Blank Formate
Blank Formate
Location
Date:
2.0 Measurements:
2.1 Current measurement (CT ratio:75/1 A)
Phase Injected Current(A) Measured Value(A)
R 1.0
Y 1.0
B 1.0
3.0 Over current Protection (I>)Setting I =0.72 xIn A, TMS= 0.05, IEC curve NINVI 1.3.
Injected Current Expected Time (Sec) Actual Trip Time(Sec )
(A) R Y B R Y B
1.44 0.218 0.218 0.218
3.6 0.093 0.093 0.093
5.0 Earth fault protection (I0>) Setting I = 0.06xInA, TMS=0.05, IEC curve NINVI 1.3.
Injected Current Expected Time (Sec) Actual Trip Time(Sec )
(A) R Y B R Y B
0.12 0.218 0.218 0.218
0.3 0.093 0.093 0.093
Remarks:TESTED AS ABOVE
TEST REPORT OF TRANSFORMER
Location
Date:
2.0 PI test :
Insulation resistance test HV – E, (5000 V) HV - LV, (5000 V) LV - E, (5000 V)
After 1 min.(Values in Ω) GΩ GΩ GΩ
After 10 min.(Va lues in Ω) GΩ GΩ -
PI Values -