UP GRADATION OF REGIONAL

INSTITUTE OF OPHTALMOLOGY AT,


IGIMS PATNA (UNDER
PMSSY PHASE-VB)

TENDER DOCUMENTS
TRANSFORMER
(Schedule of Quantities )

Date: 28/12/2021

ARCHITECT

DESIGN ACCORD CONSULTANTS


ARCHITECTURE, INTERIOR, INDUSTRIAL & LANDSCAPE DESIGN
301&302 U.S. COMPLEX,120
MATHURA ROAD OPP. APOLLO HOSPITAL
NEW DELHI -110076
EMAIL:[email protected]

SERVICE CONSULTANT

ACROBAT ENGINEERS PVT. LTD.


A-1750, Basement level, Gate No. 5,
Green Field, Near NHPC Chowk,
Faridabad-121010
Ph:-0129-2511312/13
[email protected]
www.acrobatengineers.com
UP GRADATION OF REGIONAL INSTITUTE OF OPHTALMOLOGY AT IGIMS PATNA (UNDER PMSSY PHASE-
VB)
SCHEDULE OF QUANTITY
Code
DSR DSR DSR- NSR NSR-
S.No. Description of Items Unit
2018/NS Qty Rate Amount Rate Amount
R

A TRANSFORMER

TRANSFORMER (OIL FILLED TYPE)


Supply, installation, testing & commissioning of 1600 KVA
3 phase, 33 / 0.433 KV indoor type oil filled type
transformer copper wound with DYN 11 connection and
neutral brought out for earthing. The transformer shall be
provided with (–) 5% and (+) 15% ON load tap changer on
HT side. HT side cable termination box shall be suitable
for 33 KV, 3 C x 300 mm2 XLPE cable and LT side
terminal box shall be suitable for 1600A sanwich busduct
1.0 MR with complete with all other associated equipment. The
transformer shall be supplied with Winding temperature
indication and electrical contacts for trip / alrm, Buchholz
relay of double float type with electrical contacts for low
oil level alarm and high gas pressure trip suitable for 24
volts DC and with all accessories complete as per
specifications on all respect.

Set 3

BATTERY CHARGER ;
Supply, installation, testing and commissioning of 200 AH
capacity 220 volts DC hermetically sealed maintenance
free lead acid batteries duly charged including battery
charger unit with provisions of Boost Charing, and Float
2.0 MR charging. Suitable for 240 V, including DC DB single
phase + 10% AC, 50 Hz supply consisting of 63A DP MCB
as incommer and 8No. 20A DP MCB as outgoing as per
attached specifications.
Set 1

3.0 SAFETY EQUIPMENTS;


Supply, installation, testing and commissioning of all
safety Equipments.

3.1 MR Supplying of Rubber hand gloves suitable for 33 kV.


Pair 2
Supply & fixing of Rescue Hook,Discharge Rod of 33Kv
3.2 MR
grade required in panel room Set 1
Supplying and fixing of Shock treatment chart both in
3.3 MR Regional, Hindi,Tamil & English.and framed with 5mm
thick glass as required. Each 10
Supply & fixing MV danger notice plate of 200 mm x
150mm, made of mild steel sheet of at least 2mm thick &
3.4 DSR-2.21 vitreous enamelled white on both sides and with
inscription in signal red colour on front side as required.
Each 9
Supply & fixing HT danger notice plate of 250 mm x
200mm, made of mild steel sheet of at least 2mm thick &
3.5 DSR-2.22 vitreous enamelled white on both sides and with
inscription in signal red colour on front side as required. Each 10
Supply of First aid box containing material as prescribed
3.6 MR by St. John Ambulance brigade OR Indian Red Cross
complete as required. Each 2
Providing of Insulation mat 1 meter wide & 2.5mm thick
3.7 MR to withstand 36kV dielectric strength as per IS 15652-
2006 RM 16
Providing of insulating mat 1 meter wide & 6mm thick to
3.8 MR withstand 3.3kV dielectric strength as per IS 15652- 2006 RM 160
Providing HT Single Line Diagram in wooden frame with
3.9 MR glass.in A1 Size Each 1
Providing LT Single Line Diagram in wooden frame with
4.10 MR glass.in A1 Size Each 1
Supply & fixing of 2nos. Sand bucket with stand and other
4.11 MR accessories. set 2
Supply & fixing of 1nos. Dos & don't chart and other
4.12 MR accessories. nos. 2
Supply & fixing of 1nos. Exit sign board and other
4.13 MR
accessories. nos. 2

ACROBAT ENGINEERS PVT. LTD.


IGIMS (RIO BLOCK) AT PATNA
Page 2 of 63 TRANSFORMER SYSTEM
UP GRADATION OF REGIONAL INSTITUTE OF OPHTALMOLOGY AT IGIMS PATNA (UNDER PMSSY PHASE-
VB)
SCHEDULE OF QUANTITY
Code
DSR DSR DSR- NSR NSR-
S.No. Description of Items Unit
2018/NS Qty Rate Amount Rate Amount
R

TOTAL CARRIED TO SUMMARY

ACROBAT ENGINEERS PVT. LTD.


IGIMS (RIO BLOCK) AT PATNA
Page 3 of 63 TRANSFORMER SYSTEM
UP GRADATION OF REGIONAL INSTITUTE OF OPHTALMOLOGY
AT IGIMS PATNA (UNDER PMSSY PHASE-VB)

COST OF TRANSFORMER WORK

Amount
S. No. Description of item Schedule Item Non-Schedule
DSR - 2018 Item

A TRANSFORMER 0.0 0.0

TOTAL 0.0 0.0

GRAND TOTAL 0.0

ACROBAT ENGINEERS PVT. LTD. SUMMARY SHEET


IGIMS (RIO BLOCK) AT PATNA TRANSFORMER SYSTEM
HINDUSTAN URVARAK & RASAYAN LIMITED (HURL) TOWNSHIP AT SINDRI
#REF!
DETAIL OF MEASUREMENT
S.no code Description Nos Length Breath Height Qty Unit

SUB HEAD - EARTH WORK


Earth work in excavation by mechanical means
(Hydraulic excavator)/manual means over areas
(exceeding 30 cm in depth, 1.5 m in width as well as
2.6 10 sqm on plan) including getting out and disposal
of excavated earth lead upto 50 m and lift upto 1.5
m, as directed by Engineer-in-charge.

2.6.1 All kinds of soil


f1 1.00 10 1 3.1 3.1 1.5 144.15 cum
f2 1.00 8 1 2.9 2.9 1.5 100.92 cum
f3 1.00 6 1 2.7 2.7 1.5 65.61 cum
f4 1.00 2 1 2.5 2.5 1.5 18.75 cum
329.00 cum

Filling available excavated earth (excluding rock) in


trenches, plinth, sides of foundations etc. in layers
2.25 not exceeding 20cm in depth, consolidating each cum
deposited layer by ramming and watering, lead up to
50 m and lift upto 1.5 m.
total excavation 329.00
less pcc -15.00 cum
less rcc -40.00
274.00 cum
Supplying and filling in plinth with sand under floors,
2.27 including watering, ramming, consolidating and Cum
dressing complete.
slab 1.00 1 4 2.865 2.9 0.1 3.32 cum
slab 1.00 1 4 1.5 2.9 0.1 1.74 cum
slab 1.00 1 4 2.665 2.95 0.1 3.14 cum
slab 1.00 1 4 1.87 1.22 0.1 0.91 cum
slab balcony 1.00 1 4 1.65 1 0.1 0.66 cum
slab balcony 1.00 1 4 1.75 1 0.1 0.70 cum
slab stair lobby 1.00 1 2 2.4 1.23 0.1 0.59 cum
landing 1.00 1 2 2.4 1.22 0.1 0.59 cum
mumty 1.00 1 1 5.7 2.37 0.1 1.35 cum
0.00 cum
13.00 cum
Supplying chemical emulsion in sealed containers
2.34
including delivery as specified.
Chlorpyriphos/ Lindane emulsifiable concentrate of
2.34.1 30% litre
20%
plinth area 152 0.3 45.60 litre
0.00 litre
46.00 litre
Diluting and injecting chemical emulsion for POST-
2.35 CONSTRUCTIONAL anti-termite treatment
(excluding the cost of chemical emulsion) :
Along the external wall below concrete or masonry
apron using chemical emulsion @ 2.25 litres per
2.35.2 linear metre including drilling and plugging holes
etc.:
With Chlorpyriphos/ Lindane E.C. 20% with 1%
2.35.2.1 68 metre
concentration
Treatment of soil under existing floors using
chemical emulsion @ one litre per hole, 300 mm
2.35.3 apart including drilling 12 mm diameter holes and
plugging with cement mortar 1 :2 (1 cement : 2
Coarse sand) to match the existing floor:
With Chlorpyriphos/Lindane E.C. 20% with 1%
2.35.3.1 152 sqm
concentration
Supply and stacking of Fly ash conforming to IRC-
58 at site, including carriage, loading , unloading &
2.37 stacking up to any lead (measured stacks will be cum
reduced by 20% for payment). 52.00 50% 26
Filling with available fly ash and earth (excluding
rock) in trenches or embankment in layers (each
layer should not exceed 15 cm), with intermediate
layer of compacted earth (Soil density of 98%) after
every four layers of compacted depth of fly ash,
sides & top layer of filling shall be done with earth
2.38 having total minimum compacted thickness 30 cm or cum
as decided by Engineer -in-charge, including
compacting each layer by rolling/ ramming and
watering, all complete as per drawing and direction
of Engineer -in - charge.

0.00 cum
slab 1.00 1 4 2.865 2.9 0.4 13.29 cum
slab 1.00 1 4 1.5 2.9 0.4 6.96 cum
slab 1.00 1 4 2.665 2.95 0.4 12.58 cum
slab 1.00 1 4 1.87 1.22 0.4 3.65 cum
slab balcony 1.00 1 4 1.65 1 0.4 2.64 cum
slab balcony 1.00 1 4 1.75 1 0.4 2.80 cum
slab stair lobby 1.00 1 2 2.4 1.23 0.4 2.36 cum
landing 1.00 1 2 2.4 1.22 0.4 2.34 cum
mumty 1.00 1 1 5.7 2.37 0.4 5.40 cum
0.00 cum
52.00 cum

Total of Earth work :


SUB HEAD - CONCRETE WORK
Providing and laying in position cement concrete of
4.1 specified grade excluding the cost of centering and
shuttering - All work up to plinth level :
1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded
4.1.3 cum
stone aggregate 20 mm nominal size).
under floor same as sand filling 13.00 cum
0.00 cum
13.00 cum
1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8
4.1.8 cum
graded stone aggregate 40 mm nominal size)
f1 1.00 10 1 2.1 2.1 0.1 4.41 cum
f2 1.00 8 1 1.9 1.9 0.1 2.89 cum
f3 1.00 6 1 1.7 1.7 0.1 1.73 cum
f4 1.00 2 1 1.5 1.5 0.1 0.45 cum
Plinth Beams
Along Grid 1/ A-I 1 1 1 4.378 0.43 0.1 0.188254
1 1 1 4.378 0.43 0.1 0.188254

Along Grid 2/ A-I 1 1 1 2.665 0.43 0.1 0.114595


1 1 1 2.665 0.43 0.1 0.114595

Along Grid 3/ A-I 1 1 1 2.345 0.43 0.1 0.100835


1 1 1 1.503 0.43 0.1 0.064629
1 1 1 1.503 0.43 0.1 0.064629
1 1 1 2.345 0.43 0.1 0.100835

B/W Grid 3-4/ A-I 1 1 1 0.825 0.315 0.1 0.0259875

Along Grid 4/ A-I 1 1 1 2.485 0.43 0.1 0.106855


1 1 1 2.665 0.43 0.1 0.114595
1 1 1 2.665 0.43 0.1 0.114595
1 1 1 1.733 0.43 0.1 0.074519

