2 Installing an EEV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–22
7.20 HUMIDITY SENSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–23
7.20.1 Checking the Operation of the Humidity Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–23
7.21 ECONOMIZER SOLENOID VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–25
7.21.1 Removing a Solenoid Valve Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–25
7.21.2 Removing the Solenoid Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–25
7.21.3 Installing the Solenoid Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–25
7.21.4 Installing the Solenoid Valve Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–25
7.22 ECONOMIZER EXPANSION VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–26
7.22.1 Removing the Economizer Expansion Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–26
7.22.2 Installing the Economizer Expansion Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–26
7.23 TROUBLESHOOTING P6-7 (DUV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–26
7.24 DIGITAL UNLOADER VALVE (DUV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–27
7.24.1 Removing the DUV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–27
7.24.2 Installing the DUV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–28
7.25 VALVE OVERRIDE CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–28
7.26 AUTOTRANSFORMER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–29
7.27 CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–30
7.27.1 Handling Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–30
v T-372
7.27.2 Controller Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–30
7.27.3 Loading Controller Operational Software from a USB Drive . . . . . . . . . . . . . . . . . . . . . . . . 7–30
7.27.4 Uploading a Software Configuration from a USB Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–31
7.27.5 Downloading DataCORDER Data to a USB Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–31
7.27.6 Setting the Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–31
7.27.7 Setting the Container ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–32
7.27.8 Removing and Installing a Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–33
7.27.9 Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–33
7.28 TEMPERATURE SENSOR SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–34
7.28.1 Ice Bath Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–34
7.28.2 Sensor Checkout Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–35
7.28.3 GDP Supply and Return Sensor Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–37
7.28.4 Sensor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–43
7.28.5 Sensor STS and SRS Reinstallation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–45
7.28.6 Sensor RTS and RRS Reinstallation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–45
7.28.7 Sensor DTS Reinstallation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–46
7.28.8 Sensor ETS1 and ETS2 Reinstallation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–46
7.28.9 Sensor, CPDS Reinstallation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–46
7.29 VENT POSITION SENSOR (VPS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–47
7.30 EVERFRESH SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–47
7.31 MAINTENANCE OF PAINTED SURFACES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–47
ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8–1
EU DECLARATION OF CONFORMITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9–1
WIRELESS CERTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10–1
INDEX .......................................................................... INDEX–1
T-372 vi
LIST OF ILLUSTRATIONS
FIGURE NUMBER Page
vii T-372
Figure 7.14 Humidity Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–24
Figure 7.15 Access Panel Torque Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–24
Figure 7.16 Coil View of Economizer Solenoid Valve (ESV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–25
Figure 7.17 Economizer Expansion Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–26
Figure 7.18 Adapter and O-Ring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–27
Figure 7.19 View of Digital Unloader Valve (DUV) Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–28
Figure 7.20 Autotransformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–29
Figure 7.21 Supply Sensors - Cover Assembly and Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–38
Figure 7.22 Removing Front Access Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–39
Figure 7.23 Removing Evaporator Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–39
Figure 7.24 Return Sensors - Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–39
Figure 7.25 Return Sensors - Cutting Wire Ties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–40
Figure 7.26 DataLINE - Probe Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–40
Figure 7.27 DataLINE - Calibrate Sensors Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–41
Figure 7.28 DataLINE - Enter Service Center Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–41
Figure 7.29 Ice Bath . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–42
Figure 7.30 DataLINE - Start Cal Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–42
Figure 7.31 DataLINE - Calibration Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–43
Figure 7.32 Sensor Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–44
Figure 7.33 Sensor and Cable Splice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–44
Figure 7.34 Supply Sensor Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–45
Figure 7.35 Return Sensor Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–46
Figure 7.36 Evaporator Temperature Sensor Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–46
Figure 7.37 Compressor Discharge Temperature Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7–47
Figure 8.1 Legend - Standard Unit Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8–1
Figure 8.2 Schematic Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8–2
Figure 8.3 Unit Wiring Diagram (Sheet 1 of 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8–3
Figure 8.4 Unit Wiring Diagram (Sheet 2 of 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8–4
T-372 viii
LIST OF TABLES
TABLE NUMBER Page
ix T-372
SECTION 1
SAFETY SUMMARY
1–1 T-372
The statements listed below are applicable to the refrigeration unit and appear elsewhere in this manual. These
recommended precautions must be understood and applied during operation and maintenance of the equipment
covered herein.
! WARNING
EXPLOSION HAZARD: Failure to follow this WARNING can result in death, serious personal injury
and / or property damage. Never use air or gas mixtures containing oxygen (O2) for leak testing or
operating the product. Charge only with refrigerants R-134a or R-513A as specified for the unit
model number: Refrigerant must conform to AHRI Standard 700 specification.
! WARNING
Beware of unannounced starting of the evaporator and condenser fans. The unit may cycle the
fans and compressor unexpectedly as control requirements dictate.
! WARNING
Do not attempt to remove power plug(s) before turning OFF the Start-Stop switch (ST), unit circuit
breaker(s) and external power source.
! WARNING
Make sure the power plugs are clean and dry before connecting to power receptacle.
! WARNING
Make sure that the unit circuit breaker(s) (CB-1 & CB-2) and the Start-Stop switch (ST) are in the
“O” (OFF) position before connecting to any electrical power source.
! WARNING
Make sure power to the unit is OFF and power plug disconnected before replacing the compressor.
! WARNING
Before disassembly of the compressor, be sure to relieve the internal pressure very carefully by
slightly loosening the couplings to break the seal.
! WARNING
Do not use a nitrogen cylinder without a pressure regulator.
! WARNING
Do not open the condenser fan grille before turning power OFF and disconnecting power plug.
! WARNING
Oakite No. 32 is an acid. Be sure that the acid is slowly added to the water. DO NOT PUT WATER
INTO THE ACID - this will cause spattering and excessive heat.
T-372 1–2
! WARNING
Wear rubber gloves and wash the solution from the skin immediately if accidental contact occurs.
Do not allow the solution to splash onto concrete.
! WARNING
Always turn OFF the unit circuit breakers (CB-1 & CB-2) and disconnect main power supply before
working on moving parts.
! WARNING
Installation requires wiring to the main unit circuit breaker, CB-1. Make sure the power to the unit is
off and power plug disconnected before beginning installation.
! CAUTION
When charging the unit with R-513A refrigerant, charge as a liquid only. R-513A is an azeotrope
blend containing R-1234yf and R-134a. Charging or topping off as a vapor will result in an
incorrect mixture of blend in the system.
! CAUTION
Charge water-cooled condenser or receiver according to nameplate specifications to ensure
optimal unit performance.
! CAUTION
Do not remove wire harnesses from controller modules unless you are grounded to the unit
frame with a static safe wrist strap.
! CAUTION
Unplug all controller module wire harness connectors before performing arc welding on any
part of the container.
! CAUTION
Pre-trip inspection should not be performed with critical temperature cargoes in the container.
! CAUTION
When PRE-TRIP key is pressed, economy, dehumidification and bulb mode will be deactivated.
At the completion of pre-trip activity, economy, dehumidification and bulb mode must be
reactivated.
! CAUTION
When a failure occurs during automatic testing, the unit will suspend operation awaiting
operator intervention.
! CAUTION
When Pre-Trip test Auto 2 runs to completion without being interrupted, the unit will terminate
pre-trip and display “Auto 2” “end.” The unit will suspend operation until the user depresses
the ENTER key!
1–3 T-372
! CAUTION
Allowing the scroll compressor to operate in reverse for more than two minutes will result in
internal compressor damage. Turn the Start-Stop switch OFF immediately.
! CAUTION
To prevent trapping liquid refrigerant in the manifold gauge set, make sure set is brought to
suction pressure before disconnecting.
! CAUTION
The scroll compressor achieves low suction pressure very quickly. Do not use the compressor
to evacuate the system below 0 psig. Never operate the compressor with the suction or
discharge service valves closed (front seated). Internal damage will result from operating the
compressor in a deep vacuum.
! CAUTION
The PrimeLINE unit has a hermetically sealed compressor that should not be opened and/or
repaired. Doing so can cause a loss in performance and premature system failure due to the
precision machinery and assembly required within the compressor. To repair the unit, remove
the faulty compressor and replace with an approved Carrier compressor. If the return of the
compressor is not required, follow local waste collection & recycling regulations in discarding
the compressor.
! CAUTION
Take necessary steps (place plywood over coil or use sling on motor) to prevent motor from
falling into condenser coil.
! CAUTION
Do not remove wire harnesses from module unless you are grounded to the unit frame with a
static safe wrist strap.
! CAUTION
Unplug all module connectors before performing arc welding on any part of the container.
! CAUTION
The unit must be OFF whenever a programming card is inserted or removed from the controller
programming port.
! CAUTION
Use care when cutting wire ties to avoid nicking or cutting wires.
! CAUTION
Do not allow moisture to enter wire splice area as this may affect sensor resistance.
T-372 1–4
SECTION 2
INTRODUCTION
2.1 Introduction
The Carrier Transicold PrimeLINE models 69NT40-571-000 to 199 are of lightweight aluminum frame construction,
designed to be bolted onto the front of a container and serve as the container’s front wall. Forklift pockets are
provided for unit installation and removal.
The Carrier Transicold PrimeLINE ONE™ models 69NT40-575-000 to 199 are units of lightweight aluminum frame
construction, designed to be directly installed on-site onto a welded front wall of a container.
Primeline units are self-contained, all electric units, which include cooling and heating systems to provide precise
temperature control. The units are supplied with a complete charge of refrigerant and compressor lubricating oil,
and are ready for operation upon installation.
The base unit operates on nominal 380/460 volt, 3-phase, 50/60 hertz (Hz) power. An optional autotransformer
may be fitted to allow operation on nominal 190/230, 3-phase, 50/60 Hz power. Control system power is provided
by a transformer which steps the supply power down to 18 and 24 volts, single phase.
The controller is a Carrier Transicold Micro-Link 5 microprocessor. The controller operates automatically to select
cooling, holding or heating as required to maintain the desired set point temperature within very close limits. The
unit may also be equipped with an electronic temperature recorder. The controller has a keypad and display for
viewing or changing operating parameters. The display is also equipped with lights to indicate various modes of
operation.
2.2 Refrigerant
PrimeLINE models 69NT40-571-000 to 099 and PrimeLINE ONE™ models 69NT40-575-000 to 099 are units
designed to only be charged with R-134a refrigerant.
PrimeLINE models 69NT40-571-100 to 199 and PrimeLINE ONE™ models 69NT40-575-100 to 199 are R-513A-
ready units. They are supplied with a complete charge of R-134a refrigerant. But, they are capable of being field
converted to R-513A refrigerant at a later date as requested by the unit owner. R-513A is an azeotrope blend
containing R-1234yf and R-134a. All information in this manual pertaining to R-513A is only applicable to 571-100
to 199 units or 575-100 to 199 units that have either been converted or are being converted to R-513A.
To convert a R-513A-ready unit to R-513A refrigerant, refer to procedure in Service Section 7.8.
2–1 T-372
2.4.4 Compressor
The unit is fitted with either an R-134a or an R-513A-ready scroll compressor equipped with suction and discharge
service connections. To identify an R-513A-ready compressor in the field, a green dot is located on the top of the
compressor on the DUV fitting.
2.4.6 Evaporator
The evaporator section is equipped with an electronic expansion valve (EEV).
2.5.1 Battery
The refrigeration controller may be fitted with standard replaceable batteries or a rechargeable battery pack.
Carrier-provided rechargeable batteries can be recharged via the ML5 controller and allow for wireless
communication in battery mode. A non-carrier rechargeable 3-wire battery would charge but the controller will not
monitor anything related to it. A standard 2-wire NiCAD battery would not charge.
NOTE
If ambient temperature is greater than 45 deg C, the carrier-provided rechargeable batteries will not
charge.
2.5.2 Dehumidification
The unit may be fitted with a humidity sensor. This sensor allows setting of a humidity set point in the controller. In
dehumidification mode, the controller will operate to reduce internal container moisture level.
2.5.3 USDA
The unit may be supplied with fittings for additional temperature probes, which allow recording of USDA Cold
Treatment data by the integral DataCORDER function of the Micro-Link refrigeration controller.
NOTE
The Micro-Link 5 controller has a USB micro port and wireless capability to allow viewing of
DataCORDER data.
2.5.5 Quest
Quest (Quality and Energy Efficiency in Storage and Transport) power saving mode helps shipping lines lower their
operating costs by decreasing the system’s run time, energy usage and emissions. Quest is a method of
temperature control used during steady-state perishable cooling that cycles the compressor on and off according to
supply / return air temperature conditions.
T-372 2–2
2.5.6 Autotransformer
An autotransformer may be provided to allow operation on 190/230, 3-phase, 50/60 Hz power. The
autotransformer raises the supply voltage to the nominal 380/460 volt power required by the base unit. The
autotransformer may also be fitted with an individual circuit breaker for the 230 volt power.
2.5.7 Handles
The unit may be equipped with handles to facilitate access to stacked containers. These fixed handles are located
on either side of the unit.
2.5.14 Labels
Safety Instruction and Function Code listing labels differ depending on the options installed. Labels available with
additional languages are listed in the parts list.
2.5.15 Controller
The controller is a Carrier Transicold Micro-Link 5 microprocessor. Refer to Section 4.1 for more information.
Controllers will be factory-equipped with the latest version of operational software, but will NOT be configured for a
specific model number and will need to be configured at the time of installation or sale.
Two replacement controllers are available:
1. Re-manufactured - Controller is equivalent of a new OEM controller, supplied with a 12-month warranty.
2. Repaired - Controller has had previous faults repaired and is upgraded with the latest software.
NOTE
Repaired controllers are NOT to be used for warranty repairs; only full OEM Re-manufactured
controllers are to be used.
2–3 T-372
2.5.17 EverFRESH
EverFRESH™ is a controlled atmosphere option that is able control container atmosphere by supplying nitrogen
and oxygen into the container space and simultaneously controlling levels of oxygen and carbon dioxide. This
extends the produce ripening process, which increases shelf life and enables longer cargo routes for certain
perishable commodities.
Procedures and technical information related to the EverFRESH controlled atmosphere system can be found in the
T-374 EverFRESH Manual, located in the Literature section of the Container Refrigeration website. To find the
manual from the Literature section, click on Options > EverFRESH.
2.5.18 TripWise
TripWise™ is a new premium option available for PrimeLINE units. TripWise is software logic that runs in the
background during every voyage and will let you know whenever a standard pre-trip inspection (PTI) is needed.
See Section 5.10 for more detail.
2.5.19 FuelWise
FuelWise™ is a power-saving option available for PrimeLINE units. FuelWise software works by dynamically
cycling the refrigeration system on and off to save energy while still maintaining temperature within +/- 0.25
degrees Celsius of setpoint on an hourly average.
T-372 2–4
SECTION 3
DESCRIPTION
1 2
3 3
4
16
7
15
8
14 13 12 11 10 9
3–1 T-372
3.1.2 Fresh Air Makeup Vent
The function of the upper fresh air makeup vent is to provide ventilation for commodities that require fresh air
circulation. A manually operated venting system is located in the upper left access panel.
4
10 1
15
3
14
13
12
11
1 8 7 4
T-372 3–2
3.1.4 Compressor Section
The compressor section (see Figure 3.3) includes the compressor, digital unloader valve (DUV), high pressure
switch, discharge pressure transducer (DPT), evaporator pressure transducer (EPT) and the suction pressure
transducer (SPT). The supply temperature sensor (STS) and supply recorder sensor (SRS) are located to the left
of the compressor.
8
11
10
9
16
12
13
2 3 4
7
14
6
1
15
1) Compressor 9)
Digital Unloader Valve (DUV)
2) Compressor Discharge Temperature Sensor 10)
Suction Pressure Transducer (SPT)
(CPDS) location 11)
Evaporator Pressure Transducer (EPT)
3) Discharge Connection 12)
High Pressure Switch (HPS)
4) Suction Connection location 13)
Discharge Service Valve
5) Compressor Terminal Box 14)
Suction Service Valve
6) Oil Drain location 15)
Supply Temperature Sensor (STS), Supply
7) Economizer Connection Recorder Sensor (SRS)
8) Discharge Pressure Transducer (DPT) 16) Warning Label
-----
The air-cooled condenser section (see Figure 3.4) consists of the condenser fan, condenser coil, receiver, liquid
line service valve, filter drier, fusible plug, economizer, economizer expansion valve (EEV), economizer solenoid
valve (ESV), and sight glass / moisture indicator. The condenser fan pulls air from around the coil and discharges it
horizontally through the condenser fan grille.
3–3 T-372
Figure 3.4 Air Cooled Condenser Section
2
1
9
8
10
11
12
14 13
1) Micro Channel Heat Exchanger (MCHE) Coil 8) Receiver Moisture & Liquid Indicator*
2) Grille and Venturi Assembly 9) Fusible Plug
3) Condenser Fan 10) Filter Drier
4) Condenser Coil Cover 11) Economizer
5) Condenser Fan Motor 12) Economizer Solenoid Valve (ESV)
6) Receiver 13) Economizer Expansion Valve (EXV)
7) Receiver Sight Glass* 14) Service Access Valve
-----
* Not visible in view, located behind Filter Drier.
T-372 3–4
3.1.6 Water-Cooled Condenser Section
The unit may contain a water-cooled condenser (WCC) installed as an option. When operating on the water-cooled
condenser, the condenser fan is deactivated by a water pressure switch or condenser fan switch.
Brazed Plate Water-Cooled Condenser
The brazed plate water-cooled condenser section (see Figure 3.5) consists of the brazed plate water-cooled
condenser, water couplings, a water pressure switch and a fusible plug. The receiver is retained in this
configuration and the brazed plate heat exchanger is placed between the air-cooled condenser and the receiver.
3
2
3–5 T-372
3.1.7 Control Box Section
The control box (see Figure 3.6) includes: the manual operation switches, circuit breaker (CB-1), compressor, fan
and heater contactors, control power transformer, transformer AC line filter, fuses, keypad, display module, current
sensor module, and the controller module.
1 2 3 4
14
13
8
12
9 6 7 10
11
T-372 3–6
3.2 Refrigeration System Data
! WARNING
EXPLOSION HAZARD: Failure to follow this WARNING can result in death, serious personal
injury and / or property damage. Never use air or gas mixtures containing oxygen (O2) for leak
testing or operating the product. Charge only with refrigerants R-134a or R-513A as specified
for the unit model number: Refrigerant must conform to AHRI Standard 700 specification.
Refrigerant R-134a / R-513A Conforming to AHRI standard 700 specifications.
! CAUTION
Charge water-cooled condenser or receiver according to nameplate specifications to ensure
optimal unit performance.
Refrigerant Charge WCC Brazed Plate 4.58 kg (10.1 lbs)
Receiver 4.26 kg (9.4 lbs)
Fusible Plug Melting point 99°C = (210°F)
Torque 6.2 to 6.9 mkg (45 to 50 ft-lbs)
Unit Weight Refer to unit model number plate.
Water Pressure Switch Cut-In 0.5 +/- 0.2 kg/cm2 (7 +/- 3 psig)
Cut-Out 1.6 +/- 0.4 kg/cm2 (22 +/- 5 psig)
3–7 T-372
Table 3–2 Electrical Data (Continued)
Condenser Fan Motor Nominal Supply 380 VAC / 3 Phase / 50 Hz 460 VAC / 3 Phase / 60 Hz
Full Load Amps .71 amps .72 amps
Horsepower 0.21 hp 0.36 hp
Rotations Per Minute 1450 rpm 1750 rpm
Voltage and Frequency 360 - 460 VAC +/- 2.5 Hz 400 - 500 VAC +/- 2.5 Hz
Bearing Lubrication Factory lubricated, additional grease not required.
Rotation Counter-clockwise when viewed from shaft end.
Evaporator Coil Heaters Number of Heaters 6
Rating 750 watts +5/-10% each @ 230 VAC
Resistance (cold) 66.8 to 77.2 ohms @ 20°C (68°F)
Type Sheath
Evaporator Fan Motor(s) 380 VAC / 3 Phase / 50 Hz 460 VAC / 3 Phase / 60 Hz
Full Load Amps 1.07 .9
High Speed
Full Load Amps 0.47 0.47
Low Speed
Nominal Horsepower 0.36 0.63
High Speed
Nominal Horsepower 0.05 0.8
Low Speed
Rotations Per Minute 2850 rpm 3450 rpm
High Speed
Rotations Per Minute 1425 rpm 1725 rpm
Low Speed
Voltage and Frequency 360 - 460 VAC +/- 1.25 Hz 400 - 500 VAC +/- 1.5 Hz
Bearing Lubrication Factory lubricated, additional grease not required
Rotation CW when viewed from shaft end
Fuses Control Circuit 7.5 amps (F3, F4)
Controller / DataCORDER 7.5 amps (F1, F2)
Vent Positioning Sensor Electrical Output 0.5 VDC to 4.5 VDC over 90 degree range
Supply Voltage 5 VDC +/- 10%
Supply Current 5 mA (typical)
Solenoid Valve Coils Nominal Resistance @ 7.7 ohms +/- 5%
(ESV) 24 VAC 77°F (25°C)
Maximum Current Draw 0.7 amps
DUV Coils 12 VDC Nominal Resistance @ 14.8 ohms +/- 5%
77°F (20°C)
Maximum Current Draw 929 mA
EEV Nominal Resistance Coil Feed to Ground 47 ohms
(Gray Wire)
Coil Feed to Coil Feed 95 ohms
T-372 3–8
Table 3–2 Electrical Data (Continued)
Humidity Sensor Orange wire Power
Red wire Output
Brown wire Ground
Input voltage 5 VDC
Output voltage 0 to 3.3 VDC
Output voltage readings verses relative humidity (RH) percentage:
30% 0.99 V
50% 1.65 V
70% 2.31 V
90% 2.97 V
Controller Setpoint Range -35 to +30°C (-31 to +86°F)
3–9 T-372
3.5 Refrigeration Circuit
3.5.1 Standard Operation
Starting at the compressor, (see Figure 3.7) the suction gas is compressed to a higher pressure and temperature.
The refrigerant gas flows through the discharge line and continues into the air-cooled condenser. When operating
with the air-cooled condenser active, air flowing across the coil fins and tubes cools the gas to saturation
temperature. By removing latent heat, the gas condenses to a high pressure/high temperature liquid and flows to
the receiver, which stores the additional charge necessary for low temperature operation.
When operating with the water-cooled condenser active (see Figure 3.9), the refrigerant gas passes through the
air-cooled condenser and enters the water-cooled condenser shell. The water flowing inside the tubing cools the
gas to saturation temperature in the same manner as the air passing over the air-cooled condenser. The refrigerant
condenses on the outside of the tubes and exits as a high temperature liquid. The water-cooled condenser also
acts as a receiver, storing refrigerant for low temperature operation.
The liquid refrigerant continues through the liquid line, the filter drier (which keeps refrigerant clean and dry) and
the economizer (not active during standard operation) to the electronic expansion valve (EEV).
As the liquid refrigerant passes through the variable orifice of the EEV, the pressure drops to suction pressure. In
this process some of the liquid vaporizes to a gas (flash gas), removing heat from the remaining liquid. The liquid
exits as a low pressure, low temperature, saturated mix. Heat is then absorbed from the return air by the balance of
the liquid, causing it to vaporize in the evaporator coil. The vapor then flows through the suction tube back to the
compressor.
On systems fitted with a water pressure switch, the condenser fan will be off when there is sufficient pressure to
open the switch. If water pressure drops below the switch cut out setting, the condenser fan will automatically start.
During the standard mode of operation, the normally closed digital unloader valve (DUV) controls the system
refrigerant flow and capacity by loading and unloading the compressor in frequent discrete time intervals. If the
system capacity has been decreased to the lowest allowable capacity with the DUV, the unit will enter a trim heat
mode of operation, during which the controller will pulse the evaporator heaters in sequence with the compressor
digital signal in order to absorb the excess capacity.
T-372 3–10
Figure 3.7 Refrigeration Circuit Schematic - Standard Operation
18
19
16
17
3
7
5
10 20
4 6
8 9
14
11
21
1
12
22
15
13
23
3–11 T-372
Figure 3.8 Refrigeration Circuit Schematic - Economized Operation
18
19
17 16
3
7
5
10 20
4 6
8 9
14
11
21
12 1
22
15
13
23
T-372 3–12
Figure 3.9 Refrigeration Circuit Schematic - Water-Cooled Condenser (Brazed Plate)
22
23
21 20
3
9 11
14
4 24
10 12 2
13
18
15 25
1
16
5
26
7 19
17
27
8
6
3–13 T-372
SECTION 4
MICROPROCESSOR
2 3 4 5
! CAUTION
Do not remove wire harnesses from circuit boards unless you are grounded to the unit frame
with a static safe wrist strap or equivalent static drain device.
! CAUTION
Remove the controller module and unplug all connectors before performing any arc welding
on any part of the container.
! CAUTION
When disconnecting connectors from the controller, press the latch tab prior to pulling out the
connector. Damage may occur if latch tab is not pressed in prior to removing the connector.
NOTE
Do not attempt to service the controller modules. Breaking the seal will void the warranty.
4–1 T-372
The display module (see Figure 4.2) consists of two 5-digit displays and seven indicator lights. Descriptions of the
indicator lights are provided in Table 4–1. The keypad (see Figure 4.3) consists of eleven push button switches
that act as the user’s interface with the controller. Descriptions of the switch functions are provided in Table 4–2.
CODE PRE
SELECT TRIP
MANUAL
ALARM
DEFROST/
LIST
INTERVAL
ENTER
RETURN C
SUPPLY F
BATTERY ALT
POWER MODE
T-372 4–2
4.2 Controller Software
The controller software is a custom designed program that is subdivided into configuration software and opera-
tional software. The controller software performs the following functions:
• Control supply or return air temperature to required limits, provide modulated refrigeration operation, econo-
mized operation, unloaded operation, electric heat control, and defrost. Defrost is performed to clear buildup
of frost and ice to ensure proper air flow across the evaporator coil.
• Provide default independent readouts of setpoint and supply or return air temperatures.
• Provide ability to read and (if applicable) modify the configuration software variables, operating software
function codes and alarm code indications.
• Provide a pre-trip step-by-step checkout of refrigeration unit performance including: proper component oper-
ation, electronic and refrigeration control operation, heater operation, probe calibration, pressure limiting and
current limiting settings.
• Provide battery-powered ability to access or change selected codes and setpoint without AC power con-
nected. This is only if the carrier-provided rechargeable battery option is installed.
4–3 T-372
4.3.2 Start Up - Compressor Bump Start
At start up, the controller logic will initiate a compressor bump start procedure to clear liquid refrigerant from the
compressor. If suction and discharge pressures have equalized, the compressor will perform three compressor
bump starts. A compressor bump start may also occur after a defrost cycle has been completed.
During bump start, the electronic expansion valve (EEV) will close. Relays TS, TN, TE, and TV will be de-ener-
gized (opened). The result of this action will close the economizer solenoid valve (ESV) and shut all fans off. The
compressor will start for 1 second, then pause for five seconds. This sequence will be repeated two more times.
