1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

A A
SI DG CS&D
Equipment List

B B

C C
Customer
Last Used by: z004cv6p

GOVT. OF SIKKIM
Time: 5:29:30 PM
Date: 7/18/2022

Consultant
POWER GRID CORPORATION OF INDIA
LTD.

Project
D
SIK SS04 D

Substation
132/66kV SAMARDONG S/S
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 E102 01

Contractor
CopyRight (C) Siemens Limited, India All Rights Reserved.

LoA No.
E LOA/PGCIL SIKKIM-SS04/16-17/CRP & SAS/02 E

Title
BAY-102 (LINE-2)

Drawing No. Revision


(3)G719EA-JG9127-E102 A

F F
C QT Corrected 7/12/2022 HRD Date 5/12/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) Customer Dwg No. P2 E 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. COVER SHEET SIK SS04 E10201
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 01 of 6
3005082555 (3)G719EA-JG9127-E102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Equipment List < 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.0-3/8/2018


E-Base Version: 7.0.0.1257

Sheet Version: V 1.0

DESIGNATION DETAILS MANUFACTURER MODEL DESCRIPTION DIS MOUNTING QUANTITY


A A
Case Size: 1/2 19”, 4xI, 4xV, 8 BI, 15 BO, 1 Live Status, 14 LED, Flush Mounting
Numerical Relay 7SD52
87L Siemens, Germany CT Sec: 1A, PT Sec: 110V AC, Aux Supply: 110-250V DC, 115V AC, BI Threshold 88V Boughtout Front Mount 1
Line Diff. Protn. 7SD5221-5AB99-9EN0+L0S+M0G+N5G
IEC61850, Optical EN100, Double, LC Connector
Case Size: 1/3 19”, 4xI, 4xV, 16 BI, 7 BO, 1 Live Status, 7 LED, Flush Mounting
Numerical Relay 7SJ66
67/67N Siemens, India CT Sec: 1A, PT Sec: 110V AC, Aux Supply: 110-250V DC, 115-230V AC, BI Threshold: 69V Boughtout Front Mount 1
DIR. OC & EF Protn. 7SJ6611-5DB90-1FC0+L0S
IEC 61850, Ethernet With 100Mbit/s Fiber Optic Port
Case Size: 1/3 19”, 4xI, 4xV, 7 BI, 5 BO, 1 Live Status, 7 LED, Flush Mounting
Numerical Relay 7VK61
50Z Siemens, Germany CT Sec: 1A, PT Sec: 110V AC, Aux Supply: 110-250V DC, BI Threshold 88V Boughtout Front Mount 1
LBB Protection Relay 7VK6101-5AB91-4YC0+L0S
IEC 61850, Optical, Double, LC Connector
Aux Voltage: 24-230V DC, 24-230V AC, Contacts: 2CO, S/R
Relay, Contactor 7PJ13
95.A Siemens, India Boughtout Front Mount 1
TC-1 Supervision Relay 7PJ1321-5AA21-0AA0
B B
Aux Voltage: 24-230V DC, 24-230V AC, Contacts: 2CO, S/R
Relay, Contactor 7PJ13
95.B Siemens, India Boughtout Front Mount 1
TC-2 Supervision Relay 7PJ1321-5AA21-0AA0

Aux Voltage: 24V DC, Contacts: 7NO+1NC, H/R or E/R, Flag: Yes
Relay, Contactor RXMVB2
86.1 ABB, India Case Size: 2U 12C Boughtout Front Mount 1
Trip Relay 1MYN563033-AD
Use With RXTMA Series Resistor
Aux Voltage: 24V DC, Contacts: 7NO+1NC, H/R or E/R, Flag: Yes
Relay, Contactor RXMVB2
86.2 ABB, India Case Size: 2U 12C Boughtout Front Mount 1
Trip Relay 1MYN563033-AD
Use With RXTMA Series Resistor
Aux Voltage: 24V DC, Contacts: 7NO+1NC, H/R or E/R, Flag: Yes
Relay, Contactor RXMVB2
96 ABB, India Case Size: 2U 12C Boughtout Front Mount 1
Trip Relay 1MYN563033-AD
Use With RXTMA Series Resistor
C C
Last Used by: z004cv6p

Aux Voltage: 110V DC, 220V DC (Selectable), Contacts: 2CO, S/R, Flag: Yes (LED)
Relay, Contactor TSR
80.1 ABB, India Case Size: 2U 6C, Time Delay On Dropout Is 300ms Boughtout Front Mount 1
Time: 5:29:38 PM

DC Supervision Relay IN35 200 1-AS


Date: 7/18/2022

Aux Voltage: 110V DC, 220V DC (Selectable), Contacts: 2CO, S/R, Flag: Yes (LED)
Relay, Contactor TSR
80.2 ABB, India Case Size: 2U 6C, Time Delay On Dropout Is 300ms Boughtout Front Mount 1
DC Supervision Relay IN35 200 1-AS

Aux Voltage: 110V DC, 220V DC (Selectable), Contacts: 2CO, S/R, Flag: Yes (LED)
Relay, Contactor TSR
95.1 ABB, India Case Size: 2U 6C, Time Delay On Dropout Is 300ms Boughtout Front Mount 1
Supervision Relay IN35 200 1-AS