Along Grid 5/ A-I 1 1 1 2.485 0.43 0.1 0.106855


1 1 1 2.665 0.43 0.1 0.114595
1 1 1 2.665 0.43 0.1 0.114595
1 1 1 1.733 0.43 0.1 0.074519

B/W Grid 5-6/ A-I 1 1 1 0.825 0.315 0.1 0.0259875

Along Grid 6/ A-I 1 1 1 2.345 0.43 0.1 0.100835


1 1 1 1.503 0.43 0.1 0.064629
1 1 1 1.503 0.43 0.1 0.064629
1 1 1 2.345 0.43 0.1 0.100835

B/W Grid 6-7/ A-I 1 1 1 2.665 0.43 0.1 0.114595


1 1 1 2.665 0.43 0.1 0.114595

Along Grid 7/ A-I 1 1 1 4.378 0.43 0.1 0.188254


1 1 1 4.378 0.43 0.1 0.188254

Along Grid A/1-7 1 1 1 2.16 0.43 0.1 0.09288


1 1 1 2.16 0.43 0.1 0.09288

Along Grid B/1-7 1 1 1 0.85 0.43 0.1 0.03655


1 1 1 2.403 0.43 0.1 0.103329
1 1 1 0.845 0.43 0.1 0.036335

Along Grid C/1-7 1 1 1 2.83 0.43 0.1 0.12169


1 1 1 1.22 0.43 0.1 0.05246
1 1 1 1.22 0.43 0.1 0.05246
1 1 1 2.83 0.43 0.1 0.12169

Along Grid D/1-7 1 1 1 3.91 0.43 0.1 0.16813


1 1 1 3.91 0.43 0.1 0.16813

Along Grid E/1-7 1 1 1 2.21 0.43 0.1 0.09503


1 1 1 2.403 0.43 0.1 0.103329
1 1 1 2.21 0.43 0.1 0.09503

B/W Grid E-F/1-7 1 1 1 2.398 0.43 0.1 0.103114

Along Grid F/1-7 1 1 1 3.91 0.43 0.1 0.16813


1 1 1 3.91 0.43 0.1 0.16813
Along Grid G/1-7 1 1 1 2.83 0.43 0.1 0.12169
1 1 1 1.22 0.43 0.1 0.05246
1 1 1 1.22 0.43 0.1 0.05246
1 1 1 2.83 0.43 0.1 0.12169

Along Grid I/1-7 1 1 1 2.16 0.43 0.1 0.09288


1 1 1 2.16 0.43 0.1 0.09288

BKT 1 1 2 1.105 0.315 0.1 0.069615


1 1 2 1.197 0.315 0.1 0.075411
0.00 cum
15.00 cum
Providing and laying cement concrete in retaining
walls, return walls, walls (any thickness) including
attached pilasters, columns, piers, abutments,
pillars, posts, struts, buttresses, string or lacing
4.2 courses, parapets, coping, bed blocks, anchor
blocks, plain window sills, fillets, sunken floor,etc.,
up to floor five level,excluding the cost of centering,
shuttering and finishing :

1:2:4 (1 Cement : 2 coarse sand : 4 graded stone


4.2.3 cum
aggregate 20mm nominal size)
Parapet wall 1.00 1 1 73 0.28 0.05 1.02 cum
1.00 cum

Providing and fixing at or near ground level precast


cement concrete in kerbs, edgings etc. as per
approved pattern and setting in position with cement
4.6 mortar 1:3 (1 Cement : 3 coarse sand), including the
cost of required centering, shuttering complete.

1:1½:3 (1 Cement: 1½ coarse sand(zone-III) : 3


4.6.1 graded stone aggregate 20 mm cum
nominal size) .
Around plinth 1.00 1 1 68 0.15 0.1 1.02 cum
0.00 cum
1.00 cum
Providing and laying damp-proof course 40mm thick
with cement concrete 1:2:4 (1 cement : 2 coarse
4.10 sand : 4 graded stone aggregate 12.5mm nominal sqm
size).
Plinth Beams
Along Grid 1/ A-I 1 1 1 4.378 0.23 1.00694
1 1 1 4.378 0.23 1.00694

Along Grid 2/ A-I 1 1 1 2.665 0.23 0.61295


1 1 1 2.665 0.23 0.61295

Along Grid 3/ A-I 1 1 1 2.345 0.23 0.53935


1 1 1 1.503 0.23 0.34569
1 1 1 1.503 0.23 0.34569
1 1 1 2.345 0.23 0.53935

B/W Grid 3-4/ A-I 1 1 1 0.825 0.115 0.094875

Along Grid 4/ A-I 1 1 1 2.485 0.23 0.57155


1 1 1 2.665 0.23 0.61295
1 1 1 2.665 0.23 0.61295
1 1 1 1.733 0.23 0.39859

Along Grid 5/ A-I 1 1 1 2.485 0.23 0.57155


1 1 1 2.665 0.23 0.61295
1 1 1 2.665 0.23 0.61295
1 1 1 1.733 0.23 0.39859

B/W Grid 5-6/ A-I 1 1 1 0.825 0.115 0.094875


Along Grid 6/ A-I 1 1 1 2.345 0.23 0.53935
1 1 1 1.503 0.23 0.34569
1 1 1 1.503 0.23 0.34569
1 1 1 2.345 0.23 0.53935

B/W Grid 6-7/ A-I 1 1 1 2.665 0.23 0.61295


1 1 1 2.665 0.23 0.61295

Along Grid 7/ A-I 1 1 1 4.378 0.23 1.00694


1 1 1 4.378 0.23 1.00694

Along Grid A/1-7 1 1 1 2.16 0.23 0.4968


1 1 1 2.16 0.23 0.4968

Along Grid B/1-7 1 1 1 0.85 0.23 0.1955


1 1 1 2.403 0.23 0.55269
1 1 1 0.845 0.23 0.19435

Along Grid C/1-7 1 1 1 2.83 0.23 0.6509


1 1 1 1.22 0.23 0.2806
1 1 1 1.22 0.23 0.2806
1 1 1 2.83 0.23 0.6509

Along Grid D/1-7 1 1 1 3.91 0.23 0.8993


1 1 1 3.91 0.23 0.8993

Along Grid E/1-7 1 1 1 2.21 0.23 0.5083


1 1 1 2.403 0.23 0.55269
1 1 1 2.21 0.23 0.5083

B/W Grid E-F/1-7 1 1 1 2.398 0.23 0.55154

Along Grid F/1-7 1 1 1 3.91 0.23 0.8993


1 1 1 3.91 0.23 0.8993

Along Grid G/1-7 1 1 1 2.83 0.23 0.6509


1 1 1 1.22 0.23 0.2806
1 1 1 1.22 0.23 0.2806
1 1 1 2.83 0.23 0.6509

Along Grid I/1-7 1 1 1 2.16 0.23 0.4968


1 1 1 2.16 0.23 0.4968

BKT 1 1 2 1.105 0.115 0.25415


1 1 2 1.197 0.115 0.27531

28.00 sqm

Extra for providing and mixing water proofing


per 50Kg
4.12 material in cement concrete work @ 1 kg per 50kg
cement
of cement. 28.00 20% 6
Applying a coat of residual petroleum bitumen of
penetration 80/100 of approved quality using 1.7kg
per square metre on damp proof course after
4.13 cleaning the surface with brushes and finally with a sqm
piece of cloth lightly soaked in kerosene oil.
28.00
Making plinth protection 50mm thick of cement
concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded
stone aggregate 20 mm nominal size) over 75mm
thick bed of dry brick ballast 40 mm nominal size,
4.17 well rammed and consolidated and grouted with fine sqm
sand, including necessary excavation, levelling &
dressing & finishing the top smooth.
68 1 68
Providing and laying light weight Foam Concrete of
NSI density 450-500 kg/cum in sunken portion at all cum
levels as per direction of Engineer-In-Charge.
toilet 3 4 1 2.10 1.35 0.45 15.31
15.00 cum
Total of Concrete work :
SUB HEAD - R C C WORK
Centring and shuttering including strutting, propping
5.9
etc. and removal of form for :
Foundations, footings, bases of columns, etc. for
5.9.1 sqm
mass concrete.
f1 1.00 10 1 1.9 1.9 0.23 17.48 sqm
f2 1.00 8 1 1.7 1.7 0.23 12.51 sqm
f3 1.00 6 1 1.5 1.5 0.2 7.20 sqm
f4 1.00 2 1 1.3 1.3 0.3 3.12 sqm
pcc side shuttering
f1 1.00 10 1 2.1 2.1 0.1 8.40 sqm
f2 1.00 8 1 1.9 1.9 0.1 6.08 sqm
f3 1.00 6 1 1.7 1.7 0.1 4.08 sqm
f4 1.00 2 1 1.5 1.5 0.1 1.20 sqm
Plinth Beams
Along Grid 1/ A-I 1 1 1 4.378 2 0.1 0.8756
1 1 1 4.378 2 0.1 0.8756

Along Grid 2/ A-I 1 1 1 2.665 2 0.1 0.533


1 1 1 2.665 2 0.1 0.533

Along Grid 3/ A-I 1 1 1 2.345 2 0.1 0.469


1 1 1 1.503 2 0.1 0.3006
1 1 1 1.503 2 0.1 0.3006
1 1 1 2.345 2 0.1 0.469

B/W Grid 3-4/ A-I 1 1 1 0.825 2 0.1 0.165

Along Grid 4/ A-I 1 1 1 2.485 2 0.1 0.497


1 1 1 2.665 2 0.1 0.533
1 1 1 2.665 2 0.1 0.533
1 1 1 1.733 2 0.1 0.3466

Along Grid 5/ A-I 1 1 1 2.485 2 0.1 0.497


1 1 1 2.665 2 0.1 0.533
1 1 1 2.665 2 0.1 0.533
1 1 1 1.733 2 0.1 0.3466

B/W Grid 5-6/ A-I 1 1 1 0.825 2 0.1 0.165

Along Grid 6/ A-I 1 1 1 2.345 2 0.1 0.469


1 1 1 1.503 2 0.1 0.3006
1 1 1 1.503 2 0.1 0.3006
1 1 1 2.345 2 0.1 0.469

B/W Grid 6-7/ A-I 1 1 1 2.665 2 0.1 0.533


1 1 1 2.665 2 0.1 0.533

Along Grid 7/ A-I 1 1 1 4.378 2 0.1 0.8756


1 1 1 4.378 2 0.1 0.8756

Along Grid A/1-7 1 1 1 2.16 2 0.1 0.432


1 1 1 2.16 2 0.1 0.432

Along Grid B/1-7 1 1 1 0.85 2 0.1 0.17


1 1 1 2.403 2 0.1 0.4806
1 1 1 0.845 2 0.1 0.169

Along Grid C/1-7 1 1 1 2.83 2 0.1 0.566


1 1 1 1.22 2 0.1 0.244
1 1 1 1.22 2 0.1 0.244
1 1 1 2.83 2 0.1 0.566
Along Grid D/1-7 1 1 1 3.91 2 0.1 0.782
1 1 1 3.91 2 0.1 0.782

Along Grid E/1-7 1 1 1 2.21 2 0.1 0.442


1 1 1 2.403 2 0.1 0.4806
1 1 1 2.21 2 0.1 0.442

B/W Grid E-F/1-7 1 1 1 2.398 2 0.1 0.4796

Along Grid F/1-7 1 1 1 3.91 2 0.1 0.782


1 1 1 3.91 2 0.1 0.782

Along Grid G/1-7 1 1 1 2.83 2 0.1 0.566


1 1 1 1.22 2 0.1 0.244
1 1 1 1.22 2 0.1 0.244
1 1 1 2.83 2 0.1 0.566

Along Grid I/1-7 1 1 1 2.16 2 0.1 0.432


1 1 1 2.16 2 0.1 0.432

BKT 1 1 2 1.105 2 0.1 0.442


1 1 2 1.197 2 0.1 0.4788
0.00 sqm
85.00 sqm
Walls (any thickness) including attached pilasters,
5.9.2 butteresses, plinth and string courses etc. sqm