After the final bump start, the unit will pre-position the EEV to the correct starting position, pause and then start up.
T-372 4–4
Figure 4.4 Controller Operation - Perishable Mode
+2.5qC
(+4.5qF)
Cooling, Cooling,
Unloaded Enconomized
Set +0.20qC
Point Set
Cooling, Point
-0.20qC Air Circulation -0.25qC Unloaded
-0.20qC -0.20qC
-0.50qC AirCirculation
Air Circulation
-0.50qC
Heating
Heating
Falling Rising
Temperature Temperature
If the above conditions are true for at least one hour, the evaporator fans will switch from high speed to low speed.
Evaporator fan speed will then switch every hour, as long as the four conditions are met (see Bulb mode, Section
4.3.9 for different evaporator fan speed options).
If any condition except item (1) becomes false OR if the relative humidity sensed is 2% below the dehumidification
setpoint, the high speed evaporator fans will be energized.
During dehumidification, power is applied to the defrost heaters. This added heat load causes the controller to
open the electronic expansion valve (EEV) to match the increased heat load while still holding the supply air tem-
perature very close to the setpoint. Opening the EEV reduces the temperature of the evaporator coil surface, which
increases the rate at which water is condensed and removes water from the passing air. Removing water from the
air reduces the relative humidity. When the relative humidity sensed is 2% below setpoint, the controller de-ener-
gizes the heat relay. The controller will continue to cycle heating to maintain relative humidity below the selected
setpoint. If dehumidification is terminated by a condition other than the humidity sensor, e.g., an out-of-range or
compressor shutdown condition, the heat relay is de-energized immediately.
4–5 T-372
Two timers are activated during dehumidification to prevent rapid cycling and consequent contactor wear:
1. Heater debounce timer (three minutes) - The heater debounce timer is started whenever the heater contac-
tor status is changed. The heater contactor remains energized (or de-energized) for at least three minutes
even if the setpoint criteria are satisfied.
2. Out-of-range timer (five minutes) - The out-of-range timer is started to maintain heater operation during a
temporary out-of-range condition. If supply air temperature remains outside of the user selected in-range
setting for more than five minutes, the heaters will be de-energized to allow the system to recover. The out-
of-range timer starts as soon as temperature exceeds in-range tolerance value set by Cd30.
a. At the start of each cooling or heating cycle, the evaporator fans will run in high speed for three minutes.
b. The fans are then switched to low speed any time the supply air temperature is within +/- 0.2°C (0.36°F) of
the setpoint and the return air temperature is less than or equal to the supply air temperature + 3°C (5.4°F).
c. The fans will continue to run in low speed for one hour.
d. At the end of the hour, the fans will switch back to high speed and the cycle will be repeated. If Bulb Mode is
active, Economy Fan Mode will be overridden.
T-372 4–6
4.3.11 Perishable Mode Cooling - Sequence of Operation
NOTE
In Standard Perishable Mode, the evaporator motors run in high speed. In Economy Fan Mode, the
fan speed is varied.
a. When supply air temperature is above setpoint and decreasing, the unit will cool with the condenser fan
motor (CF), compressor motor (CH), and evaporator fan motors (EF) energized, and the white COOL light
illuminated. (See Figure 4.5). Also, if current or pressure limiting is not active, the controller will close con-
tacts TS to open the economizer solenoid valve (ESV) and place the unit in economized operation.
ENERGIZED
DE-ENERGIZED
ST
F 24 VOLT POWER
HPS TC CH
IP-CM TN CF
TV EF ES
IP-EM1 IP-EM2 TE EF
HTT TH HR
TS ESV
b. When supply air temperature decreases to a predetermined tolerance above setpoint (Cd30), the green IN
RANGE light is illuminated.
c. As air temperature continues to fall, unloaded cooling starts (DUV pulses opens) as the supply air tempera-
ture approaches setpoint. (See Figure 4.4).
d. When unloaded cooling starts, EEV control will transition from a full cool superheat setpoint to a lower mod-
ulated cool superheat setpoint. Once unloading starts, the EEV controls evaporator superheat based on the
system duty cycle where instantaneous superheat will vary.
e. When the supply air temperature has fallen to within 1.9°C (3.4°F) of setpoint temperature and the average
capacity of the system has fallen below 70%, the unit will open contacts TS to close the ESV and take the
unit out of economized operation.
f. The controller continuously monitors supply air temperature. Once the supply air temperature falls below
setpoint, the controller periodically records supply air temperature, setpoint and time. A calculation is then
performed to determine temperature drift from setpoint over time. If the calculation determines that cooling
is no longer required, contacts TC and TN are opened to de-energize the compressor motor and the con-
denser fan motor. In addition the controller will close the EEV.
g. The evaporator fan motors continue to run to circulate air throughout the container. The green IN RANGE
light remains illuminated as long as the supply air temperature is within tolerance of the setpoint.
h. If the supply air temperature increases to 1.0°C (1.8°F) above setpoint and three minutes have elapsed,
contacts TC and TN close to restart the compressor and condenser fan motors in standard mode (non-
economized) operation. The white COOL light is also illuminated.
i. If the average system capacity has risen to 100% during unloaded cooling and three minutes off time has
elapsed, relay TS will energize to open the ESV, placing the unit in economized mode.
j. If the supply air increases more than 2.5°C (4.5°F) above setpoint temperature, the microprocessor will transi-
tion the evaporator superheat control from modulation back to full cool control.
4–7 T-372
4.3.12 Perishable Mode Heating - Sequence of Operation
a. If the supply air temperature decreases 0.5°C (0.9°F) below setpoint, the system enters the Heating Mode
(see Figure 4.4). The controller closes contacts TH (see Figure 4.6) to allow power flow through the heat
termination thermostat (HTT) to energize the heaters (HR). The orange HEAT light is also illuminated. The
evaporator fans continue to run to circulate air throughout the container.
b. When the supply air temperature rises to 0.2°C (0.4°F) below setpoint, contact TH opens to de-energize the
heaters. The orange HEAT light is also de-energized. The evaporator fans continue to run to circulate air
throughout the container.
c. The safety HTT is attached to an evaporator coil circuit and will open the heating circuit if overheating
occurs.
ENERGIZED
DE-ENERGIZED
ST
F 24 VOLT POWER
HPS TC CH
IP-CM TN CF
TV EF ES
IP-EM1 IP-EM2 TE EF
HTT TH HR
TS ESV
NOTE
The electronic expansion valve (EEV) and digital unloader valve (DUV) are independently operated by
the microprocessor. For full diagrams and legend, see Section 8.
T-372 4–8
4.3.16 Frozen Idle Mode
When temperature drops to setpoint minus 0.2°C (0.4°F) and the compressor has run for at least five minutes, the
unit will transition to the Frozen Idle Mode. The compressor is turned off and the evaporator fans continue to run to
circulate air throughout the container. If temperature rises above setpoint +0.2°C (0.4°F), the unit will transition back
to the Frozen Steady State Mode.
Frozen Mode
Controller Set Point at or BELOW ï10qC (+14qF),
or ï5qC (+23qF) optionally
+2.5qC
(+4.5qF)
Cooling,
Economized
+.20qC
Set Point
ï.20qC
Air Circulation
Falling Rising
Temperature Temperature
4–9 T-372
c. When the return air temperature decreases to 0.2°C (0.4°F) below setpoint, contacts TC, TS and TN are
opened to de-energize the compressor, economizer solenoid valve and condenser fan motor. The white
COOL light is also de-energized. The electronic expansion valve (EEV) will close.
d. The evaporator fan motors continue to run in low speed to circulate air throughout the container. The green
IN RANGE light remains illuminated as long as the return air is within tolerance of setpoint.
e. If return air temperature drops to 10°C (18°F) or more below setpoint, the evaporator fans switch to high speed.
f. When the return air temperature increases to 0.2°C (0.4°F) above setpoint and three minutes have elapsed,
the EEV opens and contacts TC, TS and TN close to restart the compressor, open the ESV and restart the
condenser fan motor. The white COOL light is illuminated.
Figure 4.8 Frozen Mode
ENERGIZED
DE-ENERGIZED
ST
F 24 VOLT POWER
HPS TC CH
IP-CM TN CF
TV EF ES
IP-EM1 IP-EM2 TE EF
HTT TH HR
TS ESV
NOTE
The EEV and DUV are independently operated by the microprocessor. Complete schematics and leg-
ends are located in Section 8.
4.3.20 Defrost
Defrost is initiated to remove ice buildup from the evaporator coil which can obstruct air flow and reduce the cooling
capacity of the unit. The defrost cycle may consist of up to three distinct operations depending upon the reason for
the defrost or model number configuration. The first is de-icing of the coil, the second is defrost due to a probe
check cycle and the third is a snap freeze process based on the unit model configuration.
• De-icing the coil consists of removing power to the cooling components (compressor, evaporator fans, and con-
denser fan), closing the EEV, and turning on the heaters, which are located below the evaporator coil. During
normal operation, de-icing will continue until temperatures indicate that the ice on the coil has been removed,
proper air flow has been restored, and the unit is ready to control temperature efficiently.
• If defrost was initiated by the probe check logic, then the Probe Check is carried out after the completion of the
defrost cycle. A Probe Check is initiated only when there is an inaccuracy between the controller temperature
sensors.
• Snap Freeze allows the system to cool for a period of time after de-icing, with the evaporator fans turned off and
is only carried out if configured by model number. Snap-Freeze allows for the removal of latent de-icing heat
from the evaporator coils, and freezes any remaining moisture that might otherwise be blown into the container.
For more information on Probe Diagnostics refer to Section 5.9
T-372 4–10
When the defrost mode is in the active state, defrost can be initiated when any one of the following additional con-
ditions become true:
1. Manually: While in the Defrost screen, when the Manual Defrost soft key is selected, if conditions will allow
for a defrost, a manual defrost is initiated. The Defrost Indicator light is lit, and the user is brought back to
the Main / Default screen. If conditions are NOT allowing for a defrost, a pop up message screen appears.
2. Timer: The Defrost Interval Timer reaches the user selectable Interval. The user-selected intervals are 3, 6,
9, 12, 24 Hours, Off, AUTO, or AUTO2; factory default is AUTO. Refer to Defrost Interval setting on the Trip
Settings screen.
a. Automatic defrost starts with an initial defrost at three hours and then adjusts the interval to the next
defrost based on the accumulation of ice on the evaporator coil. Following a start-up or after termination
of defrost, the time will not begin counting down until the DTS reading falls below 10°C (50°F). If the
reading of DTS rises above termination setting any time during the timer count down, the interval is reset
and the countdown starts over. The Auto defrost time is reset to three hours start time after every PTI ini-
tiation or trip start interval.
b. After a new Defrost Interval is selected, the previously selected Interval is used until the next defrost ter-
mination, the next time the DTS contacts are OPEN, or the next time power to the control is interrupted.
If the previous value or the new value is “OFF”, the newly selected value will be used immediately.
3. Probe Check: If defrost is initiated due to Probe Check immediately following the defrost cycle the evapora-
tion fans are started and run for eight minutes to stabilize the temperature throughout the container. A probe
check comparison is carried out at the end of the eight minute period if any sensor is found out of calibration.
At this time its alarm set is no longer used for control/reorder purposes.
4. Probe Check Logic: The logic determines that a Probe Check is necessary based on temperature values
currently reported by the supply and return probes
5. Delta T Logic: If the difference between return and supply air temperature (Delta T) becomes too great indi-
cating possible reduced airflow over the evaporator coil caused by ice buildup requiring a defrost.
a. In Perishable Pull Down - Delta T increases to greater than 12°C, and 90 minutes of compressor run
time have been recorded.
b. In Perishable Steady State - A baseline Delta T is recorded following the first defrost cycle after steady
state conditions are reached, (the unit is cooling, and the evaporator fans and heaters must remain in a
stable state for a period of five minutes). Defrost will be initiated if Delta T increases to greater than 4°C
above the baseline, and 90 minutes of compressor run time have been recorded.
c. In Frozen Mode - Defrost will be initiated if Delta T increases to greater than 16°C and 90 minutes of
compressor run time have been recorded.
When defrost is initiated, the controller closes the EEV, opens contacts TC, TN and TE (or TV) to de-energize the
compressor, condenser fan and evaporator fans. The controller then closes contacts TH to supply power to the
heaters. The orange DEFROST light and HEAT light are illuminated and the COOL light is also de-energized.
Figure 4.9 Defrost
ENERGIZED
DE-ENERGIZED
ST
F 24 VOLT POWER
HPS TC PB
IP-CM TN CF
TV EF ES
IP-EM1 IP-EM2 TE EF
HTT TH HR
TS ESV
4–11 T-372
The EEV and DUV are independently operated by the microprocessor. Complete schematics and legends are
located in Section 8.
Defrost will terminate when the DTS reading rises above one of two model number configurable options selection,
either an upper setting of 25.6°C (78°F) which is default or lower setting of 18°C (64°F). When the DTS reading
rises to the configured setting, the de-icing operation is terminated.
DTS Failure
When the return air temperature falls to 7°C (45°F), the controller ensures that the defrost temperature sensor
(DTS) reading has dropped to 10°C or below. If it has not, it indicates a failed DTS. A DTS failure alarm is triggered
and the defrost mode is operated by the return temperature sensor (RTS). Defrost will terminate after 1 hour. If the
DTS fails to reach is termination setting, the defrost terminate after 2 hours of operation.
Defrost Timer
If CnF23 is configured to “SAv” (save), then the value of the defrost interval timer will be saved at power down and
restored at power up. This option prevents short power interruptions from resetting an almost expired defrost inter-
val, and possibly delaying a needed defrost cycle. If the save option is not selected the defrost timer will re-initiate
and begin recounting.
If CnF11 is model number configured to OFF the operator may choose “OFF” as a defrost interval option.
If defrost does not terminate correctly and temperature reaches the set point of the Heat Termination Thermostat
(HTT) 54°C (130°F), the HTT will open to de-energize the heaters (AL259 & AL260). If the HTT does not open and
termination does not occur within two hours, the controller will terminate defrost. AL260 will be activated to inform
of a possible DTS failure.
T-372 4–12
4.3.29 Protection Mode - Condenser Fan Override
When CnF17 (Discharge Temperature Sensor) is set to “In” and CnF48 (Condenser Fan Switch Override) is set to
“On”, the condenser fan switch override logic is activated. If condenser cooling water pressure is sufficient to open
the water pressure switch (de-energizing the condenser fan) when water flow or pressure conditions are not main-
taining discharge temperature, the logic will energize the condenser fan as follows:
1. If the DUV is less than 80% open when the controller calls for it to be100% open, the condenser fan is ener-
gized. When the DUV is 100% open, the fan will de-energize.
2. If DPT reading is invalid or out of range (AL65), the condenser fan is energized and will remain energized
until system power is cycled.
3. If the system is running on condenser fan override and the high pressure switch opens, the condenser fan is
energized and will remain energized until the system power is cycled.
4.3.30 Quest
Quest (Quality and Energy Efficiency in Storage and Transport) power saving mode helps shipping lines lower their
operating costs by decreasing the system’s run time, energy usage and emissions. Quest is a method of tempera-
ture control used during steady-state perishable cooling that cycles the compressor on and off according to supply
/ return air temperature conditions.
To be eligible for steady-state control, the unit must first complete a setpoint pulldown phase and a CCPC pulldown
phase:
• During setpoint pulldown, supply air temperature is controlled according to the unit’s nominal supply air setpoint.
• During CCPC pulldown, supply air temperature is lowered somewhat relative to the nominal setpoint. Evap-
orator fans are forced to operate at high speed.
Steady-state CCPC control maintains the same lowered supply air temperature that was used during CCPC pull-
down. The compressor cycles on and off according to return air high and low limits. Depending on the fan mode of
operation selected, the evaporator fans may be programmed to run at low speed some or all of the time according
to the control logic.
4–13 T-372
4. “CLEAr” is displayed if all alarms are inactive. Press the ENTER key to clear the alarm queue. The alarm list
will clear and “-----” will be displayed.
NOTICE
AL026 is active when none of the sensors are responding. Check the ME connector on the front of
the controller. If it is loose or unplugged, reconnect it, then run a Pre-trip test (P5) to clear AL026.
Start
Troubleshooting
Yes
Did
Evaporator No Check Power Refer to CONNECT POWER
fans start? Supply Section 5.2
Yes
Yes
Yes
See alarm
Active Yes details & Refer to Controller Alarm Indications
Alarms? repair Section 4.4
No
Yes
Yes
Unit OK
T-372 4–14
4.5 Pre-Trip Diagnostics
Pre-Trip Diagnostics is an independent controller function that suspends normal refrigeration controller activities
and provides preprogrammed test routines. The test routine can be run in Auto Mode, which automatically per-
forms a preprogrammed sequence of tests, or Manual Mode, which allows the operator to select and run any of the
individual tests.
! CAUTION
Pre-trip inspection should not be performed with critical temperature cargoes in the container.
! CAUTION
When the PRE TRIP key is pressed, Economy, Dehumidification and Bulb Mode will be deacti-
vated. At the completion of the pre-trip test, Economy, Dehumidification and Bulb Mode must be
reactivated.
A pre-trip test may be initiated by use of the keypad or via communication, but when initiated by communication the
controller will execute the entire battery of tests (Auto Mode).
At the end of a pre-trip test, the message “P,” “rSLts” (pretest results) will be displayed. Press the ENTER key to
allow the user to see the results for each of the sub-tests. The results will be displayed as “PASS” or “FAIL” for each
test run to completion.
A detailed description of the pre-trip tests and test codes is provided in Table 4–9. Detailed operating instructions
are provided in Section 5.8.
4.6 DataCORDER
4.6.1 Description
Carrier Transicold “DataCORDER” software is integrated into the controller and serves to eliminate the tempera-
ture recorder and paper chart. DataCORDER Software is subdivided into operational software, configuration soft-
ware, and data memory. DataCORDER functions may be accessed by keypad selections and viewed on the
display module.
For a description of DataCORDER communications, refer to Section 4.6.15.
The DataCORDER consists of:
• Configuration software
• Operational software
• Data storage memory
• Real time clock (with internal battery backup)
• Six thermistor inputs
• Interrogation connections
• Power supply (battery pack)
4–15 T-372
4.6.2 DataCORDER Operational Software
The operational software reads and interprets inputs for use by the configuration software. The inputs are labeled
function codes.
T-372 4–16
4.6.3 DataCORDER Configuration Software
The configuration software controls the recording and alarm functions of the DataCORDER. Reprogramming to the
factory-installed configuration is achieved via the USB flash drive menu with a flash drive installed. An ML5 soft-
ware file or a compatible configuration database file must be on the USB flash drive in order to gain access to the
menu.
Displaying DataCORDER Configuration Variables
1. Press the ALT. MODE key on the keypad.
2. Use the Arrow keys until “dCF” is displayed.
3. Press the ENTER key.
4. Press an Arrow key until the left window displays the desired variable number. The right window will display
the value of this item for five seconds before returning to the normal display mode. If a longer display time is
desired, press the ENTER key to extend the display time to 30 seconds.
A list of the configuration variables is provided in Table 4–4. Descriptions of DataCORDER operation for each vari-
able setting are provided in the following paragraphs.
Standard Mode
In the Standard Mode, the user may configure the DataCORDER to record data using one of seven standard config-
urations. The seven standard configuration variables, with their descriptions, are listed in Table 4–5.
The inputs of the six thermistors (supply, return, USDA #1, USDA #2, USDA #3 and cargo probe) and the humidity
sensor input will be generated by the DataCORDER.
NOTE
The DataCORDER software uses the supply and return recorder sensors (SRS, RRS). The tempera-
ture control software uses the supply and return temperature sensors (STS, RTS).
Table 4–5 DataCORDER Standard Configurations
Standard Config Description
2 sensors (dCF02=2) 2 thermistor inputs (supply & return)
5 sensors (dCF02=5) 2 thermistor inputs (supply & return)
3 USDA thermistor inputs
6 sensors (dCF02=6) 2 thermistor inputs (supply & return)
3 USDA thermistor inputs
1 humidity input
4–17 T-372
Table 4–5 DataCORDER Standard Configurations
Standard Config Description
6 sensors (dCF02=54) 2 thermistor inputs (supply & return)
3 USDA thermistor inputs
1 cargo probe (thermistor input)
7 sensors (dCF02=64) 2 thermistor inputs (supply & return)
3 USDA thermistor inputs
1 humidity input
1 cargo probe (thermistor input)
9 sensors (dCF02=9) Not Applicable
Generic Mode
The Generic Mode allows user selection of the network data points to be recorded. The user may select up to a
total of eight data points for recording. Changing the configuration to generic and selecting which data points to
record may be done using the Carrier Transicold Data Retrieval Program. A list of the data points available for
recording follows.
1. Control mode
2. Control temperature
3. Frequency
4. Humidity
5. Phase A current
6. Phase B current
7. Phase C current
8. Main voltage
9. Evaporator expansion valve percentage
10. Discrete outputs (Bit mapped - require special handling if used)
11. Discrete inputs (Bit mapped - require special handling if used)
12. Ambient temperature sensor (AMBS)
13. Evaporator temperature sensor (ETS)
14. Compressor discharge temperature sensor (CPDS)
15. Return temperature sensor (RTS)
16. Supply temperature sensor (STS)
17. Defrost temperature sensor (DTS)
18. Discharge pressure transducer (DPT)
19. Suction pressure transducer (SPT)
20. Evaporator pressure transducer (EPT)
21. Vent position sensor (VPS)
T-372 4–18
4.6.6 Thermistor Format (dCF04)
The user may configure the format in which the thermistor readings are recorded. The short resolution is a 1 byte
format and the long resolution is a 2 byte format. The short requires less memory and records temperature with
variable resolutions depending on temperature range. The long records temperature in 0.01°C (0.02°F) steps for
the entire range.
4–19 T-372
4.6.11 Pre-Trip Data Recording
The DataCORDER will record the initiation of a pre-trip test (refer to Section 4.5) and the results of each test
included in pre-trip. The data is time-stamped and may be extracted via the Data Retrieval program. See Table 4–
10 for a description of the data stored in the DataCORDER for each corresponding pre-trip test.
USDA Recording
A special type of recording is used for USDA cold treatment purposes. Cold treatment recording requires three
remote temperature probes be placed at prescribed locations in the cargo. Provision is made to connect these
probes to the DataCORDER via receptacles located at the rear left-hand side of the unit. Four or five receptacles
are provided. The four 3-pin receptacles are for the probes. The 5-pin receptacle is for the Interrogator. The probe
receptacles are sized to accept plugs with tri-cam coupling locking devices. A label on the back panel of the unit
shows which receptacle is used for each probe.
The standard DataCORDER report displays the supply and return air temperatures. The cold treatment report dis-
plays USDA #1, #2, #3 and the supply and return air temperatures. Cold treatment recording is backed up by a bat-
tery so recording can continue if AC power is lost.
T-372 4–20
2. Calibrate the three USDA probes by ice bathing the probes and performing the calibration function with the
DataLINE. This calibration procedure generates the probe offsets which are stored in the controller and
applied to the USDA sensors for use in generating sensor type reports (see Figure 4.12).
Figure 4.12 DataCorder Probe Calibration Screen
4–21 T-372
c. Using the System Tools screen in the DataLine software perform a “trip start.” See Figure 4.14.
T-372 4–22
Figure 4.15 DataLINE and DataLINE Connect
DataLINE software
NOTE
If connecting a USB cable from the controller to a Windows 10 computer, follow the procedure in the
DataLINE manual to set up a static IP address.
Connect via Interrogator Receptacle:
• The unit may be fitted with an optional external interrogator receptacle for connection of equipment for cali-
bration and also to download recorded data from the DataCORDER.
NOTE
Downloading using the USDA port inside of the container is not supported by DataLINE.
NOTE
Wireless connectivity may only operate when ambient temperatures are above -20°C (-4°F). Connec-
tivity will be intermittent below this temperature.
The unit display module provides a wireless menu that allows access to all necessary parameters needed for wire-
less configuration and status checks.
4–23 T-372
Table 4–6 Wireless Settings Menu (nEt) Options
Option Description
EnbL Enable / Disable Wireless Connection (On/Off).
If On, wireless mode shall be initialized according to the last saved wireless role. If Off, all
existing wireless connections will be shut down and wireless is disabled.
• Controller will enable wireless by default.
• Wireless will not be initialized if the system is running a battery and not on AC / USB 5V.
• Wireless can be forcefully shut down in some cases during battery operation.
PASSW View Wireless Connection Passcode.
The wireless connectivity passcode accessed here can establish a connection from your
wireless computer / tablet / phone to the ML5 controller.
• Passcode resets every four hours (based on system clock).
• Passcode is good for the customer's fleet (assuming all clocks are set properly).
• If communicating at the passcode change time boundary, the session can run for an
additional 4 hours without changing the passcode.
4.7.2.d Communicating with the Controller using DataLINE Connect (IOS Device)
This procedure explains how to open the DataLINE Connect application and connect it directly to a unit’s controller.
1. Open the DataLINE Connect application.
2. Open the WiFi Settings menu (or Settings menu).
3. Under “Wi-Fi Login Credentials”, type in the Container ID of the unit to connect to. If this unit has already
been entered, select from the list of available wireless connections.
4. Next to “Passcode” (or “Token”), enter the passcode obtained from the Net menu on the display if it is not
already shown there. See Section 4.7.2.c for reference.
5. Select Login.
6. When DataLINE connect is connected, a message will appear “Connected to the WIFI successfully”.
7. After clicking OK to the message, the features of DataLINE Connect are now available. Refer to DataLINE
Connect user manual for more detailed procedures for using DataLINE Connect.
T-372 4–24
4.7.2.e Communicating with the Controller using DataLINE Connect (Android Device)
This procedure explains how to open the DataLINE Connect application and connect it directly to a unit’s controller.
1. Open the DataLINE Connect application.
2. Open the WiFi Settings menu (or Settings menu).
3. Verify that the “Wi-Fi ON” indicator is enabled.
4. Under “Wi-Fi Login Credentials”, specify the name of the wireless connection next to “Container ID” by
selecting from the list of available WiFi connections, or by typing in the Container ID of the unit you want to
connect to.
5. Next to “Passcode” (or “Token”), enter the passcode obtained from the Net menu on the display if it is not
already shown there. to Section 4.7.2.c for reference.
6. Select Login.
7. The message will appear “Connected to the WIFI successfully”. The controller wireless network name
appears on the top right corner of the interface.
8. After clicking OK to the message, the features of DataLINE Connect are now available. Refer to DataLINE
Connect user manual for more detailed procedures for using DataLINE Connect.
