ATOS Valve Driver 140
ATOS Valve Driver 140
E-ME-T
Analog drivers control the current to the sole-
noid of Atos proportional valves with position
transducer, regulating the spool position or
USER FUNCTIONS AND CONTROL OPTIONS USER INTERFACE
the flow according to the electronic reference
signal, adjusted by transducer’s feedback.
Features:
• bias regulation
SUPPLY 24V • scale and dissymmetrical ramps regulation
Dead Band Adjustment Spool Position Control
REFERENCE • voltage (standard) or current
SIGNALS
ENABLE
(/I option) reference signal
INPUTS
SIGNALS • voltage (standard) or current
SPOOL (/C option) feedback signal
FEEDBACK
Ramp Generator Output Protections
SPOOL
• test point for reference and feedback con-
FEEDBACK trol on front panel
Feedback
OUTPUTS
SOLENOID • factory pre-set
Fault Sense SUPPLY
• Eurocard format (DIN 41494 - plug-in unit)
• electronic filters on input and output lines
• CE mark according to EMC directive
• both sides of the card with shielded cover
with E faston connector
Applications:
Position or flow open or closed-loop regulation
systems, according to the block diagram 2 .
1 MODEL CODE
E-ME - T - 01H / * * / *
Series number
2 BLOCK DIAGRAM
RAMPS
REFERENCE
CURRENT
DEAD BAND S2 AMPLIFIER
CLOSE LOOP DRIVING
CONTROL SPOOL POSITION COIL S2 CURRENT
(AXES CARD) CONTROL
FLOW
PRESSURE
ACCELERATION
FORCE
G140
3 MAIN CHARACTERISTICS
Scale, see 7
The Scale regulation, available on the card side, permits to modify the relation between the refe-
rence signal and the position or the regulated flow. 10 kw
Modifying this regulation it is possible to fit the valve hydraulic behaviour to the effective system
conditions; in addition the two regulations available for double solenoid valves (driver E-ME-T-05H)
permit to set different hydraulic adjustments for positive and negative movements.
The Scale regulation is factory set in order to control the max valve opening with 100% of the refe-
rence signal (10V).
Bias, (dead band compensation) DIFFERENTIAL EXTERNAL REFERENCE
The bias regulations, available on the front panel (P1, P2), permit to set the correspondence
between the electrical zero of the reference signal with the beginning of the valve’s hydraulic regu-
lation, compensating the dead band and the component’s mechanical tolerances .
Modifying this regulation (see 9 , 10 ) it is possible to fit the valve hydraulic behaviour to the effec-
tive system conditions; in case of drivers for double solenoid
valves (E-ME-T-05H) the bias are active only when the reference signal is over the threshold value
= ±200 mV.
This regulation is factory set at the standard values depending to the proportional valve to be con-
trolled and it is identified by the driver set code (see 4.4).
Ramps, see 7 , 11 , 12
/I OPTION 4 ÷ 20 mA
The ramp regulation, available on the front panel, permit to modify the
time in which the valve reaches the set opening value in front of a step change of the reference
signal.
The ramp regulation is factory set at value close to zero and it can be increased up to 14 sec max
for a step change of the reference signal from 0% to 100%.
The two available regulations P3 and P4 permit to respectively regulate the ramp times for positive
and negative variations of the reference signal. In case of application of the driver in closed loop
systems, it is advisable to disable the ramp function: it is possible to permanently disable this func-
tion by means of a switch on the card side ( 7 ) or temporarily, connecting the pin 6c and 6a ( 12 ).