WATER TANK
wall horizontally outer 1 2 1 5.32 2 2.75 58.52 sqm
wall vertically outer 1 2 1 2.455 2 2.75 27.01 sqm
middle wall vertically 1 3 1 2.455 2 1.35 19.89 sqm
105.00 sqm
Suspended floors, roofs, landings, balconies and
5.9.3 sqm
access platform
slab 3.00 1 4 2.865 2.9 99.70 sqm
slab 3.00 1 4 1.5 2.9 52.20 sqm
slab 3.00 1 4 2.665 2.95 94.34 sqm
slab 3.00 1 4 1.87 1.22 27.38 sqm
slab balcony 3.00 1 4 1.65 1 19.80 sqm
slab balcony 3.00 1 4 1.75 1 21.00 sqm
slab stair lobby 3.00 1 2 2.4 1.23 17.71 sqm
landing 3.00 1 2 2.4 1.22 17.57 sqm
mumty 1.00 1 1 5.7 2.37 13.51 sqm
water tank top & bottom slab 1.00 2 1 4.92 2.455 24.16 sqm
387.00 sqm
5.9.4 Shelves Sqm
kitchen 3.00 4 1 2.185 0.6 15.73 Sqm
toilet 3.00 4 1 0.6 0.6 4.32 Sqm
20.00 Sqm
Sqm

Lintels, beams, plinth beams, girders, bressumers


5.9.5 sqm
and cantilevers.
Plinth Beams
Along Grid 1/ A-I 1 1 1 4.378 2 0.45 3.9402
1 1 1 4.378 2 0.45 3.9402

Along Grid 2/ A-I 1 1 1 2.665 2 0.45 2.3985


1 1 1 2.665 2 0.45 2.3985

Along Grid 3/ A-I 1 1 1 2.345 2 0.45 2.1105


1 1 1 1.503 2 0.45 1.3527
1 1 1 1.503 2 0.45 1.3527
1 1 1 2.345 2 0.45 2.1105

B/W Grid 3-4/ A-I 1 1 1 0.825 2 0.3 0.495


Along Grid 4/ A-I 1 1 1 2.485 2 0.45 2.2365
1 1 1 2.665 2 0.45 2.3985
1 1 1 2.665 2 0.45 2.3985
1 1 1 1.733 2 0.45 1.5597

Along Grid 5/ A-I 1 1 1 2.485 2 0.45 2.2365


1 1 1 2.665 2 0.45 2.3985
1 1 1 2.665 2 0.45 2.3985
1 1 1 1.733 2 0.45 1.5597

B/W Grid 5-6/ A-I 1 1 1 0.825 2 0.3 0.495

Along Grid 6/ A-I 1 1 1 2.345 2 0.45 2.1105


1 1 1 1.503 2 0.45 1.3527
1 1 1 1.503 2 0.45 1.3527
1 1 1 2.345 2 0.45 2.1105

B/W Grid 6-7/ A-I 1 1 1 2.665 2 0.45 2.3985


1 1 1 2.665 2 0.45 2.3985

Along Grid 7/ A-I 1 1 1 4.378 2 0.45 3.9402


1 1 1 4.378 2 0.45 3.9402

Along Grid A/1-7 1 1 1 2.16 2 0.45 1.944


1 1 1 2.16 2 0.45 1.944

Along Grid B/1-7 1 1 1 0.85 2 0.45 0.765


1 1 1 2.403 2 0.45 2.1627
1 1 1 0.845 2 0.45 0.7605

Along Grid C/1-7 1 1 1 2.83 2 0.45 2.547


1 1 1 1.22 2 0.45 1.098
1 1 1 1.22 2 0.45 1.098
1 1 1 2.83 2 0.45 2.547

Along Grid D/1-7 1 1 1 3.91 2 0.45 3.519


1 1 1 3.91 2 0.45 3.519

Along Grid E/1-7 1 1 1 2.21 2 0.45 1.989


1 1 1 2.403 2 0.45 2.1627
1 1 1 2.21 2 0.45 1.989

B/W Grid E-F/1-7 1 1 1 2.398 2 0.45 2.1582

Along Grid F/1-7 1 1 1 3.91 2 0.45 3.519


1 1 1 3.91 2 0.45 3.519

Along Grid G/1-7 1 1 1 2.83 2 0.45 2.547


1 1 1 1.22 2 0.45 1.098
1 1 1 1.22 2 0.45 1.098
1 1 1 2.83 2 0.45 2.547

Along Grid I/1-7 1 1 1 2.16 2 0.45 1.944


1 1 1 2.16 2 0.45 1.944

BKT 1 1 2 1.105 2 0.3 1.326


1 1 2 1.197 2 0.3 1.4364

First & Second Floor Beam


Along Grid 1/ A-I 2 1 1 4.378 0.23 0.32 7.62 sqm
2 1 1 4.378 0.23 0.32 7.62 sqm

Along Grid 2/ A-I 2 1 1 2.665 0.23 0.32 4.64 sqm


2 1 1 2.665 0.23 0.32 4.64 sqm

Along Grid 3/ A-I 2 1 1 2.345 0.23 0.32 4.08 sqm


2 1 1 1.503 0.23 0.32 2.62 sqm
2 1 1 1.503 0.23 0.32 2.62 sqm
2 1 1 2.345 0.23 0.32 4.08 sqm

B/W Grid 3-4/ A-I 2 1 1 0.825 0.115 0.3 1.18

Along Grid 4/ A-I 2 1 1 2.485 0.23 0.32 4.32 sqm


2 1 1 2.665 0.23 0.32 4.64 sqm
2 1 1 2.665 0.23 0.32 4.64 sqm
2 1 1 1.733 0.23 0.32 3.02 sqm

Along Grid 5/ A-I 2 1 1 2.485 0.23 0.32 4.32 sqm


2 1 1 2.665 0.23 0.32 4.64 sqm
2 1 1 2.665 0.23 0.32 4.64 sqm
2 1 1 1.733 0.23 0.32 3.02 sqm

B/W Grid 5-6/ A-I 2 1 1 0.825 0.115 0.3 1.18

Along Grid 6/ A-I 2 1 1 2.345 0.23 0.32 4.08 sqm


2 1 1 1.503 0.23 0.32 2.62 sqm
2 1 1 1.503 0.23 0.32 2.62 sqm
2 1 1 2.345 0.23 0.32 4.08 sqm

B/W Grid 6-7/ A-I 2 1 1 2.665 0.23 0.32 4.64 sqm


2 1 1 2.665 0.23 0.32 4.64 sqm

Along Grid 7/ A-I 2 1 1 4.378 0.23 0.32 7.62 sqm


2 1 1 4.378 0.23 0.32 7.62 sqm

Along Grid A/1-7 2 1 1 2.16 0.23 0.32 3.76 sqm


2 1 1 2.16 0.23 0.32 3.76 sqm

Along Grid B/1-7 2 1 1 0.85 0.23 0.32 1.48 sqm


2 1 1 2.403 0.23 0.32 4.18 sqm
2 1 1 0.845 0.23 0.32 1.47 sqm

Along Grid C/1-7 2 1 1 2.83 0.23 0.32 4.92 sqm


2 1 1 1.22 0.23 0.32 2.12 sqm
2 1 1 1.22 0.23 0.32 2.12 sqm
2 1 1 2.83 0.23 0.32 4.92 sqm

Along Grid D/1-7 2 1 1 3.91 0.23 0.32 6.80 sqm


2 1 1 3.91 0.23 0.32 6.80 sqm

Along Grid E/1-7 2 1 1 2.21 0.23 0.32 3.85 sqm


2 1 1 2.403 0.23 0.32 4.18 sqm
2 1 1 2.21 0.23 0.32 3.85 sqm

B/W Grid E-F/1-7 2 1 1 2.398 0.23 0.32 4.17 sqm

Along Grid F/1-7 2 1 1 3.91 0.23 0.32 6.80 sqm


2 1 1 3.91 0.23 0.32 6.80 sqm

Along Grid G/1-7 2 1 1 2.83 0.23 0.32 4.92 sqm


2 1 1 1.22 0.23 0.32 2.12 sqm
2 1 1 1.22 0.23 0.32 2.12 sqm
2 1 1 2.83 0.23 0.32 4.92 sqm

Along Grid I/1-7 2 1 1 2.16 0.23 0.32 3.76 sqm


2 1 1 2.16 0.23 0.32 3.76 sqm

BKT 2 1 2 1.105 0.115 0.3 3.16


2 1 2 1.197 0.115 0.3 3.42

Terrace Beams
Along Grid 1/ A-I 1 1 1 4.378 0.23 0.32 3.81 sqm
1 1 1 4.378 0.23 0.32 3.81 sqm

Along Grid 2/ A-I 1 1 1 2.665 0.23 0.32 2.32 sqm


1 1 1 2.665 0.23 0.32 2.32 sqm

Along Grid 3/ A-I 1 1 1 2.345 0.23 0.32 2.04 sqm


1 1 1 1.503 0.23 0.32 1.31 sqm
1 1 1 1.503 0.23 0.32 1.31 sqm
1 1 1 2.345 0.23 0.32 2.04 sqm

B/W Grid 3-4/ A-I 1 1 1 0.825 0.115 0.3 0.59

Along Grid 4/ A-I 1 1 1 2.485 0.23 0.32 2.16 sqm


1 1 1 2.665 0.23 0.32 2.32 sqm
1 1 1 2.665 0.23 0.32 2.32 sqm
1 1 1 1.733 0.23 0.32 1.51 sqm

Along Grid 5/ A-I 1 1 1 2.485 0.23 0.32 2.16 sqm


1 1 1 2.665 0.23 0.32 2.32 sqm
1 1 1 2.665 0.23 0.32 2.32 sqm
1 1 1 1.733 0.23 0.32 1.51 sqm

B/W Grid 5-6/ A-I 1 1 1 0.825 0.115 0.3 0.59

Along Grid 6/ A-I 1 1 1 2.345 0.23 0.32 2.04 sqm


1 1 1 1.503 0.23 0.32 1.31 sqm
1 1 1 1.503 0.23 0.32 1.31 sqm
1 1 1 2.345 0.23 0.32 2.04 sqm

B/W Grid 6-7/ A-I 1 1 1 2.665 0.23 0.32 2.32 sqm


1 1 1 2.665 0.23 0.32 2.32 sqm

Along Grid 7/ A-I 1 1 1 4.378 0.23 0.32 3.81 sqm


1 1 1 4.378 0.23 0.32 3.81 sqm

Along Grid A/1-7 1 1 1 2.16 0.23 0.32 1.88 sqm


1 1 1 2.16 0.23 0.32 1.88 sqm

Along Grid B/1-7 1 1 1 0.85 0.23 0.32 0.74 sqm


1 1 1 2.403 0.23 0.32 2.09 sqm
1 1 1 0.845 0.23 0.32 0.74 sqm

Along Grid C/1-7 1 1 1 1.22 0.23 0.32 1.06 sqm


1 1 1 1.22 0.23 0.32 1.06 sqm

Along Grid D/1-7 1 1 1 3.91 0.23 0.32 3.40 sqm


1 1 1 3.91 0.23 0.32 3.40 sqm

Along Grid E/1-7 1 1 1 2.21 0.23 0.32 1.92 sqm


1 1 1 2.403 0.23 0.32 2.09 sqm
1 1 1 2.21 0.23 0.32 1.92 sqm

B/W Grid E-F/1-7 1 1 1 2.398 0.23 0.32 2.09 sqm

Along Grid F/1-7 1 1 1 3.91 0.23 0.32 3.40 sqm


1 1 1 3.91 0.23 0.32 3.40 sqm

Along Grid G/1-7 1 1 1 1.22 0.23 0.32 1.06 sqm


1 1 1 1.22 0.23 0.32 1.06 sqm

Along Grid I/1-7 1 1 1 2.16 0.23 0.32 1.88 sqm


1 1 1 2.16 0.23 0.32 1.88 sqm

BKT 1 1 2 1.197 0.115 0.3 1.71

Mumty
Along Grid 4/ A-I 1 1 1 2.485 0.23 0.32 2.16 sqm
1 1 1 2.665 0.23 0.32 2.32 sqm