Aux Voltage: 110V DC, 220V DC (Selectable), Contacts: 2CO, S/R, Flag: Yes (LED)
Relay, Contactor TSR
95.2 ABB, India Case Size: 2U 6C, Time Delay On Dropout Is 300ms Boughtout Front Mount 1
Supervision Relay IN35 200 1-AS
D D
Aux Voltage: 110V DC, 220V DC (Selectable), Contacts: 2CO, S/R, Flag: Yes (LED)
Relay, Contactor TSR
95.3 ABB, India Case Size: 2U 6C, Time Delay On Dropout Is 300ms Boughtout Front Mount 1
Supervision Relay IN35 200 1-AS

Aux Voltage: 110V DC, Contacts: 6NO, S/R, Flag: No


Relay, Contactor RXMS1
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 E102 02

50ZX ABB, India Case Size: 2U 6C Boughtout Front Mount 1


LBB MUX. RELAY RK 216 263-AN

Aux Voltage: 110V DC, Contacts: 6NO, S/R, Flag: No


Relay, Contactor RXMS1
52A ABB, India Case Size: 2U 6C Boughtout Front Mount 1
CB TRIP MUX. RELAY RK 216 263-AN
CopyRight (C) Siemens Limited, India All Rights Reserved.

Aux Voltage: 110V DC, Contacts: 6NO, S/R, Flag: No


Relay, Contactor RXMS1
52B ABB, India Case Size: 2U 6C Boughtout Front Mount 1
CB CLOSE MUX. RELAY RK 216 263-AN

E Aux Voltage: 110V DC, Contacts: 6NO, S/R, Flag: No E


Relay, Contactor RXMS1
LCCX ABB, India Case Size: 2U 6C Boughtout Front Mount 1
GAS COMPT. ZONE TRIP MUX. RK 216 263-AN

Aux Voltage: 110-125V DC, Contacts: 2NO+2NC, S/R, Flag: No


Relay, Contactor RXME1
DCCO ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 221 052-AN

Relay Frame With Base, RHGX-19" Rack


Accessory- Relay, Contactor RHGX
CASE ABB, India Case Size: 4U 60C Boughtout Front Mount 1
RHGX-19" Rack YN1M 251 263-PA

Contacts: 2NO
Push Button 3SB5
PB.86.1 Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
3SB5 3SB50 00-0AB01+3SB54 00-0E

F F
QT Corrected 7/12/2022 HRD Date 5/12/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) E 102R 1 mm. : 1 mm.
Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. Bill of Materials SIK SS04 E10202
Customer Cmnts. 12/17/2021 BST Chkd By HEM A Sh. 02 of 6
(3)G719EA-JG9127-E102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Equipment List 3005082555 <01 03>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.0-3/8/2018


E-Base Version: 7.0.0.1257

Sheet Version: V 1.0

DESIGNATION DETAILS MANUFACTURER MODEL DESCRIPTION DIS MOUNTING QUANTITY


A A
Contacts: 2NO
Push Button 3SB5
PB.86.2 Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
3SB5 3SB50 00-0AB01+3SB54 00-0E

Contacts: 2NO
Push Button 3SB5
PB.96 Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
3SB5 3SB50 00-0AB01+3SB54 00-0E

Relay Test Block, Type:MPG


Test Block MPG
BLK-50Z Alstom, India Boughtout Front Mount 1
MPG MPG

Relay Test Block, Type:MPG


Test Block MPG
BLK-67/67N Alstom, India Boughtout Front Mount 1
MPG MPG
B B
Relay Test Block, Type:MPG
Test Block MPG
BLKA-87L Alstom, India Boughtout Front Mount 1
MPG MPG

Relay Test Block, Type:MPG


Test Block MPG
BLKB-87L Alstom, India Boughtout Front Mount 1
MPG MPG

2 Positions, 10 Ways, Handle Type: Pistol Grip, Stayput


Switch SWI
CSS Switron, India Non-Lockable, Positions: In-Out Boughtout Front Mount 1
IN-OUT Switch SWI
POS1 (0°): IN-5Ways, POS2 (+90°): OUT-5Ways
3 Positions, 15 Ways, Handle Type: Pistol Grip, Spring Return To Neutral
Switch SWI
CS52 Switron, India Non-Lockable, Postions: Trip (T)-Neutral (N)-Close (C) Boughtout Front Mount 1
CB Control Switch SWI
POS1 (-45°): T-10Ways, POS 2 (0°): N-1Ways, POS3 (+45°): C-4Ways
C C
Last Used by: z004cv6p

3P4W, Type: Link, Connection Type: Back


Test Terminal Block NW34LBC
TTB-EM Nelster, India Boughtout Front Mount 1
Time: 5:29:49 PM

NW NW34LBC
Date: 7/18/2022

Aux Voltage: 110V DC


Resistor RXTMA1
RU.1 ABB, India Case Size: 2U 6C, With 4x150Ω 5W Resistors, Used With RXMVB2 Relay Boughtout Front Mount 1
RXTMA INRK 711 004-AA

Aux Voltage: 110V DC


Resistor RXTMA1
RU.2 ABB, India Case Size: 2U 6C, With 4x150Ω 5W Resistors, Used With RXMVB2 Relay Boughtout Front Mount 1
RXTMA INRK 711 004-AA

Aux Voltage: 110V DC


Resistor RXTMA1
RU.3 ABB, India Case Size: 2U 6C, With 4x150Ω 5W Resistors, Used With RXMVB2 Relay Boughtout Front Mount 1
RXTMA INRK 711 004-AA
D D
Rating: 16A, 240V AC
Panel Accessory 38499
HTS Anchor, India Boughtout Internal Mount 1
ON/OFF Switch 38499

Rating: 30-90°C, 240V AC


Panel Accessory TH3090
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 E102 03

TH APT Control, India Boughtout Internal Mount 1


Thermostat TH3090240VAC

Solid Link With Holder


Link Holder+Link 3NW
1LKDCCO-1 Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL
CopyRight (C) Siemens Limited, India All Rights Reserved.