Gain, see 8 - only for valves with not linear regulation (spool types T, DT) 7 RAMPS AND SETTINGS
Pressure gain adjustment around “zero” increases sensitivity and positioning accuracy of the axis
and optimize the valve operation according to the stiffness of the system by increasing the hydrau-
lic gain of the valve around the hydraulic zero. Valve Opening
P3 P4
DISSYMETRICAL RISIND AND
FALLING RAMPS GENERATOR
6 INSTALLATION AND START-UP
Time
6.1 Warning:
P3 P4
– Do not insert or remove the driver while the electronic system is energized
– Connect the electronic driver according to the desired connection scheme (see 11 , 12 )
– The voltages must be always measured in reference to the GND (pin 8a of the connector)
– Refer to 8 to identify the components mentioned in the setting procedure CONNECT TO AN EFFICIENT EARTH POINT
– To check the reference signal and the regulated valve opening , use the test points T1 and T2
the on front panel
– To check the correct solenoid command for positive and negative regulations, use the two led C
FUSE
– Gradually turn potentiometer(s) (P1 for coil S1 and P2 for coil S2) until a movement of the con-
trolled actuator is obtained
– Turn slowly in the opposite sense until stop is obtained RAMP ON
B
Scale adjustment, see 7 , 9 , 10 RAMP
RAMP OFF
SWITCH
Set the scale switch (see 7 -A) depending to the selec- (STD SETTING)
Gain, see 8 , 9 - only for valves with not linear regulation (spool types T, DT) ATTENUATION
TILL 20% OF FULL P5
Front panel potentiometer P7 could be rotated to increase sensitivity and positioning accuracy of REFERENCE
the axis (clockwise rotation = increase in sensitivity). Factory preset completely counterclockwise. SIGNAL
Ramps, see 7 , 8
Reference [V]
If the card is being used in a open loop system push the switch from position ramp off (standard)
P6
to position ramp on, (see 7 -B). Calibrate the ramp settings only if dynamic impacts and tenden-
cies towards instability persist after optimizations of the whole system. Adjust the ramp settings
using the ramp potentiometers (P3 and P4) until the phenomenon has been eliminated (Clockwise
rotation = increase in ramp time).
P7 P5
P1
Power on (green)
Fail safe led (red)
Reference [V]
Bias solenoid S1 P1
(1) Bias solenoid S2 P2
P1
(1) Channel enabled led (solenoid S2) S2
P2
Reference [V]
P6
SWITCH A REFERENCE [V]
POS. 1 ±10
POS. 2 ±5
(1) Only E-ME-T-05H/*
(2) Only E-ME-T-01H/* for valves with not linear regulation (spool types T, DT)
G140
11 IMPORTANT INSTRUCTIONS
ELETTROMAGNETIC COMPATIBILITY
Atos electronic drivers and proportional valves are designed according to the 2004/108/CE Directive (Electromagnetic Compatibility) and accor-
ding to EN 50081-2 (Emission) and EN 50082-2 (Immunity) standards. The electromagnetic compatibility of electronic drivers is valid only for
wirings realized according to the typical electric connections shown in this technical table.
The device must be verified on the machine because the magnetic field may be different from the test conditions.
SAFETY
The electrical signals (for example reference signals, feedback and enable signal) of electronic drivers must not be used to realize safety condi-
tions of the machine. This is in accordance with the provisions of European directives (Safety requirements of fluid technology systems and com-
ponents-hydraulics, EN 982). Special attention must be payed to switch-on/switch-off of electronic drivers because they could produce uncontrol-
led movements of actuators operated by the proportional valves.
SCALE
INTERNAL +VCC
POWER SUPPLY FUSE INTERNAL SUPPLY +15 V
24 VDC ± 10%
SPOOL FEEDBACK
4700 µF / 40 V 4 A fast TRANZORB
POWER GND
OFFSET
-15 V
SIGNAL GND
FEEDBACK
+10 V
-10 V
+24 V SHIELD
ENABLE
+VCC
RAMP SWITCH (1) LED
RAMP 1 BIAS S1
GND REFERENCE
WITH COMMON CURRENT +VCC
GROUND FEEDBACK
RAMP 2 BIAS S2
LED S1
RAMP SWITCH OFF
FAULT
REFERENCE
P7
GAIN +VCC
LED S2
SCALE P5
+VCC
SWITCH
DIFFERENTIAL x 1 (*)
REFERENCE x 0.5
SIGNAL INPUT
LINEARIZATION CURRENT
P6 (2) FEEDBACK
(1) = Factory pre-set (2) = Only E-ME-T-01H/* for valves with not linear regulation (spool types T, DT)
SHIELD
-15V
GND
SIGNAL
+15V
Note: S1 and S2 solenoids are referred respectively to B port side and A port side. CONNECTOR TYPE 345 (see table K500)
24 VDC
FAULT
COIL S1
COIL S2
(E-ME-T-05H)
E :PROTECTIVE EARTH
TE :NOISELESS EARTH
C :ALTERNATE BONDING CONNECTION TO NOISELESS EARTH TERMINAL
07/16