Chapter3 Area Classification
Chapter3 Area Classification
Area Classification
While it was common practice prior to the early 1990s to classify While past practices achieved Zone 2 (Division 2) area
most indoor Class I Hazardous Locations as Zone 1 (Division classification by providing six air changes per hour by
1), many users now believe that most buildings function in mechanical means, recent experience has shown that in many
accordance with the definition for Class I, Zone 2. It is important Class I buildings, “adequate ventilation” often requires less than
to remember that the Hazardous Location definitions in the one air change per hour, and can be provided by the naturally
NEC and CEC are the basic requirements. There are many occurring ventilation. Often the reduced ventilation requirement
other industry documents such as the API Recommended eliminates the need for complicated and expensive ventilation
Practice for Area Classification which are only recommended systems and reduces the energy required to heat the building.
means of meeting the Code definitions and are not Code (Calculation formulas are also given in IEC 60079-10) However,
requirements. Any method that demonstrates compliance with there are many instances where buildings such as pumping
the area classification definitions meets the requirements of the stations are remotely located and not manned on a 24-hour
respective Code. basis. The buildings are designed as Zone 1 to accommodate
any unforeseen problems.
In most buildings the area classification choice is between Zone
1 and Zone 2. In making that choice there are a number of tools
that may be used. If it can be demonstrated that a building is
“adequately ventilated,” it meets one of the main requirements
of a Zone 2 classification. The other requirement for a Zone 2
classification is that in the event of an abnormal gas release
approaching or exceeding explosive levels, action must be
taken to correct the problem within a “short time.” Many
industrial users accept a 10-hour/per year “rule of thumb” limit
on exposure to “explosive gas atmospheres” for Zone 2
Hazardous Locations. If the building is on a site that is
continuously manned, or it is monitored by gas detection to shut
down the process, or alarmed to allow operating personnel to
correct the problem, the requirements for a Zone 2 classification
are often effectively met. Many skid platforms are not manned and are classified as Zone 1.
Article 501.1 of the NEC permits properly marked operation of equipment. A storage room which houses 55-
Class I, Zone 0,1 or 2 equipment to be installed in gallon drums of volatile solvents would be a typical example of
Division 2. a Division 2 location. This classification approximates Zone 2 in
IEC Standards.
3.8.2 ZONE 1
(b) Zone 1, comprising Class I locations in which:
(i) Explosive gas atmospheres are likely to occur in normal
operation; or
Division 1 areas
encompass
Table 3 in paragraph 6.5.8.3 of API-RP505—Recommended
Zones 0, 1 & 2.
Practice for Classification of Locations for Electrical Installations
at Petroleum Facilities Classified as Class I, Zone 0, Zone 1,
and Zone 2, suggests Zone 1 locations are those where there
A Class I, Division 2 location is one where volatile flammable is a flammable mixture more than 10 hours per year and less
liquids or flammable gases are handled, processed or used, but than 1,000 hours per year. Zone 1 locations normally occur
which are normally enclosed in containers from which they can around vents or in enclosed areas where there are
only escape in the case of accidental rupturing or abnormal intermittent or continuously open processes (for example, a
Cooper Crouse-Hinds Ex Digest 13
Area Classification
(iii) Explosive gas atmospheres are normally prevented by Similar to (b)(iii), there will normally be a Zone 2 area
adequate ventilation but which may occur as a result of failure classified around a Zone 1 area surrounding a vent. It is also
or abnormal operation of the ventilation system; or common for there to be a Zone 2 location around enclosed
areas classified as Zone 1 unless there is a “vapor-tight
Adequate ventilation is defined as “natural or artificial barrier” around the Zone 1 area. For example, a process
ventilation that is sufficient to prevent the accumulation of building with doors windows and other openings in the walls
significant quantities of vapor-air or gas-air mixtures in will typically have a Zone 2 area around all or portions of the
concentrations above 25% of their lower explosive limit.” building.
During “normal operation” there are small gas and vapor
releases from various components of the piping system such
as pump seals, valve packing and flange gaskets. These
releases are relatively small in comparison to abnormal
releases due to equipment failures. These releases are
referred to as “fugitive emissions.” Adequate ventilation for an
enclosed area is therefore the amount of ventilation required
to continuously dilute the fugitive emissions in that enclosed
area to concentrations below 25% of their LEL. (In practice it
is uncommon to encounter gas concentrations above 1 or 2%
of LEL.)
ZONE 1
• Areas above roofs outside storage tanks.
• Areas above floating storage tanks.
• Areas within a specified radius around the outlet pipes and
safety valves.
• Rooms without ventilation openings from a Zone 1 area.
• Areas around flexible pipelines and hoses.
• Areas around sample taking points.
• Areas around seals of pumps, compressors and similar
primary sources.
ZONE 2
• Areas around flanges and connecting valves.
• Areas outside Zone 1 around outlet pipes and safety valves.
• Areas around vent openings from Zone 2.
– ZONE 0
– ZONE 1
ZONE 2 –