D E SI G N

FIRE PROTECTION SCHEDULE FIRE PROTECTION SYMBOL LEGEND


TEMP. ORIFICE F FIRE PROTECTION SUPPLY PIPING
SYMBOL TYPE K-FACTOR FINISH ACCESSORIES SELECTION
RATING SIZE
SOLENOID VALVE WITH TAMPER SWITCH

1/2" 4.9 WHITE WHITE ESCUTCHEON RELIABLE MODEL F1 TS


155°F SEMI-RECESSED BUTTERFLY VALVE WITH TAMPER SWITCH
PENDENT QUICK RESPONSE
FLOW SWITCH
155°F SEMI-RECESSED 1/2" 5.6 WHITE WHITE ESCUTCHEON RELIABLE MODEL F3QR56
PENDENT QUICK RESPONSE. FDC FIRE DEPARTMENT CONNECTION PIPING

PIPE HANGER

POST INDICATING VALVE

FIRE DEPT. CONNECTION

ABBREVIATIONS

5901 PEACHTREE DUNWOODY RD.


CONT. CONTINUATION

ETR EXISTING TO REMAIN

TELEPHONE: 678-506-8830
N NEW HEAD

BUILDING C, SUITE 250

DYNAMIKDESIGN.COM
F FIRE

ATLANTA, GA 30328
FH FIRE HYDRANT

FDC FIRE DEPARTMENT CONNECTION

FS FLOW SWITCH

GPM GALLONS PER MINUTE

PSI POUNDS PER SQUARE INCH (WATER PRESSURE)

PIV POST INDICATING VALVE

3501 Quadrangle Boulevard

2102409
R RELOCATE HEAD

Certificate of Engineering
Licensure No. P-1651
Orlando, FL 32817
TS TAMPER SWITCH

(407) 380-0400

KYLE J. CARTIER, P.E. 44198


ADAM S. LEVINE, P.E. 53103
Suite 100

SALAS O'BRIEN
HANGER SPACING FOR CPVC PIPING

expect a difference
CONSULTANT:
NOMINAL PIPE SIZE MAX. SPACING
(INCHES) (FEET)

3/4" 5-1/2
1" 6
1-1/4" 6-1/2
1-1/2" 7
2" 8
2-1/2" 9
3" 10

FIRE PROTECTION SPRINKLER DESIGN


1. THESE DRAWINGS ARE INTENDED TO ILLUSTRATE THE DESIGN
INTENT AND AID IN THE COORDINATION OF ELEMENTS OF A FIRE
PROTECTION SPRINKLER DESIGN.

SEAL:
2. THE DESIGN OF THE FIRE PROTECTION SPRINKLER SYSTEM SHALL
BE PROVIDED IN ACCORDANCE WITH THE REQUIREMENTS OF THE
AUTHORITY HAVING JURISDICTION AND THE APPLICABLE
STANDARDS FROM THE NATIONAL FIRE PROTECTION ASSOCIATION
(NFPA).

900 BROOKSTONE CENTRE PKWY


3. THE FIRE PROTECTION SRRINKLER DESIGN SHALL BE COORDINATED
WITH OTHER ASPECTS OF THE BUILDING DESIGN INCLUDING, BUT
NOT LIMITED TO, FIRE ALARM, ELECTRICAL POWER AND LIGHTING,
REFLECTED CEILING, DUCTWORK, PLUMBING AND THE BUILDING
STRUCTURAL SYSTEM.

COLUMBUS, GA 31904
ASHEVILLE, NC 28803
4. THE FIRE PROTECTION SPRINKLER DESIGN DRAWINGS SHALL BE
SUBMITTED FOR COORDINATION PRIOR TO INSTALLATION OF THE
SYSTEM. INSTALLATION WITHOUT COORDINATION WILL BE AT THE
CONTRACTOR'S RISK AND REWORK OF THE SYSTEM SHALL BE
PROVIDED WITHOUT ADDITIONAL COST.

GENERAL NOTES

1. ALL WORK & MATERIAL SHALL BE DONE IN ACCORDANCE WITH NFPA 13, 13R AND
THE LOCAL AUTHORITY.

2. ALL RESIDENTIAL SPRINKLER HEAD SPACING TO BE IN ACCORDANCE WITH THE


MANUFACTURER'S LISTING.

3. ALL FIREWALL PENETRATIONS TO BE SEALED IN ACCORDANCE WITH THEIR

SWEETEN CREEK
PROJECT NUMBER: FDC2018-03
4. PROVIDE SIGN ON DOOR INDICATING "FIRE RISER INSIDE".

DESIGN CRITERIA

1. THE NUMBER OF DESIGN SPRINKLERS SHALL INCLUDE ALL


SPRINKLERS WITHIN A COMPARTMENT UP TO A MINIMUM OF FOUR
SPRINKLERS UNDER A FLAT, SMOOTH, HORIZONTAL CEILING. ANY
LINTEL 8" OR GREATER WILL DIVIDE AN AREA INTO TWO
COMPARTMENTS.