Along Grid 5/ A-I 1 1 1 2.485 0.23 0.32 2.16 sqm


1 1 1 2.665 0.23 0.32 2.32 sqm

Along Grid B/1-7 1 1 1 2.403 0.23 0.32 2.09 sqm

Along Grid E/1-7 1 1 1 2.403 0.23 0.32 2.09 sqm


0.00 sqm
428.00 sqm
Columns, Pillars, Piers, Abutments, Posts and Struts
5.9.6 sqm

up to plinth
column padastal 1 1 26 0.6 0.75 0.3 21.06 sqm
column 1.00 1 26 0.3 0.45 1.3 50.70 sqm
Column From Gf to Top. 1 1 26 0.3 0.45 9.45 368.55 sqm
Mumty 1 1 6 0.3 0.45 3.15 28.35 sqm
Terrace 1 1 19 0.3 0.45 3.15 89.77 sqm
WATER TANK
wall horizontally outer 1 2 1 5.32 0.2 2.75 5.85 cum
wall vertically outer 1 2 1 2.455 0.2 2.75 2.70 cum
middle wall vertically 1 3 1 2.455 0.2 1.35 1.99 cum

569.00 sqm
Stairs, (excluding landings) except spiral-staircases.
5.9.7 sqm

waist slab 3.00 1 2 3.3 1.2 23.76 sqm


tread 3.00 1 21 1.2 0.15 11.34 sqm
0.00 sqm
35.00 sqm
Small lintels not exceeding 1.5 m clear span,
moulding as in cornices, window sills, string
5.9.15 courses, bands, copings, bed plates, anchor blocks lumpsum sqm
and the like 5
5.9.16 Edges of slabs and breaks in floors and walls
5.9.16.1 Under 20 cm wide 3.00 1 1 68 204.00 metre
5.9.16.2 Above 20 cm wide sqm
5.9.17 Cornices and mouldings sqm
Weather shade, Chajjas, corbels etc., including
5.9.19 sqm
edges
V 3 6 1 0.6 0.6 6.48 sqm
W 3 4 1 0.9 0.6 6.48 sqm
13.00 sqm
Providing, hoisting and fixing up to floor five level
precast reinforced cement concrete in small lintels
not exceeding 1.5m clear span up to floor five level,
including the cost of required centering, shuttering
5.13 but , excluding the cost of reinforcement, with cum
1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) : 3
graded stone aggregate 20 mm nominal size).

D 3 4 1 1.2 0.23 0.15 0.50 cum


D1 3 4 1 0.9 0.23 0.15 0.37 cum
D2 3 4 1 0.75 0.115 0.15 0.16 cum
SL 3 8 1 1.5 0.23 0.15 1.24 cum
main door 3 1 1 1.5 0.23 0.15 0.16 cum
V 3 6 1 0.6 0.23 0.15 0.37 cum
W 3 4 1 0.9 0.23 0.15 0.37 cum
0.00 cum
3.00 cum
Providing, hoisting and fixing up to floor five level
precast reinforced cement concrete in shelves,
including setting in cement mortar 1:3 (1 cement : 3
coarse sand), cost of required centering, shuttering
5.16 and finishing with neat cement punning on exposed cum
surfaces but excluding the cost of reinforcement,
with 1:2:4 (1 cement : 2 coarse sand : 4 graded
stone aggregate 12.5 mm nominal size).

5.9.4 Shelves
cub board 3 4 3 1 0.6 0.05 1.08 cum
0.00 cum
1.00 cum
Steel reinforcement for R.C.C. work including
straightening, cutting, bending, placing in position
5.22 and binding all complete upto plinth level.

Thermo-Mechanically Treated bars of grade Fe-


5.22.6 kg
500D or more.
up to plinth 1.00 1 1 40.00 130 5,200.00 kg

Steel reinforcement for R.C.C. work including


straightening, cutting, bending, placing in position
5.22 A and binding all complete above plinth level.

Thermo-Mechanically Treated bars of grade Fe-500


5.22A.6 kg
D or more.
above plinth 1.00 1 1 147.00 130 19,110.00 kg

Add for plaster drip course/ groove in plastered


5.30 metre
surface or moulding to R.C.C. projections.
DESIGN MIX CONCRETE
Providing and laying in position machine batched
and machine mixed design mix M-25 grade cement
concrete for reinforced cement concrete work, using
cement content as per approved design mix,
including pumping of concrete to site of laying but
excluding the cost of centering, shuttering, finishing
and reinforcement, including admixtures in
recommended proportions as per IS: 9103 to
5.33 accelerate, retard setting of concrete, improve
workability without impairing strength and durability
as per direction of Engineer-in-charge.“(Note :-
Cement content considered in this item is @ 330
kg/cum.“Excess/ less cement used as per design
mix is payable/recoverable separately).

5.33.1 All works upto plinth level cum


Foundations, footings, bases of columns, etc. for
5.9.1
mass concrete.
f1 1.00 10 1 1.9 1.9 0.23 8.30 cum
trapezoidal 1.00 10 0.75 1.9 1.9 0.22 5.96 cum
f2 1.00 8 1 1.7 1.7 0.23 5.32 cum
trapezoidal 1.00 8 0.75 1.7 1.7 0.17 2.95 cum
f3 1.00 6 1 1.5 1.5 0.2 2.70 cum
trapezoidal 1.00 6 0.75 1.5 1.5 0.15 1.52 cum
f4 1.00 2 1 1.3 1.3 0.3 1.01 cum
Plinth Beams
Along Grid 1/ A-I 1 1 1 4.378 0.23 0.45 0.45 cum
1 1 1 4.378 0.23 0.45 0.45 cum
cum
Along Grid 2/ A-I 1 1 1 2.665 0.23 0.45 0.28 cum
1 1 1 2.665 0.23 0.45 0.28 cum
cum
Along Grid 3/ A-I 1 1 1 2.345 0.23 0.45 0.24 cum
1 1 1 1.503 0.23 0.45 0.16 cum
1 1 1 1.503 0.23 0.45 0.16 cum
1 1 1 2.345 0.23 0.45 0.24 cum
cum
B/W Grid 3-4/ A-I 1 1 1 0.825 0.115 0.3 0.03 cum
cum
Along Grid 4/ A-I 1 1 1 2.485 0.23 0.45 0.26 cum
1 1 1 2.665 0.23 0.45 0.28 cum
1 1 1 2.665 0.23 0.45 0.28 cum
1 1 1 1.733 0.23 0.45 0.18 cum
cum
Along Grid 5/ A-I 1 1 1 2.485 0.23 0.45 0.26 cum
1 1 1 2.665 0.23 0.45 0.28 cum
1 1 1 2.665 0.23 0.45 0.28 cum
1 1 1 1.733 0.23 0.45 0.18 cum
cum
B/W Grid 5-6/ A-I 1 1 1 0.825 0.115 0.3 0.03 cum
cum
Along Grid 6/ A-I 1 1 1 2.345 0.23 0.45 0.24 cum
1 1 1 1.503 0.23 0.45 0.16 cum
1 1 1 1.503 0.23 0.45 0.16 cum
1 1 1 2.345 0.23 0.45 0.24 cum
cum
B/W Grid 6-7/ A-I 1 1 1 2.665 0.23 0.45 0.28 cum
1 1 1 2.665 0.23 0.45 0.28 cum
cum
Along Grid 7/ A-I 1 1 1 4.378 0.23 0.45 0.45 cum
1 1 1 4.378 0.23 0.45 0.45 cum
cum
Along Grid A/1-7 1 1 1 2.16 0.23 0.45 0.22 cum
1 1 1 2.16 0.23 0.45 0.22 cum
cum
Along Grid B/1-7 1 1 1 0.85 0.23 0.45 0.09 cum
1 1 1 2.403 0.23 0.45 0.25 cum
1 1 1 0.845 0.23 0.45 0.09 cum
cum
Along Grid C/1-7 1 1 1 2.83 0.23 0.45 0.29 cum
1 1 1 1.22 0.23 0.45 0.13 cum
1 1 1 1.22 0.23 0.45 0.13 cum
1 1 1 2.83 0.23 0.45 0.29 cum
cum
Along Grid D/1-7 1 1 1 3.91 0.23 0.45 0.40 cum
1 1 1 3.91 0.23 0.45 0.40 cum
cum
Along Grid E/1-7 1 1 1 2.21 0.23 0.45 0.23 cum
1 1 1 2.403 0.23 0.45 0.25 cum
1 1 1 2.21 0.23 0.45 0.23 cum
cum
B/W Grid E-F/1-7 1 1 1 2.398 0.23 0.45 0.25 cum
cum
Along Grid F/1-7 1 1 1 3.91 0.23 0.45 0.40 cum
1 1 1 3.91 0.23 0.45 0.40 cum
cum
Along Grid G/1-7 1 1 1 2.83 0.23 0.45 0.29 cum
1 1 1 1.22 0.23 0.45 0.13 cum
1 1 1 1.22 0.23 0.45 0.13 cum
1 1 1 2.83 0.23 0.45 0.29 cum
cum
Along Grid I/1-7 1 1 1 2.16 0.23 0.45 0.22 cum
1 1 1 2.16 0.23 0.45 0.22 cum
cum
BKT 1 1 2 1.105 0.115 0.3 0.08 cum
1 1 2 1.197 0.115 0.3 0.08 cum
40.00 cum
5.33.2 All works above plinth level upto floor V level cum

Suspended floors, roofs, landings, balconies and


5.9.3
access platform
slab 3.00 1 4 2.865 2.9 0.13 12.96 cum
slab 3.00 1 4 1.5 2.9 0.13 6.79 cum
slab 3.00 1 4 2.665 2.95 0.13 12.26 cum
slab 3.00 1 4 1.87 1.22 0.13 3.56 cum
slab balcony 3.00 1 4 1.65 1 0.13 2.57 cum
slab balcony 3.00 1 4 1.75 1 0.13 2.73 cum
slab stair lobby 3.00 1 2 2.4 1.23 0.13 2.30 cum
landing 3.00 1 2 2.4 1.22 0.13 2.28 cum
mumty 1.00 1 1 5.7 2.37 0.13 1.76 cum
shelves
kitchen 3.00 4 1 2.185 0.6 0.100 1.57 cum
toilet 3.00 4 1 0.6 0.6 0.100 0.43 cum
water tank top & bottom slab 1.00 2 1 4.92 2.455 0.200 4.83 sqm

0.00 cum
54.00 cum
Lintels, beams, plinth beams, girders, bressumers
5.9.5
and cantilevers.
First & Second Floor Beam
Along Grid 1/ A-I 2 1 1 4.378 0.23 0.45 0.906246
2 1 1 4.378 0.23 0.45 0.906246

Along Grid 2/ A-I 2 1 1 2.665 0.23 0.45 0.551655


2 1 1 2.665 0.23 0.45 0.551655

Along Grid 3/ A-I 2 1 1 2.345 0.23 0.45 0.485415


2 1 1 1.503 0.23 0.45 0.311121
2 1 1 1.503 0.23 0.45 0.311121
2 1 1 2.345 0.23 0.45 0.485415