4–25 T-372
Table 4–7 Controller Configuration Variables (Continued)
Config Title Default Option
CnF45 Low Humidity Enabled Out In
CnF46 Quench / Liquid Injection Valve Type nO=0=no nC=1=nc
CnF47 Vent Position OFF UP, LOW, CUStOM
CnF49 OEM Reset Option OFF 0-off,1-std, 2-spec,3-cust
CnF50 Enhanced Bulb Mode Interface 0-out 1-in
CnF51 Timed Defrost Disable 0-out 1-in
CnF52 Oil Return Algorithm 0-out 1-in
CnF53 Water Cool Oil Return Logic 0-out 1-in
CnF55 TXV Boost Relay 0-out 1-in
CnF56 TXV Boost Circuit 0-out 1-in
CnF57 PWM Compressor Control 0-out 1-in
CnF59 Electronic Evaporator Expansion Valve 0-none 1-EC, 2-KE, 3-NA
CnF61 ACT ASC Control Enable 0-out 1-in
CnF62 Extended Temperature Control Enable 0-out 1-in
CnF63 QUEST Pre-Trip / TripWise Default State 0-on 1-off
CnF67 Air Heaters 0-out 1-in
CnF70 Enable XtendFRESH Logic 0-out 1-in
CnF71 XtendFRESH Pre-Trip / TripWise Default State 0-off 1-on
CnF74 TripWise Pre-Trip / TripWise Default State 0-off 1-on
CnF78 XtendFRESH Scrubber Output Available 0-out 1-in
Note: Configuration numbers not listed are not used in this application. These items may appear when loading configuration
software to the controller but changes will not be recognized by the controller programming.
NOTICE
Note: If the function is not applicable, the display will read “-----”
Display Only Functions - Cd01 through Cd26 are display only functions.
Cd01 Capacity Modulation Displays the DUV percent closed. The right display reads 100% when the valve
(%) is fully closed. The valve will usually be at 10% on start up of the unit except in
very high ambient temperatures.
Cd03 Compressor Motor The current sensor measures current draw in lines L1 & L2 by all of the high
Current voltage components. It also measures current draw in compressor motor leg T3.
The compressor leg T3 current is displayed.
Cd04 Line Current, Phase A The current sensor measures current on two legs. The third unmeasured leg is
calculated based on a current algorithm. The current measured is used for
control and diagnostic purposes. For control processing, the highest of the Phase
Cd05 Line Current, Phase B
A and B current values is used for current limiting purposes. For diagnostic
processing, the current draws are used to monitor component energization.
Cd06 Line Current, Phase C Whenever a heater or a motor is turned ON or OFF, the current draw increase/
reduction for that activity is measured. The current draw is then tested to
determine if it falls within the expected range of values for the component. Failure
of this test will result in a pre-trip failure or a control alarm indication.
T-372 4–26
Table 4–8 Controller Function Codes (Continued)
Code Title Description
Cd07 Main Power Voltage The main supply voltage is displayed.
Cd08 Main Power Frequency The value of the main power frequency is displayed in Hertz. The frequency
displayed will be halved if either fuse F1 or F2 is bad (alarm code AL021).
Cd09 Ambient Temperature The ambient sensor reading is displayed.
Cd10 Compressor Suction Evaporator temperature sensor reading is shown on the right display.
Temperature /
Evaporator
Temperature
Cd11 Compressor Dome Compressor discharge temperature sensor reading, using compressor dome
Temperature / temperature, is displayed.
Discharge
Temperature
Cd12 Compressor Suction Reading for evaporator pressure transducer (EPT) is shown on the left display;
Port Pressure / Press the ENTER key at Cd12 to show reading for compressor suction port
Evaporator Pressure pressure on right display.
Cd14 Compressor Discharge Compressor discharges pressure transducer reading is displayed.
Pressure
Cd15 Digital Unloader Valve The status of the valve is displayed (Open - Closed).
Cd16 Compressor Motor This code displays the compressor motor hours. Press the ENTER key while in
State / Unit Run Time Cd16 to view unit run time. Total hours are recorded in increments of 10 hours
Hour Meter (i.e., 3000 hours is displayed as 300).
Press and hold the ENTER key for 5 seconds to reset the Compressor Motor
Hour Meter display. The Unit Run Time Hour Meter cannot be reset.
Cd17 Relative Humidity (%) Humidity sensor reading is displayed. This code displays the relative humidity, as
a percent value.
Cd18 Software Revision The software revision number is displayed.
Number
Cd19 Battery Check Request backup battery test and display results or scroll to last result.
After selecting CD19, press the ENTER key while “btESt” is displayed to run the
backup battery test. While the test is running, “btESt” will flash on the display.
Once the test is complete, the Backup Battery Test Result will be displayed. After
5 seconds, the controller returns to displaying the setpoint.
For the Test Result:
• If the test result is Pass, the display will show “PASS” to indicate this.
• If the test result is End of Life, the display will show “EOL” to indicate this.
• If the test result is Fail, the display will show “FAIL” to indicate this.
• If the test result detects a temperature out of range condition (greater
than 45 deg C), the display will show “toor” to indicate this. The smart bat-
tery will not charge.
• If the test result is Non-Carrier, the display will show “not C” to indicate this.
• If the test result is No Battery, the display will show “nobAt” to indicate this.
If the ENTER key is not pressed in 5 seconds, then the controller returns to
displaying the setpoint.
Whenever the battery test is run, the Relative State of Charge (RSOC) is posted
in the download.
4–27 T-372
Table 4–8 Controller Function Codes (Continued)
Code Title Description
Cd20 Config / Model Number This code indicates the dash number of the model for which the Controller is
configured (i.e., if the unit is a 69NT40-551-100, the display will show “51100”).
To display controller configuration database information, press the ENTER key.
Values in “CFYYMMDD” format are displayed if the controller was configured
with a configuration card or with a valid OEM serial port configuration update;
YYMMDD represents the publication date of the model configuration database.
Cd21 Capacity Mode The mode of operation is displayed (Standard - Economized).
Cd22 Compressor State The status of the compressor is displayed (OFF, On).
Cd23 Evaporator Fan State Displays the current evaporator fan state (OFF, LOW, HIGH).
Cd25 Compressor Run Time This code displays the time remaining until the unit goes into defrost (in tenths of
Remaining Until an hour). This value is based on the actual accumulated compressor running
Defrost time.
Cd26 Defrost Temperature Defrost temperature sensor reading is displayed.
Sensor Reading
Configurable Functions - Cd27 through Cd37 are user-selectable functions. The operator can change the value
of these functions to meet the operational needs of the container.
Cd27 Defrost Interval (Hours This is the desired period of time between defrost cycles. Factory default is
or Automatic) “AUTO”. See Section 4.3.20 for information on Defrost Interval.
CnF11 determines whether the operator will be allowed to chose “OFF” as a
defrost interval option.
After a new Defrost Interval is selected, the previously selected Interval is used
until the next defrost termination, the next time the DTT contacts are OPEN, or
the next time power to the control is interrupted. If the previous value or the new
value is “OFF”, the newly selected value will be used immediately.
If any Auto Pre-trip sequence is initiated, Cd27 will be set to ‘AUTO’ unless
CnF49 (OEM Reset) is set to “Custom”.
Cd28 Temperature Units This code determines the temperature units (C or F) that will be used for all
(Degrees C or Degrees temperature displays. The user selects C or F by selecting function code Cd28
F) and press the ENTER key. The factory default value is Celsius units. This
function code will display “-----” if CnF34 is set to F.
Cd29 Failure Action (Mode) If all of the control sensors are out of range (alarm code AL026) or there is a
probe circuit calibration failure (alarm code AL027), the unit will enter the
shutdown state defined by this setting. The user selects one of four possible
actions as follows:
A - Full Cooling (Compressor is on, economized operation.)
b - Partial Cooling (Compressor is on, standard operation.)
C - Evaporator Fan Only (Evaporator fans on high speed, not applicable with
frozen setpoints.)
d - Full System Shutdown - Factory Default (Shut down every component in unit.)
T-372 4–28
Table 4–8 Controller Function Codes (Continued)
Code Title Description
Cd30 In-Range Tolerance The in-range tolerance will determine the temperature band around the setpoint
which will be designated as in-range.
For normal temperature control, control temperature is considered in range if it is
within setpoint in-range Tolerance. There are four possible values:
1 = +/- 0.5°C (+/-0.9°F)
2 = +/- 1.0°C (+/-1.8°F)
3 = +/- 1.5°C (+/-2.7°F)
4 = +/- 2.0°C (+/-3.6°F) - Factory Default
If the control temperature is in-range, the green IN-RANGE light is illuminated.
In-range tolerance shall be set to +/- 2.0°C upon activation of dehumidification or
Bulb Mode (Cd33, Cd35, Cd48).
When CCPC is actively controlling, in-range tolerance is not considered.
“-----” will be displayed whenever Dehumidification or Bulb Mode is enabled or
when CCPC with six hour re-activation is actively controlling.
“-----” will be displayed whenever Frozen Economy Mode is operating.
Cd31 Stagger Start Offset The stagger start offset time is the amount of time that the unit will delay at start-
Time (Seconds) up, thus allowing multiple units to stagger their control initiation when all units are
powered up together. The eight possible offset values are 0 (Factory Default), 3,
6, 9, 12, 15, 18 or 21 seconds.
Cd32 System Current Limit The current limit is the maximum current draw allowed on any phase at any time.
(Amperes) Limiting the unit’s current reduces the load on the main power supply. When
desirable, the limit can be lowered. Note, however, that capacity is also reduced.
The five values for 460 VAC operation are: 15, 17, 19, 21, or 23 amperes. The
factory default setting is 21 amperes.
Cd33 Humidity Setpoint This is the value in percent to which the system will dehumidify. There are
configuration variables that determine whether dehumidification capabilities are
installed. In the Test Mode, the setpoint will be temporarily set to 1%, allowing the
test of dehumidification. After 5 minutes, the normal setpoint is restored. If the
unit is configured for dehumidification, then the entire setpoint range will apply to
dehumidification. If Pre-trip is initiated, this value will be set to “OFF”
automatically.
(Replaced by Cd48 interface if CnF50 Enhanced Bulb Mode Interface is active.)
Cd34 Economy Mode (On- The current state of the Economy Mode option, “-----”, On, or Off. CnF22
Off) determines whether Economy Mode offered. Economy Mode is a user selectable
mode of operation provided for power saving purposes.
Cd35 Bulb Mode The current state of the Bulb Mode option, “-----”, nOr, or bULb.
(Replaced by Cd48 if CnF50, Enhanced Bulb Mode, is active.)
Bulb Mode is an extension of dehumidification control (Cd33). If dehumidification
(CnF04) is set to “Off,” Cd35 will display “Nor” and the user will be unable to
change it. CnF28 determines whether the Bulb Mode selection is offered.
After a dehumidification setpoint has been selected and entered for code Cd33,
the user may then change Cd35 to “bulb.” After Bulb Mode has been selected
and entered, the user may then utilize function codes Cd36 and Cd37 to make
the desired changes.
4–29 T-372
Table 4–8 Controller Function Codes (Continued)
Code Title Description
Cd36 Evaporator Fan Speed This is the desired evaporator fan speed for use during the bulb Dehumidification
and Humidification Mode option.
(Replaced by Cd48 if CnF50, Enhanced Bulb Mode, is active.)
This code is enabled only if in the Dehumidification Mode (Cd33) and Bulb Mode
(Cd35) has been set to “bulb.” If these conditions are not met, “alt” will be
displayed (indicating that the evaporator fans will alternate their speed) and the
display cannot be changed.
If a dehumidification setpoint has been selected along with Bulb Mode then “alt”
may be selected for alternating speed, “Lo” for low speed evaporator fan only, or
“Hi” for high speed evaporator fan only.
If a setting other than “alt” has been selected and Bulb Mode is deactivated in any
manner, then selection reverts back to “alt.”
Cd37 Variable DTT Setting This is the variable defrost termination thermostat setting to be used with the
(Bulb Mode) optional Bulb Mode functionality. This item is only displayed if the Bulb Mode
option is configured on.
(Replaced by Cd48 interface if CnF50 Enhanced Bulb Mode Interface is active.)
Display Only Functions - Cd38 through Cd40 are display only functions.
Cd38 Secondary Supply Cd38 will display the current supply recorder sensor (SRS) reading for units
Temperature Sensor configured for four probes. If the unit is configured with a DataCORDER, Cd38
will display “-----.” If the DataCORDER suffers a failure, Cd38 will display the
supply recorder sensor reading.
Cd39 Secondary Return Cd39 will display the current return recorder sensor (RRS) reading for units
Temperature Sensor configured for four probes. If the unit is configured with a DataCORDER, Cd39
will display “-----.” If the DataCORDER suffers a failure, Cd39 will display the
return recorder sensor reading.
Cd40 Container Identification If a valid container id exists, the default display for Cd40 will be “cd40_XXXXX”
Number where “XXXXX” is the 5th character through the 9th character of the container id.
Press the Enter key while on Cd40 to display “id_YYYYYYY” where “YYYYYYY”
is the 5th character to the 11th character of the container id.
If no valid container id exists or the container id is blank, the default display will
have Cd40 on the left display and the right display will alternate between “_nEEd”
and “___id”. Press the ENTER key while on Cd40 in this state to prompt the Set
Id Interface.
On start up if the container id is not valid, Cd40 will be brought up on the display
for the first minute of power up. This can be left by either entering a container id
or leaving the code select normally.
Cd40 is configured at commissioning to read a valid container identification
number. The reading will not display alpha characters; only the numeric portion
of the number will display.
Cd41 Valve Override SERVICE FUNCTION: This code is used for troubleshooting, and allows manual
positioning of the economizer solenoid valve, electronic expansion valve, and
digital unloader valve. Provides readings such as: Percent Capacity, EEV,
Capacity Mode, LIV and DUV. See Section 7.25 for operating instructions.
Configurable Functions - Cd43 is a user-selectable function. The operator can change the value of this function
to meet the operational needs of the container.
Cd43 XtendFRESH Mode Cd43 has three selectable modes of operation:
FRESH - All XtendFRESH operations are enabled and setpoints for CO2 and O2
can be edited.
OFF - All XtendFRESH operations are disabled.
TEST - the operator has the ability to test operation of mechanical components,
test and calibrate the CO2 sensors and verify the validity of the O2 sensor.
T-372 4–30
Table 4–8 Controller Function Codes (Continued)
Code Title Description
Display Only Function - Cd44 is a display only function.
Cd44 XtendFRESH Values | When XtendFRESH option enabled:
EverFRESH Values Cd44 allows the user to view the following XtendFRESH values: CO2 setpoint,
CO2 percentage, O2 setpoint, O2 percentage, and O2 voltage.
For the CO2 setpoint, the range is from 0 to 19% in 1% increments with a default
setting of 5%. For the O2 setpoint, the range is from 3% to 21% in 1% increments
with a default setting of 10%.
When EverFRESH option enabled:
Cd44 allows the user to view the following EverFRESH values: CO2 setpoint,
CO2 percentage, O2 setpoint, O2 percentage, O2 voltage, and MPT pressure.
For the CO2 setpoint, the range is from 2 to 19% in 1% increments with a default
setting of 5%. For the O2 setpoint, the range is from 3% to 17% in 1% increments
with a default setting of 10%.
Configurable Functions - Cd45 through Cd48 are user-selectable functions. The operator can change the value
of these functions to meet the operational needs of the container.
Cd45 Vent Position Sensor Values: 0 to 240 for UPPER / 0 to 225 for LOWER
(VPS) Position This function code will be dashed out if not configured for VPS.
When configured for VPS, Cd45 displays the current vent position in units of 5
CMH (units displayed as “CM”) or CFM (units displayed as “CF”) depending on
the selection of Cd46 (Airflow display units), Cd28 (Metric/Imperial) or the
pressing of the deg C/F key.
Cd45 will display whenever the control detects movement via the sensor unless
AL50 is active. Cd45 will display for 30 seconds, then time out and return to the
normal display mode.
Cd46 Airflow Display Units Selects the airflow units to be displayed by Cd45 if configured for Vent Position
Sensor or displayed by “USER/FLO” under Cd43 if configured for Autoslide.
CF = Cubic Feet per Minute
CM = Cubic Meters per Hour
bOth = Displays CF or CM depending on the setting of Cd28 (Metric/Imperial) or
the pressing of the degree C/F key.
Cd47 Variable Economy Used when Economy Mode (CnF22) is set to 3-cust. Display will show “----” when
Temperature Setting the unit is not configured for Economy Mode.
When the unit has a perishable setpoint and Economy Mode is active, at the start
of each cooling or heating cycle, high speed evaporator fans will run for 3
minutes. After three minutes, the evaporator fans will be switched to low speed
any time that the supply temperature is within +/- 0.25°C of the setpoint and the
return temperature is less than or equal to the supply temperature + the user
selected Cd47 (values are 0.5°C - 4.0°C, default is 3.0°C).
4–31 T-372
Table 4–8 Controller Function Codes (Continued)
Code Title Description
Cd48 Dehumidification / Bulb Initially Cd48 will display current dehumidification-mode; bUlb - bulb cargo mode,
Cargo Mode Parameter dEhUM - normal dehumidification, or OFF - off. This display is steady.
Selection Press the ENTER key to take the interface down into a hierarchy of parameter
selection menus (mode, setpoint, evaporator speed, DTT setting). Press the
ENTER key in any parameter selection menu to commit selection of the currently
displayed parameter and cause the interface to descend into the next parameter
selection menu. All parameter selection menus alternate between a blank display
and the current selection in the right hand display.
Press the CODE SELECT key in a selection menu to cancel the current selection
activity and ascend back up to the next higher selection menu (or to Cd48 display
mode if that is the next higher).
If the operator does not press any key for five seconds, the interface reverts to
normal system display and the current selection menu is cancelled, but any
previously committed changes are retained.
Available parameters and parameter ranges are a function of configuration
options and previously selected parameters as indicated above.
Whenever any pre-trip test is initiated, dehumidification-mode goes to OFF.
Whenever dehumidification-mode goes to OFF:
• Dehumidification control setpoint goes to0%RHinternally but will then ini-
tialize to 95% RH when dehumidification-mode leaves OFF.
• Evaporator speed select goes to Alt for units without PWM Compressor
Control (Cnf57 = Out), Evaporator speed select goes to Hi for units with
PWM Compressor Control (Cnf57 = In).
• DTT setting goes to 25.6_C or 18.0_C, depending on Cnf41.
Whenever dehumidification-mode is set to bUlb, DTT setting goes to 18.0°C if it
had been set higher.
Whenever dehumidification-mode is set to dEhUM, DTT setting goes to 25.6°C
or 18.0°C, depending on Cnf41.
For units without PWM Compressor Control (Cnf57 = Out):
• Whenever dehumidification control setpoint is set below 65% RH evapo-
rator speed select goes to LO if it had been set to Hi.
• Whenever dehumidification control setpoint is set above 64% RH evapo-
rator speed select goes to Alt if it had been set to LO.
For units with PWM Compressor Control (Cnf57 = In):
• Whenever dehumidification control setpoint is set below 60% RH, the
evaporator fan speed is set to LO, the user has the ability to set the evap-
orator fan speed to Hi via the keypad.
• Whenever dehumidification control setpoint is set equal to or above 60%
RH, the evaporator fan speed is set to Hi, the user has the ability to set
the evaporator fan speed to LO via the keypad.
Display Only Function - Cd49 is a display only function.
Cd49 Days Since Last Displays the number of days since last successful pre-trip sequence.
Successful Pre-Trip Press the ENTER key to view the number of days since the last successful pre-
trip for Auto1, Auto2, and Auto2 in sequence.
Press the CODE SELECT key to step back through the list and ultimately to exit
the Cd49 display.
Configurable Functions - Cd50 through Cd53 are user-selectable functions. The operator can change the value
of these functions to meet the operational needs of the container.Cd50
T-372 4–32
Table 4–8 Controller Function Codes (Continued)
Code Title Description
Cd50 QUEST Enable / ”OFF” = disabled.
Disable ”On” = enabled.
”SEtPt” = suspended by setpoint too low.
”CAHUM” = suspended by CA or humidity control.
”ACt” = suspended by ACT active.
”FAIL” = all return temperature probe failure for QUEST.
”PrtrP” = pre-trip active.
”C LIM” = suspended by cool limit logic.
”PULL” = pulldown active.
“ALArM ” = suspended by shutdown alarm
Press the ENTER key, Arrow keys, and then ENTER key to select “OFF” or “On”.
If “On” is selected, QUEST operation may be suspended as indicated by one of
the suspension codes listed above. If QUEST is not “OFF” and is not suspended,
“On” will be displayed.
Cd51 Automatic Cold Automatic Cold Treatment (ACT) mode:
Treatment (ACT) Mode Cd51 increments of (1 day)_(1hr), Display: default “0_0 “
Parameter Selection
“done” mm-dd this will be display is ACT has completed
“ACt” value “On” “OFF” or “----“Display /Select: default “OFF“
“trEAt” value °C / °F on 0.1 degree increments Display/Select: default “0.0°C“
“DAyS” value “0 – 99” increments of 1 Display/Select: default “0”
“ProbE” value Probe positions ex ’1 2 _ 4’ ’1 _ 3 _’ Display: default “---- “
“SPnEW” value °C / °F on 0.1° increments Display/Select: default “10.0°C “
Initially Cd51 will display current countdown timer increments of (1 day)_(1hr),
default “0_0.
See Section 5.11 for procedure to set ACT using Cd51.
Press the ENTER key to take the interface down into a hierarchy of parameter
selection menus (act, treat, days, probe and spnew setting).
Press the ENTER key in any of the parameter selection menus to commit
selection of the currently displayed parameter and cause the interface to
descend into the next parameter selection menu. All parameter selection menus
alternate between a blank display and the current selection in the right hand
display.
Press the CODE SELECT key in a selection menu to cancel the current selection
activity and ascend back up to the next higher selection menu (or to Cd51 display
mode if that is the next higher).
If the operator does not press any key for five seconds, the interface reverts to
normal system display and the current selection menu is cancelled, but any
previously committed changes are retained.
Parameter with the exception of “Act” may not be altered if Cd51 is re-entered if
“Act” is “On”. When ACT has completed including reaching the new setpoint
“done” on the left display and the MONTH DAY of completion on the right display
will be displayed as the second entry in the menu. Turning ACT off clears this
entry. This action also resets Cd51 to initial time remaining. ACT must then be
turned on to view or modify the additional parameters.
Whenever any auto pre-trip test or Trip Start is initiated, ACT mode goes to OFF.
4–33 T-372
Table 4–8 Controller Function Codes (Continued)
Code Title Description
Cd53 Automatic Setpoint Automatic Setpoint Change (ASC) Mode:
Change (ASC) Mode Cd53 increments of (1 day)_(1hr), Display: default “0_0 “
Parameter Selection
“done” mm-dd this will be display is ASC has completed
“ASC” value “On” “OFF” Display /Select: default “OFF“
“nSC” value “1 - 6” (This is the value “n” for the subsequent entries).
“SP (n-1)” value °C / °F on 0.1 degree increments Display/Select: default
“10.0°C“
“DAY (n-1)” value “1 – 99” increments of 1 Display/Select: default “1“
“SP (n)” value °C / °F on 0.1 degree increments Display/Select: default “10.0°C
Initially Cd53 will display current count down timer increments of (1 day)_(1hr),
default “0_0
Press the ENTER key to take the interface down into a hierarchy of parameter
selection menus, (mode, act, treat, days, probe and spnew setting). Press the
ENTER key in any of the parameter selection menus to select the currently
displayed parameter and cause the interface to descend into the next parameter
selection menu. All parameter selection menus alternate between a blank display
and the current selection in the right hand display.
Press the CODE SELECT key in a selection menu to cancel the current selection
activity and ascend back up to the next higher selection menu (or to Cd53 display
mode if that is the next higher).
If the operator does not press any key for five seconds the interface reverts to
normal system display and the current selection menu is cancelled, but any
previously committed changes are retained.
Available parameters and parameter ranges are a function of configuration
options and previously selected parameters as indicated above.
Parameter with the exception of “ASC” may not be altered if Cd53 is re-entered
if “ASC” is “On”. When ASC has completed including reaching the last setpoint
“done” on the left display and the MONTH DAY of completion on the right display
will be displayed as the second entry in the menu. Turning ASC off clears this
entry. This action also resets Cd53 to initial time remaining. ASC must then be
turned on to view or modify the additional parameters.
Whenever any auto pre-trip test or Trip Start is initiated, ASC mode goes to OFF.
Display Only Functions - Cd54 through Cd58 are display only functions.
Cd54 Suction Port Superheat Reading for evaporator superheat (suction temperature minus suction saturation
/ Electronic Expansion temperature as calculated from suction pressure) is shown on the right display.
Valve Status Press the ENTER key at Cd54 to show reading for EEV position (in %) on left
display.
Cd55 Discharge Superheat Cd55 will display discharge superheat (discharge temperature minus discharge
saturation temperature as calculated from discharge pressure) values in C /F as
calculated by the discharge temperature minus the discharge saturation
temperature as calculated from discharge pressure.
“-----” will be displayed if selection is not valid.
T-372 4–34
Table 4–8 Controller Function Codes (Continued)
Code Title Description
Cd58 Water Pressure Switch Cd58 will display “CLOSE” if the WPS or CFS switch contacts are closed or if
/ Condenser Fan these options are not installed. “OPEn” is displayed when the WPS or CFS switch
Switch State or contacts are open. When the WPS/CFS Override Logic is “TRUE”, the right
Override Logic State display will flash on all units.
NOTE:
1. This CLOSE/OPEn state displayed in this Code Select function only applies to
units that have the ability to detect the state of a WPS/CFS. This function should
not be relied upon to display the condition of the switch on units that don’t have
a WPS/CFS switch connected to ECG2 exclusively.
2. The right display will flash if the WPS/CFS Override Logic is TRUE on all units.
This is always the case, whether the unit has a WPS or CFS installed or not.
3. The ability of the WPS/CFS Override Logic to control the condenser fan is
limited. It is not possible for this logic to control the fan on units that have the WPS
or CFS wired in series with the fan contactor. Units wired in this configuration can
indicate that the WPS/CFS Override Logic is active by flashing the right display,
however, the wiring will not allow for control of the condenser fan.
Configurable Functions - Cd59 through Cd61 are user-selectable functions. The operator can change the value
of these functions to meet the operational needs of the container.
Cd59 Pump Down Logic Cd59 allows operation of the pump down logic control. The display will flash
between “STArT PdN” and “PrESS EnTEr”.
Upon entering Cd59 the operator will be required to acknowledge that they want
to initiate the pump down control. The display will flash between “STArT PdN”
and “PrESS EnTEr”. Once the decision to continue is confirmed pump down logic
will begin, and will take complete control of the unit until pump down either
succeeds or fails. This operation can not be halted once it begins without power
cycling the unit.
After pump down logic has been initiated, the operator will be notified to close the
Liquid Line Valve, the display will flash between “CLOSE LLV” and “PrESS
EnTEr”. Once complete the display will read “P dN” to the left, and the current
suction pressure to the right.
If the automatic pump down logic succeeds within 20 minutes, the unit will turn
itself off, and the display will notify the operator that pump down is complete by
flashing between “P dN DOnE” and “SHUT OFF”. The operator must then shut
off the unit.
If the automatic pump down logic does not complete within 20 minutes, the unit
will drop out of Cd59 and return to its previous control condition.
Cd63 FuelWise Cd63 is used to enable FuelWise.