Solid Link With Holder


Link Holder+Link 3NW
1LKDCCO-2 Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

E Solid Link With Holder E


Link Holder+Link 3NW
2LKDCCO-1 Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
2LKDCCO-2 Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
ETL-1 Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
ETL-2 Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

F F
QT Corrected 7/12/2022 HRD Date 5/12/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) E 102R 1 mm. : 1 mm.
Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. Bill of Materials SIK SS04 E10203
Customer Cmnts. 12/17/2021 BST Chkd By HEM A Sh. 03 of 6
(3)G719EA-JG9127-E102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Equipment List 3005082555 <02 04>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.0-3/8/2018


E-Base Version: 7.0.0.1257

Sheet Version: V 1.0

DESIGNATION DETAILS MANUFACTURER MODEL DESCRIPTION DIS MOUNTING QUANTITY


A A
Solid Link With Holder
Link Holder+Link 3NW
ETL-3 Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
ETL-4 Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
LK-67/67N-N Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
LK-87L-N Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL
B B
Solid Link With Holder
Link Holder+Link 3NW
LK-BCU-N Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
LK-BVT1-N Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
LK-BVT-N Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

Rating: 10A
Fuse Holder+Fuse 3NW
FS1-TC1 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10
C C
Last Used by: z004cv6p

Rating: 10A
Fuse Holder+Fuse 3NW
FS1-TC2 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
Time: 5:30:00 PM

3NW 3NW20NNSF+3NWNS10
Date: 7/18/2022

Rating: 10A
Fuse Holder+Fuse 3NW
FS2-TC1 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10

Rating: 10A
Fuse Holder+Fuse 3NW
FS2-TC2 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10

Rating: 16A
Fuse Holder+Fuse 3NW
FS1-AC Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16
D D
Rating: 16A
Fuse Holder+Fuse 3NW
FS1-LCC1 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16

Rating: 16A
Fuse Holder+Fuse 3NW
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 E102 04

FS1-LCC2 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1


3NW 3NW20NNSF+3NWNS16

Rating: 16A
Fuse Holder+Fuse 3NW
FS1-LCCAC Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16
CopyRight (C) Siemens Limited, India All Rights Reserved.

Rating: 16A
Fuse Holder+Fuse 3NW
FS2-AC Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16

E Rating: 16A E
Fuse Holder+Fuse 3NW
FS2-LCC1 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16

Rating: 16A
Fuse Holder+Fuse 3NW
FS2-LCC2 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16

Rating: 16A
Fuse Holder+Fuse 3NW
FS2-LCCAC Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16

Rating: 2A
Fuse Holder+Fuse 3NW
FS-67/67N-B Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS2

F F
QT Corrected 7/12/2022 HRD Date 5/12/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) E 102R 1 mm. : 1 mm.
Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. Bill of Materials SIK SS04 E10204
Customer Cmnts. 12/17/2021 BST Chkd By HEM A Sh. 04 of 6
(3)G719EA-JG9127-E102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Equipment List 3005082555 <03 05>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.0-3/8/2018


E-Base Version: 7.0.0.1257

Sheet Version: V 1.0

DESIGNATION DETAILS MANUFACTURER MODEL DESCRIPTION DIS MOUNTING QUANTITY


A A
Rating: 2A
Fuse Holder+Fuse 3NW
FS-67/67N-R Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-67/67N-Y Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-87L-B Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-87L-R Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS2
B B
Rating: 2A
Fuse Holder+Fuse 3NW
FS-87L-Y Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-BCU-B Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-BCU-R Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-BCU-Y Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS2
C C
Last Used by: z004cv6p

Rating: 2A
Fuse Holder+Fuse 3NW
FS-BVT1-R Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
Time: 5:30:11 PM

3NW 3NW20NNSF+3NWNS2
Date: 7/18/2022

Rating: 2A
Fuse Holder+Fuse 3NW
FS-BVT-R Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS2

Rating: 4A
Fuse Holder+Fuse 3NW
FS1-50Z Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS4

Rating: 4A
Fuse Holder+Fuse 3NW
FS1-67 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS4
D D
Rating: 4A
Fuse Holder+Fuse 3NW
FS1-86.1 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS4

Rating: 4A
Fuse Holder+Fuse 3NW
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 E102 05

FS1-86.2 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1


3NW 3NW20NNSF+3NWNS4

Rating: 4A
Fuse Holder+Fuse 3NW
FS1-87L Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS4
CopyRight (C) Siemens Limited, India All Rights Reserved.

