Sizing Valve
Sizing Valve
Sizing Type: Water Flow is Turbulent Solving for: Cv Noise is Hydrodynamic Flow is Volumetric
Variable Name Units Minimum Normal Maximum Other
SERVICE & SIZING
Inlet Temperature (T1) deg F 170.0000 176.0000 176.0000 176.0000
Inlet Pressure (P1) psig 26.000 22.000 29.000 30.000
Pressure Change (dP) psi 2.000 2.000 2.000 2.000
Volumetric Flow Rate Liquid (Ql) barrel/d 100000.00 150000.00 50000.00 16000.00
Pressure Recovery Factor (Fl) 0.774 0.724 0.810 0.790
Valve style modifier (Fd) 0.428 0.499 0.310 0.172
Cavitation coefficient (Kc) 0.150 0.150 0.150 0.150
Atmospheric Pressure psi 14.69 14.69 14.69 14.69
Pipe Size Up in 16 16 16 16
Pipe Schedule Up STD STD STD STD
Pipe Size Down in 20 20 20 20
Pipe Schedule Down STD STD STD STD
Nominal Valve Diameter (dv) in 14.000 14.000 14.000 14.000
NOISE CALCULATION
Hydrodynamic Trim Standard Trim Standard Trim Standard Trim Standard Trim
Valve Lpa (LpAe1m) dB(A) 55 57 52 < 50
VELOCITY OUTPUTS
V1 Pipe ft/s 5.121 7.682 2.561 0.819
V2 Pipe ft/s 3.214 4.821 1.607 0.514
Item Notes:
Actuator Sizing Calculation
Customer: Puffer Colombia
Contact: Contact: Ginna K Moreno
Customer Reference: Sales Office Reference: Lead Time:
Item: 1 Rev: Qty: 1 Quote: 352-GM-230921-0032000 Rev: A
Tags: Date Last Modified: 09/21/2023
Description: NPS 14 8532 Origin Cert PL Special Tagging 1061 Size 68 Special Tagging DVC6200 377 Volume Tanks Factory Mtgs
DVC6200/DVC2000 Process Level 3 Global Drawings
Service Description:
Variable Name Values Units
Supply Pressure 80 psig
Operating Range 85 psig
Gas or Liquid? Liquid
Delta-P-Shutoff 30.00 psi
Type 377 Trip Valve Yes
Volume Tank Yes
Sizing Type: Water Flow is Turbulent Solving for: Cv Noise is Hydrodynamic Flow is Volumetric
Variable Name Units Minimum Normal Maximum Other
SERVICE & SIZING
Inlet Temperature (T1) deg F 170.0000 176.0000 176.0000 176.0000
Inlet Pressure (P1) psig 26.000 22.000 29.000 30.000
Pressure Change (dP) psi 2.000 2.000 2.000 2.000
Volumetric Flow Rate Liquid (Ql) barrel/d 100000.00 150000.00 50000.00 20000.00
Pressure Recovery Factor (Fl) 0.677 0.618 0.716 0.730
Valve style modifier (Fd) 0.405 0.465 0.286 0.191
Cavitation coefficient (Kc) 0.150 0.150 0.150 0.150
Atmospheric Pressure psi 14.69 14.69 14.69 14.69
Pipe Size Up in 16 16 16 16
Pipe Schedule Up STD STD STD STD
Pipe Size Down in 20 20 20 20
Pipe Schedule Down STD STD STD STD
Nominal Valve Diameter (dv) in 12.000 12.000 12.000 12.000
NOISE CALCULATION
Hydrodynamic Trim Standard Trim Standard Trim Standard Trim Standard Trim
Valve Lpa (LpAe1m) dB(A) 56 58 52 < 50
VELOCITY OUTPUTS
V1 Pipe ft/s 5.121 7.682 2.561 1.024
V2 Pipe ft/s 3.214 4.821 1.607 0.643
Item Notes:
Actuator Sizing Calculation
Customer: Puffer Colombia
Contact: Contact: Ginna K Moreno
Customer Reference: Sales Office Reference: Lead Time:
Item: 2 Rev: Qty: 1 Quote: 352-GM-230921-0032000 Rev: A
Tags: Date Last Modified: 09/21/2023
Description: NPS 12 8580 Special Tagging 1061 Size 60 Special Tagging DVC6200 377 Volume Tanks Factory Mtgs
DVC6200/DVC2000 Process Level 3 Global Drawings
Service Description:
Variable Name Values Units
Shaft Size 1.500 in
Push Down to: Close
Max Rotation 90 deg
Supply Pressure 80 psig
Operating Range 85 psig
Gas or Liquid? Liquid
Delta-P-Shutoff 30.00 psi
Type 377 Trip Valve Yes
Volume Tank Yes