Following a power cycle, the state of the function select code is retained at its
state prior to the power cycle if CNF72 = Default ON else if Default OFF this will
be set to OFF. If “On”, this function select code will be set to “OFF” when any trip
start occurs or any pretrip test is initiated.
Event 120 shall be logged when ever CD63 is Turned ON OR if CD63 state is ON
at Mid night.
“-----” will be displayed if Cnf72 is configured OFF.
4–35 T-372
Table 4–8 Controller Function Codes (Continued)
Code Title Description
Cd65 TripWise If the function is off, display "OFF". If the function is on, display "ON".
“-----” will be displayed if the TripWise option is not active for the current
configuration.
Press the ENTER key. The existing entry will flash. Use the Arrow keys to
alternate between OFF and ON. Press ENTER again to set the Expiration
Interval.
Left display: “dAyS”
Right display: Expiration Interval 2 through 365 in 1 day increments.
Default value is 30.
Cd66 Instantaneous Power Real power in kW currently being used by the system.
(kW) Value is “-----“,“ nnn.n
Display “-----“ if not configured else nnn.n
Cd67 Total Power (kW-hr) Energy used by the system, in kW-hrs, since last Trip Start.
Value is “-----“,“ nnnnn
Display “-----“ if not configured else nnnnn
Cd70 Temp Setpoint Lock Cd70 locks out setpoint selection, requiring the user to manually turn the lock off,
prior to making a setpoint change. If the setpoint lock is “ON”, and the user
attempts to enter a new setpoint, a message “SPLK” (Setpoint Lock) is in the left
display and “ON” in the right display for five seconds.
Press the ENTER key. “SPLK” will display along with the current setting of “ON”
or “OFF”. Use the Arrow keys to change the selection - the new selection will then
flash for five seconds. Press the ENTER key to confirm the new selection.
An event will be recorded in the DataCorder each time the action of turning it
“ON” or “OFF” is taken.
Default setting is “OFF”. Unit will default to “OFF” with the selection of PTI or a
TripStart on the unit.
Cd71 EverFRESH Mode Cd71 has three selectable modes of operation:
FRESH - All EverFRESH operations are enabled and setpoints for CO2 and O2
can be edited.
OFF - All EverFRESH operations are disabled.
PURGE - the operator has the ability to suspend EverFRESH operations while
per-charging gas levels in the container.
Cd74 Controller Diagnostic Request Test “tESt”, Displayed Test Result “PASS,” “FAIL0,” “FAIL1,” “FAIL2”
After selecting CD70, press the ENTER key while “tESt” is displayed to run the
Controller Self Diagnostic test. While the test is running, “tESt” will flash on the
display. Once the test is complete, the Test Result will be displayed. After 30
seconds, the controller returns to displaying the setpoint.
"PASS" will be the result if all power sources are present and at the correct level,
there are no input faults, and all output tests pass.
"FAIL0" will be the test result if a power source is not available or not at the
correct level.
"FAIL1" will be the test result if all power sources are present and at the correct
level, but there is an input fault.
"FAIL2" will be the test result if all power sources are present and at the correct
level, and there are no input faults, but an output test fails.
T-372 4–36
4.10 Controller Alarm Indications
There are three alarm categories:
• AL0XX Refrigeration Critical Alarms
• AL2XX Refrigeration Non-Critical Alarms
• AL9XX Atmosphere Critical and Non-Critical Alarms
4–37 T-372
AL020 Control Fuse (F3) Open
Cause: Control power fuse (F3 or F4) is open.
Component Check F3 fuse.
Troubleshooting If fuse is open, check PA, PB, CH coils for short to ground.
Corrective Action If short is found, replace the defective coil. Replace the fuse.
Component Check F4 fuse.
Troubleshooting If fuse is open, check ESV coil resistance at CA1 to TRX2. If short to ground,
or if resistance is less than 4 ohms, coil is defective. Check CF, ES, EF, HR
coils for short to ground. If short is found, coil is defective.
Corrective Action Replace the defective coil. Replace the fuse.
Component Check voltage at QC1.
Troubleshooting If voltage not present, check ST7. If voltage is present, it indicates a
defective microprocessor.
Corrective Action See Controller Service Section 7.27.
T-372 4–38
AL024 Compressor IP Open
Cause: Compressor internal protector (IP) is open.
Component Compressor
Troubleshooting Shut down unit disconnect power and check resistance of compressor
windings at contactor T1-T2, T2-T3.
Corrective Action Monitor unit, if alarm remains active or is repetitive replace the compressor
at the next available opportunity. See Compressor Service, Section 7.9.
4–39 T-372
AL028 Low Suction Pressure
Component Suction Pressure Transducer (SPT)
Troubleshooting Confirm accurate SPT pressure readings. See Manifold Gauge Set
Section 7.2.
Corrective Action Replace SPT if defective.
Component Discharge Pressure Transducer (DPT)
Troubleshooting Confirm accurate DPT pressure readings. See Manifold Gauge Set
Section 7.2.
Corrective Action Replace DPT if defective.
T-372 4–40
AL214 Phase Sequence Detect Fault
Cause: Controller is unable to determine the correct phase relationship.
Component N/A
Troubleshooting Power cycle the unit.
Corrective Action Resetting the unit may correct problem, monitor the unit.
Component Wiring
Troubleshooting Check unit wiring.
Confirm pressure readings during start-up; suction pressure should
decrease and discharge pressure should increase.
Corrective Action Correct wiring.
Component Current Sensor
Troubleshooting Check Cd41, right most digit:
If display is 3 or 4, check compressor / sensor wiring.
If display is 5, the current sensor is defective.
Corrective Action Replace current sensor if defective.
4–41 T-372
AL219 Discharge Temperature High
Cause: Discharge temperature exceeds 135°C (275°F) for 10 minutes within the last hour.
Component Restrictions in the refrigeration system.
Troubleshooting Ensure the discharge service valve is fully open.
Corrective Action Open the discharge service valve as needed.
Troubleshooting Check the unit for air flow restrictions.
Corrective Action Clean or remove any debris from coils.
Component Non-condensables in the refrigeration system.
Troubleshooting With the unit off allow system to stabilize to ambient temperature.
Check system pressure against Pressure Temperature Chart. See Table
7–4, Table 7–5.
Corrective Action Correct as required. See Refrigerant Charge Section 7.7.1.
Component Additional Alarms such as AL216, AL024.
Troubleshooting Check compressor operation.
Corrective Action If the alarm persists, it may indicate a failing compressor, replace the
compressor. See Compressor Service Section 7.9.
T-372 4–42
AL253 Battery Pack Fault
Cause: Any of the USDA1, USDA2, or USDA3 probes have been detected AND the Backup Battery Test
Result is Failure. Or, no Battery.
Component Battery
Troubleshooting Perform battery test in function code Cd19 to determine failure mode of
battery.
Corrective Action To clear the alarm, replace the battery pack. See Section 7.27.9 Battery
Replacement. If after replacement the alarm continues, run Cd19 to
determine whether the replaced battery is good.
4–43 T-372
AL259 Heat Termination Thermostat (HTT) Open
Cause: Heat Termination Thermostat (HTT) is open.
Component Heat Termination Thermostat (HTT)
Troubleshooting Check resistance between CA21 and CA10. If 0 ohms, switch closed. if
infinite (OL), switch open.
Corrective Action Replace HTT if defective. See Sensor Replacement Section 7.28.
T-372 4–44
AL264 Discharge Temperature Sensor (CPDS) Fault
Troubleshooting Test the CPDS. See Sensor Checkout Procedure, Section 7.28.2.
Corrective Action Replace the CPDS if defective. See Sensor Replacement Section 7.28.
AL266 Suction Pressure Transducer (SPT), Evaporator Pressure Transducer (EPT) Fault
Cause: Suction Pressure Transducer (SPT) or Evaporator Pressure Transducer (EPT) out of range.
Component Suction Pressure Transducer (SPT); Evaporator Pressure Transducer (EPT)
Troubleshooting Confirm accurate SPT and EPT pressure readings. See Manifold Gauge
Set Section 7.2. Performing a pre-trip 5-9 test will also check the
transducers.
Corrective Action Replace SPT / EPT if defective.
Troubleshooting Monitor
Corrective Action If the alarm persists, it may indicate a failing compressor. See Compressor
Service Section 7.9.
4–45 T-372
AL271 Return Recorder Sensor (RRS) Fault
Cause: Return Recorder Sensor (RRS) is out of range.
Component Return Recorder Sensor (RRS)
Troubleshooting Perform pre-trip P5.
Corrective Action If P5 passes, no further action is required. If P5 fails, replace the defective
sensor as determined by P5. See Temperature Sensor Service Section
7.28.
T-372 4–46
AL286 RTC Battery Low
Corrective Action If alarm stays active, replace battery.
4–47 T-372
AL910 Carbon Dioxide Sensor (CO2) Fault
Cause: Triggered anytime the CO2 sensor reading is outside of the normal operation range, after an initial
signal was detected.
Action: Control O2 to setpoint. Controlling O2 may allow CO2 to increase. Replace sensor as soon as
possible. If both AL909 and AL910 are active, run the EverFRESH Air Compressor (EAC) and open
the EverFRESH Air Valve (EA).
Component CO2 Sensor
Troubleshooting Check wiring (refer to schematic), and check for bad connections or wires
improperly positioned.
Check the voltage on the back of MD connectors pin MD09 (-) and MD03
(+12 VDC) with the controller energized. If 12 VDC is not available, check
the controller. If 12 VDC is available, check the back of pin MD02 for a
voltage between 1.0 - 4.7 VDC. If not present, replace the sensor.
If part is available, remove the upper fresh air panel and evaporator motor
and replace the sensor. If no part is available, take no action and service
at next PTI.
T-372 4–48
AL929 Loss of Atmospheric Control
Component Water Drain Valve (WDV)
Troubleshooting A closed or plugged WDV or filter housing could prevent any air from
entering the container. P20-3 tests valve operation.
Potential failure results:
• MPT pressure fails to change when the valve is energized. Check
for signs of blockage by removing the WDV housing and particu-
late filter housings. Clean any debris. While removed, inspect the
WDV and associated piping for blockage.
• EA current not correct. Access function code Cd74 and perform a
ML5 self-check to verify the controller is functioning properly. If it
fails, replace the controller. If it passes self-check, replace the WDV.
Component EverFRESH Nitrogen Valve (EN)
Troubleshooting An open or leaky EN valve would allow N2 to go into the sensor sensing
chamber causing an inaccurate reading. P20-5 tests this valve.
Potential failure results:
• If tests fail, remove the EN and verify the valve is not clogged or
damaged.
• EA current is not correct. Access function code Cd74 and perform
a ML5 self-check to verify the controller is functioning properly. If it
fails, replace the controller. If it passes self-check, replace the EN.
4–49 T-372
AL977 Membrane Pressure Transducer (MPT) Fault
Cause: When the EverFRESH Air Compressor (EAC) is running and pressure is not between -5 psig and
200 psig or the EAC has been OFF for five minutes and pressure is not within the range of -5 psig
and 5 psig.
Component Membrane Pressure Transducer (MPT)
Troubleshooting With the EverFRESH system off for 15 minutes, bring up function code
Cd44 and scroll to "EF Pt". Verify that the value is between -5 psig and 5
psig. A "- - - - " value indicates a failed sensor or harness. Pressure outside
of range indicates a bad sensor, replace the sensor.
Component ML5 Controller
Troubleshooting Access function code Cd74 to perform an ML5 self-diagnostic test.
T-372 4–50
AL980 Fresh Air Valve (EA) Fault
Cause: When the system energizes the EverFRESH Air Valve (EA) solenoid and membrane pressure does
not drop 40 psi, the alarm is triggered. The alarm triggers OFF when membrane pressure transducer
(MPT) pressure drop is more than 40 psi when EA is opened.
Component EverFRESH Air Valve (EA) Solenoid
Troubleshooting Run a P20 test to verify mechanical and electrical performance of the
solenoid.
If the electrical test fails, replace the valve.
If the mechanical test fails, check for obstructions blocking system flow.
Remove obstructions. If it still fails, replace the valve.
Component ML5 Controller
Troubleshooting Access function code Cd74 to perform an ML5 self-diagnostic test.
4–51 T-372
AL996 Scrubber Rotation Fault
Cause: Feedback from the Scrubber Motor to the controller is not sensed when the motor is turning.
Component Scrubber Fuse
Troubleshooting Check to see if Scrubber Fuse is blown. Replace Fuse if necessary.
Component Scrubber Motor
Troubleshooting Run Test Mode and verify scrubber bed is turning. If back panel cannot be
removed to check, verify the scrubber amperage consumption, read at XS
contactor wire XSL1. If between 40 and 200mA, motor is rotating properly.
If no current detected, check and replace FX3. If current spiking to 350mA
for 2 seconds then dropping to 90mA, the scrubber motor is located. If
scrubber motor is locked, further inspection of the scrubber bed is
required. Unit will control CO2 with the fresh air solenoid when this alarm
occurs if scrubber inaccessible.
If Scrubber Motor not operating, follow the troubleshooting flowchart in
XtendFresh manual and take appropriate action.
LO Low Main Voltage (Function Codes Cd27-38 disabled and No alarm stored.)
Cause: This message will be alternately displayed with the setpoint whenever the supply voltage is less than
75% of its proper value.
T-372 4–52
4.11 Controller Pre-Trip Test Codes
Table 4–9 Controller Pre-Trip Test Codes
NOTE:
“Auto” or “Auto1” menu includes the: P0, P1, P2, P3, P4, P5, P6 and rSLts. “Auto2” menu includes P0, P1, P2, P3,
P4, P5, P6, P7, P8, P9, P10 and rSLts. “Auto3” menu includes P0, P1, P2, P3, P4, P5, P6, P7 and P8.
P0-0 Pre-Trip Initiated: Container identifier code, Cd18 Software Revision Number, Cd20
Configuration Display, Container Unit Model Number, & configuration database identifier
Indicator Lamps, LEDs, and CFMMYYDD are displayed in sequence.
Displays Next the unit will indicate the presence or non-presence of an RMU
according to whether any RMU inquiry messages have been received
since the unit was booted.
Units equipped with Autoslide Enabled (Cnf44) will cause the vent to seek
to its closed position, followed by two sequences of opening to 100% and
returning to the closed position. No other autoslide mode of operation will
be available until the two cycles of opening and closing have completed.
Since the system cannot recognize lights and display failures, there are no
test codes or results associated with this phase of pre-trip. To know if the
test passes the operator must observe that the LCD display elements and
the indicator lights behave as described below.
P1 Tests - Heaters Current Draw: Heater is turned on, then off. Current draw must fall within specified
range. No other system components will change state during this test.
P1-0 Heaters Turned On Heater starts in the off condition, current draw is measured, and then the
heater is turned on. After 15 seconds, the current draw is measured again.
The change in current draw is then recorded.
Test passes if the change in current draw test is in the range specified.
P1-1 Heaters Turned Off Heater starts in the off condition, current draw is measured, and then the
heater is turned on. After 15 seconds, the current draw is measured again.
The change in current draw is then recorded.
Test passes if the change in current draw test is in the range specified.
P2 Tests - Condenser Fan Current Draw: Condenser fan is turned on, then off. Current draw must fall
within specified range. No other system components will change state during this test. If the Water Pres-
sure Switch is open this test will be skipped.
P2-0 Condenser Fan On Condenser fan starts in the off condition, current draw is measured, and
condenser fan is then turned on. After 15 seconds the current draw is
measured again. The change in current draw is then recorded.
Test passes if change in current draw test is in the specified range.
P2-1 Condenser Fan Off Condenser fan is then turned off. After 10 seconds the current draw is
measured. The change in current draw is then recorded.
Test passes if change in current draw test is in the specified range.
P3 Tests - Low Speed Evaporator Fan Current Draw: The system must be equipped with a low speed
evaporator fan, as determined by CnF02, the Evaporator Fan Speed Select configuration variable. Low
speed evaporator fan is turned on, then off. Current draw must fall within specified range. No other sys-
tem components will change state during this test.
P3-0 Low Speed Evaporator Fan High speed evaporator fans will be turned on for 20 seconds, the fans will
Motors On be turned off for 4 seconds, current draw is measured, and then the low
speed evaporator fans are turned on. After 60 seconds the current draw is
measured again. The change in current draw is then recorded.
Test passes if change in current draw test is in the specified range.
P3-1 Low Speed Evaporator Fan Low speed evaporator fans are then turned off. After 10 seconds the
Motors Off current draw is measured. The change in current draw is then recorded.
Test passes if change in current draw test is in the specified range.
4–53 T-372
Table 4–9 Controller Pre-Trip Test Codes (Continued)
P4 Tests - High Speed Evaporator Fans Current Draw: High speed evaporator fans are turned on,
then off. Current draw must fall within specified range and measured current changes must exceed spec-
ified ratios. No other system components will change state during this test.
NOTE
If unit configured for single evaporator fan operation and either AL11 or AL12 is active at the start of
either test, then the test will fail immediately. If AL11 or AL12 become active during the test, then the
test will fail upon conclusion of the test.
P4-0 High Speed Evaporator Fan Evaporator fans start in the off condition, current draw is measured, then
Motors On high speed evaporator fans will be turned on. After 60 seconds the current
draw is measured again. The change in current draw is then recorded.
Test passes if change in current draw in the specified range AND
measured current changes exceed specified ratios.
If the three phase motors are configured IN, the change ratio test is
skipped.
P4-1 High Speed Evaporator Fan High speed evaporator fans are then turned off. After 10 seconds the
Motors Off current draw is measured. The change in current draw is then recorded.
Test passes if change in current draw test is in the specified range.
P5 Tests - Air Stream Temperature Sensor Tests: Tests the validity of the Air Stream Temperature Sensors.
P5-0 Supply/Return Probe Test The High Speed Evaporator Fan is turned on and run for eight minutes,
with all other outputs de-energized. A temperature comparison is made
between the return and supply probes.
Test passes if temperature comparison falls within the specified range.
NOTE
If this test fails, “P5-0” and “FAIL” will be displayed. If both Probe
tests (this test and the PRIMARY/SECONDARY) pass, display
will read “P5” “PASS.”
P5-1 Supply Probe Test This test if for units equipped with secondary supply probe only.
The temperature difference between primary supply probe and secondary
supply probe is compared.
Test passes if temperature comparison falls within the specified range.
NOTE
If this test fails, “P5-1” and “FAIL” will be displayed. If both Probe
tests (this and the SUPPLY/RETURN TEST) pass, because of
the multiple tests, the display will read “P5” “PASS.”
P5-2 Return Probe Test For units equipped with secondary return probe only.
The temperature difference between return temperature sensor (RTS) and
return temperature sensor (RRS) probe is compared.
Test passes if temperature comparison falls within the specified range.
NOTES
1. If this test fails, “P5-2” and “FAIL” will be displayed. If both
Probe tests (this test and the SUPPLY/RETURN) pass, because
of the multiple tests, the display will read “P 5,” “PASS.”
2. The results of pre-trip tests 5-0, 5-1 and 5-2 will be used to
activate or clear control probe alarms.
T-372 4–54
Table 4–9 Controller Pre-Trip Test Codes (Continued)
P5-3 Evaporator Fan Direction Test With evaporator fan running on high speed, measure the temperature
difference between the primary supply and primary return probes. Turn the
heaters on for 60 seconds then measure the temperature difference
between the primary supply and primary return probes for up to 120
additional seconds.
This is a Pass/Fail test. The test passes if differential of STS is 0.25°C
higher than RTS.
Test P5-0 must pass before this test is run.
P5-7 Primary vs. Secondary This is a Pass/Fail test of the primary evaporator temperature sensor
Evaporator Temperature (ETS1) and secondary evaporator temperature sensor (ETS2).
Sensor Test Test passes if secondary evaporator temperature sensor (ETS2) is within
+/- 0.5°C of the primary evaporator temperature sensor (ETS1).
P5-8 Future Expansion This is no longer active and will be displayed as “-----” at this time.
P5-9 Suction (Evaporator) Units equipped with a secondary Evaporator pressure transducer.
Pressure Transducer Test Test passes if suction pressure transducer (SPT) is within +/- 1.5 psi of the
evaporator pressure transducer (EPT).
Test P5-8 must pass before this test is run.
P5-10 Humidity Sensor Controller This is a Pass / Fail / Skip test of the humidity sensor configuration.
Configuration Verification Test passes if the controller configuration has humidity sensor in.
Test
Test fails if the controller configuration has humidity sensor out and Vout
is greater than 0.20 Volts for the humidity sensor.
Test is skipped if the controller configuration has the humidity sensor out
and Vout is less than 0.20 Volts.
Test P5-9 must pass before this test is run.
P5-11 Humidity Sensor Installation This is a Pass/Fail test of humidity sensor installation (sensor is present).
Verification Test Test passes if Vout is greater than 0.20 Volts for the humidity sensor.
Test fails if Vout is less than 0.20 Volts for the humidity sensor.
Test P5-10 must pass before this test is run.
P5-12 Humidity Sensor Range This is a Pass/Fail test of the Humidity Sensor Range.
Check Test Test passes if Vout for humidity sensor is between 0.33 and 4 Volts.
Test fails if Vout is outside of this range.
Test P5-11 must pass before this test is run.
P6 Tests - Refrigerant Probes, Compressor and Refrigerant Valves: Pass/Fail testing is performed
for the compressor, EEV, DUV, LIV (if equipped), ESV, and the refrigerant pressure and temperature sen-
sors.
P6-0 Discharge Thermistor Test If Alarm 64 is active the test fails. Otherwise, the test passes.
P6-1 Suction Thermistor Test If the Suction Temperature Sensor (CPSS) both is configured ON and is
invalid, the test fails. Otherwise the test passes.
P6-2 Discharge Pressure If Alarm 65 is active any time during the first 45 second period, the test
Transducer Test fails. Otherwise, the test passes.
P6-3 Suction Pressure Transducer If Alarm 66 is active the test fails. Otherwise the test passes.
Test
P6-4 Compressor Current Draw Compressor current is tested before and 10 seconds after start up. If
Test current does not increase, the test fails. P6-7 is run at the end of P6-4. If
this test fails, P6-6 is skipped.
4–55 T-372
Table 4–9 Controller Pre-Trip Test Codes (Continued)
P6-5 Compressor Leak Test Pre-trip P6-5 ensures that the compressor holds pressure. After
compressor pump up and pump down, the compressor is turned off for 62
seconds. When suction side pressure holds (less than 8 psi rise) for 10
seconds, P6-5 passes, otherwise the Compressor Leak Test fails.
See the July 2017 issue of TechLine for a procedure to assist the
technician in troubleshooting a P6-5 occurrence.
NOTE
P6-6 through P6-10 are conducted by changing status of each valve and comparing suction pressure
change and/or compressor current change with predetermined values. Tests will cause compressor and
condenser fans to cycle on and off as needed to generate the pressure required for individual pre-trip sub
tests. The compressor will start in order to build discharge pressure, followed by compressor pump down
sequence. At the conclusion of compressor pump down sequence, the compressor will shut down and
the valve test will start.
P6-6 Economizer Valve Test Passes if suction pressure increases a minimum of 4 psia when the valve
opens for 15 seconds.
P6-7 Digital Unloader Valve Test Passes if pressure and current changes are within 3 seconds of DUV
switch signal and either the pressure change or the current draw change
is above 5 psi or above 1.5A, respectively.
P6-9 Liquid Injection Valve Test (If equipped) Test passes if change of suction pressure is greater than 4
psia when the valve opens for 10 seconds. Otherwise, it fails.
P6-10 Electronic Expansion Valve The test records the suction pressure during the open valve position and
Test passes if the suction pressure increase is above 3 psi when the valve
opens for 10 seconds.
NOTE
P7-0 & P8 are included with “Auto 2 & Auto 3” only. P9-0 through P10 are included with “Auto2” only.
P7 Tests - High Pressure Tests: Unit is run at full capacity without condenser fan running to make sure
that the HPS opens and closes properly.
P7-0 High Pressure Switch (HPS) Test is skipped if sensed ambient temperature is less than 7.2°C (45°F),
Opening Test return air temperature is less than -17.8°C (0°F), or the water pressure
switch is open.
With the unit running, the condenser fan is turned off and a 900 second
(15 minute) timer is started. The right display shows Discharge Pressure
if the sensor is configured and valid, else Discharge Temperature. The unit
needs to disable Discharge Pressure limit and enable Current Limit
checks.
The test fails immediately if:
-Ambient Temperature Sensor invalid
-Composite Return Temperature Sensor invalid
-HPS is open
The test fails if:
-HPS fails to open before 900 seconds total test time.
-Evaporator or Compressor IP Alarm.
-Calculated Dome Temperature exceeds 137.78°C (280°F).
-Discharge pressure exceeds 370 psig.
-Compressor Current exceeds limits
The test passes if HPS opens within the 15 minute time limit.
T-372 4–56
Table 4–9 Controller Pre-Trip Test Codes (Continued)
P7-1 High Pressure Switch (HPS) If return temperature greater than -2.4°C, set setpoint to -5.0°C, else set
Closing Test setpoint to -30°C. Restart unit according to normal startup logic. Run unit
normally for 120 seconds.
The test passes if the high pressure switch closes within 75 seconds after
end of Test 7-0, else the test fails.
Test P7-0 must pass for this test to execute.
P8 Tests - Perishable Mode Tests: Pre-trip tests P7-0 and P7-1 must have passed or have been
skipped for these tests to execute.
P8-0 Perishable Mode Test If the control temperature is below 15.6°C, the setpoint is changed to
15.6°C, and a 180 Minute timer is started. The control will then be placed
in the equivalent of normal heating. If the control temperature is above
15.6°C. at the start of the test, then the test proceeds immediately to test
8-1. While in test 8-0 the right display will show the value of the control
temperature.
The test fails if the 180 Minute timer expires before the control temperature
reaches setpoint - 0.3°C. If the test fails, it will not auto-repeat. There is no
pass display for this test. Once the control temperature reaches setpoint,
the test proceeds to test 8-1.
P8-1 Perishable Mode Pull Down Control temperature must be at least 15.6°C (60°F).
Test / eAutoFresh CO2 The setpoint is changed to 0°C (32°F), and a 180-minute timer is started.
Sensor Calibration The left display will read “P8-1,” the right display will show the supply air
temperature. The unit will then start to pull down the temperature to the
0°C setpoint.
The test passes if the container temperature reaches setpoint before the
180-minute timer expires.
On units where the CO2 Sensor Status indicates that a CO2 sensor is
present, calibration of the CO2 sensor will be attempted during P8-1. Once
P8-1 begins, calibration will be attempted when the supply temperature
goes below 5°C. If the CO2 sensor voltage reads within the 0.95
<>1.15Vdc range before the end of P8-1, the sensor will be calibrated by
holding the CO2 zero line low for 4 seconds. Once calibration is performed,
the sensor voltage will be verified to make sure it is in the 0.95 to 1.05 Vdc
range. If the voltage is not within this range, CO2 sensor calibration fails.
P8-2 Perishable Mode Maintain Test P8-1 must pass for P8-2 to execute.