Rating: 4A
Fuse Holder+Fuse 3NW
FS1-BCU Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS4

E Rating: 4A E
Fuse Holder+Fuse 3NW
FS2-21 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS4

Rating: 4A
Fuse Holder+Fuse 3NW
FS2-50Z Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS4

Rating: 4A
Fuse Holder+Fuse 3NW
FS2-67 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS4

Rating: 4A
Fuse Holder+Fuse 3NW
FS2-86.1 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS4

F F
QT Corrected 7/12/2022 HRD Date 5/12/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) E 102R 1 mm. : 1 mm.
Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. Bill of Materials SIK SS04 E10205
Customer Cmnts. 12/17/2021 BST Chkd By HEM A Sh. 05 of 6
(3)G719EA-JG9127-E102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Equipment List 3005082555 <04 06>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.0-3/8/2018


E-Base Version: 7.0.0.1257

Sheet Version: V 1.0

DESIGNATION DETAILS MANUFACTURER MODEL DESCRIPTION DIS MOUNTING QUANTITY


A A
Rating: 4A
Fuse Holder+Fuse 3NW
FS2-86.2 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS4

Rating: 4A
Fuse Holder+Fuse 3NW
FS2-BCU Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS4

Rating: 32A
Fuse Holder+Fuse 3NW
FS1-DC1 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS32

Rating: 32A
Fuse Holder+Fuse 3NW
FS1-DC2 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS32
B B
Rating: 32A
Fuse Holder+Fuse 3NW
FS2-DC1 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS32

Rating: 32A
Fuse Holder+Fuse 3NW
FS2-DC2 Siemens, India Aux Voltage: XX V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS32

Rating: 100W, 240V AC


Panel Accessory SH100
HT APT Control, India Boughtout Internal Mount 1
Space Heater SH100W240

Rating: 18W, 240V AC, Type: CFL


Panel Accessory CFL
CFL Philips, India Boughtout Internal Mount 1
Cubicle Illumination CFL18W
C C
Last Used by: z004cv6p

Rating: 16A & 6A, 3PIN, 240V AC


Panel Accessory 38819
PS Anchor, India Boughtout Internal Mount 1
Time: 5:30:22 PM

Power Socket With Switch 38819


Date: 7/18/2022

R1=R2=R3=R4=3.3K–25W
Resistor SURE
RU Sure, India Silicon Coated Radial Terminal Wire Wound Resistors With Assembly Boughtout Internal Mount 1
Resistor For BCU SSRA
Assembled On “Hylem” Plate With 10 Way Terminal Connector
Contacts: 1NO+2NC
Panel Accessory 3SE3
CFLS Siemens, India Boughtout Internal Mount 1
Limit Switch 3SE3023-0A

D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 E102 06
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
QT Corrected 7/12/2022 HRD Date 5/12/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) E 102R 1 mm. : 1 mm.
Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. Bill of Materials SIK SS04 E10206
Customer Cmnts. 12/17/2021 BST Chkd By HEM A Sh. 06 of 6
(3)G719EA-JG9127-E102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Equipment List 3005082555 <05 ->
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

A A
SI DG CS&D
General Arrangement

B B

C C
Customer
Last Used by: z004cv6p

GOVT. OF SIKKIM
Time: 5:28:00 PM
Date: 7/18/2022

Consultant
POWER GRID CORPORATION OF INDIA
LTD.

Project
D
SIK SS04 D

Substation
132/66kV SAMARDONG S/S
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 F102 01

Contractor
CopyRight (C) Siemens Limited, India All Rights Reserved.

LoA No.
E LOA/PGCIL SIKKIM-SS04/16-17/CRP & SAS/02 E

Title
BAY-102 (LINE-2)

Drawing No. Revision


(3)G719EA-JG9127-F102 A

F F
C QT Corrected 7/12/2022 HRD Date 5/19/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) Customer Dwg No. P2 F 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. Front View SIK SS04 F10201
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 01 of 4
3005082555 (3)G719EA-JG9127-F102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: General Arrangement < 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-0.1-1/10/2012
Sheet Version: 0.1
E-Base Version: 7.0.0.1257

FRONT VIEW

A A
PANEL NAME PLATE S. NO. ▲2 DESIGN. DESCRIPTION TYPE MANUFACTURER
1 BCU Bay Control Unit 6MD85 Siemens, Germany
132kV PROTECTION PANEL
1U
2 CASE RHGX-19" Rack RHGX ABB, India

LINE-2 (BAY-102) 3 50Z LBB Protection Relay 7VK61 Siemens, Germany

LCCX

80.2
86.1

86.2

52A
96
4 67/67N DIR. OC & EF Protn. 7SJ66 Siemens, India
PANEL REF:102R
4U
CASE

5 87L Line Diff. Protn. 7SD52 Siemens, Germany

DCCO

50ZX
RU.1

RU.2

RU.3
95.1

95.2

95.3

80.1

52B
6 50ZX LBB MUX. RELAY RXMS1 ABB, India
1U

7 52A CB TRIP MUX. RELAY RXMS1 ABB, India


8 52B CB CLOSE MUX. RELAY RXMS1 ABB, India
9 80.1 DC Supervision Relay TSR ABB, India

87L 67/67N 10 80.2 DC Supervision Relay TSR ABB, India


B B
7U

11 86.1 Trip Relay RXMVB2 ABB


12 86.2 Trip Relay RXMVB2 ABB
13 95.1 Supervision Relay TSR ABB, India
14 95.2 Supervision Relay TSR ABB, India
CS52 CSS
15 95.3 Supervision Relay TSR ABB, India
3U

16 95.A TC-1 Supervision Relay 7PJ13 Siemens, India

PB.86.1PB.96 PB.86.2 17 95.B TC-2 Supervision Relay 7PJ13 Siemens, India


1U

18 96 Trip Relay RXMVB2 ABB


19 DCCO Auxiliary Relay RXME1 ABB, India
20 LCCX GAS COMPT. ZONE TRIP MUX. RXMS1 ABB, India
21 RU.1 RXTMA RXTMA1 ABB, India
C 22 RU.2 RXTMA RXTMA1 ABB, India C
7U
Last Used by: z004cv6p