CLIENT:
NO. DRAWING RELEASE DATE
DESIGN DEVELOPMENT 08/27/2021
PERMIT SET 12/03/2021
IFC SET 10/16/2023

TITLE:

LEGEND, NOTES
AND SCHEDULES

SHEET NUMBER:

FP0-01
© COPYRIGHT 2021 DYNAMIK DESIGN
D E SI G N
A3-09 B2
FLOOR CONTROL
A3-09 B2
VALVE

STANDPIPE
STAIR 01

5901 PEACHTREE DUNWOODY RD.


STAIR 02 A3-05 A5
A3-05 A5 STANDPIPE

TELEPHONE: 678-506-8830
BUILDING C, SUITE 250

DYNAMIKDESIGN.COM
A3-01 A1 A3-09 B2-HC

ATLANTA, GA 30328
A3-09 B2 WET PIPE SPRINKLER
SYSTEM FOR THE FLOOR

A3-06 A6

A3-06 A6

A3-02 A2

3501 Quadrangle Boulevard

2102409
Certificate of Engineering
A3-02 A2

Licensure No. P-1651


Orlando, FL 32817

(407) 380-0400

KYLE J. CARTIER, P.E. 44198


ADAM S. LEVINE, P.E. 53103
Suite 100
A3-04 A4
A3-04 A4

SALAS O'BRIEN
expect a difference
CONSULTANT:
BLDG 400 OVERALL PLAN - LEVEL 01 - FIRE PROTECTION
2 SCALE: 1/16" = 1'-0"

SEAL:

900 BROOKSTONE CENTRE PKWY


COLUMBUS, GA 31904
ASHEVILLE, NC 28803

SWEETEN CREEK
PROJECT NUMBER: FDC2018-03
FLOOR
CONTROL STAIR 01
VALVE
STANDPIPE

STAIR 02

STANDPIPE

CLIENT:
A3-09 B2 A3-09 B2

WET PIPE SPRINKLER


SYSTEM FOR THE FLOOR

NO. DRAWING RELEASE DATE


A3-06 A6-HC DESIGN DEVELOPMENT 08/27/2021
A3-06 A6 GMP SET 09/17/2021
PERMIT SET 12/03/2021
A3-02 A2 IFC SET 10/16/2023
A3-02 A2
KEY PLAN
A3-04 A4 A3-04 A4
BLDG 600

6" FIRE
RISER OUT TO FDC

TITLE:
BLDG 400

BLDG 500
BLDG 400
B

B
OVERALL PLAN -
LEVEL B & 01
BLDG 400 OVERALL PLAN - LEVEL B - FIRE PROTECTION
1 SCALE: 1/16" = 1'-0" A
A SHEET NUMBER:

FP1-10
© COPYRIGHT 2021 DYNAMIK DESIGN
D E SI G N
5901 PEACHTREE DUNWOODY RD.

TELEPHONE: 678-506-8830
BUILDING C, SUITE 250

DYNAMIKDESIGN.COM
ATLANTA, GA 30328
3501 Quadrangle Boulevard

2102409
Certificate of Engineering
Licensure No. P-1651
Orlando, FL 32817

(407) 380-0400

KYLE J. CARTIER, P.E. 44198


ADAM S. LEVINE, P.E. 53103
Suite 100

SALAS O'BRIEN
expect a difference
CONSULTANT:
SEAL:

900 BROOKSTONE CENTRE PKWY


COLUMBUS, GA 31904
ASHEVILLE, NC 28803
FLOOR CONTROL
A3-09 B2 A3-09 B2 VALVE

SWEETEN CREEK
PROJECT NUMBER: FDC2018-03
STANDPIPE
STAIR 01

STAIR 02

A3-05 A5 A3-05 A5
STANDPIPE

A3-01 A1 A3-08 B1 A3-05 A5 A3-08 B1 A3-01 A1


A3-09 B2

CLIENT:
A3-09 B2 WET PIPE SPRINKLER
SYSTEM FOR THE FLOOR

NO. DRAWING RELEASE DATE


A3-06 A6-HC DESIGN DEVELOPMENT 08/27/2021
A3-06 A6 PERMIT SET 12/03/2021
IFC SET 10/16/2023
A3-02 A2
A3-02 A2
KEY PLAN
A3-04 A4 A3-08 B1 A3-08 B1 A3-04 A4

BLDG 600

TITLE:
BLDG 400

BLDG 500
BLDG 400
B

B
OVERALL PLAN -
LEVEL 02-04
BLDG 400 OVERALL PLAN - LEVEL 02-04 - FIRE PROTECTION
1 SCALE: 1/16" = 1'-0" A
A SHEET NUMBER:

FP1-11
© COPYRIGHT 2021 DYNAMIK DESIGN
D E SI G N
A3-09 B2 A3-05 A5 A3-08 B1 A3-08 B1 A3-05 A5 A3-09 B2

STANDPIPE

STANDPIPE

5901 PEACHTREE DUNWOODY RD.


STAIR 04 STAIR 03

FLOOR CONTOL
VALVE

TELEPHONE: 678-506-8830
MECH

BUILDING C, SUITE 250

DYNAMIKDESIGN.COM
ATLANTA, GA 30328
A3-08 B2 A3-05 A5 A3-02 A2 A3-05 A2 A3-05 A5 A3-09 B2

ELEC.