Temperature Test A fifteen minute timer is started, and the system will attempt to minimize
control temperature error (supply temperature minus setpoint) until the
timer expires. The control temperature will be sampled each minute
starting at the beginning of P8-2.
During P8-2, the left display will read “P8-2,” and the right display will show
the supply air temperature.
When the test is completed, the average control temperature error will be
compared to the pass/fail criteria.
Test passes if the average temperature error is within +/- 1.0°C.
Test fails if the average temperature error is greater than +/- 1.0°C, or if
the DataCORDER supply temperature probe is invalid. If the test fails, the
control probe temperature will be recorded as -50.0°C.
P9 Test - DTT Close and Open Test: The DTT in this control is not a physical device, with actual metallic
contacts, it is a software function that acts similar to a thermostat. Using various temperature inputs, the
DTT function determines whether a thermostat mounted on the Evaporator Coil would have OPEN or
CLOSED contacts. Primarily, the DTT function operates based on the temperature reading from the
Defrost Termination Sensor.
4–57 T-372
Table 4–9 Controller Pre-Trip Test Codes (Continued)
P9-0 DTT Closed and Open Test During P9-0 the defrost temperature sensor (DTS) reading will be
displayed on the left display. The right display will show the supply air
temperature.
The unit will run FULL COOL for 30 minutes maximum until the DTT is
considered closed. This step may not have to be executed. Once the DTT
is considered closed, the unit simulates defrost by running the heaters for
up to two hours, or until the DTT is considered open.
Test fails if:
The DTT is not considered closed after the 30 minutes of full
cooling.
HTT opens when DTT is considered closed or if return air tem-
perature rises above 48°C (120°F).
Test passes if the DTT is considered open within the 2 hour heat cycle
time limit.
P10 Tests - Frozen Mode Tests:
P10-0 Frozen Mode Heat Test If the container temperature is below 7.2°C, the setpoint is changed to
7.2°C, and a 180 Minute timer is started. The control will then be placed in
the equivalent of normal heating. If the container temperature is above
7.2°C. at the start of the test, then the test proceeds immediately to test
10-1. During this test, the control temperature will be shown on the right
display.
The test fails if the 180 Minute timer expires before the control temperature
reaches setpoint - 0.3°C. If the test fails, it will not auto-repeat. There is no
pass display for this test. Once the control temperature reaches setpoint,
the test proceeds to test 10-1.
P10-1 Frozen Mode Pulldown Test Control temperature must be at least 7.2°C (45°F)
The setpoint is changed to -17.8°C. The system will then attempt to pull
down the control temperature to setpoint using normal frozen mode
cooling. During this test, the control temperature will be shown on the right
display.
The test passes if the control temperature reaches setpoint minus 0.3°C
before the 180 minute timer expires. Otherwise, the test fails. Upon failure
and when initiated by an automatic pre-trip sequence, P10-1 will auto-
repeat once by starting P10-0 over again.
P10-2 Frozen Mode Maintain Test P10-1 must pass for this test to execute.
Temperature Test Same as for test 8-2 except the control temperature is the return probe
temperature.
The average error must be +/-1.6°C. If the DataCORDER supply
temperature probe is invalid, the test fails and the control probe
temperature will be recorded as -50°C. Upon failure and when initiated by
an automatic pre-trip sequence, P10-2 will auto-repeat by starting P10-0
over again.
Table 4–10 DataCORDER Pre-Trip Result Records
Test Title Data
1-0 Heater On Pass / Fail / Skip Result, Change in current for Phase A, B and C
1-1 Heater Off Pass / Fail / Skip Result, Change in currents for Phase A, B and C
2-0 Condenser Fan On Pass / Fail / Skip Result, Water pressure switch (WPS) - Open / Closed,
Change in currents for Phase A, B and C
2-1 Condenser Fan Off Pass / Fail / Skip Result, Change in currents for Phase A, B and C
3-0 Low Speed Evaporator Fan On Pass / Fail / Skip Result, Change in currents for Phase A, B and C
3-1 Low Speed Evaporator Fan Off Pass / Fail / Skip Result, Change in currents for Phase A, B and C
4-0 High Speed Evaporator Fan On Pass / Fail / Skip Result, Change in currents for Phase A, B and C
4-1 High Speed Evaporator Fan Off Pass / Fail / Skip Result, Change in currents for Phase A, B and C
5-0 Supply / Return Probe Test Pass / Fail / Skip Result, STS, RTS, SRS and RRS
5-1 Secondary Supply Probe (SRS) Pass / Fail / Skip
Test
5-2 Secondary Return Probe (RRS) Pass / Fail / Skip
Test
5-3 Evaporator Fan Direction Test Pass / Fail / Skip
5-7 Primary vs. Secondary Pass / Fail / Skip
Evaporator Temperature
Sensor Test
5-8 Future Expansion “-----”
5-9 Primary vs. Secondary Pass / Fail / Skip
Evaporator Pressure
Transducer Test
5-10 Humidity Sensor Controller Pass / Fail / Skip
Configuration Verification Test
5-11 Humidity Sensor Installation Pass / Fail / Skip
Verification Test
5-12 Humidity Sensor Range Check Pass / Fail / Skip
Test
6-0 Discharge Thermistor Test Pass / Fail / Skip
6-1 Suction Thermistor Test Pass / Fail / Skip
6-2 Discharge Pressure Transducer Pass / Fail / Skip
Test
6-3 Suction Pressure Transducer Pass / Fail / Skip
Test
6-4 Compressor Current Draw Test Pass / Fail / Skip
6-5 Compressor Leak Test Pass / Fail / Skip
6-6 Economizer Valve Test Pass / Fail / Skip
6-7 Digital Unloader Valve Test Pass / Fail / Skip
6-9 Liquid Injection Valve Test (If Pass / Fail / Skip
equipped)
6-10 Electronic Expansion Valve Pass / Fail / Skip
Test
7-0 High Pressure Switch Closed Pass / Fail / Skip Result, AMBS, DPT or CPT (if equipped)
Input values that component opens
4–59 T-372
Table 4–10 DataCORDER Pre-Trip Result Records (Continued)
Test Title Data
7-1 High Pressure Switch Open Pass / Fail / Skip Result, STS, DPT or CPT (if equipped)
Input values that component closes
8-0 Perishable Mode Heat Test Pass / Fail / Skip Result, STS, time it takes to heat to 16°C (60°F)
8-1 Perishable Mode Pulldown Test Pass / Fail / Skip Result, STS, time it takes to pull down to 0°C (32°F)
8-2 Perishable Mode Maintain Test Pass / Fail / Skip Result, Averaged DataCORDER supply temperature
(SRS) over last recording interval.
9-0 Defrost Test Pass / Fail / Skip Result, DTS reading at end of test, line voltage, line
frequency, time in defrost.
10-0 Frozen Mode Heat Test Pass / Fail / Skip Result, STS, time unit is in heat.
10-1 Frozen Mode Pulldown Test Pass / Fail / Skip Result, STS, time to pull down unit to -17.8°C (0°F).
10-2 Frozen Mode Maintain Test Pass / Fail / Skip Result, Averaged DataCORDER return temperature
(RRS) over last recording interval.
T-372 4–60
SECTION 5
OPERATION
5.1 Inspection
! WARNING
Beware of unannounced starting of the evaporator and condenser fans. The unit may cycle the
fans and compress or unexpectedly as control requirements dictate.
! WARNING
Do not attempt to remove power plug(s) before turning OFF the Start-Stop switch (ST), unit cir-
cuit breaker(s) and external power source.
! WARNING
Make sure the power plugs are clean and dry before connecting to power receptacle.
5–1 T-372
PROCEDURE:
1. Make sure the Start-Stop switch (ST), located on the control panel, is in “0” position (Off).
2. Make sure circuit breaker CB-1, located in the control box, and CB-2, located on the transformer, are both in
“0” position (Off).
3. Plug in and lock the 460 VAC power plug at the receptacle on the transformer.
4. Plug the 230 VAC (black) cable into a de-energized 190/230 VAC, 3-phase power source and energize the
power source.
5. Set circuit breakers CB-1 and CB-2 to “I” position (On).
6. Close and secure the control box door.
T-372 5–2
Figure 5.2 Upper Fresh Air Make Up Flow Chart
AIR AIR
FLOW FLOW
(CMH) (CMH) 60HZ
50HZ
250 300
TBAR TBAR
250 1 1/2”
200 1 1/2”
TBAR
TBAR 200 2 5/8”
2 5/8”
150 TBAR 3”
TBAR 3”
150
100
100
50 50
0
0
0 10 20 30 40 50 60 70 80 90 100
0 10 20 30 40 50 60 70 80 90 100
PERCENT OPEN
PERCENT OPEN
NOTE
The user has four minutes to make necessary adjustments to the vent setting. This time calculation
begins on the initial movement of the sensor. The vent can be moved to any position within the four min-
utes. On completion of the first four minutes, the vent is required to remain stable for the next four min-
utes. If vent position changes are detected during the four-minute stability period, AL250 will be
generated. This provides the user with the ability to change the vent setting without generating multiple
events in the DataCORDER.
5–3 T-372
5.5.1 Water-Cooled Condenser with Water Pressure Switch
1. Connect the water supply line to the inlet side of the condenser and the discharge line to the outlet side of
the condenser (see Figure 3.5).
2. Maintain a flow rate of 11 to 26 liters per minute (3 to 7 gallons per minute). The water pressure switch will
open to de-energize the condenser fan relay. The condenser fan motor will stop and will remain stopped
until the water pressure switch closes.
3. To shift to air-cooled condenser operation, disconnect the water supply and the discharge line to the water-
cooled condenser. The refrigeration unit will shift to air-cooled condenser operation when the water pressure
switch closes.
! CAUTION
When condenser water flow is below 11 lpm (3 gpm) or when water-cooled operation is not in
use, the CFS switch MUST be set to position “1” or the unit will not operate properly.
4. To shift to air-cooled condenser operation, stop the unit, set the CFS switch to position “I” and restart the
unit. Disconnect the water lines to the water-cooled condenser.
! WARNING
Make sure that the unit circuit breaker(s) CB-1 & CB-2 and the Start-Stop switch (ST) are in the
“O” (OFF) position before connecting to any electrical power source.
NOTE
The electronic phase detection system will check for proper compressor rotation within the first 30 sec-
onds. If rotation is not correct, the compressor will be stopped and restarted in the opposite direction. If
the compressor is producing unusually loud and continuous noise after the first 30 seconds of operation,
stop the unit and investigate.
T-372 5–4
5.7.3 Start Temperature Recorder in DataCORDER
1. Check and, if required, set the DataCORDER Configuration in accordance with desired recording parame-
ter. See Section 4.6.4.
2. Enter a “Trip Start” with the following instructions:
a. Press the ALT MODE key.
b. When the left display shows “dC”, press the ENTER key.
c. Use the Arrow keys to bring up function code dC30.
d. Press and hold the ENTER key for five seconds.
e. The “Trip Start” event will be entered in the DataCORDER.
! CAUTION
Pre-trip inspection should not be performed with critical temperature cargoes in the container.
! CAUTION
When PRE-TRIP key is pressed, economy, dehumidification and bulb mode will be deactivated.
At the completion of pre-trip activity, economy, dehumidification and bulb mode must be reac-
tivated.
Pre-trip diagnosis provides automatic testing of the unit components using internal measurements and comparison
logic. The program will provide a “PASS” or “FAIL” display to indicate test results.
The testing begins with access to a pre-trip selection menu. The user may have the option of selecting one of two
automatic tests.
These tests will automatically perform a series of individual pre-trip tests. The user may also scroll down to select
any of the individual tests.
When only the short sequence is configured, it will appear as “AUtO” in the display. Otherwise “AUtO1” will indicate
the short sequence and “AUtO2” will indicate the long sequence. The test short sequence will run tests P0 through
P6. The long test sequence will run tests P0 through P10.
A detailed description of the pre-trip test codes is listed in Table 4–9. If no selection is made, the pre-trip menu
selection process will terminate automatically. However, dehumidification and bulb mode must be reactivated man-
ually if required.
Scrolling down to the “rSLts” code and pressing ENTER will allow the user to scroll through the results of the last
pre-trip testing run. If no Pre-testing has been run (or an individual test has not been run) since the unit was pow-
ered up, “- - - -” will be displayed.
NOTE
Pre-trip may also be initiated via communications. The operation is the same as for the keypad initiation
described below except that should a test fail, the pre-trip mode will automatically terminate. When initi-
ated via communications, a pre-trip test may not be interrupted with an arrow key, but the pre-trip test
can be terminated with the PRE-TRIP key.
5–5 T-372
Prior to starting a pre-trip test, very the following:
• Unit voltage (Cd07) is within tolerance
• Unit amperage draw (Cd04, Cd05, Cd06) are within expected limits
• All alarms are cleared and rectified.
2. To Run an Automatic Test: Scroll through the selections by pressing the Up or Down Arrow keys to display
AUTO, AUTO 1, AUTO 2 or AUTO 3 as desired, then press the ENTER key.
• The unit will execute the series of tests without any need for direct user interface. These tests vary in
length, depending on the component under test.
• While tests are running, “P#-#” will appear on the left display; the #’s indicate the test number and sub-
test. The right display will show a countdown time in minutes and seconds, indicating the amount of time
remaining in the test.
When a Pre-trip Auto 1 test runs to completion without a failure, the unit will exit Pre-trip mode
and return to normal control operation. However, dehumidification and bulb mode must be
reactivated manually if required.
! CAUTION
When a Pre-trip Auto 2 test runs to completion without being interrupted, the unit will terminate
Pre-trip and display “Auto 2” “end.” The unit will suspend operation until the user depresses
the ENTER key!
3. When an automatic test fails, it will be repeated once. A repeated test failure will cause “FAIL” to be shown
on the right display, with the corresponding test number to the left. The user may then press the Down Arrow
key to repeat the test, the Up Arrow key to skip to the next test, or the PRE-TRIP key to terminate testing.
The unit will wait indefinitely or until the user manually enters a command.
! CAUTION
When a failure occurs during automatic testing, the unit will suspend operation awaiting oper-
ator intervention.
4. To Run an Individual Test: Scroll through the selections by pressing the Up or Down Arrow keys to display
an individual test code. Press the ENTER key when the desired test code is displayed.
• Individually selected tests, other than the LED / Display test, will perform the operations necessary to ver-
ify the operation of the component. At the conclusion, “PASS” or “FAIL” will be displayed. This message
will remain displayed for up to three minutes, during which time a user may select another test. If the
three minute time period expires, the unit will terminate Pre-trip and return to control mode operation.
• While the tests are being executed, the user may terminate the Pre-trip diagnostics by pressing and hold-
ing the PRE-TRIP key. The unit will then resume normal operation. If the user decides to terminate a test
but remain at the test selection menu, the user may press the Up Arrow key. When this is done, all test
outputs will be de-energized and the test selection menu will be displayed.
• Throughout the duration of any Pre-trip test (except the P-7 high pressure switch tests), the current limit-
ing and pressure limiting processes are both active. The current limiting process only is active for P-7.
T-372 5–6
5.8.2 Displaying Pre-Trip Test Results
1. Press the PRE-TRIP key to access the Pre-trip test selection menu. “SELCt PrtrP” will be displayed.
2. Press the Arrow keys until the message “P,” “rSLts” (Pre-trip results) is displayed.
3. Press the ENTER key. The results for all Pre-trip sub tests are available from this menu (i.e., 1-0, 1-1, etc).
The results will be displayed as “PASS” or “FAIL” for all the tests run to completion since power up. If a
test has not been run since power up, “- - - - -” will be displayed.
Once all Pre-test activity is completed, dehumidification and bulb mode must be reactivated manually if
required.
5–7 T-372
5.10 TripWise (Option)
TripWiseTM is a new premium option available for PrimeLINE and PrimeLINE with Edge units. TripWise is software
logic that runs during every voyage as often as possible to indicate whether a standard Pre-trip Inspection (PTI) is
needed and skip unless necessary. The tests run in the background and are similar to those completed as part of
the standard PTI selection, which includes the following:
• Alarm Presence • Defrost Temperature Sensor
• Evaporator Motor Current • Electronic Expansion Valve
• Heater Current • RMU Presence
• Condenser Motor Current • Compressor Test
• Compressor Current • Digital Loader / Unloader Valves
• Humidity Sensor • Economizer Valve
• Supply / Return Sensors • Temperature Control
• Evaporator Temperature and Pressure Sensors • Suction / Discharge Temperature and Pressure
COOL HEAT DEFROST IN RANGE ALARM SUPPLY RETURN COOL HEAT DEFROST IN RANGE ALARM SUPPLY RETURN
Pressing the ENTER key while “SELCt | PrtrP” is displayed will enter into the Pre-trip test menu. Pressing the
Arrow keys will navigate through the standard PTI test selections menu.
NOTE
If “-----” is displayed, the TripWise function option is not active on the unit. To add this option to the unit,
the equipment owner would need to contact their Regional Carrier Sales Manager.
4. Use the Arrow keys to toggle between “ON” and “OFF” and then press the ENTER key to select the desired
option.
5. If “ON” is selected, the display will show “dAYS”. This is the expiration time (2 through 365 in 1 day incre-
ments). Use the Arrow keys to change the parameter and then press the ENTER key to confirm.
NOTE
The expiration interval is the total maximum days allowed between the running of each test. For exam-
ple, if days are set to 30 and the low speed evaporator fan test has not run within those 30 days, the
TripWise expired message will be displayed. If the TripWise expired message is displayed, it is recom-
mended to Pre-trip the unit following customer specific guidelines prior to the next trip.
T-372 5–8
5.10.3 TripWise Status Event
A TripWise status event will be recorded in the DataCORDER recorder when the PTI is selected. In the current
DataLINE software release, the event will show the status of the unit.
In DataLINE, perform an all data download by selecting from the drop down menu “TripWise Summary” and then
select a date in “User Logged Events” as shown in the Figure below.
5–9 T-372
This will generate the status / results in a DataLINE TripWise Summary Report as shown in the Figure below.
Status
Results
T-372 5–10
5.11 Automatic Cold Treatment (Option)
Cold Treatment has been employed as an effective post-harvest method for the control of Mediterranean and certain
other tropical fruit flies. Exposing infested fruit to temperatures of 2.2°C (3.6°F) or below for specific time periods
results in the mortality of various life stages for this group of insects.
Automated Cold Treatment (ACT) in the Carrier Transicold unit is a method to simplify the task of completing cold
treatment by automating the process of changing the setpoints. ACT is set up through function code Cd51. Refer to
Function Code table in this manual for Cd51 menu processing and displays.
NOTE
ACT, setup with Cd51, and Automatic Setpoint Change (ASC), setup with Cd53, will not work simultane-
ously. Setting one will deactivate the other.
5. “trEAt" is now displayed in the left display and the right will be flashing the last setting (shown as XX.X°C).
Use the Arrow keys to select the desired cold treatment setpoint and press the ENTER key.
NOTE
"trEAt" is the maximum value that the USDA probes need to remain below, to pass the Cold Treatment pro-
tocol. For instance, if the treat value is set at 35.0°F (1.7°C) then the USDA probe temperatures must
remain below 35.0°F (1.7°C) to pass.
6. "dAyS" is now displayed in the left display and the right will be flashing. Use the Arrow keys to select the
desired days for cold treatment and press the ENTER key.
7. "ProbE" is now displayed in the left display and the right will display the probe numbers that are connected.
Press the ENTER key. For instance, if "1234" is displayed, then all four of the probes are connected.
5–11 T-372
8. "SPnEW" is now displayed in the left display and the right will be flashing. Use the Arrow keys to select the
desired setpoint after the cold treatment process has successfully completed and press the ENTER key.
This would be the final temperature prior to the delivery of the cargo.
9. Cd51 is now displayed in the left display and the right will display days / hours remaining in cold treatment.
10. The unit will start to countdown once all detected USDA probes have reached the specified cold treatment
temperature. The cold treatment process will continue until the specified number of days is reached. During
operation, Cd51 will show the number of days and hours remaining in the cold treatment.
NOTE
Once the cold treatment process has been initiated, setpoint change via the keypad is disabled.
11. While the unit is operating in ACT mode, the left hand display will alternate between "COLd" and setpoint.
The right hand display will alternate between "trEAt" and the cargo temperature. Once the treatment time
has been completed, the setpoint temperature will increase to the "SPnEW" setting chosen in step 8.
12. When the cold treatment process is complete, the "SPnEW" setpoint will be displayed in the left hand dis-
play and cargo temperature in the right hand display, alternating with "COLd" "Done". "COLd" "Done" will
continue to alternate with the setpoint and cargo temperature until ACT is turned off.
T-372 5–12
5.12 Automatic Setpoint Change (ASC) Cd53
Automatic Setpoint Change (ASC) allows up to 6 setpoint changes to be pre-programmed over defined periods of
time using Cd53.
1. Press the CODE SELECT key.
2. Use the Arrow keys to scroll to Cd53, then press the ENTER key.
3. Use the Arrow keys to scroll to ON, then press the ENTER key. If ASC is already ON, selecting OFF will ter-
minate ASC.
4. Select the desired number of setpoint changes (nSC) by scrolling through the available “flashing” options (1
– 6) in the right display, then press the ENTER key.
5. Select the initial setpoint: With (SP 0) in the left display, select by scrolling to the desired “flashing” setpoint
in the right display and press ENTER.
6. Select the days desired for initial setpoint (SP 0): With (DAY 0) in the left display, select by scrolling to the
desired “flashing” days (1 to 99) in the right display and press ENTER.
7. Select the next setpoint (SP 1): With (SP 1) in the left display, select by scrolling to the desired “flashing” set-
point in the right display and press ENTER.
8. Continue to select each additional setpoint.
9. Select a final setpoint (SP x): With (SP x) in the left display, select by scrolling to the desired “flashing” set-
point in the right display and press ENTER.
While the unit is operating in ASC mode, the left hand display will alternate between current unit setpoint and
“ASC”. The right hand display will alternate between current control temperature and “ACtvE”. The user can deter-
mine the amount of time left at the current setpoint by selecting Cd53. The amount of time left will be displayed in
the right display (XX (days) / XX (hours). By sequentially pressing ENTER, set parameters can be viewed.
At completion of ASC mode, the left hand display will alternate between current unit setpoint “ASC”. The right hand
display will alternate between current control temperature and “Done”.
The display will remain this way until ASC is turned off. The user can determine the date of completion by selecting
Cd53. With (done) in the left display, the date of completion will be displayed in the right display (Month / Day).
ASC can be manually turned off by selecting Cd53, scrolling to “Off” and pressing the ENTER key.
ACS will be automatically turned off after three days without power, or if a Pre-trip is initiated.
ACS (Cd53) will work independently of Automatic Cold Treatment (ACT) (Cd51). Setting one deactivates the other.
5–13 T-372
SECTION 6
TROUBLESHOOTING
6–1 T-372
Condition Possible Cause Remedy / Reference
Section
6.3 Unit Runs but has Insufficient Cooling
Abnormal pressures Section 6.7
Abnormal temperatures Section 6.15
Abnormal currents Section 6.16
Controller malfunction Section 6.9
Evaporator fan or motor defective Section 7.17
Refrigeration system
Compressor service valves or liquid line shutoff valve Open valves completely
partially closed
Frost on coil Section 6.10
Digital unloader valve stuck open Replace
Electronic expansion valve Replace
6.4 Unit will not Heat or has Insufficient Heating
Start-Stop switch (ST) OFF or defective Check
No operation of any kind Circuit breaker OFF or defective Check
External power source OFF Turn ON
Circuit breaker or fuse defective Replace
Control Transformer defective Replace
No control power Evaporator fan internal motor protector open Section 7.17
Heat relay defective Check
Heater termination thermostat open Section 7.15
Heater(s) defective Section 7.15
Heater contactor or coil defective Replace
Evaporator fan motor(s) defective or rotating back- Section 7.15 / Section 7.17
wards
Unit will not heat or has Evaporator fan motor contactor defective Replace
insufficient heat
Controller malfunction Section 6.9
Defective wiring Replace
Loose terminal connections Tighten
Low line voltage Section 3.3
6.5 Unit will not Terminate Heating
Controller improperly set Reset
Controller malfunction Section 6.9
Unit fails to stop heating
Heater termination thermostat remains closed along Section 7.15
with the heat relay
6.6 Unit will not Defrost Properly
Defrost timer malfunction (Cd27) Table 4–7
Loose terminal connections Tighten
Will not initiate defrost Defective wiring Replace
automatically Defrost temperature sensor defective or heat termina- Replace
tion thermostat open
Heater contactor or coil defective Replace
T-372 6–2
Condition Possible Cause Remedy / Reference
Section
Manual defrost switch defective Replace
Will not initiate defrost
Keypad is defective Replace
manually
Defrost temperature sensor open Replace
Initiates but relay (DR) drops Low line voltage Section 3.3
out
Heater contactor or coil defective Replace
Initiates but does not defrost
Heater(s) burned out Section 7.15
Frequent defrost Wet load Normal
6.7 Abnormal Pressures
Condenser coil dirty Section 7.11.2
Condenser fan rotating backwards Section 7.11
Condenser fan inoperative Section 7.12
High discharge pressure
Refrigerant overcharge or non-condensibles Section 7.3
Discharge service valve partially closed Open
Electronic expansion valve (EEV) control malfunction Replace
Incorrect software and/or controller configuration Check
Failed suction pressure transducer (SPT) or evapora- Replace
tor pressure transducer (EPT)
Suction service valve partially closed\ Open
Filter drier partially plugged Section 7.14
Low suction pressure Low refrigerant charge Section 7.3
No evaporator air flow or restricted air flow Section 7.15
Excessive frost on evaporator coil Section 6.6
Evaporator fan(s) rotating backwards Section 7.17.3
EEV control malfunction Replace
Failed digital unloader valve (DUV) Replace
6–3 T-372
Condition Possible Cause Remedy / Reference
Section
6.9 Microprocessor Malfunction
Incorrect software and/or controller configuration Check
Defective sensor Section 7.28
Will not control
Defective wiring Check
Low refrigerant charge Section 7.3
6.10 No Evaporator Air Flow or Restricted Air Flow
Frost on coil Section 6.6
Evaporator coil blocked
Dirty coil Section 7.15
Evaporator fan motor internal protector open Section 7.17
No or partial evaporator air Evaporator fan motor(s) defective Section 7.17
flow Evaporator fan(s) loose or defective Section 7.17
Evaporator fan contactor defective Replace
6.11 Electronic Expansion Valve Malfunction
Incorrect software and/or controller configuration Check
Failed suction pressure transducer (SPT) or evapora- Replace
tor pressure transducer (EPT)
Suction service valve partially closed Open
Filter drier partially plugged Section 7.14
Low refrigerant charge Section 7.3
Low suction pressure
No evaporator air flow or restricted air flow Section 7.15
Excessive frost on evaporator coil Section 6.6
Evaporator fan(s) rotating backwards Section 7.17.3
EEV control malfunction Section 7.19
Failed digital unloader valve (DUV) Replace
Loose or insufficiently clamped sensor Replace
Foreign material in valve Section 7.19
Failed suction pressure transducer (SPT) or evapora- Replace
High suction pressure with tor pressure transducer (EPT)
low superheat EEV control malfunction Replace
Improperly seated powerhead Ensure powerhead is
locked and in place
Failed suction pressure transducer (SPT) or evapora- Replace
Liquid slugging in tor pressure transducer (EPT)
compressor
Failed EEV Replace
6.12 Autotransformer Malfunction
Circuit breaker (CB-1 or CB-2) tripped Check
Autotransformer defective Section 7.26
Unit will not start
Power source not turned ON Check
460 VAC power plug is not inserted into the receptacle Section 5.2.1
T-372 6–4
Condition Possible Cause Remedy / Reference
Section
6.13 Water-Cooled Condenser or Water Pressure Switch
Dirty coil
High discharge pressure Section 7.13
Non-condensibles
Condenser fan starts and Water pressure switch malfunction Check
stops Water supply interruption Check
6.14 Compressor Operating in Reverse
NOTE
The compressor may start in reverse for up to 10 seconds to determine correct phase rotation
if required for phase detection.