BCU BCU BCU BCU


23 RU.3 RXTMA RXTMA1 ABB, India
Time: 9:15:14 PM

24 CS52 CB Control Switch SWI Switron, India


Date: 7/18/2022

2200

25 CSS IN-OUT Switch SWI Switron, India


2315

26 PB.86.1 3SB5 3SB5 Siemens, India


1U

27 PB.86.2 3SB5 3SB5 Siemens, India


28 PB.96 3SB5 3SB5 Siemens, India
29 BLK-50Z MPG MPG Alstom, India
30 BLK-67/67N MPG MPG Alstom, India
50Z
EM** 31 BLKA-87L MPG MPG Alstom, India
10U

32 BLKB-87L MPG MPG Alstom, India


33 TTB-EM NW NW34LBC Nelster, India
D D

BLK-50Z
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 F102 02

1U
3U

BLK-67/67N BLKA-87L
15.00mm Anti Vibration Pad
CopyRight (C) Siemens Limited, India All Rights Reserved.

3U

TTB-EM BLKB-87L

E E
3U

95.A 95.B

NOTE:**EM is not in siemens scope of supply.


Dimension shall be 250(W)X350(H).
100

800

F F
C QT Corrected 7/12/2022 HRD Date 5/19/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) Customer Dwg No. P2 F 102R 1 mm. : 10 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. Front View SIK SS04 F10202
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 02 of 4
3005082555 (3)G719EA-JG9127-F102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: General Arrangement <01 03>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-0.1-1/10/2012
Sheet Version: 0.1
E-Base Version: 7.0.0.1257

SIDE VIEW
A A

275
400

80
SLOT FOR BUS WIRING

B B

C C
Last Used by: z004cv6p

TOP VIEW
FRONT
Time: 5:28:21 PM

800
Date: 7/18/2022

2200
120 249 62 249 120

2315
100 Ø14.0 HOLES (4x)

127
25
D D

519
800
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 F102 03
CopyRight (C) Siemens Limited, India All Rights Reserved.

15mm Anti Vibration Pad

154
E 121
E
12

EARTH BUSBAR SLOT

54
SWING FRAME

65
OUTER FULL TOUGHNED GLASS/
0

PERSPEX SHEET HINGE DOOR


100

800
827
FRONT
F F
C QT Corrected 7/12/2022 HRD Date 5/19/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) Customer Dwg No. P2 F 102R 1 mm. : 10 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. Side & Top View SIK SS04 F10203
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 03 of 4
3005082555 (3)G719EA-JG9127-F102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: General Arrangement <02 04>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-0.1-1/10/2012
Sheet Version: 0.1
E-Base Version: 7.0.0.1257
SWING DOOR INTERNAL VIEW
REAR VIEW 135.00

A A
CFL
RH1
CFLS
LH1

MH1

XB:AC(1-5) XB:DC2(1-3) XB:VT(1-20)


FH1

XB:DC1

XB:DC2
XB:AC

XB:BB

XB:VT
XB:DC1

XB:DC1

XB:DC1

XB:DC2

XB:DC2

XB:DC2
XB:AC

XB:AC

XB:AC

XB:AC

XB:AC

XB:BB

XB:BB

XB:BB

XB:BB

XB:BB

XB:BB

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT
10

11

12

13

14

15

16

17

18

19

20
LHMR1 RH1

9
LCCX
80.2

86.2

86.1
52A
BHMR1

96
XB:DC1(1-3) XB:BB(1-6)
MH2
LH2 RH2

CASE

DCCO
50ZX
RU.3

RU.2

RU.1
80.1

95.3

95.2

95.1
52B
BHMR2

BUS WIRING SLOT BUS WIRING SLOT


FH2 MH3

1LKDCCO-1
1LKDCCO-2
2LKDCCO-1
2LKDCCO-2
FS-BVT1-R
LK-BVT1-N
FS-BCU-R

LK-BCU-N
FS-BCU-Y
FS-BCU-B

FS-BVT-R
LK-BVT-N
LH3 RH3

ETL-1
ETL-2
ETL-3
ETL-4
BHMR3

LHMR2 RH2

67/67N 87L
B MNPL3
B
LH4 RH4

MH4

FS-67/67N-R
FS-67/67N-Y
FS-67/67N-B
LK-67/67N-N
FS1-LCCAC
FS2-LCCAC
FS1-LCC1
FS2-LCC1
FS1-LCC2
FS2-LCC2

FS-87L-R
FS-87L-Y
FS-87L-B
LK-87L-N
FS1-TC1
FS2-TC1
FS1-TC2
FS2-TC2

HTS

TH
PS
CSS CS52 RU LHMR3 BHMR4 RH3

FH3

MNPL2

PB.86.2 PB.96PB.86.1 LH5 RH5

MH5

FH4

FS1-BCU
FS2-BCU
FS1-DC1
FS2-DC1
FS1-DC2
FS2-DC2

FS1-86.1
FS2-86.1
FS1-86.2
FS2-86.2
FS1-50Z
FS2-50Z

FS1-87L
FS1-AC
FS2-AC

FS1-67
FS2-67

FS2-21
LHMR4 RH4
BHMR5

MNPL1

C C
Last Used by: z004cv6p

BCU BCU BCU BCU


LH6 RH6

MH6
Time: 9:15:46 PM

LV1

MV1 MV2
Date: 7/18/2022

FV1 FV2

X:DC2 (1-3) X:AC (1-3)

