SAP Transformer -I Unlocked
SAP Transformer -I Unlocked
Protection of Transformer
Abnormal conditions may arise, power transformers may suffer only from:-
(i) Open circuits
(ii) Overheating
(iii) Winding short-circuits e.g. earth-faults, phase-to-phase faults and inter-turn faults.
1. Open circuit:-
An open circuit in one phase of a 3-phase transformer may cause undesirable
heating. In practice, relay protection is not provided against open circuits because this
condition is relatively harmless. On the occurrence of such a fault, the transformer can be
disconnected manually from the system.
2. Overheating:-
Overheating of the transformer is usually caused by sustained overloads or short-
circuits and very occasionally by the failure of the cooling system. The relay protection is
also not provided against this contingency and thermal accessories are generally used to
sound an alarm or control the banks of fans.
3. Winding short-circuits:-
Winding short-circuits (also called internal faults) on the transformer arise from
deterioration of winding insulation due to overheating or mechanical injury. When an
internal fault occurs, the transformer must be disconnected quickly from the system
because a prolonged arc in the transformer may cause oil fire.
(i) Buchholz devices: - providing protection against all kinds of incipient faults i.e. slow
developing faults such as insulation failure of windings, core heating, fall of oil level due to
leaky joints etc.
(ii) Earth-fault relays: - providing protection against earth-faults only.
(iii) Overcurrent relays: - providing protection mainly against phase-to-phase faults and
overloading.
(iv) Differential system: - (or circulating-current system) providing protection against both earth
and phase faults.
Protection of transformer 2
5. During normal operating conditions, the secondaries of CTs carry identical currents.
Therefore, the currents entering and leaving the pilot wires at both ends are the same and
no current flows through the relays
6. If a ground or phase-to-phase fault occurs, the currents in the secondaries of CTs will no
longer be the same and the differential current flowing through the relay circuit will clear
the breaker on both sides of the transformer.
7. The-protected zone is limited to the region between CTs on the high-voltage side and the
CTs on the low-voltage side of the power transformer. It is worthwhile to note that this
scheme also provides protection for short-circuits between turns on the same phase
winding
8. When a short-circuit occurs between the turns, the turn-ratio of the power transformer is
altered and causes unbalance between current transformer pairs.
9. If turn-ratio of power transformer is altered sufficiently, enough differential current may
flow through the relay to cause its operation. However, such short-circuits are better
taken care of by Buchholz relays.
Protection of transformer 3
5. The three leads of the primary winding of power transformer are taken through the core
of a current transformer which carries a single secondary winding. The operating coil of a
relay is connected to this secondary.
6. Under normal conditions (i.e. no fault to earth), the vector sum of the three phase currents
is zero and there is no resultant flux in the core of current transformer no matter how
much the load is out of balance.
7. Consequently, no current flows through the relay and it remains inoperative. However, on
the occurrence of an earth-fault, the vector sum of three phase currents is no longer zero.
8. The resultant current sets up flux in the core of the C.T. which induces e.m.f. in the
secondary winding. This energises the relay to trip the circuit breaker and disconnect the
faulty transformer from the system.
Protection of transformer 4
5. Fig. shows the schematic arrangement of combined leakage and overload protection.
6. In this system of protection, two overload relays and one leakage or earth relay are
connected as shown. The two overload relays are sufficient to protect against phase-to-
phase faults.
7. The trip contacts of overload relays and earth fault relay are connected in parallel.
Therefore, with the energizing of either overload relay or earth relay, the circuit breaker
will be tripped.
Protection of transformer 5
1. For Earth fault beyond transformer at point ‘F1’ the current in the
relay is negligible and hence relay does not operate.
2. For Earth fault in transformer at point ‘F2’ the current in the relay is
the difference of I1 and I 2, which is sufficient to operate the relay.
3. Very sensitive relays operate on external faults/switching surges also
4. To avoid such operations the relays are set to operate for earth fault current of the order
of 15 % of rated winding current.
5. Thus the setting protects are stricted portion of the winding and hence
called restricted earth fault protection.
Protection of transformer 6
Buchholz Relay:-
Construction:-
1. Fig.shows the constructional details of a Buchholz relay. It takes the form of a domed
vessel placed in the connecting pipe between the main tank and the conservator.
2. The device has two elements. The upper element consists of a mercury type switch
attached to a float. The lower element contains a mercury switch mounted on a hinged
type flap located in the direct path of the flow of oil from the transformer to the
conservator.
3. The upper element closes an alarm circuit during incipient faults whereas the lower
element is arranged to trip the circuit breaker in case of severe internal faults.
Protection of transformer 7
Operation:-
Advantages
1. It is the simplest form of transformer protection.
2. It detects the incipient faults at a stage much earlier than is possible with other forms of
protection.
Disadvantages
1. It can only be used with oil immersed transformers equipped with conservator tanks.
2. The device can detect only faults below oil level in the transformer. Therefore, separate
protection is needed for connecting cables.