! CAUTION
Allowing the scroll compressor to operate in reverse for more than two minutes will result in
internal compressor damage. Turn the start- stop switch OFF immediately.
Incorrect wiring of compressor
Electrical Incorrect wiring of compressor contactor(s) Check
Incorrect wiring of current sensor
6.15 Abnormal Temperatures
Condenser coil dirty Section 7.11.2
Condenser fan rotating backwards Section 7.12
Condenser fan inoperative Section 7.12.1
Refrigerant overcharge or non-condensibles Section 7.3
Discharge service valve partially closed Open
Electronic expansion valve (EEV) control malfunction Replace
High discharge temperature Failed suction pressure transducer (SPT) or evapora- Replace
tor pressure transducer (EPT)
Discharge temperature sensor drifting high Replace
Failed economizer expansion valve, economizer coil, Replace
or economizer solenoid valve
Plugged economizer expansion valve, economizer Replace
coil, or economizer solenoid valve
Loose or insufficiently clamped sensor Replace
6.16 Abnormal Currents
Unit reads abnormal currents Current sensor wiring Check
6–5 T-372
SECTION 7
SERVICE
! WARNING
EXPLOSION HAZARD Failure to follow this WARNING can result in death, serious personal
injury and / or property damage. Never use air or gas mixtures containing oxygen (O2) for leak
testing or operating the product. Charge only with refrigerants R-134a or R-513A as specified
for the unit model number: Refrigerant must conform to AHRI Standard 700 specification.
NOTE
Use a refrigerant recovery system whenever removing refrigerant. When working with refrigerants you must
comply with all local government environmental laws. In the U.S.A., refer to EPA section 608.
NOTE
Annual maintenance procedures for PrimeLINE units 69NT40-561 can be found in the 62-10327 Annual
Maintenance Manual, located in the Literature section of the Container Refrigeration website. To find the
manual from the Literature section, click on Container Units > All Container Units > Operation.
2 3
1 4
7 6 5
7–1 T-372
When both valves are backseated (all the way out), high pressure vapor will flow into the low side.
When the suction pressure valve (1) is open and the discharge pressure valve (4) shut, the system can be charged
through the utility connection (6). Oil can also be added to the system.
A manifold gauge / hose set with self-sealing hoses (see Figure 7.2) is required for service of the models covered
within this manual. The manifold gauge/hose set is available from Carrier Transicold (part number 07-00294-00,
which includes items 1 through 6, Figure 7.2).
NOTE
It is recommended that the manifold gauge set be dedicated to specified refrigerant (R-134a or R-513A).
4 3
4
7 5
2
1) RED Refrigeration and/or Evacuation 5) High Side Field Service Coupling (Red
Hose (SAE J2196/R-134a) Knob)
2) Hose Fitting (0.5-16 Acme) 6) BLUE Refrigeration and/or Evacuation
3) YELLOW Refrigeration and/or Hose (SAE J2196/R-134a)
Evacuation Hose (SAE J2196/R-134a) 7) Low Side Field Service Coupling (Blue
4) Hose Fitting with O-ring (M14 x 1.5) Knob)
-----
T-372 7–2
With the valve stem midway between frontseat and backseat, both of the service valve connections are open to the
access valve path. For example, the valve stem is first fully backseated when connecting a manifold gauge to mea-
sure pressure. Then, the valve is opened 1/4 to 1/2 turn to measure the pressure.
1
2
5
! CAUTION
To prevent trapping liquid refrigerant in the manifold gauge set, make sure set is brought to
suction pressure before disconnecting.
7–3 T-372
! CAUTION
The scroll compressor achieves low suction pressure very quickly. Do not use the compressor to
evacuate the system below 0 psig. Never operate the compressor with the suction or discharge
service valves closed (frontseated). Internal damage will result from operating the compressor in
a deep vacuum.
! WARNING
EXPLOSION HAZARD Failure to follow this WARNING can result in death, serious personal
injury and / or property damage. Never use air or gas mixtures containing oxygen (O2) for leak
testing or operating the product. Charge only with refrigerants R-134a or R-513A as specified
for the unit model number: Refrigerant must conform to AHRI Standard 700 specification.
1. The recommended procedure for finding leaks in a system is with an appropriate electronic leak detector.
Testing joints with soapsuds is satisfactory only for locating large leaks.
2. If the system is without refrigerant, charge the system with refrigerant to build up pressure between 2.1 to
3.5 bar (30.5 to 50.8 psig). To ensure complete pressurization of the system, refrigerant should be charged
at the compressor suction valve and the liquid line service valve. Remove refrigerant cylinder and leak-
check all connections.
NOTE
Only refrigerant R-134a or R-513A, as specified for the unit model number, should be used to pressurize the
system. Any other gas or vapor will contaminate the system, which will require additional purging and evacuation
of the system.
3. If required, remove refrigerant using a refrigerant recovery system and repair any leaks. Check for leaks.
4. Evacuate and dehydrate the unit. See Section 7.6.
5. Charge unit. See Section 7.7.
T-372 7–4
7.6 Evacuation and Dehydration
7.6.1 General
Moisture is detrimental to refrigeration systems. The presence of moisture in a refrigeration system can have many
undesirable effects. The most common are copper plating, acid sludge formation, “freezing-up” of metering devices
by free water, and formation of acids, resulting in metal corrosion.
7.6.2 Preparation
1. Evacuate and dehydrate only after completing a pressure leak test. See Section 7.5.
2. Essential tools to properly evacuate and dehydrate any system include a vacuum pump (8m3/hr = 5 cfm
volume displacement) and an electronic vacuum gauge. The pump is available from Carrier Transicold, P/N
07-00176-11. The micron gauge is P/N 07-00414-00.
3. If possible, keep the ambient temperature above 15.6°C (60°F) to speed evaporation of moisture. If the
ambient temperature is lower than 15.6°C (60°F), ice might form before moisture removal is complete. Heat
lamps or alternate sources of heat may be used to raise the system temperature.
4. Additional time may be saved during a complete system pump down by replacing the filter drier with a
section of copper tubing and the appropriate fittings. Installation of a new drier may be performed during the
charging procedure.
11 1
10
9
3
8
S D
6 5
NOTE
Refer to Partial System procedure for information pertaining to partial system evacuation and dehydration.
1. Remove all refrigerant using a refrigerant recovery system.
7–5 T-372
2. The recommended method to evacuate and dehydrate the system is to connect evacuation hoses at the
compressor suction and liquid line service valve (see Figure 7.4). Make sure the service hoses are suited
for evacuation purposes.
NOTE
To prevent the area between the Economizer Solenoid Valve (ESV) and the compressor from being isolated
during evacuation, it is necessary to open the ESV using a magnet tool (Carrier Transicold P/N 07-00512-00).
3. Remove the ESV coil from the valve body. Place the magnet tool over the valve stem. An audible click will
be heard when the ESV opens.
NOTE
Make sure to replace the valve coil before restating the unit. Starting the unit with the coil removed from the
valve will burn out the coil.
4. Test the evacuation setup for leaks by backseating the unit service valves and drawing a deep vacuum with
the vacuum pump and gauge valves open. Shut off the pump and check to see if the vacuum holds. Repair
leaks if necessary.
5. Midseat the refrigerant system service valves.
6. Open the vacuum pump and electronic vacuum gauge valves, if they are not already open. Start the vacuum
pump. Evacuate the unit until the electronic vacuum gauge indicates 2000 microns. Close the electronic
vacuum gauge and vacuum pump valves. Shut off the vacuum pump. Wait a few minutes to be sure the
vacuum holds.
7. Break the vacuum with either clean refrigerant (R-134a or R-513A as specified for the unit model number) or
dry nitrogen. Raise system pressure to roughly 0.14 bar (2 psig), monitoring it with the compound gauge.
8. If refrigerant was used, remove using a refrigerant recovery system. If nitrogen was used, relieve the pressure.
9. Repeat steps 6 and 7 one time.
10. Remove the copper tubing and change the filter drier. Evacuate unit to 500 microns. Close the electronic
vacuum gauge and vacuum pump valves. Shut off the vacuum pump. Wait five minutes to see if vacuum
holds. This procedure checks for residual moisture and/or leaks.
11. With a vacuum still in the unit, the refrigerant charge may be drawn into the system from a refrigerant
container on weight scales.
! WARNING
EXPLOSION HAZARD Failure to follow this WARNING can result in death, serious personal
injury and / or property damage. Never use air or gases containing oxygen (O2) for leak testing
or operating the product. Charge only with refrigerants R-134a or R-513A as specified for the
unit model number: Refrigerant must conform to AHRI Standard 700 specification.
NOTE
Use a refrigerant recovery system whenever removing refrigerant. When working with refrigerants you must
comply with all local government environmental laws. In the U.S.A., refer to EPA Section 608.
1. Connect the gauge manifold to the compressor discharge and suction service valves. For units operating on
a water-cooled condenser, change over to air-cooled operation.
T-372 7–6
2. Bring the container temperature to approximately 0°C (32°F) or below. Then set the controller setpoint to -
25°C (-13°F).
3. Partially block the condenser coil inlet air. If covering the lower portion of the coil is not sufficient, remove the
left hand infill panel and cover the left side of the coil. Increase the area blocked until the compressor
discharge pressure is raised to approximately 12.8 bar (185 psig).
4. On units equipped with a receiver, the level should be between the glasses. On units equipped with a
watercooled condenser, the level should be at the center of the glass. If the refrigerant level is not correct,
see Section 7.7.2 and Section 7.7.3 to add or remove refrigerant as required.
! CAUTION
When charging the unit with R-513A refrigerant, charge as a liquid only. R-513A is an azeotrope
blend containing R-1234yf and R-134a. Charging or topping off as a vapor will result in an
incorrect mixture of blend in the system.
6. Upon completion, change the refrigerant label (Carrier P/N 76-50235-00) on the front of the unit indicating
the change in refrigerant.
7–7 T-372
7.9 Compressor
! WARNING
Make sure power to the unit is OFF and power plug disconnected before replacing the compressor.
! WARNING
Before disassembly of the compressor, be sure to relieve the internal pressure very carefully
by slightly loosening the couplings to break the seal.
! CAUTION
The scroll compressor achieves low suction pressure very quickly. Do not use the compressor
to evacuate the system below 0 psig. Never operate the compressor with the suction or
discharge service valves closed (frontseated). Internal damage will result from operating the
compressor in a deep vacuum.
! CAUTION
The PrimeLINE unit has a hermetically sealed compressor that should not be opened and/or
repaired. Doing so can cause a loss in performance and premature system failure due to the
precision machinery and assembly required within the compressor. To repair the unit, remove
the faulty compressor and replace with an approved Carrier compressor. If the return of the
compressor is not required, follow local waste collection & recycling regulations in discarding
the compressor.
NOTICE
Replacement compressors are supplied without oil.
NOTE
If the compressor is not operational, frontseat the suction and discharge service valves and go to step 5 below.
2. Frontseat the manual liquid line valve and allow the unit to pull-down to 0.1 kg/cm2 (1 psig).
3. Place the Start-Stop switch (ST) to “0”, turn the unit circuit breaker (CB-1) OFF, and disconnect power to the unit.
4. Frontseat the discharge and suction service valves.
5. Remove all remaining refrigerant from the compressor using a refrigerant recovery system.
6. Remove the compressor terminal cover, disconnect the ground wire and pull the cable plug from the
compressor terminals. Install the terminal cover back after removing the power cable.
NOTE
Inspect the power cable (plug) terminals to ensure they are not deformed or have any signs of heat or
arcing. If any damage is noted, replace the power cable.
7. Remove the Rotalock fittings from the suction and discharge service connections, and uncouple the
unloader and economizer lines from the compressor.
8. Cut the dome ambient temperature sensor (CPDS) wires. The replacement compressor comes with a
CPDS already assembled.
9. Remove and save the compressor base mounting bolts. Discard the four top resilient mounts and washers.
10. Remove (slide out) the old compressor from the unit.
T-372 7–8
11. Inspect the compressor base plate for wear. Replace, if necessary.
12. Wire tie the compressor base plate to the compressor, and slide the new compressor into the unit. (See
Figure 7.5).
1 6
2
7
3
10
4
11
12
13
5
14
18. Connect (butt-splice and heat shrink) the new compressor dome temperature sensor with the old sensor
wires removed in step 8. Wire-tie any loose wiring as appropriate.
19. Evacuate the compressor to 1000 microns if the unit was pumped down before the replaced compressor
was removed. Otherwise, evacuate the complete unit and charge it with refrigerant (see Section 7.6.1 and
Section 7.7.1).
7–9 T-372
20. Open the compressor terminal cover and connect the compressor power cable following the steps below:
a. Liberally coat the orange gasket surfaces with the Krytox lubricant.
b. Install the orange gasket part onto the compressor fusite with the grooved or threaded side out. Ensure
that the gasket is seated onto the fusite base.
c. Coat the inside of the power plug (female) connector pins with the Krytox lubricant, and insert the plug
onto the compressor terminal connections. Make sure the orange gasket has bottomed out onto the
fusite and fits securely onto the terminal pins while fully inserted into the orange plug.
d. Connect the green ground wire to the grounding tab located inside the terminal box of the compressor
using the self-tapping grounding screw. Close the compressor terminal box using the terminal cover
removed in step 20.
21. Backseat all service valves, connect the power to the unit and run for at least 20 minutes.
22. Perform a leak check of the system.
! WARNING
Do not use a nitrogen cylinder without a pressure regulator.
NOTE
The high pressure switch is non-adjustable.
1. Remove switch as outlined in Figure 7.10.2.
2. Connect ohmmeter or continuity light across switch terminals. Ohm meter will indicate no resistance or
continuity light will be illuminated if the switch closed after relieving compressor pressure.
3. Connect hose to a cylinder of dry nitrogen (see Figure 7.6).
1
5
2
6
3
7
4
T-372 7–10
7.10.2 Replacing High Pressure Switch
1. Remove the refrigerant charge.
2. Disconnect wiring from defective switch. The high pressure switch is located on the discharge connection or
line and is removed by turning counterclockwise.
3. Install a new high pressure switch after verifying switch settings.
4. Evacuate, dehydrate and recharge the system.
5. Start the unit, verify refrigeration charge and oil level.
! WARNING
Do not remove the condenser fan grille before turning power OFF and disconnecting the power plug.
1. Make sure the unit is powered off and the plug is disconnected.
2. Remove the condenser fan grille.
3. Starting from the top of the coil, use a water hose with a nozzle to wash the coil from the inside out.
4. Systematically wash across the inside top face of the coil until the water runs clean.
5. Wash down the center section, and then through the bottom of the coil. Continue washing until the water
runs clear.
6. After the coil is clean, rinse the condenser fan to remove any dirt build up from the blades.
7. Replace the condenser fan grille ensuring that it is centered around the fan.
! WARNING
Do not remove the condenser fan grille before turning power OFF and disconnecting the power plug.
2. Remove the condenser fan grille. Retain all bolts and washers for reuse.
3. Remove the condenser fan.
4. Remove the infill panels to the left and right of the condenser fan shroud.
5. Remove the condenser fan shroud.
6. Unplug the condenser fan motor.
7. Remove and retain sufficient putty from around the motor wire harness to allow the harness to be slid back
through the side support bracket.
8. Cut the top and bottom drain lines midway between the side support bracket and the first cable tie,
approximately 150mm (6”) from the side support bracket.
9. Remove and retain sufficient putty from around the drain lines to allow the tubes to be slid back through the
side support bracket.
10. Remove the filter drier.
7–11 T-372
11. Unbraze the inlet connection to the coil.
12. Remove the cushion clamps securing the liquid line to the top and bottom receiver brackets. Retain all
clamps and securing hardware.
13. Place a support under the condenser coil before releasing the coil from the frame.
14. Remove the lower mounting bracket bolts from the inside of the coil.
15. Remove the top mounting bracket bolts and grille extension mount from inside the coil.
16. Remove the side support bracket mounting bolts.
17. Slide the condenser assembly with the receiver out of the unit.
T-372 7–12
Figure 7.7 Condenser Fan Position
37mm (1.5”)
Fan
Shroud
19. Use Loctite “H” on the fan set screws, and tighten.
20. Refit left and right infill panels.
21. Refit the condenser fan grille, ensuring the grille is properly centered around the condenser fan.
22. Evacuate the entire unit. See Section 7.6.
23. Recharge the unit with the charge shown on the unit serial plate. See Section 7.7. It is important for proper
unit operation that the charge is weighed into the unit.
! WARNING
Do not remove the condenser fan grille before turning power OFF and disconnecting the power plug.
1. Remove the condenser fan grille. Retain all bolts and washers for reuse.
2. Remove the condenser fan by loosening the two set screws.
3. Disconnect the condenser fan motor wiring.
! CAUTION
Take necessary steps (place plywood over coil or use sling on motor) to prevent motor from
falling into condenser coil.
4. Note the number of shims on each side of the motor as the same configuration will be required to refit the
new motor.
5. Remove the fan motor mounting hardware and remove the motor.
6. Loosely mount the new motor using new lock nuts.
7. Connect the fan motor wiring to the new fan motor.
8. Replace the shims in the same configuration as they were removed.
9. Tighten the fan motor mounting bolts to properly secure the motor.
7–13 T-372
10. To make sure that the motor is aligned properly, slide the condenser fan onto the motor shaft reversed but
do not secure.
11. Rotate the fan to make sure the fan blades do not contact the shroud:
• If the fan motor is misaligned vertically, add or remove shims to align.
• If the fan motor is not properly centered, loosen the mounting bolts, and adjust the motor position on the
bracket, and then secure the motor.
12. Remove the condenser fan, and connect the fan motor wiring to the fan motor.
13. Place the condenser fan on the shaft facing the correct direction. Adjust the fan to the correct position,
37mm (1.5”) from the fan shroud, see Figure 7.7.
14. Use Loctite “H” on the fan set screws, and tighten.
15. Refit the left and right infill panels.
16. Refit the condenser fan grille, ensuring the grille is properly centered around condenser fan.
NOTE
When Oakite Compound No. 32 is used for the first time, the local Oakite technical service representative
should be called in for suggestions in planning the procedure. The representative will advise the reader on
how to do the work with a minimum dismantling of equipment: how to estimate the time and amount of
compound required; how to prepare the solution; how to control and conclude the de-scaling operation by
rinsing and neutralizing equipment before putting it back into service. The representative’s knowledge of
metals, types of scale, water conditions and de-scaling techniques will be highly useful.
T-372 7–14
9. Flush.
10. Put the unit back in service under normal load and check head (discharge) pressure.
! WARNING
Oakite No. 32 is an acid. Be sure that the acid is slowly added to the water. DO NOT PUT
WATER INTO THE ACID - this will cause spattering and excessive heat.
! WARNING
Wear rubber gloves and wash the solution from the skin immediately if accidental contact
occurs. Do not allow the solution to splash onto concrete.
5. Fill the tubes with this solution by filling from the bottom. See Figure 7.8.
5 7
1
6 8
3
10
4 11
12
1) Pump 7) Vent
2) Suction 8) Close vent pipe valve when pump is
3) Tank running
4) Pump support 9) Condenser
5) Priming Connection (Centrifugal pump 10) Remove water regulating valve
50 gpm at 35’ head) 11) Return
6) Globe valves 12) Fine mesh screen
-----
NOTE
It is important to provide a vent at the top for escaping gas.
7–15 T-372
6. Allow the Oakite No. 32 solution to soak in the tube coils for several hours, periodically pump-circulating it
with an acid-proof pump.
An alternate method may be used whereby a pail (see Figure 7.9) filled with the solution and attached
to the coils by a hose can serve the same purpose by filling and draining. The solution must contact the
scale at every point for thorough de-scaling. Air pockets in the solution should be avoided by regularly
opening the vent to release gas. Keep flames away from the vent gases.
7. The time required for de-scaling will vary, depending upon the extent of the deposits. One way to determine
when de-scaling has been completed is to titrate the solution periodically, using titrating equipment provided
free by the Oakite technical service representative. As scale is being dissolved, titrate readings will indicate
that the Oakite No. 32 solution is losing strength. When the reading remains constant for a reasonable time,
this is an indication that scale has been dissolved.
Vent pipe
3’ to 4’
Condenser
8. When de-scaling is complete, drain the solution and flush thoroughly with water.
NOTE
If condenser cooling water is not being used as drinking water or is not re-circulated in a closed or tower system,
neutralizing is not necessary.
9. Following the water flush, circulate a 56.7 gram (2 ounce) per 3.785 liter (1 U.S. gallon) solution of Oakite
Aluminum Cleaner® 164 through the tubes to neutralize. Drain this solution.
10. Flush the tubes thoroughly with fresh water.
11. Put the unit back in service and operate under normal load. Check the head pressure. If normal, a thorough
de-scaling has been achieved.
What You Can Do For Further Help:
Contact the Engineering and Service Department of OAKITE PRODUCTS CO., 675 Central Avenue, New Provi-
dence, NJ 07974 U.S.A. (or visit www.oakite.com)
T-372 7–16
7.14.2 Replacing the Filter Drier:
1. Pump down the unit (see Section 7.4). If the unit is not equipped with service values, evacuate the unit.
Then replace filter drier.
2. Evacuate the low side in accordance with Section 7.6.
3. After unit is in operation, inspect for moisture in the system and check charge.
! WARNING
Always turn OFF the unit circuit breakers (CB-1 & CB-2) and disconnect main power supply
before working on moving parts.
2. With power OFF and power plug removed, remove the screws securing the panel covering the evaporator
section (upper panel).
3. Disconnect the defrost heater wiring.
4. Remove the mounting hardware from the coil.
5. Unsolder the two coil connections, one at the distributor and the other at the coil header.
6. Disconnect the defrost temperature sensor (see Section 7.28) from the coil.
7. Remove middle coil support.
8. After defective coil is removed from unit, remove defrost heaters and install on replacement coil.
9. Install coil assembly by reversing above steps.
10. Leak check connections. Evacuate and add refrigerant charge.
7–17 T-372
The heaters are wired directly back to the contactor and if a heater failure occurs during a trip, the heater set containing
that heater may be disconnected at the contactor.
The next pre-trip (P1) will detect that a heater set has been disconnected and indicate that the failed heater should be
replaced.
! WARNING
Always turn OFF the unit circuit breakers (CB-1 & CB-2) and disconnect main power supply
before working on moving parts.
All of the checks performed during this procedure should be carried out using a 500v Meg-ohm tester.
1. Connect the ground wire from the insulation tester to a fixed ground point, preferably the ground plate in the
control box.
2. At the load side of the heater contactor, check the insulation resistance to ground.
If readings are > 2 Mohm, then the heaters are operating properly and no action is needed.
If readings are < 1 Mohm, then the faulty heater needs to be identified. Proceed to step 3 for units with a
heater access panel or step 4 for units without a heater access panel.
If readings are between 1 and 2 Mohm, then the heaters need to be re-tested with the following steps:
a. Reconnect the unit to power and power the unit on.
b. Set the unit set point to a minimum of 10°C higher than the current temperature of the container. Allow
the unit to go into heat mode, reach the temperature set point and maintain for 10-15 minutes.
c. Power the unit off. Allow the unit to cool to ambient temperature.
d. Connect the ground wire from the insulation tester to a fixed ground point, preferably the ground plate in
the control box.
e. At the load side of the heater contactor, check the insulation resistance to ground.
If readings are > 1 Mohm, then the heaters are operating properly and no action is needed.
If readings are < 1 Mohm, then the faulty heater needs to be identified. Proceed to step 3 for units
with a heater access panel or step 4 for units without a heater access panel.
3. Identify the faulty heater(s) for units with a heater access panel:
a. Open the access panel and cut out all wire splices to isolate all heaters inside of the unit.
b. Repeat the Megger test on each individual heater. Connect the ground clip to the outer metal sheath of
the heater and the test clip to one of the wires from the same heater.
c. Replace any heater where the readings are < 1 Mohm.
4. Identify the faulty heater(s) for units without a heater access panel:
a. Remove all six connections from the Heater (HR) contactor load side, which splits the six heaters into
three separate pairs.
b. Identify the following three wires: DHTL, DHML, DHBL. There is one from each load connection.
c. Repeat the Megger test on each pair of heaters to identify the faulty heater pair. Connect the ground clip
from the insulation tester to a fixed ground point on the unit, preferably the ground plate in the control
box. Connect the test clip to one of the wires stated above.
d. Test all three wires and replace any heater pair that has readings < 1 Mohm.
5. If the unit is loaded, and the heater can not be immediately replaced, perform the following steps:
a. Identify the wire at the opposite end of the faulty heater pair: DHTL - DHTR, DHML - DHMR, DHBL -
DHBR.
b. Isolate the two wires.
T-372 7–18
c. Reconnect the remaining good wiring pairs to their original connections.
d. The unit will fail the PTI test P1-0 at the next pre-trip inspection. Repair action can be taken at that time.
! WARNING
Before servicing the unit, make sure the circuit breakers (CB-1 & CB-2) and start-stop switch
(ST) are in the OFF position and the power plug is disconnected.
a. With the heater pair identified, remove the upper back panel inside the container.
b. Identify the center point connection for the heater pair (black wiring from heaters) either against the unit
back wall or in the wiring loom.
c. Cut the splice to separate the two heaters.
d. Carry out a Megger check on the two heaters in the same way as for units with heater panel. Replace
any heater where the Megger readings are < 1 Mohms.
NOTE
If all heaters are above the acceptable limit with the wiring disconnected, then this indicates that the
fault was in one or more of the wire splices that were removed.
e. Remove the hold-down clamp securing the heater(s) to the coil.
f. Verify that the heaters are not hot before handling them.
g. Lift the bent end of the heater (with the opposite end down and away from the coil). Move the heater to
the side enough to clear the heater end support and remove.
h. To install heater, reverse steps.
i. Reconnect all wiring using new splices and heat shrink where needed. The heat shrink MUST have a
'melt-able' liner to ensure that the connections are properly sealed when shrunk. This can be seen as a
'Ring' of melt liner pushed from under the heat shrink at each end of the shrink tube.
NOTE
Failure to use melt liner heat shrink allows moisture to 'wick' up under the heat shrink and cause a
leakage path.
