Thermal Dispersion
& Paddle Type Flow Switch
PRODUCT INTRODUCTION

OPERATING PRINCIPLE
Thermal dispersion flow switches measure the When liquid is flowing, there is a temperature
velocity of a liquid inside a pipe or channel. difference between the two sensors. The
The switch’s probe contains two key components temperature difference has an inverse relationship
– a heating sensor and temperature sensor. The with the flow velocity (fast flowing liquids will result
heating sensor is positioned closest to the flowing in greater heat differences and vice versa).
liquid and provides a consistent heat. The Since the device contains no moving parts, has no
temperature sensor measures the temperature wear and tear and maintains a long lifespan.
emitted from the heating sensor.

FEATURES APPLICATION
High sensitivity and accuracy. Petrochemicals, Hydroelectric plants, Shipyard,
Suitable for corrosive and hazardous HVAC Systems, Steel Industry Food and Beverage,
conditions. Pharmaceutical,Optics and Semiconductor Industry,
Able to be calibrated for liquids with different Cooling pipes flow control
densities and impurities. Any pipes carrying liquid where flow measurement
Suitable for complex locations with easy is needed.
installation.
Customized probe lengths available.
Three different output signals options.

1
PRODUCT SPECIFICATIONS

HEX38 HEX38

HEX38

40.5

59.5
40.5 M12 72.5
M12
Drawings
M12
G 1/2" f16
L
31 (Max.200)
G 1/2"
f7.4
1/2"PF L=31
f7.4 f7.4

Model SP200 Compact model SP201 Extension model SP202 High Temp. model

Water: 1~150 cm/s Water: 1~150 cm/s Water: 1~150 cm/s


Measuring range
Oil: 3~300 cm/s Oil: 3~300 cm/s Oil: 3~300 cm/s

Ambient temp. -20 ~ 80BC -20 ~ 80BC -20 ~ 80BC

Operating temp. -20 ~ 80BC -20 ~ 80BC -20 ~ 120BC


Open Collector : NPN / PNP (<400mA)
Alarm output
Relay : 1A/30Vdc, 0.3A/125Vac (NO or NC)

Operating pressure 100 bar (max.) 100 bar (max.) 100 bar (max.)

Flow velocity below set point- Red LED on, Open


Led indication Flow velocity equals set point- Yellow LED on, Close
Flow velocity above set point- 4 Green LED to indicate flow speed, Close

Housing SUS304 / 316 / 316L

Wetted part SUS304 / 316 / 316L

Protection level IP67

Warm-up time Approx.15 Sec Approx.15 Sec Approx.15 Sec

Connection thread G1/2, G1/4, NPT1/2 G1/2, NPT1/2 G1/2, G1/4, NPT1/2

Operating voltage 19 ~ 30Vdc

Power consumption 50mA (max.)

3-wire NPN/PNP
Power-brown
Wiring
Grounding-blue
Output-black

Accessory Gasket, 2m Cable

2
40
M12

Drawings
106

L=31
1/2"PF
f7.4
30 19.8

Model SP220 Economy model

Water: 1~150 cm/s


Measuring range
Oil: 3~300 cm/s

Ambient temp. -20 ~ 80BC

Operating temp. -20 ~ 80BC

Open Collector : NPN / PNP (<400mA)


Alarm output
Relay : 1A/30Vdc, 0.3A/125Vac (NO or NC)

Operating pressure 100 bar (max.)

Flow velocity below set point- Red LED on, Open


Flow velocity equals set point- Yellow LED on, Close
Led indication
Flow velocity above set point- 4 Green LED to indicate
flow speed, Close

Housing PC
Wetted part SUS304 / 316 / 316L

Protection level IP65

Warm-up time Approx.15 Sec

Connection thread G1/2, NPT1/2

Operating voltage 19 ~ 30Vdc

Power consumption 50mA (max.)


3-wire NPN/PNP
Power-brown
Wiring
Grounding-blue
Output-black
Accessory Gasket, 2m Cable

Footnote Sensitivity and Alarm setting not available.

3
f70
Sight Window
f70 f70

46
78
46 46
78 78
Drawings
PG 32

32 32
G1/2"
L
(Max.200)
31 G1/2" 31 G1/2"
f7.4 f7.4 f7.4
f38 f38 f38

Cert. Number GYJ12.1521x Cert. Number GYJ12.1521x


SP210 SP170-(½) SP171-(½) Explosion-proof
Model Stainless Steel model Explosion Proof model extension model
Water: 1~150 cm/s
Measuring range
Oil: 3~300 cm/s

Ambient temp. -20 ~ 80BC

Operating temp. -20 ~ 80BC

Alarm output Relay: 5A/250Vac Relay: 3A/250Vac

Operating pressure 100 bar (max.)

Flow velocity below set point- Red LED on, Open


Led indication Flow velocity equals set point- Yellow LED on, Close
Flow velocity above set point- 4 Green LED to indicate flow speed, Close

Housing SUS304
Wetted part SUS304 / 316 / 316L

Protection level IP67

Warm-up time Approx.15 Sec

Connection thread G1/2, NPT1/2

Operating voltage 19 ~ 30Vdc

Power consumption 60mA (max.)