X:SP (1-5)
X:AC
X:AC X:SP
3
X:SP
X:AC
5
2

X:CT (1-50) X:DC1 (1-3)


X:SP
X:AC
4
FH5 1
X:SP
3
X:DC1 X:SP
2
X:DC1
X:SP
3
1
X:DC1
2

X:CB (1-12)
X:DC1
X:CB
1
X:CB
12
X:DC2 X:CB
11
X:DC2
X:CB
3
10
X:DC2
X:CB
2
9
X:DC2
X:CB
1
8
X:CB
X:CT 7
X:CB
X:CT 6
50

X:LCC (1-68)
X:CB
5 X:LCC
X:CT
X:CB
49 X:LCC
4
68
X:CB
X:CT X:LCC
3
48 67
X:CB
X:LCC
2
X:CT 66
47 X:CB
X:LCC

X:DPC (1-8)
1
65
X:CT
X:LCC

50Z X:DPC
46
64
X:LCC
X:CT X:DPC 63
45 8
X:LCC
X:DPC 62
X:CT 7

X:ISL (1-60)
44
X:DPC X:ISL X:LCC

EM**
61
6
X:CT X:ISL X:LCC
43 X:DPC 60 60
5
X:ISL X:LCC
X:CT X:DPC 59 59
42 4
X:ISL X:LCC
X:DPC 58 58
X:CT 3
X:ISL X:LCC
41 X:DPC 57 57
2
X:ISL X:LCC
X:CT X:DPC 56 56
40 1
X:ISL X:LCC
55 55
X:CT
39 X:TC1 X:ISL X:LCC
54 54

X:TC1 (1-8)
X:TC1
X:CT 8 X:ISL X:LCC
38 53 53

D D
X:TC1
7 X:ISL X:LCC
X:CT 52 52
37 X:TC1
6 X:ISL X:LCC
51 51
X:CT X:TC1
5 X:ISL X:LCC
36
50 50
X:TC1
4 X:ISL X:LCC
X:CT
49 49
35 X:TC1
3 X:ISL X:LCC
48 48
X:CT X:TC1
34 2 X:ISL X:LCC
47 47
X:TC1
X:CT X:ISL X:LCC

X:TC2 (1-8)
1
33 46 46
RV2
X:CT X:TC2 X:ISL
45
X:LCC
45
32
X:ISL X:LCC
X:TC2
44 44
8
X:CT
X:ISL X:LCC
31 X:TC2
43 43
7
LVMR1 LV2 BVMR1 MV4 BVMR2 MV3 BVMR3 RV3 RV1 RV1 RV2
X:ISL X:LCC
X:CT X:TC2
42 42
30 6

BLK-50Z X:CT
29
X:TC2
5
X:TC2
4
X:ISL
41
X:ISL
40
X:LCC
41
X:LCC
40
X:CT X:ISL X:LCC
X:TC2
28 39 39
3
X:ISL X:LCC
X:TC2
X:CT 38 38
2
27
X:ISL X:LCC
X:TC2
37 37
1
X:CT
X:ISL X:LCC
26

X:C (1-12)
X:C 36
X:ISL
36
X:LCC
X:CT
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 F102 04

X:C 35 35
25
12 X:ISL X:LCC
X:C 34 34
X:CT
24 11 X:ISL X:LCC
X:C 33 33
X:CT 10 X:ISL X:LCC
FH6 23 X:C
9
32
X:ISL
32
X:LCC
X:CT X:C 31 31
22 8 X:ISL X:LCC
X:C 30 30
X:CT 7 X:ISL X:LCC
21
X:C 29 29
6 X:ISL X:LCC
X:CT
X:C 28 28
20
5 X:ISL X:LCC
X:C 27 27
X:CT
19 4 X:ISL X:LCC
X:C 26 26
X:CT 3 X:ISL X:LCC
18 X:C 25 25
2 X:ISL X:LCC

BLKA-87L BLK-67/67N
X:CT X:C 24 24
17 1 X:ISL X:LCC
23 23

X:CVT (1-15)
X:CT
16 X:CVT X:ISL
22
X:LCC
22
X:ISL X:LCC
X:CT X:CVT
21 21
15 15
X:ISL X:LCC
X:CT X:CVT 20 20
14 14 X:ISL X:LCC
19 19
X:CT X:CVT X:ISL X:LCC
13 13 18 18
X:ISL X:LCC
X:CT X:CVT 17 17
CopyRight (C) Siemens Limited, India All Rights Reserved.

12 12
X:ISL X:LCC
16 16

FH7 X:CT
11
X:CVT
11
X:ISL
15
X:LCC
15
X:ISL X:LCC
X:CT X:CVT
14 14
10 10
X:ISL X:LCC
13 13
X:CT X:CVT
9 9 X:ISL X:LCC
12 12
X:CT X:CVT X:ISL X:LCC
8 8 11 11
X:ISL X:LCC

BLKB-87L
X:CT X:CVT 10 10
7 7
X:ISL X:LCC

TTB-EM X:CT
6

X:CT
X:CVT
6

X:CVT
9
X:ISL
8
X:ISL
7
9
X:LCC
8
X:LCC
7
5 5
X:ISL X:LCC
6 6
X:CT X:CVT
4 4 X:ISL X:LCC
5 5
X:CT X:CVT X:ISL X:LCC
3 3 4 4
X:ISL X:LCC

E E
X:CT X:CVT 3 3
2 2
X:ISL X:LCC
2 2
X:CT X:CVT
X:ISL X:LCC
1 1
FH8 1 1

95.B 95.A

E-BB

123.00
FH10
HT

0
100

155.00 510.00 135.00

15
800

F F
C QT Corrected 7/12/2022 HRD Date 5/19/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) Customer Dwg No. P2 F 102R 1 mm. : 10 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. Internal Layout SIK SS04 F10204
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 04 of 4
3005082555 (3)G719EA-JG9127-F102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: General Arrangement <03 ->
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

A A
SI DG CS&D
Wiring Schematics

B B

C C
Customer
Last Used by: z004cv6p

GOVT. OF SIKKIM
Time: 5:30:32 PM
Date: 7/18/2022

Consultant
POWER GRID CORPORATION OF INDIA
LTD.