! WARNING
Always turn OFF the unit circuit breakers (CB-1 & CB-2) and disconnect main power supply
before working on moving parts.
1. Remove the access panel by removing the mounting bolts and TIR locking device. Reach inside of the unit
and remove the Ty-Rap securing the wire harness loop. Disconnect the connector by twisting to unlock and
pulling to separate.
2. Loosen the four 1/4-20 clamp bolts that are located on the underside of the fan deck at the sides of the fan
assembly. Slide the loosened clamps back from the fan assembly.
3. Slide the fan assembly out from the unit and place on a sturdy work surface.
7–19 T-372
7.17.2 Disassemble the Evaporator Fan Assembly
1. Attach a spanner wrench to the two 1/4-20 holes located in the fan hub. Loosen the 5/8-18 shaft nut by
holding the spanner wrench stationary and turning the 5/8-18 nut counter-clockwise (see Figure 7.11).
2. Remove the spanner wrench. Use a universal wheel puller and remove the fan from the shaft. Remove the
washers and key.
3. Remove the four 1/4-20 x 3/4 long bolts that are located under the fan that support the motor and stator
housing. Remove the motor and plastic spacer.
NOTE
When removing the black nylon evaporator fan blade, care must be taken to assure that the blade is not
damaged. In the past, it was a common practice to insert a screwdriver between the fan blades to keep it from
turning. This practice can no longer be used, as the blade is made up of a material that will be damaged. It is
recommended that an impact wrench be used when removing the blade. Do not use the impact wrench when
reinstalling, as galling of the stainless steel shaft can occur.
2. Apply Loctite to the 1/4-20 x 3/4 long bolts and torque to 0.81 mkg (70 inch-pounds).
3. Place one 5/8 flat washer on the shoulder of the fan motor shaft. Insert the key in the keyway and lubricate
the fan motor shaft and threads with a graphite-oil solution (such as Never-seez).
4. Install the fan onto the motor shaft. Place one 5/8 flat washer with a 5/8-18 locknut onto the motor shaft and
torque to 40 foot-pounds.
3
4
2
T-372 7–20
5. Install the evaporator fan assembly in reverse order of removal. Torque the four 1/4-20 clamp bolts to 0.81
mkg (70 inch-pounds). Connect the wiring connector.
6. Replace the access panel making sure that the panel does not leak. Make sure that the TIR locking device
is lockwired. Torque the access panel hardware to 69 kg-cm (60 in/lbs.) using a crossing pattern as shown in
Figure 7.12. Repeat the pattern twice for a proper seal.
7–21 T-372
7.18.2 Cleaning Procedure
1. Remove the upper evaporator access panel inside of the unit.
2. Spray the surface with water before applying the cleaning solution. This helps the cleaner work better.
3. Liberally apply the prepared cleaner solution (5 parts water and 1 part cleaner).
4. Allow the cleaner to soak in for five to seven minutes.
5. Assess area for rinsing. Follow all local regulations regarding disposal of waste water.
6. Thoroughly rinse the cleaner and surrounding area, floor, etc. When rinsing where heavy foaming solution is
present, it is very important to take the time to thoroughly rinse the equipment and surroundings.
7. Always rinse the empty coil cleaner bottle, cap tightly and dispose of properly.
! WARNING
Always turn OFF the unit circuit breakers (CB-1 & CB-2) and disconnect main power supply
before working on moving parts.
1. Pump down the compressor (see Section 7.4) and frontseat both suction and discharge valves.
2. Turn unit power off and remove power from the unit.
3. Remove the coil.
4. Remove the valve. The preferred method of removing the valve is to cut the connection between the brazed
section and the valve, using a small tube cutter. Remove the valve.
Alternatively, use a wet rag to keep the valve cool. Heat inlet and outlet connections to valve body and
remove valve.
5. Clean the valve stem with mild cleaner, if necessary.
T-372 7–22
Figure 7.13 Electronic Expansion Valve
Flow
Direction
This procedure is to be performed in an effort to ease the troubleshooting of the humidity sensor. When performing
this procedure and while working on the unit, always follow the proper lockout/tagout procedures.
Items Required:
Procedure:
NOTE
To ensure saturation, add additional salt until it settles at the bottom without dissolving while shaking.
7–23 T-372
9. Remove the cap and insert the humidity sensor into the bottle through the bottle opening and pull the connector
back through the drilled hole in the cap. Then, secure the cap and seal the wire going through the cap.
NOTE
Make sure that the sensor is not at all in contact with the salt water.
1 2
14. This displays the humidity sensor reading. Verify the reading is between 60% and 85% relative humidity.
15. If the humidity sensor display is outside of this range, reconfirm the salt mixture and retest. If not in range,
replace the sensor at the next opportunity.
16. Wipe clean and reinstall the humidity sensor and access panel. Torque the access panel hardware to 69 kg-
cm (60 in.-lbs.) using a crossing pattern similar to the numbering below.
T-372 7–24
7.21 Economizer Solenoid Valve
7.21.1 Removing a Solenoid Valve Coil
! WARNING
Always turn OFF the unit circuit breakers (CB-1 & CB-2) and disconnect main power supply
before working on moving parts.
1. Turn unit power off and remove power from the unit. Disconnect leads.
2. Remove the top screw and o-ring. Remove the coil and save mounting hardware, seals and spacer for
reuse (see Figure 7.16). See Valve Coil Installation Procedure.
4
5
7–25 T-372
7.22 Economizer Expansion Valve
The economizer expansion valve (see Figure 7.17) is an automatic device that maintains constant superheat of
the refrigerant gas leaving at the point of bulb attachment, regardless of suction pressure.
Unless the valve is defective, it seldom requires maintenance other than periodic inspection to ensure that the ther-
mal bulb is tightly secured to the suction line and wrapped with insulating compound.
NOTE
The economizer expansion valve is a hermetic valve, it does not have adjustable superheat.
Inlet
Outlet
T-372 7–26
To confirm what caused the test to fail, perform the following additional test.
1. Connect the manifold gauge set to discharge service valve (DSV) and suction service valve (SSV).
2. Front seat the SSV and pump down the compressor.
3. Front seat the DSV valve to isolate the compressor.
4. Disconnect the DUV from the top of compressor and install a 1/2 to 1/4 flared adapter / O-ring (P/N 40-
50076-00sv).
1/2” 1/4”
O-Ring
5. Using refrigerant (R-134a or R-513A as specified for the unit model number) or Nitrogen, pressurize the line
to 50 psi (3.5 bar) at the adapter connection and close supply at the tank. Pressure should hold as the valve
is normally closed. If pressure drops, check for leaks at the installed fitting (part number 40-50076-00sv);
repair and retest. If pressure increases at the suction service valve and decreases at the pressure supply;
the valve is leaking and should be replaced. If no leak proceed to step 6.
6. Energize the DUV by removing the coil and placing a magnet on the valve stem opening the valve. If the
pressure does not increase at the SSV and decrease at the supply, replace the valve as it did not open.
If a magnet is not available, a jumper procedure can be used as follows:
1. Remove all four controller fuses (F1, F2, F3a, F3b).
2. Remove the KA6 wire from the KA controller connector on the front of the controller.
3. Disconnect the X1 wire from the 24VAC side of the transformer (black wire) and locate it away from the
transformer.
4. Jumper between the black transformer wires to the KA6 wire removed from the connector.
5. Connect power to the unit and turn the circuit breaker on. The DUV coil is now energized.
6. Pressure should drop.
7. Power the circuit breaker off, reconnect wires and reinstall fuses.
8. If the valve opens and closes properly, the failure mode is with the compressor and it should be changed at
the earliest opportunity.
! CAUTION
The scroll compressor achieves low suction pressure very quickly. Do not use the compressor
to evacuate the system below 0 psig. Never operate the compressor with the suction or
discharge service valves closed (frontseated). Internal damage will result from operating the
compressor in a deep vacuum.
2. Turn unit power off and remove power from the unit.
3. Loosen the bolt on top of the DUV and remove the coil assembly.
7–27 T-372
NOTE
There is a small spacer tube between the top of the valve and the 12 VDC coil that needs to be reinstalled into
the solenoid valve coil. When removing the coil, it may fall out when lifted from the valve body. Take care that the
spacer is not lost; the valve will not function correctly without it.
4. Remove the clamps holding the DUV to the discharge line.
5. Loosen the nuts attaching the DUV to the top of the compressor.
6. Remove the valve. The preferred method of removing the solenoid valve is to cut the connection between
the brazed section and the valve, using a small tube cutter. Remove valve. (see Figure 7.19).
Alternatively, use a wet rag to keep valve cool. Heat outlet connection to valve body and remove valve.
4 5
6
3
NOTE
Confirm that the small spacer tube is inserted into the coil prior to attaching it to the valve body. The valve will not
function correctly without it.
7. Leak check and evacuate the low side of unit as applicable. See Section 7.6.1.
8. Open the service valves.
T-372 7–28
is automatically terminated and the valves return to normal machinery control. To operate the override:
1. Press the CODE SELECT key.
2. Use the Arrow keys until Cd41 is displayed in the left window. The right window will display a controller
communications code.
3. Press the ENTER key. The left display will show a test name alternating with the test setting or time remaining.
4. Use the Arrow keys to scroll to the desired test, and then press the ENTER key. “SELCt” will appear in the
left display.
5. Use the Arrow keys to scroll to the desired setting, and then press the ENTER key. Selections available for
each of the tests are provided in Table 7–1.
6. If the timer is not operating, follow the above procedure to display the timer. Use an Arrow key to scroll to the
desired time interval and press the ENTER key to start the timer.
7. The above described sequence may be repeated during the timer cycle to change to another override.
7.26 Autotransformer
If the unit does not start, check the following:
1. Verify the 460 VAC (yellow) power cable is plugged into the receptacle (see Figure 7.20) and locked in place.
2. Verify that circuit breakers CB-1 and CB-2 are in the “ON” position. If the circuit breakers do not hold in,
check voltage supply.
3. Using a voltmeter, and with the primary supply circuit ON, check the primary (input) voltage (460 VAC). Next,
check the secondary (output) voltage (230 VAC). The transformer is defective if output voltage is not available.
7–29 T-372
7.27 Controller
7.27.1 Handling Modules
! CAUTION
Do not remove wire harnesses from circuit boards unless you are grounded to the unit frame
with a static safe wrist strap or equivalent static drain device.
! CAUTION
Remove the controller module and unplug all connectors before performing any arc welding
on any part of the container.
The guidelines and cautions provided herein should be followed when handling the modules. These precautions
and procedures should be implemented when replacing a module, when doing any arc welding on the unit, or when
service to the refrigeration unit requires handling and removal of a module.
1. Obtain a grounding wrist strap (Carrier Transicold P/N 07-00304-00) and a static dissipation mat (Carrier
Transicold P/N 07-00277-00). The wrist strap, when properly grounded, will dissipate any potential static
buildup on the body. The dissipation mat will provide a static-free work surface on which to place and/or
service the modules.
2. Disconnect and secure power to the unit.
3. Place strap on wrist and attach the ground end to any exposed unpainted metal area on the refrigeration
unit frame (bolts, screws, etc.).
4. Carefully remove the module. Do not touch any of the electrical connections if possible. Place the module
on the static mat.
NOTE
The strap should be worn during any service work on a module, even when it is placed on the mat.
NOTE
If “no USb” is displayed, wait up to 15 seconds for this message to be replaced with a different message. If “no
USb” continues to be displayed, remove and insert the USB flash drive and repeat steps 3 and 4.
5. Use the Arrow keys until “UP LoAd” is displayed, then press the ENTER key.
6. “LOAd XXXX” is now on the display. If more than one ML5 software revision file is on the USB flash drive at
the root level, press the Arrow keys until the desired revision is displayed.
7. Press the ENTER key to load the software to the controller.
8. When “PULL USB NOW” is displayed, remove the USB drive from the port.
9. The following messages will appear to confirm successful programming: “LoAd SoFt” and “Pro SoFt” will
each appear for several seconds and then “Restart” appears briefly. Then, the controller restarts.
10. As the controller starts up, the message “Cd 18” displays the new software loaded and then “Pro donE”
appears.
T-372 7–30
7.27.4 Uploading a Software Configuration from a USB Drive
1. Place the Start-Stop switch (ST) to “I” to turn the unit On. Wait for controller information to be displayed.
2. Insert the USB flash drive containing the software configuration files into the controller micro USB port. The
software multi-configuration files will have an extension of .ml5.
3. Press the ALT. MODE key on the keypad.
4. Use the Arrow keys until “USb” is displayed, then press the ENTER key.
NOTE
If “no USb” is displayed, wait up to 15 seconds for this message to be replaced with a different message. If “no
USb” continues to be displayed, remove and insert the USB flash drive and repeat steps 3 and 4.
5. Use the Arrow keys until “SEt UP” is displayed, then press the ENTER key.
6. Use the Arrow keys until “ruN COnFG” is displayed, then press the ENTER key.
NOTE
If more than one configuration database file is on the USB flash drive at the root level, then only the file with the
latest date will be considered.
7. The display module will go blank briefly and then display “551000”, based on the operational software
installed.
8. Use the Arrow keys to scroll through the list to obtain the proper model number, then press the ENTER key.
9. Once the model number is selected, the display will show the message “re Start” briefly, and then the
controller will restart.
10. Remove the USB flash drive from the USB port.
11. Use the Arrow keys to navigate to function code Cd20 and confirm that the correct model configuration is
displayed. The model displayed in Cd20 should match what is shown on the unit nameplate.
NOTE
If “no USb” is displayed, wait up to 15 seconds for this message to be replaced with a different message. If “no
USb” continues to be displayed, remove and insert the USB flash drive and repeat steps 3 and 4.
5. Use the Arrow keys until “dn LoAd” is displayed, then press the ENTER key.
6. The Download Menu is now displayed. The amount of free space available on the drive is displayed first.
Use the Arrow keys to scroll down through the choices: ALL, trIP, 30dAy, 60dAy, and 90dAy.
7. Confirm the selection by pressing the ENTER key. The download starts.
8. While the download is in progress, the display will show “dLOAd” flashing.
9. When the download is complete, the display will show “dLOAd donE”.
10. Remove the USB flash drive from the USB port.
NOTE
The USB must have an ML5 software file or ML5 configuration file on the root level. If not, the “SEt UP” menu will
not be accessible from underneath the “USb” menu.
7–31 T-372
3. Press the ALT. MODE key on the keypad.
4. Use the Arrow keys until “USb” is displayed, then press the ENTER key.
NOTE
If “no USb” is displayed, wait up to 15 seconds for this message to be replaced with a different message. If “no
USb” continues to be displayed, remove and insert the USB flash drive and repeat steps 3 and 4.
5. Use the Arrow keys until “SEt UP” is displayed, then press the ENTER key.
6. Use the Arrow keys until “SEt tIM” is displayed, then press the ENTER key.
7. The date values are displayed in YYYY MM-DD format. Configure the date using the keypad.
• The values will be edited from left to right: the year first (YYYY), then month (MM) and then day (DD).
• Press the Arrow keys to increase or decrease a date value.
• Press the ENTER key to confirm the date value being modified and bring up the next value for editing.
• Press the CODE SELECT key to return to the previous date value.
8. Once date editing is complete and the day (DD) value is selected, press the ENTER key.
9. The time values are now displayed in HH MM format. Configure the time using the keypad.
• The values will be edited from left to right: the hours first (HH), then minutes (MM).
• Press the Arrow keys to increase or decrease a time value.
• Press the ENTER key to confirm the time value being modified and bring up the next value for editing.
• Press the CODE SELECT key to return to the previous time value.
10. Once time editing is complete, with the minutes (MM) value active, press the ENTER key.
11. The display returns to the USb menu. The date and time will be committed when the ENTER key is pressed.
NOTE
If “no USb” is displayed, wait up to 15 seconds for this message to be replaced with a different message. If “no
USb” continues to be displayed, remove and insert the USB flash drive and repeat steps 3 and 4.
5. Use the Arrow keys until “SEt UP” is displayed, then press the ENTER key.
6. Use the Arrow keys until “SEt Id” is displayed, then press the ENTER key. The current ID is displayed.
7. Configure the Container ID using the keypad.
• The first four characters are Alpha type and the last seven are numeric.
• The character being modified will always be on the right most position on the display.
• Press the Arrow keys to scroll through the selectable characters available.
• Press the ENTER key to confirm the choice and shift the selected character one position to the left to
modify the next character.
• Press the CODE SELECT key to shift the characters one position to the right (backspace) to modify the
previous character.
8. When the last value of Container ID is entered, press the ENTER key to enter the information to the controller.
T-372 7–32
7.27.8 Removing and Installing a Controller
Removal:
1. Disconnect all front wire harness connectors and move wiring out of the way.
2. The lower controller mounting is slotted. Loosen the top mounting screw (see Figure 4.1) and lift up and out.
3. Remove the module.
4. When removing the replacement module from its packaging, note how it is packaged. When returning the
old module for service, place it in the packaging in the same manner as the replacement. The packaging
has been designed to protect the module from both physical and electrostatic discharge damage during
storage and transit.
Installation:
1. Install the module by reversing the removal steps.
2. Torque values for mounting screws (see Figure 4.1) are 0.23 mkg (20 inch-pounds). Torque value for the
connectors is 0.12 mkg (10 inch-pounds).
4. Using a Driver Bit, Carrier Transicold part number 07-00418-00, loosen the left hand screw on the battery
pack cover then remove the second screw on the outer edge of the battery pack cover.
5. Remove the old battery from the bracket and assemble the new battery to the bracket.
6. Secure the battery wires from the battery along the previous route and then reconnect the BA connector.
Heat shrink a ferrite clamp to the harness to reduce electromagnetic voltage transients onto this interface.
7–33 T-372
7. Replace wire ties that were removed. Replace shields and close the control panel door.
Notes:
• Wherever possible, use a thermometer that is regularly calibrated by an accredited test lab. Contact your
instrument representative if the reference thermometer is not showing correct readings.
• Always use a temperature measurement reference instrument which is of higher accuracy than the device
checked – for e.g., a thermometer with a rated accuracy of +/- 0.2 °C should be used to check a device with
a rated accuracy +/- 0.3 °C.
• A thermally insulated container, tub open to atmosphere and large enough to contain crushed ice and water
should be used. The tub should be large enough to contain the unit’s sensor and the reference thermometer.
• Enough distilled water should be available to make ice cubes and to set up a proper and stable ice-water tri-
ple-point mixture. Prepare ice using distilled water.
• Pre-cool distilled water for testing.
Procedure:
1. Prepare a mixture of clean ice using distilled water in a clean insulated container. If possible, the person
handling should be wearing latex gloves.
a. Crush or chip the ice to completely fill the container. Finer ice particles will produce a more accurate mixture.
b. Add enough pre-cooled distilled water to fill the container.
c. Stir the mixture for a minimum of 2 minutes to ensure water is completely cooled and good mixing has
occurred.
d. The mixture should generally contain about 85% ice with distilled water occupying the rest of the space.
e. Add more ice as the ice melts.
2. Stir the ice water slurry mixture to maintain a temperature 0°C (32°F).
3. Constantly monitor the temperature of the ice water slurry with your reference thermometer. Ensure that the
temperature of the bath has stabilized. The criterion for stability generally is to take two readings at 1 minute
intervals, and the two readings should give you 0°C (32°F).
T-372 7–34
7.28.2 Sensor Checkout Procedure
This procedures is to be performed to verify the accuracy of a temperature sensor. This procedure describes how
to check using a ice-water bath and also by using an OHM check.
1. Remove the sensor and place in a 0°C (32°F) ice-water bath. The ice-water bath is prepared by filling an
insulated container (of sufficient size to completely immerse the bulb) with ice cubes or chipped ice, then
filling the voids between the ice with water and agitating until the mixture reaches 0°C (32°F) measured on a
laboratory thermometer.
2. Start the unit and check the sensor reading on the control panel. Readings should be 0°C (32°F).
If the reading is correct, reinstall the sensor. If the reading is incorrect, continue with the next step.
3. If the reading is off slightly, then re-calibrate. If the reading is not within 0°C (32°F) +/- 0.25 degrees, replace
the sensor and re-check.
4. A sensor can be tested against from the control box utilizing the carrier harness adapter.
The carrier harness adapter part numbers are 22-50485-00 (CA connector), 22-50486-00 (CC
connector) and 22-50487-00 (ME connector). All readings from the adapter will be resistance readings
with power removed and the harness disconnected from the ML5 controller.
5. Locate the proper wires to be ohmed on the system schematic and check against the temperature
resistance chart provided in Table 7–2 and Table 7–3. If unable to soak in an ice bath, the sensor resistance
can be compared against a calibrated sensor located with the sensor being tested.
NOTE
Performing resistance checks on the controller connector is discouraged due to potential damage to the pins.
Resistive Sensors:
• STS, SRS, RTS, RRS: ice-bath, GDP calibration, replace. Remove check against chart. Ambient - easy to
ice-bath check on display, if bad reading replace, remove ohm against chart.
• DTS: ice-bath check on display, if bad replace, can remove and check against chart.
• CPDS: remove from compressor, ice-bath check against display, if bad replace, can remove and check
against chart.
• ETS1 / ETS2: ice-bath check against display, if bad replace, can remove and check against
• USDA 1-4: ice-bath, GDP, remove at socket check resistance
7–35 T-372
Table 7–2 Sensor Resistance - AMBS, DTS, ETS, RRS, RTS, SRS, STS
°C °F OHMS °C °F OHMS
-40 -40 336,500 6 42.8 24,173
-39 -38.2 314,773 7 44.6 23,017
-38 -36.4 294,600 8 46.4 21,922
-37 -34.6 275,836 9 48.2 20,886
-36 -32.8 258,336 10 50 19,900
-35 -31 242,850 11 51.8 18,975
-34 -29.2 228,382 12 53.6 18,093
-33 -27.4 214,164 13 55.4 17,258
-32 -25.6 200,909 14 57.2 16,466
-31 -23.8 188,545 15 59 15,715
-30 -22.0 177,000 16 60.8 15,002
-29 -20.2 166,360 17 62.6 14,325
-28 -18.4 156,426 18 64.4 13,683
-27 -16.6 147,148 19 66.2 13,073
-26 -14.8 138,478 20 68 12,494
-25 -13 130,374 21 69.8 11,944
-24 -11.2 122,794 22 71.6 11,420
-23 -9.4 115,702 23 73.4 10,923
-22 -7.6 109,063 24 75.2 10,450
-21 -5.8 102,846 25 77 10,000
-20 -4 97,022 26 78.8 9,572
-19 -2.2 91,563 27 80.6 9,164
-18 -0.4 86,445 28 82.4 8,777
-17 1.4 81,644 29 84.2 8,407
-16 3.2 77,139 30 86 8,055
-15 5 72,910 31 87.8 7,720
-14 6.8 68,938 32 89.6 7,401
-13 8.6 65,206 33 91.4 7,096
-12 10.4 61,699 34 93.2 6,806
-11 12.2 58,401 35 95 6,529
-10 14 55,330 36 96.8 6,265
-9 15.8 52,381 37 98.6 6,013
-8 17.6 49,634 38 100.4 5,772
-7 19.4 47,047 39 102.2 5,543
-6 21.2 44,610 40 104.0 5,323
-5 23 42,314 41 105.8 5,114
-4 24.8 40,149 42 107.6 4,914
-3 26.6 38,108 43 109.4 4,723
-2 28.4 36,182 44 111.2 4,540
-1 30.2 34,365 45 113 4,365
0 32 32,650 46 114.8 4,198
1 33.8 31,030 47 116.6 4,038
2 35.6 29,500 48 118.4 3,885
3 37.4 28,054 49 120.2 3,739
4 39.2 26,688 50 122 3,599
5 41 25,396
T-372 7–36
Table 7–3 Sensor Resistance - PrimeLINE CPDS
°C °F OHMS °C °F OHMS
-40 -40 2,889,600 18 64.4 117,656
-38 -36.4 2,532,872 20 68.0 107,439
-36 -32.8 2,225,078 22 71.6 98,194
-34 -29.2 1,957,446 24 75.2 89,916
-32 -25.6 1,724,386 25 77 86,113
-30 -22.0 1,522,200 26 78.8 82,310
-28 -18.4 1,345,074 28 82.4 75,473
-26 -14.8 1,190,945 30 83.0 69,281
-24 -11.2 1,056,140 32 89.6 63,648
-22 -7.6 938,045 34 93.2 58,531
-20 -4.0 834,716 36 96.8 53,887
-18 -0.4 743,581 38 100.4 49,656
-16 3.2 663,593 40 104.0 45,812
-14 6.8 593,030 42 107.6 42,294
-12 10.4 530,714 44 111.2 39,078
-10 14.0 475,743 46 114.8 36,145
-8 17.6 426,904 48 118.4 33,445
-6 21.2 383,706 50 122.0 30,985
-4 24.8 345,315 52 125.6 28,724
-2 28.4 311,165 54 129.2 26,651
0 32.0 280,824 56 132.8 27,750
2 35.6 253,682 58 136.4 23,005
4 39.2 229,499 60 140.0 21,396
6 42.8 207,870 62 143.6 19,909
8 46.4 188,494 64 147.2 18,550
10 50.0 171,165 66 150.8 17,294
12 53.6 155,574 68 154.4 16,133
14 57.2 141,590 70 158.0 15,067
16 60.8 129,000 72 161.6 14,078
! WARNING
Before removing the Supply or Return air sensors from the unit, turn the ON/OFF switch and
circuit breaker to the OFF position. Disconnect the power plug from the unit. Follow proper
lockout/tagout procedures to ensure the power cannot inadvertently be energized. It is
important that all dismantling work is done and tools and personnel are away from the unit
before powering on the unit for calibration.
7–37 T-372
! WARNING
When performing the Return Air Sensor calibration, disconnect both evaporator motors.
Before proceeding with the calibration procedure, ensure that controller software version is 5368 or higher and
DataLINE version 3.1 or higher is installed onto the download device. Only the latest DataLINE and controller
software will allow users to carry out Good Distribution Practice (GDP) calibration. Do not downgrade the
software after installing the latest software.
Before proceeding with the calibration procedure, it is recommended to check the sensors by running pre-trip
P5-0. This test checks the sensor values. If the test fails, identify and correct the faulty sensor and rerun the test.
Tools Required:
• Socket screwdrivers set
• Phillips screwdriver
• Standard hand tools
• Interrogator cable
• Laptop with DataLINE 3.1 or above installed
• Clean insulated container for distilled water and ice
• A regularly calibrated reference thermometer, recommended to be of accuracy up to 2 decimal places.
T-372 7–38
GDP Calibration, Removing Return Sensors (RTS/RRS) from Unit:
1. Remove both front access panels from the unit by removing 8 fasteners from each panel (see Figure 7.22).
Save all hardware for re-installation.
Figure 7.22 Removing Front Access Panels
2. On the right side, disconnect the fan motor wiring, loosen the fastener and remove (slide) the evaporator
motor from the unit (see Figure 7.23).