5-wire Relay Output
Power- red
Wiring Grounding- black
COM- white
F G NC C NO
NC- yellow
NO- blue
Accessory Gasket, 2m Cable

4 4
INSTALLATION

INSTALLATION
1. Use the water-proof gasket provided 4. Screw tightly to avoid. Can be installed
2. The distance "a" should be 4 times larger from various angles. For best sensitivity
than the switches’ screw diameter. (Fig. 1) and response speed, please install using in
3. The pipe is bubble free for proper the demonstrated in Fig. 4
functioning. (Fig. 2) 5. Installing a filter upstream can decrease
4. For not-completely-filled pipes, install from liquid impurities which can reduce wear
the bottom. The liquid level needs to be and tear on the switch.
higher than the probe height. (Fig. 3)

a³4xd d

Fig. 1 Fig. 2

Fig. 3 Fig. 4

5
WIRING AND CONNECTIONS
2

3 1 SENSITIVITY ALARM

Fig. 5
Wire terminal diagram Fig. 6
(NPN, PNP and 1A relay output type)

WIRING

3-wire 3 Blue 4-wire 1 Brown


) )
1 ) Brown 3 ) Blue
NPN
4 Black 2 Green
) )
NO 4 Black
Fig. 7, NPN output type wiring )
Fig. 10, Relay output type wiring (NO)

1 ) Brown 1 )
Brown

PNP 3 ) Blue 3 ) Blue

4 ) Black 2 ) Green

NC 4 Black
Fig. 8, PNP output type wiring )
Fig. 11, Relay output type wiring (NC)

SCREW TABLE
5-wire
Red
Standard
Black Screw PF,BSP PT,NPT
Relay Screw head L Screw head L
White
COM 1/4” 8.5mm 25mm 10mm 25mm
Yellow 1/2” 10.5mm 31mm 19mm 40mm
NC 1” 16mm 36mm 20mm 40mm
Blue
NO
Extension
Fig. 9, Relay output type wiring PF,BSP PT,NPT
Screw
Screw head Screw head
1/2” 11.5mm 16mm 16mm 20mm
1” 16mm 20mm

Screw head

6
MODEL NUMBER / ORDER CODE COMPARISON TABLE

Model Number Order Code


SP200 SPX10000-A
SP201 SPX10000-B
SPX10200-A
SP202
SPX10200-B
SP220 SPX10100-A
SP210 SPX10000-C
SP170 SPX1007B-C
SP171 SPX1007B-D

7
ORDER INFORMATION

05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22

SPX1 9999- 99999999999999

05 06 Model
00: Standard
01: Economy(ABS)
02: Hi-temperation

07 08 Certification
00: None
7B: NEPSI-Exia
B0: DNV

09 Construction
A: Compact type
B: Extension type
C: Stainless steel type
D: Stainless steel extension type

Connection
10 11 12 13 14 15

Thread item A4: 3/8" 01: PT male


AA: JIS A2: 1/4" 03: PF male
AB: ISO A5: 1/2" 05: BSP male
AC: ANSI A7: 3/4" 07: NPT male
A8: 1" 13: GAS male

16 17 Material
MA: SUS 304
MB: SUS 316
MC: SUS 316L

18 Output signal
A: NPN
B: PNP
C: Relay 1A/30Vdc, 0.3A/125Vac(NO)
D: Relay 1A/30Vdc, 0.3A/125Vac(NC)
E: SPDT 3A/5A, 250Vac(Only stainless steel type )

19 20 21 22 Length
Code Description
0031~0200 0031(PF), 0040(NPT/PT)mm, Max.0200
0070~0200 0070~0200mm

8
PADDLE TYPE FLOW SWITCH

PRINCIPLE SECTIONAL DRAWINGS


Flow Switch can detect liquid movement in pipes.
When the liquid is static or nonexistent, the spring
is fully extended pulling the magnet downward and
1. O-Ring 7
opening the switch.
As flow occurs and the paddle is thrusted forward 2. Paddle
20BC~30BC (or more) the paddle will push the 3. Axis
magnet upward and actuate the switch (closing the 1
circuit) 4. Reed switch
The length of paddle can be adjusted to the pipe's 5. Spring
diameter. 6. Magnet
5
7. Housing 6
9
8. Screw 4
8
9. Center rod 3
1"
1-1/4"
1-1/2"

2"
2-1/2"
spring 3"

magnet 2

reed switch
NEPSI
axis
MODEL: SF1710 MODEL: SF1800
paddle Explosion proof model Standard model
(L-Housing) (E-Housing)

80
Switch on in case of liquid flowing in pipes
80

*1/2"NPT
spring
16 19
16 19

magnet

reed switch

axis

paddle

Switch off in case of no moving liquid in pipes

* Optional part
1/2"NPT

9
Model SF1710 SF1800
Spec.
Housing material Aluminum Alloy, Ex d IIC T6~T4 Aluminum Alloy, IP 65
Operation temp. -30BC~100BC -30BC~150BC
Wetted material SUS304 SUS304
Operation pressure Max. 355 PSIG Max. 355 PSIG
Pressure drop allowance 3 PSIG 3 PSIG
Set point tolerance K25% K25%
Repeatability tolerance K5% K5%
Contact capacity 60W 220Vac/200Vdc, SPDT 60W 220Vac/200Vdc, SPDT

FLOW CONTROL RANGE TABLE

1" 1-1/2" 2" 2-1/2" 3"


Flow Volume
Gallon Act. De-Act. Act. De-Act. Act. De-Act. Act. De-Act. Act. De-Act.
Paddle Length Min.

