OFFICE OF TH}i PRO.

IECT DIRECTOIT
MPPWD (PIU), NIRMAN BHAWAN, BHOPAL
SCHEDULE OF RATES ELECTII.ICAL WORKS i.e. (01/1212{)20)
(W/ADDENDUMNO.-01)
The rates of lbllowing items (Electrical SOR i.e. 0111212020) are added in chapter no-45 and
NABL/CPRI test charges as under and rates shall be aplicable with etlbct from the date of issue of
order i.e. ....10312022
No. F-97-171 l202llE&M SOn/ Adtlendum l..lG.l.. Btrop:rto Dt. ...OJ./0flZOZZ
CHAPTER 45
MEDICAL GAS PIPELINE SYSTEM (NIGPS)
Item Sub Ilate
No Ilpm
Itenr Nanrc Descriptinn of Itenr Unit
t'in Ils\
.,
I ,l 6
Supply,instal lation,testing and comnr issioning ol' [u I ly, airtontatic
rnedical isolation panel 1br OT and ICU , isolatotecl power
distribLrtion panelas per ItsC 60364-7-710 and BIS SP 30-2011
part -3 section 4of medical establishntents.ntedical isolaton
Medical
45.r8 lsolation transformer, earth fault location system and rentote indicator
panel should be CE certified irnported from foriegn countries witlr
Panel
4 Digit nurnber european notified body no. , coLrntry of origin
mention on it and consists of fbllorving:

i) I no. Of isolation transfbrmer having primary voltage :2304 |

volt and secondaly voltage 230 volt as per IEC 60364-7-710


and IEC 61558-2-15 , r.r,ith equipment supply voltrrge rarrgc'
70 to 260 volt and frequency range 42 to 460 hz.

ii) I no. of 63 Arrrp lOKA Dp, ELCB.30 rna leakage currenr on


prinrary side and I no. 63 Amp ,lOKA,DP,MCB on
secondary side of isolation transformer.

iii) panel must have provision for two different power supply at
primary side of transformel and system should be designcd
and installed to facilitate the automatic changeover ltom
main ciistributin systenr to electrical safefy porver source
feeding essential loads as per IEC 60364-5-536-2.2.4.

iv) l2 no. of 2OArnp,lOKA , DP,MCI] for outgoings.

v) Isolation transformer shall be provided with overload ancl


ovcr tenrperature rnonitoring alarm through PTC.
vi) environrent qualification : Ambient temp: l0 deg ce lcius to
55 deg celcius. relative humidity : 950% non condensing.
Medical
Isolation
vii) I2no. of core cllrrent transiornrcr having response sensitivity
45.r8.r Panel with
0.2mAmp.
automatic
fault locator
viii) I set of exhaust lan and lllter.
ix) [nsulation Monitor shall be as ]'er IFC 61557-8.
x) I no. of earth fault locator s),stem as per IEC 61557-9 r.vith
injection less than lrnAnrp.
xi) integrated digital voltrnetcr and ammeter and provison of
l,ED indicator fbr mains supply and tJp supply.

Page 1 of 2
-/ rtre
-

Item Sub l{a tc


Itenr Nanrc Description of Item tJnit /in llc\
Nn I fpm
I 1 3 I f, 6

xii) power consumption shorrld be less than l4VA.rrlaxinlLllll


leakage current capacitance shold be less than -5 nlicro f'arad
, nleasuring injected current less than 50rnicrcl Arnp and
noise level less than 28 db.
xiii) I no. of load current nleasuring transformer.
xiv) Panel should be capable oldetecting all combinatiorr of
capacitive and restive faults,including balanccd . unbalanced
and hybrid faults. A self test and self calibration tunction is
included.'l'he above work will bc housed in l6 gaugc MS
enclosure floor/rvall ntounted duly coated u'ith approvcd
colour shade. cable e ntrl' lronr top,prewirecl .cartlring"etc.
required to corrrpletc the.iob in 450W*4001)* i 900[l mrn
dirrcnsion. Subrlitting of'St.D ol panel to Irrrgincer-in-
charge befbre corttrnencelrent olwork .

45.18, L. L l0 KVA a I:ach t 25(XXX) 00

45.18.1.2 EKVA ,^. - ( / l;uclr I l13.l0(x).(x)

No. F-97-l7f t202llE&M SOll./ Addcncrum/...1..6't Bhoprl, Dt. ..b1,.rc11i2(t22


Copy is forwarded to:-
l. P.A to Hon'ble Minister, M.P.P.w.D. Bhopal
2. The Principal Secretarv to Govt. of M.P P.W.D Bhopal
3, The Secretary to Govt. ol M.P.P,W.D' Bhopal
4. The trngineerrn -Chief, M.P.P.W.D. Bhopal
-5. The Chief l'echnical Examiner. M.P. Bhopal.
6. The Irrincipal Secretary to Govt. of M.P. l-lousirtg &Environrnent Bhopal
7. The Accountant General' M.P. Cwalior/Bhopal.
8. The Secretary to Hon'ble Lokayukta. M.l']' Bhopal'
9. The Chief Engineer P.W.D... ' M'P'
l0.TheAdditionalProjectDirectorP.w'D.(PIU)
I l. The Chief Engineer, M.P' R'D.C' Bhopal.
12. The Chief Engineer Rural Engineering Services. M.P' Bhopal'
13. The Comntissioncr, llousing Board' M.P. Bhopal.
14. The Commissioner. BhoPal.
15. The Collector, BhoPal.
16. The Superintending Engineer, Capital Project Circle CPA Bhopal'
17. The Superintending Engineer M.P'P.W.D.
lB. Pro.ject [:ngineer, M.P.P W.D
l'he Divisional
19. 'l'he I:xectrtive [:ngineer. M.P.P.W.D. Division'
20. Chainlan, Contractor Association' MP Bhopal.
21. I1' Cell

--fuy
PRO.I FIC'I- D I ltllcroli.
P\\ l) PIL l]llol,,\ l.

fbq

Page 2 ol 2