B/W Grid 3-4/ A-I 2 1 1 0.825 0.115 0.3 0.056925

Along Grid 4/ A-I 2 1 1 2.485 0.23 0.45 0.514395


2 1 1 2.665 0.23 0.45 0.551655
2 1 1 2.665 0.23 0.45 0.551655
2 1 1 1.733 0.23 0.45 0.358731

Along Grid 5/ A-I 2 1 1 2.485 0.23 0.45 0.514395


2 1 1 2.665 0.23 0.45 0.551655
2 1 1 2.665 0.23 0.45 0.551655
2 1 1 1.733 0.23 0.45 0.358731

B/W Grid 5-6/ A-I 2 1 1 0.825 0.115 0.3 0.056925

Along Grid 6/ A-I 2 1 1 2.345 0.23 0.45 0.485415


2 1 1 1.503 0.23 0.45 0.311121
2 1 1 1.503 0.23 0.45 0.311121
2 1 1 2.345 0.23 0.45 0.485415

B/W Grid 6-7/ A-I 2 1 1 2.665 0.23 0.45 0.551655


2 1 1 2.665 0.23 0.45 0.551655

Along Grid 7/ A-I 2 1 1 4.378 0.23 0.45 0.906246


2 1 1 4.378 0.23 0.45 0.906246

Along Grid A/1-7 2 1 1 2.16 0.23 0.45 0.44712


2 1 1 2.16 0.23 0.45 0.44712

Along Grid B/1-7 2 1 1 0.85 0.23 0.45 0.17595


2 1 1 2.403 0.23 0.45 0.497421
2 1 1 0.845 0.23 0.45 0.174915

Along Grid C/1-7 2 1 1 2.83 0.23 0.45 0.58581


2 1 1 1.22 0.23 0.45 0.25254
2 1 1 1.22 0.23 0.45 0.25254
2 1 1 2.83 0.23 0.45 0.58581
Along Grid D/1-7 2 1 1 3.91 0.23 0.45 0.80937
2 1 1 3.91 0.23 0.45 0.80937

Along Grid E/1-7 2 1 1 2.21 0.23 0.45 0.45747


2 1 1 2.403 0.23 0.45 0.497421
2 1 1 2.21 0.23 0.45 0.45747

B/W Grid E-F/1-7 2 1 1 2.398 0.23 0.45 0.496386

Along Grid F/1-7 2 1 1 3.91 0.23 0.45 0.80937


2 1 1 3.91 0.23 0.45 0.80937

Along Grid G/1-7 2 1 1 2.83 0.23 0.45 0.58581


2 1 1 1.22 0.23 0.45 0.25254
2 1 1 1.22 0.23 0.45 0.25254
2 1 1 2.83 0.23 0.45 0.58581

Along Grid I/1-7 2 1 1 2.16 0.23 0.45 0.44712


2 1 1 2.16 0.23 0.45 0.44712

BKT 2 1 2 1.105 0.115 0.3 0.15249


2 1 2 1.197 0.115 0.3 0.165186

Terrace Beams
Along Grid 1/ A-I 1 1 1 4.378 0.23 0.45 0.453123
1 1 1 4.378 0.23 0.45 0.453123

Along Grid 2/ A-I 1 1 1 2.665 0.23 0.45 0.2758275


1 1 1 2.665 0.23 0.45 0.2758275

Along Grid 3/ A-I 1 1 1 2.345 0.23 0.45 0.2427075


1 1 1 1.503 0.23 0.45 0.1555605
1 1 1 1.503 0.23 0.45 0.1555605
1 1 1 2.345 0.23 0.45 0.2427075

B/W Grid 3-4/ A-I 1 1 1 0.825 0.115 0.3 0.0284625

Along Grid 4/ A-I 1 1 1 2.485 0.23 0.45 0.2571975


1 1 1 2.665 0.23 0.45 0.2758275
1 1 1 2.665 0.23 0.45 0.2758275
1 1 1 1.733 0.23 0.45 0.1793655

Along Grid 5/ A-I 1 1 1 2.485 0.23 0.45 0.2571975


1 1 1 2.665 0.23 0.45 0.2758275
1 1 1 2.665 0.23 0.45 0.2758275
1 1 1 1.733 0.23 0.45 0.1793655

B/W Grid 5-6/ A-I 1 1 1 0.825 0.115 0.3 0.0284625

Along Grid 6/ A-I 1 1 1 2.345 0.23 0.45 0.2427075


1 1 1 1.503 0.23 0.45 0.1555605
1 1 1 1.503 0.23 0.45 0.1555605
1 1 1 2.345 0.23 0.45 0.2427075

B/W Grid 6-7/ A-I 1 1 1 2.665 0.23 0.45 0.2758275


1 1 1 2.665 0.23 0.45 0.2758275

Along Grid 7/ A-I 1 1 1 4.378 0.23 0.45 0.453123


1 1 1 4.378 0.23 0.45 0.453123

Along Grid A/1-7 1 1 1 2.16 0.23 0.45 0.22356


1 1 1 2.16 0.23 0.45 0.22356

Along Grid B/1-7 1 1 1 0.85 0.23 0.45 0.087975


1 1 1 2.403 0.23 0.45 0.2487105
1 1 1 0.845 0.23 0.45 0.0874575

Along Grid C/1-7 1 1 1 1.22 0.23 0.45 0.12627


1 1 1 1.22 0.23 0.45 0.12627

Along Grid D/1-7 1 1 1 3.91 0.23 0.45 0.404685


1 1 1 3.91 0.23 0.45 0.404685

Along Grid E/1-7 1 1 1 2.21 0.23 0.45 0.228735


1 1 1 2.403 0.23 0.45 0.2487105
1 1 1 2.21 0.23 0.45 0.228735

B/W Grid E-F/1-7 1 1 1 2.398 0.23 0.45 0.248193

Along Grid F/1-7 1 1 1 3.91 0.23 0.45 0.404685


1 1 1 3.91 0.23 0.45 0.404685

Along Grid G/1-7 1 1 1 1.22 0.23 0.45 0.12627


1 1 1 1.22 0.23 0.45 0.12627

Along Grid I/1-7 1 1 1 2.16 0.23 0.45 0.22356


1 1 1 2.16 0.23 0.45 0.22356

BKT 1 1 2 1.197 0.115 0.3 0.082593

Mumty

Along Grid 4/ A-I 1 1 1 2.485 0.23 0.45 0.2571975


1 1 1 2.665 0.23 0.45 0.2758275

Along Grid 5/ A-I 1 1 1 2.485 0.23 0.45 0.2571975


1 1 1 2.665 0.23 0.45 0.2758275
Along Grid B/1-7 1 1 1 2.403 0.23 0.45 0.2487105

Along Grid E/1-7 1 1 1 2.403 0.23 0.45 0.2487105


0.00 cum
37.00 cum
Columns, Pillars, Piers, Abutments, Posts and Struts
5.9.6

up to plinth
column padastal 1 1 26 0.6 0.75 0.3 3.51 cum
column 1 1 26 0.3 0.45 1.3 4.56 cum

Column From Gf to Top. 1 1 26 0.3 0.45 9.45 33.1695 cum


Mumty 1 1 6 0.3 0.45 3 2.43 cum
Terrace 1 1 19 0.3 0.45 1 2.565 cum
0.00 cum
46.00 cum
Stairs, (excluding landings) except spiral-staircases.
5.9.7

waist slab 3.00 1 2 3.3 1.2 0.15 3.56 cum


tread 3.00 1 21 1.2 0.15 0.15 1.70 cum
0.00 cum
5.00 cum
Weather shade, Chajjas, corbels etc., including
5.9.19
edges
V 3 6 1 0.6 0.6 0.1 0.65 cum
W 3 4 1 0.9 0.6 0.1 0.65 cum
1.00 cum

Total Above Plinth 147.00 cum

Extra for providing richer mixes at all floor levels


Note:- Excess/less cement over the specified
5.34 cement content used is payable /recoverable
separately.
Providing M-30 grade concrete instead of M-25
5.34.1 grade BMC/ RMC. (Note:- Cement content cum
considered in M-30 is @ 340 kg/ cum) 46.00
Providing M-35 grade concrete instead of M-25
5.34.2 grade BMC/ RMC. (Note : Cement content cum
considered in M-35 is @ 350 kg/ cum)
Providing M-40 grade concrete instead of M-25
5.34.3 grade BMC/ RMC.(Note : Cement content cum
considered in M-40 is @ 360 kg/ cum)
Add for using extra cement in the items of design
5.35 mix over and above quintal
the specified cement content therein. 2
SUB HEAD - BRICK WORK
Brick work with common burnt clay F.P.S. (non
6.1 modular) bricks of class designation 7.5 in
foundation and plinth in:
6.1.2 Cement mortar 1:6 (1 cement : 6 coarse sand)

b/W Plinth Beam & FFL


Along Grid 1/ A-I 1 1 1 4.378 0.23 0.278 0.28
1 1 1 4.378 0.23 0.278 0.28

Along Grid 2/ A-I 1 1 1 2.665 0.23 0.278 0.17


1 1 1 2.665 0.23 0.278 0.17

Along Grid 3/ A-I 1 1 1 2.345 0.23 0.278 0.15


1 1 1 1.503 0.23 0.278 0.10
1 1 1 1.503 0.23 0.278 0.10
1 1 1 2.345 0.23 0.278 0.15

B/W Grid 3-4/ A-I 1 1 1 0.825 0.23 0.278 0.05

Along Grid 4/ A-I 1 1 1 2.485 0.23 0.278 0.16


1 1 1 2.665 0.23 0.278 0.17
1 1 1 2.665 0.23 0.278 0.17
1 1 1 1.733 0.23 0.278 0.11

Along Grid 5/ A-I 1 1 1 2.485 0.23 0.278 0.16


1 1 1 2.665 0.23 0.278 0.17
1 1 1 2.665 0.23 0.278 0.17
1 1 1 1.733 0.23 0.278 0.11

B/W Grid 5-6/ A-I 1 1 1 0.825 0.23 0.278 0.05

Along Grid 6/ A-I 1 1 1 2.345 0.23 0.278 0.15


1 1 1 1.503 0.23 0.278 0.10
1 1 1 1.503 0.23 0.278 0.10
1 1 1 2.345 0.23 0.278 0.15

