FCU-E2
FCU-E2
Output Data [Data provided at same ESP to facilitate selection. Airflow will slightly differ due to different ESP]
HIGH MEDIUM LOW
Altitude [ m ] 0 0 0
Air Flow Rate [ m³/h ] 1596 1522 879
E.S.P. [ Pa ] 88 88 88
Cooling Data
Coil Rows [ # ] 3 3 3
On Coil DB / WB [ °C ] 24.0 / 18.0 24.0 / 18.0 24.0 / 18.0
Off Coil DB / WB [ °C ] 13.7 / 12.6 13.9 / 12.8 12.2 / 11.6
Total Duty [ kW ] 8.18 7.50 5.24
Sensible Duty [ kW ] 5.56 5.20 3.49
Enter./Leave. Water Temp. [ °C ] 7.0 / 12.0 7.0 / 12.0 7.0 / 12.0
Water Flow Rate [ L/s ] 0.391 0.359 0.251
Water Pressure Drop [ kPa ] 36.52 29.72 15.95
Sound Pressure Level [ at 1 m. ] [Pls. refer to catalogue for conditions] Electrical Data
Frequency 125 250 500 1K 2K 4K 8K Global Rated Power Supply : 220V/1P/50 Hz.
High [ dBA ] 43.8 46.0 47.7 50.7 47.7 43.7 35.7 55.2 Power Input : Approx. @ Design / Max. [ Watts ] 249.5 / 345.0
Medium [ dBA ] 42.6 44.7 46.3 49.2 46.1 41.8 33.5 53.7 Motor Insulation : B
Low [ dBA ] 37.6 39.5 40.4 43.3 39.5 33.9 24.3 47.8 Motor IP Rating : IP 20
Dimensional Data
Unit Dimensions [ mm ] LxWxH 775 x 1209 x 295 A : 991 B : 1209 C : 1021 D : 927.10
Pack Dimensions [ mm ] LxWxH 897 x 1311 x 516 Pack Weight [ KG ] 42.11 Unit Weight [ KG ] 38.14
Printed : Thu, Nov. 19, 2015 [ Performance are based upon standard configuration ] Page 1 of 1
Version : 4 : 0 : 0
Note : Following continuous improvement,data is subjected to change without prior notice