sprinklers-design
sprinklers-design
"Design"
Automatic Sprinkler Systems
"Fundamental Design Procedure"
1. Forward
• Sprinkler system piping are designed (sized) using either
"Pipe Schedule" or "Hydraulic Calculations".
• Hydraulically calculated systems are generally more
efficient and economical.
• The Design criteria means: Hydraulic calculation of the
operation area; i.e, the piping is sized to deliver the required
flow and pressure for each head in the area, and sizing the
pipe back to the system water supply in order to deliver the
demand for the area of operation.
• The minimum flow pressure of any one sprinkler is 7 psi
above atmospheric.
SD-1
2. Hydraulic Calculations and Sprinkler Design: General
Hydraulic calculations are based on the concepts and principles
of hydraulics and fluid mechanics expressed in the form of a
hydraulic model that incorporates a sequence of pre-defined
physical accounting procedures:
• Determine the type of hazard and select values for density
and area per sprinkler that are applicable to the design area.
• Density multiplied by area per sprinkler gives the flow
required at the most remote sprinkler.
• Use this value along with the sprinkler K-Factor to check
the minimum starting pressure, which should exceed 7 psi.
• Select the next point upstream, calculate the pressure due to
elevation and friction loss and add this to the minimum
starting pressure at the most remote sprinkler.
• Extend this process to each and every node all the way back
to the source node.
• If there are loops and grids along the way, route the flow
through all the pipe segments in accordance with the
principles of hydraulics and fluid mechanics.
• Add fixed pressure devices such as detector checks and
valves to derive the total sprinkler pressure and flow at the
source node.
SD-2
• Compare the total sprinkler pressure and flow with what is
available on the water supply graph as determined by a
hydrant flow test.
• If the total sprinkler pressure exceeds what is available on
the graph, modify the design by increasing pipe sizes or
changing the geometry of the piping network and repeat the
calculation until the total sprinkler pressure is
accommodated by the graph.
SD-3
A Case Study
60 ft
60 ft
75 ft
SD-4
SD-5
Design Procedure: Hydraulic Calculations
SD-6
Maximum Sprinkler Spacing
Light hazard occupancies 15ft.
Ordinary hazard occupancies 15ft.
Extra hazard occupancies 12ft.
SD-7
6. Layouts of Sprinkler Piping
15 ft
15 ft
22.5 ft
6th floor
5th floor 10 ft
4th floor
3rd floor
2nd floor
1th floor
To water supply
area of operation
Total area
area of operation
Water supply
Total area
15 ft
15 ft
22.5 ft
SD-10
• The number of sprinklers in the operation area =
operation area/coverage area per sprinkler = 800/225= 8
• So, 8 sprinklers are expected (as a maximum) to open in
case of fire. This is the only number of sprinklers which are
to be hydraulically calculated.
SD-11
• The total flow required for this 6th floor =
flow density x operation area x 1.15
=190 gpm
• Note: the factor 1.15 is called the flow factor and this is to
account for the friction loss in pipes
4 8
Line #2 Line #4
22.5 ft
3 7
Riser
CM #1
2 6
Line #1 Line #3 15 ft
1 5
∆P 4.52 (20)1.85
= = 0.164 psi / ft
L (120)1.85 (1) 4.87
∴Total friction loss in the 15 ft. long-pipe =
0.164X15=2.46 psi
SD-13
6) Now, the pressure at sprinkler head 2 =
SD-15
15) Using This K value for lines 3 & 4 (since they are identical
to lines 1 & 2), the gpm to lines 3 & 4 can be determined
from: Q = 19.41 26 = 98.97gpm
Note: The operation area requires 83.7 + 98.97 = 182.67
gpm, not 20 gpm x 8 heads, this is of course due to
friction, which justifies the flow factor of 1.15 used before.
Q gpm @ P psi.
18) To check the demand vs. the city water main supply, plot
the demand on the city water supply graph (it is a straight
line representing the flow Q in gpm plotted as Q1.85 vs. the
Pressure P in psi). If the demand is below the supply, the
supply will satisfy the demand. But if the demand is above
the supply line, the supply will not satisfy the demand. It is
always recommended to have the calculated system
SD-16
demand fall at least 10 psi below the supply line ??.
SD-17
Hydraulic Calculation Sheet
1/2" orifice K=5.6 0.09 GPM/S.F. over 1800 S.F. 225 S.F./Head
Nozzle Flow in Pipe Fittings Pipe Equiv. Friction Required Elev. Notes
Type& G.P.M. Size & Length Loss psi
Location Device psi/ft
line #1 q LGTH 10 PT 12.76
1" FTG 0 TOT. 0.164 PF 2.46
1 Q 20
10 PE 0.0
2 q 21.85 LGTH 7.5 PT 15.22
1.25" T FTG 8.0 0.217 PF 3.37
Q 41.85
TOT. 15.5 PE 0.0
SD-18
SD-19