Project
D
SIK SS04 D

Substation
132/66kV SAMARDONG S/S
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 01

Contractor
CopyRight (C) Siemens Limited, India All Rights Reserved.

LoA No.
E LOA/PGCIL SIKKIM-SS04/16-17/CRP & SAS/02 E

Title
BAY-102 (LINE-2)

Drawing No. Revision


(3)G719EA-JG9127-W102 A

F F
C QT Corrected 7/12/2022 HRD Date 3/20/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. Front View SIK SS04 W10201
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 01 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics < 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

PANEL PANEL
SHEET NO. DESCRIPTION DRAWING NUMBER SHEET NO. DESCRIPTION DRAWING NUMBER
A REFERENCE REFERENCE A
Front View 50Z MULTI. CKT.
01 (3)G719EA-JG9127-W101 101R 21 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
List of Documents GR-A 3-PH TRIP RELAY
02 (3)G719EA-JG9127-W101 101R 22 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
List of Documents GR-B 3-PH TRIP RELAY
03 (3)G719EA-JG9127-W101 101R 23 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
LIST OF REFERENCE DRAWINGS 96 TRIP RELAY
04 (3)G719EA-JG9127-W101 101R 24 (3)G719EA-JG9127-W101 101R
B Wiring Schematics Wiring Schematics B
LEGENDS CB CLOSE & TRIP CONTACT MULTI.
05 (3)G719EA-JG9127-W101 101R 25 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
SYSTEM SLD CT AND VT CIRCUIT FOR BCU
06 (3)G719EA-JG9127-W101 101R 26 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
PROTECTION SLD BINARY INPUT CIRCUIT FOR BCU
07 (3)G719EA-JG9127-W101 101R 27 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
TRIP MATRIX VT SELCTION LOGIC
08 (3)G719EA-JG9127-W101 101R 28 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
C C
Last Used by: z004cv6p

Cover Sheet VT SELECTION & ENERGY METER CKT


09 (3)G719EA-JG9127-W101 101R 29 (3)G719EA-JG9127-W101 101R
Time: 5:30:40 PM
Date: 7/18/2022

Wiring Schematics Wiring Schematics


CT CORE DISTRIBUTION ISOL. INTERLOCK LOGIC
10 (3)G719EA-JG9127-W101 101R 30 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
CT INPUT CIRCUIT ISOL & E/SW CONTROL CKT
11 (3)G719EA-JG9127-W101 101R 31 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
CVT CORE DISTRIBUTION ISOL & E/SW CONTROL CKT
12 (3)G719EA-JG9127-W101 101R 32 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
D D
BUS VT DISTRIBUTION CB TC-1 CKT
13 (3)G719EA-JG9127-W101 101R 33 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
DC DISTRIBUTION CIRCUIT CB TC-2 CKT
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 02

14 (3)G719EA-JG9127-W101 101R 34 (3)G719EA-JG9127-W101 101R


Wiring Schematics Wiring Schematics
AC DISTRIBUTION CIRCUIT CB MANUAL TRIP & CLOSE CKT
15 (3)G719EA-JG9127-W101 101R 35 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
CopyRight (C) Siemens Limited, India All Rights Reserved.

CT AND VT CIRCUIT FOR 87L BCU INPUT CKT. FOR LCC


16 (3)G719EA-JG9127-W101 101R 36 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
E BINARY INPUT CIRCUIT 87L BCU INPUT CKT. FOR LCC E
17 (3)G719EA-JG9127-W101 101R 37 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
CT AND VT CIRCUIT FOR 67/67N BCU INPUT CKT. FOR LCC
18 (3)G719EA-JG9127-W101 101R 38 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
BINARY INPUT CIRCUIT FOR 67/67N BB INTERFACING CKT.
19 (3)G719EA-JG9127-W101 101R 39 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics
CT AND BI CIRCUIT FOR 50Z PLCC CH-1/2 CIRCUIT
20 (3)G719EA-JG9127-W101 101R 40 (3)G719EA-JG9127-W101 101R
Wiring Schematics Wiring Schematics

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 3/20/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) 0000 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. List of Documents SIK SS04 W10202
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 02 of 52
(3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics 3005082555 <01 03>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

