Project Name BUFT Sold To

Location P.O. No.


Consultant/Engineer York Contract No.
Contractor Last Revision Date Thursday, November 19, 2015

PERFORMANCE DATA SHEET


Unit Tag Qty Offered Model Offered Air Flow Offered Total Duty Offered Sens. Duty

FCU-E2 1 YDFC 10 ST CB 3 X G2 X A5 L 1522 m³/h 7.5 kW 5.2 kW


Input Data
General Data Air Side Fluid Side (Cooling Data)
Unit Type : Cooling Only Target Air Flow [ m³/h ] 0 EWT [ °C ] 7.0
Series / Range : YDFC / CB Air Side (Cooling Data) LWT [ °C ] 12.0
Motor Type : High Static Req. Tot. Duty [ kW ] 7.03 Max. WPD [ kPa ] 60
Specified ESP [ Pa ] 88 EAT-DB / WB [ °C ] 24.0 / 18.0 Fluid Side (Heating Data)
Specified Speed : Medium Air Side (Heating Data) EWT [ °C ] ---
Motor Voltage : 220V/1P/50 Hz. Req. Tot. Duty [ kW ] --- LWT [ °C ] ---
Identification : EAT-DB / WB [ °C ] -- / -- Max. WPD [ kPa ] ---
Unit Data
FCU Range : Standard Type Ceiling Concealed with Back Plenum Coil Tube Diameter : 3/8"
Selected Model Size : 10 Inlet Direction : Back Fin Spacing [FPI]/ Rows : 12 / 3
Fan Plenum : Yes Filter Media : N/A :
No. of Fan(s) / Motor(s) : 2/1 Filter Rail : 27mm Coil Connection : Left
Options & Special Requests

Output Data [Data provided at same ESP to facilitate selection. Airflow will slightly differ due to different ESP]
HIGH MEDIUM LOW
Altitude [ m ] 0 0 0
Air Flow Rate [ m³/h ] 1596 1522 879
E.S.P. [ Pa ] 88 88 88
Cooling Data
Coil Rows [ # ] 3 3 3
On Coil DB / WB [ °C ] 24.0 / 18.0 24.0 / 18.0 24.0 / 18.0
Off Coil DB / WB [ °C ] 13.7 / 12.6 13.9 / 12.8 12.2 / 11.6
Total Duty [ kW ] 8.18 7.50 5.24
Sensible Duty [ kW ] 5.56 5.20 3.49
Enter./Leave. Water Temp. [ °C ] 7.0 / 12.0 7.0 / 12.0 7.0 / 12.0
Water Flow Rate [ L/s ] 0.391 0.359 0.251
Water Pressure Drop [ kPa ] 36.52 29.72 15.95
Sound Pressure Level [ at 1 m. ] [Pls. refer to catalogue for conditions] Electrical Data
Frequency 125 250 500 1K 2K 4K 8K Global Rated Power Supply : 220V/1P/50 Hz.
High [ dBA ] 43.8 46.0 47.7 50.7 47.7 43.7 35.7 55.2 Power Input : Approx. @ Design / Max. [ Watts ] 249.5 / 345.0
Medium [ dBA ] 42.6 44.7 46.3 49.2 46.1 41.8 33.5 53.7 Motor Insulation : B
Low [ dBA ] 37.6 39.5 40.4 43.3 39.5 33.9 24.3 47.8 Motor IP Rating : IP 20

Dimensional Data

E : 960 F : 381 G : 178 H : 290 I : 226 J : 190 K : 775 L : 28 M : 162.56

Water Content [ Liters ] 2

Unit Dimensions [ mm ] LxWxH 775 x 1209 x 295 A : 991 B : 1209 C : 1021 D : 927.10
Pack Dimensions [ mm ] LxWxH 897 x 1311 x 516 Pack Weight [ KG ] 42.11 Unit Weight [ KG ] 38.14
Printed : Thu, Nov. 19, 2015 [ Performance are based upon standard configuration ] Page 1 of 1