WET PIPE SPRINKLER


SYSTEM FOR THE FLOOR

3501 Quadrangle Boulevard

2102409
Certificate of Engineering
Licensure No. P-1651
Orlando, FL 32817
BLDG 500 OVERALL PLAN - LEVEL 02-04 - FIRE PROTECTION

(407) 380-0400
3

KYLE J. CARTIER, P.E. 44198


ADAM S. LEVINE, P.E. 53103
Suite 100
SCALE: 1/16" = 1'-0"

SALAS O'BRIEN
expect a difference
CONSULTANT:
OUT TO FDC 6" FIRE RISER

A3-09 B2-HC A3-05 A5 A3-07 A7 A3-08 B2 A3-05 A5 A3-09 B2

SEAL:
STANDPIPE

STANDPIPE

900 BROOKSTONE CENTRE PKWY


STAIR 04 STAIR 03

FLOOR CONTOL
VALVE
MECH

COLUMBUS, GA 31904
ASHEVILLE, NC 28803
A3-09 B2 A3-05 A5 A3-02 A2 A3-02 A2 A3-05 A5 A3-09 B2

ELEC.

WET PIPE SPRINKLER


SYSTEM FOR THE FLOOR

BLDG 500 OVERALL PLAN - LEVEL 01 - FIRE PROTECTION


2

SWEETEN CREEK
SCALE: 1/16" = 1'-0"

PROJECT NUMBER: FDC2018-03

CLIENT:
NO. DRAWING RELEASE DATE
DESIGN DEVELOPMENT 08/27/2021
GMP SET 09/17/2021
PERMIT SET 12/03/2021
IFC SET 10/16/2023

KEY PLAN
FLOOR
CONTROL STANDPIPE STANDPIPE
VALVE
WET PIPE SPRINKLER
STSYEM FOR THE FLOOR BLDG 600

STAIR 04 STAIR 03

MECH

TITLE:
A3-09 B2 A3-05 A5 A3-02 A2 A3-02 A2 A3-05 A5 A3-09 B2 BLDG 400

ELEC.

B
BLDG 500
BLDG 500
B OVERALL PLAN

A SHEET NUMBER:
A

BLDG 500 OVERALL PLAN - LEVEL B - FIRE PROTECTION


1 SCALE: 1/16" = 1'-0"
FP1-20
© COPYRIGHT 2021 DYNAMIK DESIGN
D E SI G N
A3-09 B2
A3-10 B2-A

5901 PEACHTREE DUNWOODY RD.


FLOOR
CONTROL
VALVE

TELEPHONE: 678-506-8830
STANDPIPE STANDPIPE

BUILDING C, SUITE 250

DYNAMIKDESIGN.COM
A3-03 A3

ATLANTA, GA 30328
A3-09 B2

ELEC

??
A3-09 B2

3501 Quadrangle Boulevard


A3-06 A6

2102409
Certificate of Engineering
Licensure No. P-1651
A3-06 A6

Orlando, FL 32817

(407) 380-0400

KYLE J. CARTIER, P.E. 44198


ADAM S. LEVINE, P.E. 53103
Suite 100
A3-06 A6

WET PIPE SPRINKLER

SALAS O'BRIEN
SYSTEM FOR THE FLOOR

expect a difference
CONSULTANT:
A3-06 A6-HC

A3-09 B2

BLDG 600 OVERALL PLAN - LEVEL 01-04 - FIRE PROTECTION


2 SCALE: 1/16" = 1'-0"

SEAL:

900 BROOKSTONE CENTRE PKWY


COLUMBUS, GA 31904
ASHEVILLE, NC 28803
OUT TO FDC

SWEETEN CREEK
6" FIRE
RISER

PROJECT NUMBER: FDC2018-03


1

A3-09 B2
A3-10 B2-A

STAIR 05

FLOOR
CONTROL MECH
VALVE
STAIR 06

A3-03 A1

CLIENT:
STANDPIPE
STANDPIPE

ELEC.

NO. DRAWING RELEASE DATE


DESIGN DEVELOPMENT 08/27/2021
GMP SET 09/17/2021
PERMIT SET 12/03/2021
1 IFC REVISIONS 10/16/2023
WET PIPE SPRINKLER IFC SET 10/16/2023
SYSTEM FOR THE FLOOR KEY PLAN

BLDG 600

TITLE:
BLDG 400

BLDG 500
BLDG 600
B

B
OVERALL PLAN -
LEVEL B & 01-04
BLDG 600 OVERALL PLAN - LEVEL B - FIRE PROTECTION
1 SCALE: 1/16" = 1'-0" A SHEET NUMBER:
A

FP1-30
© COPYRIGHT 2021 DYNAMIK DESIGN