B/W Grid 6-7/ A-I 1 1 1 2.665 0.23 0.278 0.17


1 1 1 2.665 0.23 0.278 0.17

Along Grid 7/ A-I 1 1 1 4.378 0.23 0.278 0.28


1 1 1 4.378 0.23 0.278 0.28

Along Grid A/1-7 1 1 1 2.16 0.23 0.278 0.14


1 1 1 2.16 0.23 0.278 0.14

Along Grid B/1-7 1 1 1 0.85 0.23 0.278 0.05


1 1 1 2.403 0.23 0.278 0.15
1 1 1 0.845 0.23 0.278 0.05

Along Grid C/1-7 1 1 1 2.83 0.23 0.278 0.18


1 1 1 1.22 0.23 0.278 0.08
1 1 1 1.22 0.23 0.278 0.08
1 1 1 2.83 0.23 0.278 0.18

Along Grid D/1-7 1 1 1 3.91 0.23 0.278 0.25


1 1 1 3.91 0.23 0.278 0.25

Along Grid E/1-7 1 1 1 2.21 0.23 0.278 0.14


1 1 1 2.403 0.23 0.278 0.15
1 1 1 2.21 0.23 0.278 0.14

B/W Grid E-F/1-7 1 1 1 2.398 0.23 0.278 0.15

Along Grid F/1-7 1 1 1 3.91 0.23 0.278 0.25


1 1 1 3.91 0.23 0.278 0.25

Along Grid G/1-7 1 1 1 2.83 0.23 0.278 0.18


1 1 1 1.22 0.23 0.278 0.08
1 1 1 1.22 0.23 0.278 0.08
1 1 1 2.83 0.23 0.278 0.18

Along Grid I/1-7 1 1 1 2.16 0.23 0.278 0.14


1 1 1 2.16 0.23 0.278 0.14

BKT 1 1 2 1.105 0.23 0.278 0.14


1 1 2 1.197 0.23 0.278 0.15
8.00 cum
Brick work with common burnt clay F.P.S. (non
modular) bricks of class designation 7.5 in
6.4 superstructure above plinth level up to floor V level
in all shapes and sizes in :
6.4.2 Cement mortar 1:6 (1 cement : 6 coarse sand) cum
on grid A-E/1-5 horizontally
on grid-1 3.00 4 1 4.38 0.23 2.7 32.64
on grid-2 3.00 4 1 2.665 0.23 2.7 19.86
on grid-3 3.00 4 1 2.345 0.23 2.7 17.47
on grid-4 3.00 4 1 1.73 0.23 2.7 12.89
on grid-4 3.00 4 1 2.665 0.23 2.7 19.86
vertically
on grid-a 3.00 4 1 2.16 0.23 2.7 16.10
on grid-b 3.00 4 1 0.85 0.23 2.7 6.33
on grid-b 3.00 4 0.25 2.4 0.23 2.7 4.47
on grid-d 3.00 4 1 0.8 0.23 2.7 5.96
on grid-e 3.00 4 0.5 2.21 0.23 2.7 8.23
parapet wall 1.00 1 1 72 0.23 1.2 19.87
mumty 1.00 1 2 5.7 0.23 2.55 6.69
1.00 1 2 2.4 0.23 2.55 2.82
D 3 4 -1 1.2 0.23 2.4 -7.95
SL 3 8 -1 1.5 0.23 2.55 -21.11
main door 3 1 -1 1.5 0.23 2.1 -2.17
V 3 6 -1 0.6 0.23 0.9 -2.24
W 3 4 -1 0.9 0.23 1.65 -4.10
0.00 cum
0.00 cum
136.00 cum

Extra for brick work / AAC block masonry / Tile brick


masonry in superstructure above floor V level, for
6.5 each four floors or part thereof by mechanical cum
means.

Half brick masonry with common burnt clay F.P.S.


(non modular) bricks
6.13 of class designation 7.5 in superstructure above
plinth level up to floor
V level.
6.13.2 Cement mortar 1:4 (1 cement :4 coarse sand)
on grid A-E/1-5 horizontally
on grid-3 3.00 4 1 1.615 2.7 52.33
on grid-4-3 3.00 4 1 0.755 2.7 24.46
vertically
on grid-b-c 3.00 4 1 2.9 2.7 93.96
on grid-b-c 3.00 4 1 1.15 2.7 37.26
on grid-d 3.00 4 1 0.715 2.7 23.17
on grid-d 3.00 4 1 1.38 2.7 44.71
electrical shaft 3.00 2 1 1.58 2.85 27.02
shaft 3.00 2 1 1.315 2.85 22.49
D1 3 4 -1 0.9 2.1 -22.68 sqm
D2 3 4 -1 0.75 2.1 -18.90 sqm
284.00

Extra for providing and placing in position 2 Nos


6.15 6mm dia. M.S. bars at every third course of half sqm
brick masonry. 284.00

Providing and laying autoclaved aerated cement


blocks masonry with 100 mm thick AAC blocks in
super structure above plinth level up to floor V level
6.38 in cement mortar 1:4 (1 cement : 4 coarse sand ). cum
The rate includes providing and placing in position 2
Nos 6 mm dia M.S. bars at every third course of
masonry work.

Total of Brick Work :


SUB HEAD - MARBLE AND GRANITE WORK
Marble work gang saw cut (polished and machine
cut) of thickness 18 mm for wall lining (veneer work),
backing filled with a grout of average 12 mm thick in
cement mortar 1:3 (1 cement : 3 coarse sand),
including pointing with white cement mortar 1:2 (1
8.1 white cement : 2 marble dust) with an admixture of
pigment to match the marble shade (To be secured
to the backing by means of cramps, which shall be
paid for separately).

Raj Nagar Plain white marble/ Udaipur green


8.1.1
marble/ Zebra black marble.
8.1.1.2 Area of slab over 0.50 sqm sqm
Providing and fixing 18mm thick gang saw cut mirror
polished (premoulded and prepolished) machine cut
for kitchen platforms, vanity counters ,window sills ,
facias and similar locations of required size of
approved shade, colour and texture laid over 20mm
thick base cement mortar 1:4 (1 cement : 4 coarse
8.2 sand) with joints treated with white cement, mixed
with matching pigment, epoxy touch ups, including
rubbing, curing moulding and polishing to edge to
give high gloss finish etc. complete at all levels.

8.2.2 Granite of any colour and shade


Area of slab upto 0.50 sqm (Granite having basic
8.2.2.1 sqm
rate not less than Rs. 1900 per sqm)
Area of slab over 0.50 sum. (Granite having basic
8.2.2.2
rate not less than Rs. 2000 per sqm)
kitchen 3.00 4 1 2.185 0.6 15.73 sqm
toilet 3.00 4 1 0.6 0.6 4.32 sqm
20.00 sqm

Extra for providing edge moulding to 40 mm thick


Sand stone counters, Vanities Planter etc. including
8.3 machine polishing etc. complete as per design
approved by Engineer-in-Charge.
8.3.2 Granite work metre
kitchen 3.00 4 1 2.185 26.22 metre
toilet 3.00 4 1 0.6 7.20 metre
33.00 metre
Extra for fixing marble /granite stone over and above
corresponding basic item, in facia and drops of
8.4 width upto 150 mm with epoxy resin based adhesive metre
including cleaning etc. complete.
kitchen 3.00 4 1 2.185 26.22 metre
toilet 3.00 4 1 0.6 7.20 metre
33.00 metre
Extra for providing opening of required size & shape
for wash basins/ kitchen sink in kitchen platform,
vanity counters and similar location in
8.5 marble/Granite/stone work including necessary each
holes for pillar taps etc. including rubbing and
polishing of cut edges etc. complete.

kitchen 3.00 4 1 1 12.00 each


toilet 3.00 4 1 1 12.00 each
24.00 each
Total of Marble Work :
SUB HEAD - WOOD AND PVC WORK
Providing wood work in frames of doors, windows,
clerestory windows and other frames, wrought
framed and fixed in position with hold fast lugs or
9.1 with dash fasteners of required dia & length ( hold
fast lugs or dash fastener shall be paid for
separately).

9.1.1 Second class teak wood cum


Providing and fixing ISI marked flush door shutters
conforming to IS : 2202 (Part I) decorative type, core
of block board construction with frame of 1st class
9.20 hard wood and well matched teak 3 ply veneering
with vertical grains or cross bands and face veneers
on both faces of shutters.

35 mm thick including ISI marked Stainless Steel


9.20.1 sqm
butt hinges with necessary screws
Providing and fixing ISI marked flush door shutters
conforming to IS: 2202 (Part I) non-decorative type,
core of block board construction with frame of 1st
9.21 class hard wood and well matched commercial 3
ply veneering with vertical grains or cross bands and
face veneers on both faces of shutters :

35 mm thick including ISI marked Stainless Steel


9.21.1
butt hinges with necessary screws.
D 3 4 1 1.2 2.4 34.56 sqm
D1 3 4 1 0.9 2.1 22.68 sqm
D2 3 4 1 0.75 2.1 18.90 sqm
main door 3 1 1 1.5 2.1 9.45 sqm
86.00 sqm
25 mm thick (for cupboard) including ISI marked
9.21.3 nickel plated bright finished M.S. piano hinges with sqm
necessary screws
cub board 3 4 1 1 2.1 25.20 sqm
25.00 sqm
Extra for providing lipping with 2nd class teak wood
battens 25 mm minimum depth on all edges of
9.23 shutters (over all area of door shutter to be sqm
measured) Over item no. 9.20 and 9.21. 86.00
Extra for providing vision panel not exceeding 0.1
sum in all type of flush doors (cost of glass
9.24 excluded) (overall area of door shutter to be
measured) :
9.24.1 Rectangular or square. sqm
Extra for cutting rebate in flush door shutters (Total
9.26 25.00 sqm
area of the shutter to be measured).
Providing and fixing bright finished brass 100 mm
mortice latch and lock with 6 levers and a pair of
9.76 lever handles of approved quality with necessary Each
screws etc. complete.
Providing and fixing aluminium extruded section
body tubular type universal hydraulic door closer
(having brand logo with ISI, IS : 3564, embossed on
9.84 the body, door weight upto 36 kg to 80 kg and door Each
width from 701 mm to 1000 mm), with double speed
adjustment with necessary accessories and screws
etc. complete.

D 3 4 1 12.00 each
D1 3 4 1 12.00 each
D2 3 4 1 12.00 each
SL 3 8 1 24.00 each
main door 3 1 1 3.00 each
63.00 each
Providing and fixing special quality chromium plated
brass cupboard locks with six levers of approved
9.90 quality including necessary screws etc. complete.

9.90.1 Size 40 mm Each


cub board 3 4 1 12.00 Each
12.00 Each
Providing and fixing aluminium sliding door bolts, ISI
marked anodised (anodic coating not less than
9.96 grade AC 10 as per IS : 1868), transparent or dyed
to required colour or shade, with nuts and screws
etc. complete :
9.96.1 300x16 mm each
D 3 4 1 12.00 each
main door 3 1 1 3.00 each
15.00 each

9.96.2 250x16 mm each


D1 3 4 1 12.00 each
D2 3 4 1 12.00 each
24.00 each
Providing and fixing aluminium tower bolts, ISI
marked, anodised (anodic coating not less than
9.97 grade AC 10 as per IS : 1868 ) transparent or dyed
to required colour or shade, with necessary screws
etc. complete :
9.97.1 300x10 mm each
D 3 4 1 2 24.00 each
D1 3 4 1 2 24.00 each
D2 3 4 1 2 24.00 each
SL 3 8 1 2 48.00 each
120.00 each
9.97.4 150x10 mm each

W 3 4 1 2 24.00 each
cub board 3 4 1 2 24.00 each
48.00 each
9.97.5 100x10 mm each
V 3 6 1 2 36.00 each
36.00 each

Providing and fixing aluminium handles, ISI marked,


anodised (anodic coating not less than grade AC 10
9.100 as per IS : 1868) transparent or dyed to required
colour or shade, with necessary screws etc.
complete :
9.100.1 125 mm each
D 3 4 1 2 24.00 each
D1 3 4 1 2 24.00 each
D2 3 4 1 2 24.00 each
SL 3 8 1 2 48.00 each
main door 3 1 1 2 6.00 each
cub board 3 4 1 2 24.00 each
150.00 each
9.100.2 100mm each
V 3 6 1 2 36.00 each
W 3 4 1 2 24.00 each
60.00 each
9.100.3 75 mm each
Providing and fixing aluminium hanging floor door
stopper, ISI marked, anodised (anodic coating not
9.101 less than grade AC 10 as per IS : 1868) transparent
or dyed to required colour and shade, with
necessary screws etc. complete.
9.101.2 Twin rubber stopper each
D 3 4 1 12.00 each
D1 3 4 1 12.00 each
D2 3 4 1 12.00 each
36.00 each
Providing and fixing bright finished brass 100 mm
mortice latch and lock, ISI marked, with six levers
and a pair of anodised (anodic coating not less than
9.103 grade AC 10 as per IS : 1868) aluminium lever each
handles of approved quality with necessary screws
etc. complete.
D1 3 4 1 1 12.00 each
12.00 each
Providing and fixing magnetic catcher of approved
quality in cupboard / ward robe shutters, including
9.114 fixing with necessary screws etc. complete.