7–39 T-372
4. Cut all the wire ties (see Figure 7.25) that are securing the sensors to the harness and remove sensor.
Figure 7.25 Return Sensors - Cutting Wire Ties
! WARNING
Before powering on the unit, it is important to ensure that all dismantling work is done and
tools are away and service personnel are not working on the unit at the time of power on.
2. Open DataLINE version 3.1 or above. From the DataLINE launch pad, click on the Probe Calibration button
(see Figure 7.26) to go to the Probe Calibration screen. A pop-up window will appear reminding the user to
ensure proper ice bath temperature. Click OK to acknowledge.
Figure 7.26 DataLINE - Probe Calibration
T-372 7–40
3. On the Probe Calibration screen, click on the Calibrate Supply sensors or Calibrate Return sensors button
(see Figure 7.27).
Figure 7.27 DataLINE - Calibrate Sensors Button
4. A Location of Service pop-up window will appear (see Figure 7.28). In the appropriate fields, enter the
Service Center Name and Service Center Location where the calibration is being performed. Then, click the
Save button. A pop-up window will appear reminding the user to ensure proper ice bath temperature. Click
OK to acknowledge and remember to maintain the Ice bath at 0°C (32°F).
Figure 7.28 DataLINE - Enter Service Center Information
5. Prepare the ice bath. Refer to the Ice bath preparation procedure.
Ensure that the set-up (i.e. ice bath, sensors, reference thermometer) has reached a stable state before
beginning the calibration process. Ensure that the set-up is clean and the reference thermometer is
regularly maintained and calibrated.
7–41 T-372
6. Place the ice bath in a location near sensors (see Figure 7.29). For Return Sensors, place the ice bath on
an elevated platform (ladder) of appropriate height.
7. Once temperature stability is ensured, submerge the sensors in the ice water slurry. Make certain that the
sensors do not contact the container sides or bottom, or each other. Continuously stir the slurry mixture
during calibration.
8. Ensure that the Ice bath is at 0°C (32°F) using the calibrated reference thermometer. Confirm that the
sensor readings have stabilized and the sensors are within +/- 0.3°C (0.5°F). The readings can be taken
from the Uncal column in the Current Probe Offset Temperatures table.
9. Then, after confirming the sensor readings have stabilized, click on the Start Cal button (see Figure 7.30).
After clicking Start Cal, the process begins automatically and will complete in less than 5 minutes.
Figure 7.30 DataLINE - Start Cal Button
10. Continue to stir the ice bath during the testing. Calibration will fail if the stability cannot be achieved or the
sensor offset is greater than 0.3°C (0.5°F). Replace the sensor and recalibrate the sensors. See the
Section 7.28.4 for sensor replacement procedures.
T-372 7–42
11. Once the calibration has completed, a pop-up will appear with the message Calibrate Complete. Click OK to
acknowledge and the results will then be displayed on the screen in the Results column (see Figure 7.31).
Figure 7.31 DataLINE - Calibration Results
12. After completing the calibration event, download a DCX file and check that all of the following information is
captured: service center name, location, the results of the calibration and the offset applied. Ensure that all
the information is captured and the event is considered a success when all the intended sensors in
calibration have passed.
13. After the completion of the calibration, restore the unit to its original state.
! WARNING
Always turn OFF the unit circuit breaker (CB-1) and disconnect main power supply before
removing electrical parts.
1. Place the Start-Stop switch (ST) to “0” to turn the unit Off. Disconnect the power supply.
NOTE
Include white date code label when cutting out and removing defective sensors. The label could be required for
warranty returns.
2. Cut the cable. Slide the cap and grommet off the bulb type sensor and save for reuse. Do not cut the
grommet.
3. Cut one wire of existing cable 40 mm (1-1/2 inches) shorter than the other wire.
4. Cut the replacement sensor wires (opposite colors) back 40 mm (1-1/2 inches). See Figure 7.32.
7–43 T-372
Figure 7.32 Sensor Types
40 mm (1 1/2 in)
Sensor 2 or 3 wires as
required
3 4
! CAUTION
Do not allow moisture to enter wire splice area as this may affect sensor resistance.
12. Slide large heat shrink tubing over both splices and shrink.
T-372 7–44
13. Position sensor in unit as shown in Figure 7.33 and re-check sensor resistance:
Figure 7.35 - Return Sensor Positioning
Figure 7.34 - Supply Sensor Positioning
Figure 7.36 - ETS Sensor Positioning
14. Reinstall sensor. Refer to:
Section 7.28.5 - For STS and SRS Reinstallation
Section 7.28.6 - For RRS and RTS Reinstallation
Section 7.28.7 - For DTS Reinstallation
Section 7.28.8 - For ETS1 and ETS2 Reinstallation
NOTE
The P5 Pre-Trip test must be run to deactivate probe alarms (see Section 5.8).
Supply Air
Stream
5 6mm (1/4”)
7–45 T-372
Figure 7.35 Return Sensor Positioning
2 1 .0 ”
25.4cm
3
7–47 T-372
Table 7–4 R-134a Refrigerant Pressure Temperature Chart
Note: Underline figures are inches of mercury vacuum
°F °C PSIG °C °F BAR
-40 -40.0 14.8 -40 -40.0 -0.49
-38 -38.9 13.9 -39 -38.2 -0.46
-36 -37.8 13.0 -38 -36.4 -0.43
-34 -36.7 12.0 -37 -34.6 -0.40
-32 -35.6 10.9 -36 -32.8 -0.37
-30 -34.4 9.8 -35 -31.0 -0.34
-28 -33.3 8.7 -34 -29.2 -0.30
-26 -32.2 7.5 -33 -27.4 -0.27
-24 -31.1 6.3 -32 -25.6 -0.23
-22 -30.0 5.0 -31 -23.8 -0.20
-20 -28.9 3.7 -30 -22.0 -0.16
-18 -27.8 2.3 -29 -20.2 -0.12
-16 -26.7 0.8 -28 -18.4 -0.07
-14 -25.6 0.3 -27 -16.6 -0.03
-12 -24.4 1.1 -26 -14.8 0.02
-10 -23.3 1.9 -25 -13.0 0.06
-8 -22.2 2.8 -24 -11.2 0.11
-6 -21.1 3.6 -23 -9.4 0.16
-4 -20.0 4.6 -22 -7.6 0.22
-2 -18.9 5.5 -21 -5.8 0.27
0 -17.8 6.5 -20 -4.0 0.33
2 -16.7 7.5 -19 -2.2 0.39
4 -15.6 8.5 -18 -0.4 0.45
6 -14.4 9.6 -17 1.4 0.51
8 -13.3 10.8 -16 3.2 0.57
10 -12.2 11.9 -15 5.0 0.64
12 -11.1 13.1 -14 6.8 0.71
14 -10.0 14.4 -13 8.6 0.78
16 -8.9 15.7 -12 10.4 0.85
18 -7.8 17.0 -11 12.2 0.93
20 -6.7 18.4 -10 14.0 1.01
22 -5.6 19.9 -9 15.8 1.09
24 -4.4 21.3 -8 17.6 1.17
26 -3.3 22.9 -7 19.4 1.25
28 -2.2 24.5 -6 21.2 1.34
30 -1.1 26.1 -5 23.0 1.43
32 0.0 27.8 -4 24.8 1.53
34 1.1 29.5 -3 26.6 1.62
36 2.2 31.3 -2 28.4 1.72
38 3.3 33.1 -1 30.2 1.82
40 4.4 35.0 0 32.0 1.93
T-372 7–48
Table 7–4 R-134a Refrigerant Pressure Temperature Chart
Note: Underline figures are inches of mercury vacuum
°F °C PSIG °C °F BAR
42 5.6 37.0 1 33.8 2.04
44 6.7 39.0 2 35.6 2.15
46 7.8 41.1 3 37.4 2.26
48 8.9 43.2 4 39.2 2.38
50 10.0 45.4 5 41.0 2.50
52 11.1 47.7 6 42.8 2.62
54 12.2 50.0 7 44.6 2.75
56 13.3 52.4 8 46.4 2.88
58 14.4 54.9 9 48.2 3.01
60 15.6 57.4 10 50.0 3.15
62 16.7 60.0 11 51.8 3.29
64 17.8 62.7 12 53.6 3.43
66 18.9 65.4 13 55.4 3.58
68 20.0 68.2 14 57.2 3.73
70 21.1 71.1 15 59.0 3.88
72 22.2 74.1 16 60.8 4.04
74 23.3 77.1 17 62.6 4.21
76 24.4 80.2 18 64.4 4.37
78 25.6 83.4 19 66.2 4.54
80 26.7 86.7 20 68.0 4.72
82 27.8 90.0 21 69.8 4.90
84 28.9 93.5 22 71.6 5.08
86 30.0 97.0 23 73.4 5.27
88 31.1 100.6 24 75.2 5.46
90 32.2 104.3 25 77.0 5.65
92 33.3 108.1 26 78.8 5.85
94 34.4 112.0 27 80.6 6.06
96 35.6 115.9 28 82.4 6.27
98 36.7 120.0 29 84.2 6.48
100 37.8 124.2 30 86.0 6.70
102 38.9 128.4 31 87.8 6.93
104 40.0 132.7 32 89.6 7.15
106 41.1 137.2 33 91.4 7.39
108 42.2 141.7 34 93.2 7.63
110 43.3 146.4 35 95.0 7.87
112 44.4 151.1 36 96.8 8.12
114 45.6 156.0 37 98.6 8.37
116 46.7 160.9 38 100.4 8.63
118 47.8 166.0 39 102.2 8.90
120 48.9 171.2 40 104.0 9.17
122 50.0 176.5 41 105.8 9.44
124 51.1 181.8 42 107.6 9.72
7–49 T-372
Table 7–4 R-134a Refrigerant Pressure Temperature Chart
Note: Underline figures are inches of mercury vacuum
°F °C PSIG °C °F BAR
126 52.2 187.4 43 109.4 10.01
128 53.3 193.0 44 111.2 10.30
130 54.4 198.7 45 113.0 10.60
132 55.6 204.6 46 114.8 10.90
134 56.7 210.6 47 116.6 11.21
136 57.8 216.7 48 118.4 11.53
138 58.9 222.9 49 120.2 11.85
140 60.0 229.2 50 122.0 12.18
142 61.1 235.7 51 123.8 12.51
144 62.2 242.3 52 125.6 12.85
146 63.3 249.0 53 127.4 13.20
148 64.4 255.9 54 129.2 13.56
150 65.6 262.9 55 131.0 13.92
56 132.8 14.28
57 134.6 14.66
58 136.4 15.04
59 138.2 15.42
60 140.0 15.82
61 141.8 16.22
62 143.6 16.63
63 145.4 17.04
64 147.2 17.47
65 149.0 17.90
Table 7–5 R-513A Refrigerant Pressure Temperature Chart
Note: Underline figures are inches of mercury vacuum
°F °C PSIG °C °F BAR
-40 -40.0 9.8 -40 -40.0 -0.32
-38 -38.9 8.6 -39 -38.2 -0.28
-36 -37.8 7.4 -38 -36.4 -0.25
-34 -36.7 6.2 -37 -34.6 -0.21
-32 -35.6 4.9 -36 -32.8 -0.17
-30 -34.4 3.6 -35 -31.0 -0.13
-28 -33.3 2.2 -34 -29.2 -0.09
-26 -32.2 0.7 -33 -27.4 -0.05
-24 -31.1 0.4 -32 -25.6 0.00
-22 -30.0 1.1 -31 -23.8 0.04
-20 -28.9 1.9 -30 -22.0 0.09
-18 -27.8 2.8 -29 -20.2 0.14
-16 -26.7 3.7 -28 -18.4 0.19
-14 -25.6 4.6 -27 -16.6 0.25
-12 -24.4 5.5 -26 -14.8 0.30
-10 -23.3 6.5 -25 -13.0 0.36
-8 -22.2 7.5 -24 -11.2 0.42
-6 -21.1 8.5 -23 -9.4 0.48
-4 -20.0 9.6 -22 -7.6 0.54
-2 -18.9 10.7 -21 -5.8 0.61
0 -17.8 11.9 -20 -4.0 0.67
2 -16.7 13.1 -19 -2.2 0.74
4 -15.6 14.3 -18 -0.4 0.81
6 -14.4 15.6 -17 1.4 0.89
8 -13.3 16.9 -16 3.2 0.96
10 -12.2 18.3 -15 5.0 1.04
12 -11.1 19.7 -14 6.8 1.12
14 -10.0 21.1 -13 8.6 1.21
16 -8.9 22.6 -12 10.4 1.29
18 -7.8 24.2 -11 12.2 1.38
20 -6.7 25.8 -10 14.0 1.47
22 -5.6 27.5 -9 15.8 1.56
24 -4.4 29.2 -8 17.6 1.66
26 -3.3 30.9 -7 19.4 1.76
28 -2.2 32.7 -6 21.2 1.86
30 -1.1 34.6 -5 23.0 1.97
32 0.0 36.5 -4 24.8 2.07
34 1.1 38.5 -3 26.6 2.18
36 2.2 40.5 -2 28.4 2.30
38 3.3 42.6 -1 30.2 2.41
40 4.4 44.8 0 32.0 2.53
7–51 T-372
Table 7–5 R-513A Refrigerant Pressure Temperature Chart
Note: Underline figures are inches of mercury vacuum
°F °C PSIG °C °F BAR
42 5.6 47.0 1 33.8 2.65
44 6.7 49.3 2 35.6 2.78
46 7.8 51.6 3 37.4 2.91
48 8.9 54.0 4 39.2 3.04
50 10.0 56.5 5 41.0 3.18
52 11.1 59.0 6 42.8 3.32
54 12.2 61.6 7 44.6 3.46
56 13.3 64.3 8 46.4 3.60
58 14.4 67.0 9 48.2 3.75
60 15.6 69.8 10 50.0 3.91
62 16.7 72.7 11 51.8 4.06
64 17.8 75.7 12 53.6 4.22
66 18.9 78.7 13 55.4 4.39
68 20.0 81.8 14 57.2 4.56
70 21.1 85.0 15 59.0 4.73
72 22.2 88.2 16 60.8 4.91
74 23.3 91.6 17 62.6 5.09
76 24.4 95.0 18 64.4 5.27
78 25.6 98.5 19 66.2 5.46
80 26.7 102.1 20 68.0 5.65
82 27.8 105.7 21 69.8 5.85
84 28.9 109.5 22 71.6 6.05
86 30.0 113.3 23 73.4 6.26
88 31.1 117.3 24 75.2 6.47
90 32.2 121.3 25 77.0 6.68
92 33.3 125.4 26 78.8 6.90
94 34.4 129.6 27 80.6 7.13
96 35.6 133.9 28 82.4 7.36
98 36.7 138.3 29 84.2 7.59
100 37.8 142.8 30 86.0 7.83
102 38.9 147.4 31 87.8 8.07
104 40.0 152.0 32 89.6 8.32
106 41.1 156.8 33 91.4 8.57
108 42.2 161.7 34 93.2 8.83
110 43.3 166.7 35 95.0 9.10
112 44.4 171.8 36 96.8 9.37
114 45.6 177.0 37 98.6 9.64
116 46.7 182.3 38 100.4 9.92
118 47.8 187.7 39 102.2 10.21
120 48.9 193.3 40 104.0 10.50
122 50.0 198.9 41 105.8 10.79
124 51.1 204.7 42 107.6 11.10
T-372 7–52
Table 7–5 R-513A Refrigerant Pressure Temperature Chart
Note: Underline figures are inches of mercury vacuum
°F °C PSIG °C °F BAR
126 52.2 210.5 43 109.4 11.40
128 53.3 216.5 44 111.2 11.72
130 54.4 222.7 45 113.0 12.04
132 55.6 228.9 46 114.8 12.36
134 56.7 235.2 47 116.6 12.70
136 57.8 241.7 48 118.4 13.03
138 58.9 248.3 49 120.2 13.38
140 60.0 255.1 50 122.0 13.73
142 61.1 261.9 51 123.8 14.09
144 62.2 268.9 52 125.6 14.45
146 63.3 276.1 53 127.4 14.82
148 64.4 283.3 54 129.2 15.20
150 65.6 290.8 55 131.0 15.58
56 132.8 15.97
57 134.6 16.37
58 136.4 16.77
59 138.2 17.18
60 140.0 17.60
61 141.8 18.03
62 143.6 18.46
63 145.4 18.90
64 147.2 19.35
65 149.0 19.80
7–53 T-372
Table 7–6 Recommended Bolt Torque Values (Dry, Non-Lubricated for 18-8 Stainless Steel)
Bolt Diameter Threads In-Lbs Ft-Lbs N-m
Free Spinning
#4 40 5.2 0.4 0.6
#6 32 9.6 0.8 1.1
#8 32 20 1.7 2.3
#10 24 23 1.9 2.6
1/4 20 75 6.3 8.5
5/16 18 132 11 14.9
3/8 16 240 20 27.1
7/16 14 372 31 42
1/2 13 516 43 58.3
9/16 12 684 57 77.3
5/8 11 1104 92 124.7
3/4 10 1488 124 168.1
Non Free Spinning (Locknuts etc.)
1/4 20 82.5 6.9 9.3
5/16 18 145.2 12.1 16.4
3/8 16 264 22.0 29.8
7/16 14 409.2 34.1 46.2
1/2 13 567.6 47.3 64.1
9/16 12 752.4 62.7 85
5/8 11 1214.4 101.2 137.2
3/4 10 1636.8 136.4 184.9
T-372 7–54
SECTION 8
ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS
Figure 8.1 Legend - Standard Unit Configuration
8–1 T-372
ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS
Figure 8.2 Schematic Diagram
T-372 8–2
ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS
Figure 8.3 Unit Wiring Diagram (Sheet 1 of 2)
8–3 T-372
ELECTRICAL WIRING SCHEMATIC AND DIAGRAMS
Figure 8.4 Unit Wiring Diagram (Sheet 2 of 2)
T-372 8–4
SECTION 9
EU DECLARATION OF CONFORMITY
We, manufacturer: Carrier Transicold Pte Ltd
251 Jalan Ahmad Ibrahim
Singapore 629146
Declare, under our sole responsibility, that the PrimeLINE Container Unit:
Model: 69NT40-571
is in conformity with the provisions of the following European Directives:
• Machinery Directive 2006/42/EC following Annex VIII
• Electromagnetic Compatibility Directive 2014/30/EU following Annex II
• Radio Equipment Directive 2014/53/EU Annex II
The assembly was assessed for applicability under the Pressure Equipment Directive, 2014/68/EU, but determined
to be outside of the scope based on the exclusion indicated in PED Article 1, Paragraph 2.f. The assembly was
determined to be no higher than PED Category I and is covered by the Machinery Directive 2006/42/EC.
Shaun Bretherton
Service Engineering Manager of CTL Rotterdam
Pittsburgstraat 21 3047 BL Rotterdam
Netherlands
9–1 T-372
SECTION 10
WIRELESS CERTIFICATION
CCXXxxLPyyyZzW
R 006-XXXXXX XX-XXXX/XXXX
This device complies with Part 15 of the FCC Rules. Operation is subject to the following
two conditions: (1) this device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
This device contains licence-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic
Development Canada's licence-exempt RSS(s). Operation is subject to the following two conditions:
2. This device must accept any interference, including interference that may cause undesired operation of the
device.
Cet appareil contient des émetteurs / récepteurs exemptés de licence conformes aux RSS (RSS) d'Innovation, Sci-
ences et Développement économique Canada. Le fonctionnement est soumis aux deux conditions suivantes:
2. Cet appareil doit accepter toutes les interférences, y compris celles susceptibles de provoquer un
fonctionnement indésirable de l'appareil.
10–1 T-372
China RoHS per SJ/T 11364-2014
Index–1 T-372
Economizer Connection Location 3–3 Frozen Steady State 4–8
Economizer Expansion Valve (EXV) Install 7–26 Function Codes, Check During Start-Up 5–4
Economizer Expansion Valve (EXV) Location 3–3 Fusible Plug Location 3–3
Economizer Expansion Valve (EXV) Remove 7–26
Economizer Expansion Valve (EXV) Service 7–26 G
GDP Sensor Calibration 7–37
Economizer Heat Exchanger Location 3–1
Economizer Location 3–3 H
Economizer Solenoid Valve (ESV) Install 7–25 Handles 2–3
Economizer Solenoid Valve (ESV) Location 3–3 HEAT light 4–11
Economizer Solenoid Valve (ESV) Remove 7–25 Heat Termination Thermostat (HTT) Location 3–2
Economizer Solenoid Valve (ESV) Service 7–25 High Pressure Switch (HPS) Location 3–3
Electrical Data 3–7 High Pressure Switch (HPS) Replace 7–11
Electronic Expansion Valve (EEV) Description 3–10 High Pressure Switch (HPS) Service 7–10
Electronic Expansion Valve (EEV) Install 7–22 Humidity Sensor (HS) Location 3–2
Electronic Expansion Valve (EEV) Location 3–2 Humidity Sensor (HS) Troubleshooting 7–23
Electronic Expansion Valve (EEV) Remove 7–22 Humidity Sensor (TS) Service 7–23
Electronic Expansion Valve (EEV) Service 7–22
Evacuate and Dehydrate 7–5 I
Evacuate and Dehydrate - Complete System 7–5 Indicator Lights 4–2
Evacuate and Dehydrate - Partial System 7–6 Inspection 5–1
Evaporator 2–2 Interrogator 2–2
Evaporator Coil Heaters Location 3–2 Interrogator Connector Receptacle (ICR) Location 3–2
Evaporator Coil Location 3–2 Introduction 2–1, 9–1
Evaporator Coil Replace 7–17
Evaporator Coil Service 7–17
K
Keypad 4–1
Evaporator Fan #1 Location 3–2
Keypad Location 3–1
Evaporator Fan #2 Location 3–2
Evaporator Fan and Motor Assembly 7–19 L
Evaporator Fan Assembly 7–20 Labels 2–3
Evaporator Fan Assembly Replace 7–19
Evaporator Fan Operation 2–2, 4–12 M
Evaporator Heaters Megger Testing 7–18 Manifold Gauge Set 7–1
Evaporator Heaters Service 7–17 Manifold Gauge Set Evacuate 7–2
Evaporator Pressure Transducer (EPT) Location 3–3 Manifold Gauge Set Remove 7–3
Evaporator Section 3–2 Manifold Gauge Set, Connect 7–3
Evaporator Section Cleaning 7–21 Manual Pump Down 7–4
Evaporator Temperature Sensor (ETS1/ETS2) Install 7– Micro-Link 5 Microprocessor 4–1
46 Microprocessor 4–1
Evaporator Temperature Sensors (ETS1/ETS2) Loca- Modes of Operation 4–3
tion 3–2
O
F Oil Drain Location 3–3
Failure Action 4–12 Operating Precautions 1–1
Filter Drier Location 3–3 Operation 5–1
Filter Drier Replace 7–17 Operational Software (Cd Function Codes) 4–3
Filter Drier Service 7–16 Options Label Location 3–1
First Aid 1–1
Fork Lift Pockets Location 3–1 P
Painted Surfaces 7–47
Fresh Air Makeup Vent 2–3, 3–2
Perishable Dehumidification 4–5
Fresh Air Makeup Vent Adjustment 5–2
Perishable Dehumidification - Bulb Mode 4–6
Frozen “Heat” Mode 4–9
Perishable Economy 4–6
Frozen Economy Mode 4–9
Perishable Heating 4–4
Frozen Idle Mode 4–9
Perishable Idle, Air Circulation 4–4
Frozen Mode - Temperature Control 4–8
Perishable Mode Cooling - Sequence of Operation 4–7
Frozen Mode Cooling - Sequence of Operation 4–9
T-372 Index–2
Perishable Mode Heating - Sequence of Operation 4–8 Suction Connection Location 3–3
Perishable Mode Temperature Control 4–4 Suction Pressure Transducer (SPT) Location 3–3
Perishable Pulldown 4–4 Suction Service Valve Location 3–3
Perishable Steady State 4–4 Supply Recorder Sensor (SRS) Install 7–45
Physical Inspection 5–4 Supply Recorder Sensor (SRS) Location 3–3
Plate Set 2–2 Supply Temperature Sensor (STS) Install 7–45
Power Cables and Plug Location 3–1 Supply Temperature Sensor (STS) Location 3–3
Pressure Readout 2–1
Pre-Trip 4–15 T
Temperature Control Microprocessor System 4–1
Pre-Trip Diagnosis 5–5
Temperature Readout 2–1
Probe Check 4–11
Temperature Sensor Service 7–34
Probe Diagnostics 5–7
TripWise (Option) 5–8
Protection Modes of Operation 4–12
Troubleshooting 6–1
Pump Down the Unit 7–3
Troubleshooting P6- 7 (DUV) 7–26
Push Button Switches 4–2
Q U
Unit Display Location 3–1
Quest - 2–2
Unit Nameplate Location 3–1
R Upper Air 2–3
Receiver Liquid Level / Moisture Indicator Location 3–3 Upper Fresh Air Makeup Vent 2–3, 5–2
Receiver Location 3–3 USDA 2–2
Receiver Sight Glass Location 3–3 USDA Probes Location 3–2
Refrigerant Charge, Checking 7–6
Refrigerant Leak Check 7–4 V
VAC Power, Connect to 190/230 5–1
Refrigerant, Adding Full Charge to System 7–7
VAC Power, Connect to 380/460 5–1
Refrigerant, Adding Partial Charge to System 7–7
Valve Override Controls 7–28
Refrigerant, Converting to R-513A 7–7
Vent Position Sensor (VPS) 5–3
Refrigeration Circuit Description 3–10
Vent Position Sensor (VPS) Service 7–47
Refrigeration System Data 3–7
Return Recorder Sensor (RRS) Install 7–45 W
Return Recorder Sensor (RRS) Location 3–2 Warning Label Location 3–3
Return Temperature Sensor (RTS) 4–12 Water Cooling 2–3
Return Temperature Sensor (RTS) Install 7–45 Water-Cooled Condenser (WCC) Cleaning 7–14
Return Temperature Sensor (RTS) Location 3–2 Water-Cooled Condenser (WCC) with Condenser Fan
Switch 5–4
S Water-Cooled Condenser (WCC) with Water Pressure
Safety and Protective Devices 3–9 Switch 5–4
Safety Notices 1–1 Water-Cooled Condenser, Connect 5–3
Safety Summary 1–1 Wireless 4–23
Sensor Checkout 7–35 Wireless Enable or Disable 4–24
Service 7–1 Wireless Settings Menu 4–23
Service Access Valve Location 3–3
Service Connections 7–2
Specific Hazard Statements 1–1
Standard Mode 4–17
Standard Operation Description 3–10
Start Temperature Recorder 5–5
Start Up - Compressor Bump Start 4–4
Start Up - Compressor Phase Sequence 4–3
Starting and Stopping Instructions 5–4
Starting the Unit 5–4
Start-Stop Switch (ST) Location 3–1
Start-Up Inspection 5–4
Stopping the Unit 5–4
Index–3 T-372
Carrier Transicold Division,
Carrier Corporation
P.O. Box 4805
Syracuse, NY 13221 USA
www.carrier.com/container-refrigeration/