1" 4.7 3.9 10.9 8.3 19.9 16.1


1-1/4" 7.7 6.1 16.5 12.3 31.3 22.8
1-1/2" 5.7 4.5 13.4 9.5 25.2 18.5
2" 8.4 6.3 15.1 12.8 29.7 21.9
2-1/2" 13.9 10 20.4 15.4
3" 17.1 12.8
※1 Gallon=3.7854 Litter

INSTALLATION CAUTION
1. The paddle length is dependent on the lowest 1. The pressure and temperature ranges as shown in
paddle point to actuate the switch. Cut the pad- the catalog, must not be exceeded and also take
dle at appropriate pipe size mark or wherever the abrupt pressure and temperature into consid-
desired. The minimum is 1". erations.
2. The paddle must be at a right angle to the di- 2. Large sudden changes in liquid temperature and
rection of flow density (specific gravity) changes will influence
3. The FLOW mark on the screw must be the flow switch accuracy
parallel to the pipe. 3. Although highly rigid and durable, shock and vibra-
4. Before installing the unit to a tee pipe, tion should be minimized.
apply thread seal tape to the screw and then 4. Excessive fluid debris might inhibit paddle opera-
tighten. tion. Occasionally remove switch and clean off
any debris.
5. Sealing electrical connections and the connection
will reduce moisture damage.
1 Not recommended for 1" or smaller NPT plastic pipes.

(32Max)

10
MODEL NUMBER / ORDER CODE COMPARISON TABLE /
ORDER INFORMATION

Model Number Order Code


SF1800 SFX10000-A1EAAA801
SF1710 SFX1007C-A1LAAA801

07 08 11 12 13 14 15 16 17 18 19 20

SFX1 0 0 99 - A 1 9999999999
07 08 Certification
00: None
7C:NEPSI-Exd

11 Housing
Code Description
E Aluminum, 1/2"PF-88x84
L Aluminum, 1/2"PF-80x80

Connection
12 13 14 15 16 17

Thread A8: 1" 01: PT male


AA: JIS 07: NPT male
AC: ANSI

18 19 Material
MA: SUS 304
MB: SUS 316
MC: SUS 316L

20 Paddle length
A: 1" F: 3"
B: 1-1/4" G: 3-1/2"
C: 1-1/2" H: 4"
D: 2" X: Standard
E: 2-1/2"

11
Global Network

Germany
China

U.S.
Taiwan U.S.
Singapore
Malaysia

Indonesia

Asia North America Europe


Taiwan California, U.S. Germany
FineTek Co., Ltd. - Taipei Head Quarter Aplus Finetek Sensor Inc. - US Office FineTeK GmbH - Germany Office
No.16, Tzuchiang St., Tucheng Industrial Park 355 S. Lemon Ave, Suite D, Walnut, Frankfurter Str. 62, OG D-65428
New Taipei City 236, Taiwan CA 91789 Ruesselsheim, Germany
TEL: 886-2-2269-6789 TEL: 1 909 598 2488 TEL: +49-(0)6142-17608-0
FAX: 886-2-2268-6682 FAX: 1 909 598 3188 FAX: +49-(0)6142-17608-20
EMAIL: [email protected] EMAIL: [email protected] EMAIL: [email protected]

China Illinois, U.S. Mütec Instruments GmbH - Germany Office


Fine automation Co., Ltd. - Shanghai Factory Aplus Finetek Sensor Inc. Bei den Kämpen 26
No.451 DuHui Rd, MinHang District, Shanghai, TEL: 1 815 632-3132 21220 Seevetal-Ramelsloh, Germany
China 201109 FAX: 1 815 716 8464 TEL: + 49 (0)4185-8083-0
TEL: 86-21-6490-7260 EMAIL: [email protected] FAX: + 49 (0)4185-8083-80
EMAIL: [email protected] EMAIL: [email protected]

Singapore
FineTek Pte Ltd. - Singapore Office
No. 60 Kaki Bukit Place, #07-06 Eunos
Techpark 2 Lobby B, Singapore 415979
TEL: 65-6452-6340
EMAIL: [email protected]

Indonesia
FineTek Co., Ltd. - Indonesia Office
Ruko Golden 8 Blok H No.38
Gading Serpong, Tangerang, Indonesia
TEL: 62 (021)-2923-1688
EMAIL: [email protected]
Distributor:
Malaysia
FineTek Co., Ltd. - Malaysia Office
8-05, Plaza Azalea, Persiaran Bandaraya,
Seksyen 14, 40000 Shah Alam, Selangor, Malaysiac
TEL: 603-5524-7168
EMAIL: [email protected]

08-SPFEP-011118

You might also like