9.114.1 Triple strip vertical type


cub board 3 4 1 12.00 each
12.00 each
Providing & Fixing decorative high pressure
laminated sheet of plain / wood grain in gloss /
matt / suede finish with high density protective
9.127 surface layer and reverse side of adhesive bonding
quality conforming to IS : 2046 Type S including
cost of adhesive of approved quality.

9.127.2 1.0 mm thick. 197 sqm


Providing and fixing fly proof stainless steel grade
304 wire gauge, to windows and clerestory windows
9.135 using wire gauge with average width of aperture 1.4
mm in both directions with wire of dia. 0.50 mm all
complete.
9.135.2 With 12 mm mild steel U beading sqm
SL 3 8 1 1.5 2.55 91.80 sqm
V 3 6 1 0.6 0.9 9.72 sqm
W 3 4 1 0.9 1.65 17.82 sqm
main door 3 1 1 1.5 2.1 9.45 each
129.00 sqm
SUB HEAD - S T E E L WORK
Structural steel work in single section, fixed with or
without connecting plate, including cutting, hoisting,
10.1 fixing in position and applying a priming coat of kg
approved steel primer all complete.
Structural steel work riveted, bolted or welded
in built up sections, trusses and framed work,
10.2 including cutting, hoisting, fixing in position and kg
applying a priming coat of approved steel
primer all complete.
Providing and fixing 1 mm thick M.S. sheet sliding-
shutters, with frame and diagonal braces of 40x40x6
mm angle iron, 3 mm M.S. gusset plates at the
10.4 junctions and corners, 25 mm dia pulley, 40x40x6 sqm
mm angle and T- iron guide at the top and bottom
respectively, including applying a priming coat of
approved steel primer.

mumty door 1 1 1 1 2.1 2.10


2.00 sqm
Providing and fixing T-iron frames for doors,
windows and ventilators of mild steel Tee-sections,
10.13 joints mitred and welded, including fixing of
necessary butt hinges and screws and applying a
priming coat of approved steel primer.
Fixing with 15x3 mm lugs 10 cm long embedded in
cement
concrete block 15x10x10 cm of C.C. 1:3:6 (1
10.13.1 Cement : 3
coarse sand : 6 graded stone aggregate 20 mm
nominal size).
cub board 3 4 1 7.3 87.60
88.00 m
weight@5kg/m 88.00 5 440 kg
Providing and fixing pressed steel door frames
conforming to IS: 4351, manufactured from
commercial mild steel sheet of 1.60 mm thickness,
including hinges, jamb, lock jamb, bead and if
required angle threshold of mild steel angle of
section 50x25 mm, or base ties of 1.60 mm, pressed
mild steel welded or rigidly fixed together by
10.14 mechanical means, including M.S. pressed butt
hinges 2.5 mm thick with mortar guards, lock strike-
plate and shock absorbers as specified and applying
a coat of approved steel primer after pre-treatment
of the surface as directed by Engineer-in-charge:

10.14.1 Profile B
Fixing with adjustable lugs with split end tail to each
10.14.1.1
jamb
D 3 4 1 5.4 64.80 metre
D1 3 4 1 5.1 61.20 metre
D2 3 4 1 4.95 59.40 metre
185.00 metre
Steel work in built up tubular ( round, square or
rectangular hollow tubes etc.) trusses etc. including
cutting, hoisting, fixing in position and applying a
10.16 priming coat of approved steel primer, including
welding and bolted with special shaped washers etc.
complete.

10.16.3 Electric resistance or induction butt welded tubes kg


Providing and fixing M.S. fan clamp type I or II of 16
mm dia M.S. bar, bent to shape with hooked ends in
10.17 R.C.C. slabs or beams during laying, including each
painting the exposed portion of loop, all as per
standard design complete
Providing and fixing circular/ Hexagonal cast iron or
M.S. sheet box for ceiling fan clamp of internal dia
140mm, 73mm height, top lid of 1.5mm thick M.S.
sheet with its top surface hacked for proper bonding,
top lid shall be screwed into the cast iron/ M.S.
10.18 sheet box by means of 3.3mm dia. round headed each
screws, one lock at the corners. Clamp shall be
made of 12mm dia M.S. bar bent to shape as per
standard drawing.

21
Providing and fixing mild steel round holding down
10.19 bolts with nuts and washer plates complete. kg

Steel work welded in built up sections/ framed work


including cutting, hoisting, fixing in position and
10.25 applying a priming coat of approved steel primer
using structural steel etc. as required.

In stringers, treads, landings etc. of stair cases


including use of chequered plate wherever required,
10.25.1 all complete kg

In gratings, frames, guard bar, ladder, railings,


10.25.2 brackets, gates and similar works.

D 1 4 1 1.2 2.4 11.52 sqm


11.52
weight@40kg/m2 11.52 40 460.8 kg
ladder for mumty 100 kg
561.00
Providing and fixing hand rail of approved size by
welding etc. to steel ladder railing, balcony railing,
10.26 staircase railing and similar works, including
applying priming coat of approved steel primer.

10.26.1 M.S. tube


stair 3.00 1 1 7.3 21.90 m
ramp 1.00 1 2 5.87 11.74 m
balcony-1 3 4 1 1.50 18.00 m
utility balcony 3 4 1 1.70 20.40 m
72.04 m

weight@25kg/m 72.04 25 1,801.00 kg


Say 1801.00 kg

SUB HEAD - FLOORING WORK

gf to 2nd floor
v bed room 3 4 1 2.90 2.90 100.92 sqm
v living room 3 4 1 2.70 2.95 95.58 sqm
v passage 3 4 1 1.02 1.74 21.24 sqm
c kitchen 3 4 1 1.50 1.89 33.93 sqm
c balcony-1 3 4 1 1.50 0.93 16.65 sqm
c utility balcony 3 4 1 1.70 0.95 19.38 sqm
c toilet 3 4 1 2.10 1.35 34.02 sqm
k lobby 3 1 1 3.78 2.40 27.18 sqm
k stair landing 3 1 1 2.40 1.20 8.64 sqm
k stair tread 3 1 21 1.20 0.30 22.68 sqm
ch ramp 1 1 1 4.87 1.34 6.50 sqm
k stair ground 1 1 1 4.20 2.40 10.08 sqm
0.00 sqm
0.000 0.00 sqm

Total 396.80 Sqm


Say 397.00 Sqm

Kota Stone Flooring (K) 69.00 sqm


Polish Granite (G) 0.00 sqm
Anti skid Ceramic flooring (C) 104.00 sqm
Plain Concrete flooring (P) 0.00 sqm
VDC 0.00 sqm
Flamed Granite (FG) 0.00 sqm
Vitrified Tiles (V) 218.00 sqm
Chequerred Tiels (CH) 7.00 sqm

Total 398.00 sqm


dado/skirting
gf to 2nd floor
v bed room 3 4 1 2.90 2.90 0.1 13.92 sqm
v living room 3 4 1 2.70 2.95 0.1 13.56 sqm
v passage 3 4 1 1.02 1.74 0.1 6.61 sqm
c kitchen 3 4 1 1.50 1.89 2.1 170.60 sqm
c balcony-1 3 4 1 1.50 0.93 0.1 5.82 sqm
c utility balcony 3 4 1 1.70 0.95 0.1 6.36 sqm
c toilet 3 4 1 2.10 1.35 2.1 173.88 sqm
k lobby 3 1 1 3.78 2.40 1.2 44.46 sqm
k stair landing 3 1 1 2.40 1.20 8.64 sqm
k stair tread 3 1 21 1.20 0.15 11.34 sqm
ch ramp 0 1 1 4.87 1.34 2.1 0.00 sqm
k stair ground 3 1 1 4.20 2.40 1.2 47.52 sqm
c D2 3 4 -1 0.75 2.1 -18.90 sqm
c kitchen 3 4 -1 1.62 2.1 -40.82 sqm
0.000 0.00 sqm

Total 442.99 Sqm


Say 442.99 Sqm

Kota Stone (K) 112.00 sqm


Polish Granite (G) 0.00 sqm
Anti skid Ceramic f(C) 297.00 sqm
Plain Concrete (P) 0.00 sqm
VDC 0.00 sqm
Flamed Granite (FG) 0.00 sqm
Vitrified Tiles (V) 34.00 sqm
Chequerred Tiels (CH) 0.00 sqm

SUB HEAD - FINISHING WORK


13.1 12 mm cement plaster of mix :
13.1.2 1:6 (1 cement : 6 fine sand) sqm
gf to 2nd floor
v bed room 3 4 1 2.90 2.90 2.9 403.68 sqm
v living room 3 4 1 2.70 2.95 2.9 393.24 sqm
v passage 3 4 1 1.02 1.74 2.9 191.75 sqm
v kitchen 3 4 1 1.50 1.89 0.9 73.12 sqm
c balcony-1 3 4 1 1.50 0.93 2.9 168.78 sqm
c utility balcony 3 4 1 1.70 0.95 2.9 184.44 sqm
c toilet 3 4 1 2.10 1.35 0.9 74.52 sqm
c lobby 3 1 1 3.78 2.40 1.8 66.69 sqm
c stair landing 0 1 1 2.40 1.20 0.00 sqm
c stair tread 0 1 21 1.20 0.15 0.00 sqm
c ramp 0 1 1 4.87 1.34 0.9 0.00 sqm
k stair ground 3 1 1 4.20 2.40 1.8 71.28 sqm
D 3 4 -1 1.2 2.4 -34.56 sqm
D1 3 4 -1 0.9 2.1 -22.68 sqm
D2 3 4 -1 0.75 2.1 -18.90 sqm
SL 3 8 -1 1.5 2.55 -91.80 sqm
main door 3 1 -1 1.5 2.1 -9.45 sqm
V 3 6 -1 0.6 0.9 -9.72 sqm
W 3 4 -1 0.9 1.65 -17.82 sqm
0.00 sqm
0.000 0.00 sqm

Total 1422.56 Sqm


50% Say 711.00 Sqm
15 mm cement plaster on the rough side of single or
13.2
half brick wall of mix :
13.2.2 1:6 (1 cement : 6 fine sand) 50% 1422.56 711 sqm
12 mm cement plaster finished with a floating coat
13.7
of neat cement of mix :
13.7.2 1:4 (1 cement: 4 fine sand) sqm
13.16 6 mm cement plaster of mix :
13.16.1 1:3 (1 cement: 3 fine sand) 397.00 sqm
18 mm cement plaster in two coats under layer 12
mm thick cement plaster 1:5 (1 cement: 5 coarse
sand) and a top layer 6mm thick cement plaster 1:3
13.12 (1 cement: 3 coarse sand) finished rough with
sponge.

up to plinth 1.00 1 1 142.59 0.45 64.17 sqm


gf to 3rd 3.00 1 1 142.59 3.15 1347.48 sqm
parapet wall 1.00 1 1 142.59 2 1.2 342.22 sqm
mumty 1 1 1 4.20 2.40 3 39.60 sqm
SL 3 8 -1 1.5 2.55 -91.80 sqm
main door 3 1 -1 1.5 2.1 -9.45 sqm
V 3 6 -1 0.6 0.9 -9.72 sqm
W 3 4 -1 0.9 1.65 -17.82 sqm

1665.00 sqm

Extra for providing and mixing water proofing per bag


material in cement plaster work in proportion of 50kg
13.21 recommended by the manufacturers.Per bag of 50 cement
kg cement used in the mix used in
16.65 the mix
Extra for plastering exterior walls of height more
13.22 than 10 m from ground level for every additional sqm
height of 3 m or part thereof.
parapet wall 1.00 1 1 142.59 2 1.2 342.22 sqm
mumty 1 1 1 4.80 3.15 3 47.70 sqm
390.00 sqm
Providing and applying plaster of paris putty of 2
13.26 mm thickness over plastered surface to prepare the sqm
surface even and smooth complete
Distempering with oil bound washable distemper of
13.41 approved brand and manufacture to give an even
shade
New work (two or more coats) over and including
13.41.1 sqm
priming coat with cement primer.
Finishing walls with textured exterior paint of
required shade :
13.45 13.45.1 New work (Two or more coats applied @
3.28 ltr/10 sqm) over and including priming coat of
exterior primer applied @ 2.20kg/10 sqm 1,665.00 sqm
13.68 French spirit polishing :
Two or more coats on new works including a
13.68.1 sqm
coat of wood filler
Providing and applying white cement based putty of
average thickness 1 mm, of approved brand and
13.80 manufacturer, over the plastered wall surface to sqm
prepare the surface even and smooth complete.

Internal plaster 1423.00


ceiling plaster 397.00
1820.00 sqm
Distempering with 1st quality acrylic distemper,
having VOC (Volatile Organic Compound ) content
less than 50 grams/ litre, of approved brand and
13.81 manufacture, including applying additional coats
wherever required, to achieve even shade and
colour.

13.81.2 Two coats 397.00 sqm


Wall painting with acrylic emulsion paint, having
VOC (Volatile Organic Compound ) content less
than 50 grams/ litre, of approved brand and
13.82 manufacture, including applying additional coats
wherever required, to achieve even shade and
colour.

13.82.2 Two coats 1423.00 sqm


Painting with synthetic enamel paint of approved
13.62 brand and manufacture of required colour to give an
even shade :
Two or more coats on new work over an under coat
13.62.1 of suitable shade with ordinary paint of approved sqm
brand and manufacture
Cub board door 25.00
Door steel frame 185.00 40% 74
Ms railing 72.04
Ladder /gates 30.00
201.00
Total of Finishing work :
SUB HEAD - ALUMINIUM WORK
Providing and fixing aluminium work for doors,
windows, ventilators and partitions with extruded
built up standard tubular sections/ appropriate Z
sections and other sections of approved make
conforming to IS: 733 and IS : 1285, fixed with rawl
plugs and screws or with fixing clips, or with
expansion hold fasteners including necessary filling
up of gaps at junctions, at top, bottom and sides
with required PVC/neoprene felt etc. Aluminium
21.1 sections shall be smooth, rust free, straight, mitred
and jointed mechanically wherever required
including cleat angle, Aluminium snap beading for
glazing / panelling, C.P. brass / stainless steel
screws, all complete as per architectural drawings
and the directions of Engineer-in-charge. (Glazing
and panelling to be paid for separately) :
21.1.1 For fixed portion.
Powder coated aluminium (minimum thickness of
21.1.1.2
powder coating 50 micron)
Double frame for mesh & glass shutter
SL 3 8 1 1.5 2.55 91.80 sqm
V 3 6 1 0.6 0.9 9.72 sqm
W 3 4 1 0.9 1.65 17.82 sqm
119.00 sqm

weight@20kg/m2 119.00 20 2380.00 kg

Total Weight 2380.00 kg

For shutters of doors, windows & ventilators


including providing and fixing hinges/ pivots and
making provision for fixing of fittings wherever
21.1.2 required including the cost of PVC / neoprene
gasket required (Fittings shall be paid for
separately).

Powder coated aluminium (minimum thickness of


21.1.2.2 2380.00 70% 1666.00 kg
powder coating 50 micron)

Providing and fixing 12 mm thick prelaminated


particle board flat pressed three layer or graded
wood particle board conforming to IS: 12823 Grade l
Type ll, in panelling fixed in aluminum doors,
21.2 windows shutters and partition frames with C.P.
brass / stainless steel screws etc. complete as per
architectural drawings and directions of engineer-in-
charge.

Pre-laminated particle board with decorative


21.2.2
lamination on both sides
Providing and fixing glazing in aluminium door,
window, ventilator shutters and partitions etc. with
EPDM rubber / neoprene gasket etc. complete as
21.3 per the architectural drawings and the directions of
Engineer-in-charge . (Cost of aluminium snap
beading shall be paid in basic item):

With float glass panes of 5 mm thickness (weight not


21.3.2
less than 12.50 kg/ sqm)
SL 3 8 1 1.5 2.55 91.80 sqm
V 3 6 1 0.6 0.9 9.72 sqm
W 3 4 1 0.9 1.65 17.82 sqm
119.00 sqm

Filling the gap in between aluminium frame, Upvc


frame & adjacent RCC/ Brick/ Stone work by
21.8 providing weather silicon sealant over backer rod of
approved quality as per architectural drawings and
direction of Engineer-in-charge complete.
21.8.1 Upto 5mm depth and 5 mm width metre
SL 3 8 1 6.6 2 2.55 807.84 metre
V 3 6 1 3 2 0.9 97.20 metre
W 3 4 1 5.1 2 1.65 201.96 metre
1107.00 metre

Providing and fixing aluminium tubular handle bar


32 mm outer dia, 3.0 mm thick & 2100 mm long with
21.12 SS screws etc .complete as per direction of
Engineer-in-Charge.
Powder coated minimum thickness 50 micron
21.12.2 each
aluminium tubular handle bar
Providing and fixing Brass 100mm mortice latch and
lock with 6 levers without pair of handles (best make
21.13 of approved quality) for aluminium doors including each
necessary cutting and making good etc. complete.

Providing and fixing anodised aluminium (anodised


transparent or dyed to required shade according to
IS: 1868. Minimum anodic coating of grade AC 15)
sub frame work for windows and ventilators with
21.14 extruded built up standard tubular sections of kg
approved make conforming to IS: 733 and IS: 1285,
fixed with dash fastener of required dia and size
(Dash fastener to be paid for separately).

Providing and fixing aluminium casement


windows fastener of required
21.15 length for aluminium windows with necessary
screws etc. complete.
Powder coated minimum thickness 50 micron
21.15.2 each
aluminium
Providing and fixing anodised aluminium grill
(anodised transparent or dyed to required shade
according to IS: 1868 with minimum anodic coating
of grade AC 15) of approved design/pattern, with
approved standard section and fixed to the existing
window frame with C.P. brass/ stainless steel
screws @ 200 mm centre to centre, including cutting
21.17 the grill to proper opening size for fixing and kg
operation of handles and fixing approved anodised
aluminium standard section around the opening, all
complete as per requirement and direction of
Engineer-in-charge. (Only weight of grill to be
measured for payment).

SUB HEAD - WATER PROOFING WORK


Providing and laying water proofing treatment in
sunken portion of WCs, bathroom etc., by applying
cement slurry mixed with water proofing cement
compound consisting of applying
a) First layer of slurry of cement @ 0.488 kg/sum
mixed with water proofing cement compound @
0.253 kg/sum. This layer will be allowed to air cure
for 4 hours.b) Second layer of slurry of cement @
22.5 0.242 kg/sum mixed with water proofing cement sqm
compound @ 0.126 kg/sum. This layer will be
allowed to air cure for 4 hours followed with water
curing for 48 hours.
(The rate includes preparation of surface, treatment
and sealing of all joints, corners, junctions of pipes
and masonry with polymer mixed slurry.)

kitchen 3 4 1 1.50 1.89 33.93 sqm


balcony-1 3 4 1 1.50 0.93 16.65 sqm
utility balcony 3 4 1 1.70 0.95 19.38 sqm
toilet 3 4 1 2.10 1.35 34.02 sqm
toilet 3 4 1 2.10 1.35 0.450 37.26 sqm
141.00 sqm
Providing and laying integral cement based water
proofing treatment including preparation of surface
as required for treatment of roofs, balconies,
terraces etc consisting of following operations:
(a) Applying a slurry coat of neat cement using 2.75
kg/sqm of cement admixed with water proofing
compound conforming to IS. 2645 and approved by
Engineer-in-charge over the RCC slab including
adjoining walls upto 300 mm height including
cleaning the surface before treatment.
(b) Laying brick bats with mortar using broken
bricks/brick bats 25 mm to 115 mm size with 50% of
cement mortar 1:5 (1 cement : 5 coarse sand)
admixed with water proofing compound conforming
22.7 to IS : 2645 and approved by Engineer-in-charge
over 20 mm thick layer of cement mortar of mix 1:5
(1 cement :5 coarse sand) admixed with water
proofing compound conforming to IS : 2645 and
approved by Engineer-in-charge to required slope
and treating similarly the
adjoining walls upto 300 mm height including
rounding of junctions
of walls and slabs.
(c) After two days of proper curing applying a
second coat of cement slurry using 2.75 kg/ sqm of
cement admixed with water proofing compound
conforming to IS : 2645 and approved by
Engineerin- charge.
(d) Finishing the surface with 20 mm thick jointless
cement mortar of mix 1:4 (1 cement :4 coarse sand)
admixed with water proofing compound conforming
to IS : 2645 and approved by Engineerin- charge
including laying glass fibre cloth of approved quality
in top layer of plaster and finally finishing the surface
with trowel with neat cement slurry and making
pattern of 300x300 mm square 3 mm deep.
(e) The whole terrace so finished shall be flooded
with water for a minimum period of two weeks for
curing and for final test. All above operations to be
done in order and as directed and specified by the
Engineer-in-Charge :

With average thickness of 120 mm and minimum


22.7.1 126 sqm
thickness at khurra as 65 mm
UP GRADATION OF REGIONAL INSTITUTE OF OPHTALMOLOGY AT IGIMS PATNA (UNDER PMSSY PHASE-VB)

INVENTRY

FOR EXHUST
Exhaust FAN

16A SWITCH
TELEPHONE

6A SWITCH
LIGHT(20w)
18W DOWN

SEC. POINT

6A SOCKET
SEC. LIGHT
(1200mm)

PR. POINT
PR. LIGHT
( 300mm)

CONTROL

CONTROL
LIGHTER

SWITCH
SOCKET

SOCKET

SOCKET
AREA DESCRIPTION

16A AC
POINT
S.No.

TUBE

2X6A
PTS.

PTS.

MCB

MCB
FAN
A EXTERNAL ROOMS
1 HT METER ROOM 3 2 1 1
2 SUBSTATION 1 1 12 3 9 4 1
3 HT PANEL ROOM 3 2 1 1
4 STAIRCASE 6 2 4
5 JE ROOM 1 1 1 4 2 2 3 1 1
6 STORE ROOM 1 2 1 1 1 1 1
7 UPS & BATTERY ROOM 1 4 2 2 1 1 2 1
8 TOILET 1 2 2 1
9 POL ROOM 4 2 2 1 1 2 1
10 PLUMBING PLANT ROOM 1 1 2 4 2 1 1 1

TOTAL 3 4 3 10 36 16 18 4 4 4 6 15 4 3
10% ADD 0.3 0.4 0.3 1 3.6 1.6 1.8 0.4 0.4 0.4 0.6 1.5 0.4 0.3
GRAND TOTAL 3 4 3 11 40 18 20 4 4 4 7 17 4 3

ACROBAT ENGINEERS PVT. LTD.


IGIMS (DENTAL NUCLEAR MEDICINE) AT PATNA
62
1 SWITCH CONTROL
18
1.1 Primary Point

1.2 Secondry Point 20

1.3 No of circuit 6 x 8meter per circuit = 47 RM

5M wire for light to 6A switch 77

TOTAL 124

2 MCB Control

2.1 Primary Point 4

2.2 Secondry Point 4

No of circuit 1 x 15meter per circuit = 15 RM

5meter per point = 75 RM

TOTAL 199

Total-2 X 1.5 sq. mm + 1 X 1.5


3 199
sq. mm earth wire
Total-2 X 2.5 sq. mm + 1 X 2.5
4 15M PER POINT FOR 6A SWITCH SOCKET 308
sq. mm earth wire
Total-2 X 4.0 sq. mm + 1 X 4.0
5 20M PER POINT FOR 16A SWITCH SOCKET 396
sq. mm earth wire

ACROBAT ENGINEERS PVT. LTD.


IGIMS (DENTAL NUCLEAR MEDICINE) AT PATNA