PANEL PANEL
SHEET NO. DESCRIPTION DRAWING NUMBER SHEET NO. DESCRIPTION DRAWING NUMBER
A REFERENCE REFERENCE A
SWITCH & BLOCK CONTACT DISTRIBUTION
41 (3)G719EA-JG9127-W101 101R
Wiring Schematics
Cover Sheet
42 (3)G719EA-JG9127-W101 101R
Wiring Schematics
CONNECTION DIAGRAM FOR 87L
43 (3)G719EA-JG9127-W101 101R
Wiring Schematics
CONNECTION DIAGRAM FOR 67/67N
44 (3)G719EA-JG9127-W101 101R
B Wiring Schematics B
CONNECTION DIAGRAM FOR 50Z
45 (3)G719EA-JG9127-W101 101R
Wiring Schematics
CONNECTION DIAGRAM FOR BCU
46 (3)G719EA-JG9127-W101 101R
Wiring Schematics
CONNECTION DIAGRAM FOR BCU
47 (3)G719EA-JG9127-W101 101R
Wiring Schematics
CONNECTION DIAGRAM FOR BCU
48 (3)G719EA-JG9127-W101 101R
Wiring Schematics
C C
Last Used by: z004cv6p

CONNECTION DIAGRAM FOR BCU


49 (3)G719EA-JG9127-W101 101R
Time: 5:30:55 PM
Date: 7/18/2022

Wiring Schematics
BI & BO LIST FOR 87L,50Z & 67/67N
50 (3)G719EA-JG9127-W101 101R
Wiring Schematics
BI & BO LIST FOR BCU
51 (3)G719EA-JG9127-W101 101R
Wiring Schematics
BI & BO LIST FOR BCU
52 (3)G719EA-JG9127-W101 101R
Wiring Schematics
D D
LIST OF GOOSE MESSAGE
53 (3)G719EA-JG9127-W101 101R
Wiring Schematics
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 03
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 3/20/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) 0000 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. List of Documents SIK SS04 W10203
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 03 of 52
(3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics 3005082555 <02 04>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

A A

B B

400KV
PRIMARY EQUIPMENTS DRAWING NO MAKE OF THE EQUIPMENTS
SLD C/ENGG/NER/ARP/NAHARLAGUN/SLD/001 PGCIL
CAPACITIVE VOLTAGE TRANSFORMER 3-CAO 10135 CGL
PLCC NA ─
TRANSFORMER C600 0139, C6000/40-R1 PRIME MEIDEN
C LCC ZF40-145/T2 500-40 JIANGSU JIUGKE SMART ELECTRIC CO-LTD. C
Last Used by: z004cv6p

Time: 5:31:08 PM
Date: 7/18/2022

D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 04
CopyRight (C) Siemens Limited, India All Rights Reserved.

E **NOTE:INPUTS ARE NOT AVAILAABLE. E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 3/20/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. LIST OF REFERENCE DRAWINGS SIK SS04 W10204
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 04 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <03 05>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

SYMBOL & DESCRIPTION SYMBOL & DESCRIPTION SYMBOL & DESCRIPTION

A A
L+ L-
HOOTER

CAPACITIVE VOLTAGE TRANSFORMER

POWER SUPPLY
BELL
CIRCUIT BREAKER

-S
ISOLATOR
PUSH BUTTON
B B

CURRENT TRANSFORMER

STABLIZING RESISTOR

SURGE ARRESTER

VARIASTOR
EARTH BAR

C SWITCH CONTACT C
Last Used by: z004cv6p

WAVE TRAP
Time: 5:31:16 PM
Date: 7/18/2022

SOCKET
FUSE

1S2

1S2

1S2
I II III
LINK

1S2

1S2

1S2
CURRENT TRANSFORMER SECONDARY

DISCONNECTING TERMINAL
D D

NON-DISCONNECTING TERMINAL OPERATING COIL


132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 05

RELAY TEST BLOCK


CopyRight (C) Siemens Limited, India All Rights Reserved.

CURRENT COIL

OPEARTING/REST COIL

E LATCHED CONTACT-NO E

I> I>
LATCHED CONTACT-NC

MCB

SPACE HEATER

FLOURCENT LAMP BINARY INPUT


F Unless otherwise specified, wires are PVC 1.5 GY F
C QT Corrected 7/12/2022 HRD Date 3/20/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. LEGENDS SIK SS04 W10205
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 05 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <04 06>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

A A

132kV MAIN BUS-I


B (31.5kA, 1s) B

132kV MAIN BUS-II


(31.5kA, 1s)
106-89PTAE 106-89PTBE
104-89BCB 104-89BCA
101-89B 101-89A 102-89B 102-89A 103-89B 103-89A 105-89B 10589A 106-89PTA 106-89PTB 107-89B 107-89A 108-89B 108-89A
104-89BCBE
101-89AE 102-89AE 103-89AE 104-89BCAE 105-89AE 107-89AE 108-89AE
P2 P2
C3 C4 BUS VT-1 BUS VT-2
P2 P2 P2 CT P2 P2
C2 C5 P2
C3 C3 C3 104-CTA 104-CTB C3 C3
C3
C C1 C
Last Used by: z004cv6p

C2 101-CTA C2 102-CTA C2 103-CTA P1 P1 C2 105-CTA C2 107-CTA C2 108-CTA


C1 C1 C1 104-52 C1 C1 C1
Time: 5:31:26 PM
Date: 7/18/2022

P1 P1 P1 P1 P1 P1
BUS COUPLER
101-52 102-52 103-52 105-52 107-52 108-52
P1 P1 P1 P1 P1 P1
C1 C1 C1 C1 C1 C1
101-CTB 102-CTB 103-CTB 105-CTB 107-CTB 108-CTB
C2 C2 C2 C2 C2 C2
P2 P2 P2 P2 P2 P2
101-89LE2 102-89LE2 103-89TE2 105-89TE2 107-89LE2 108-89LE2

101-89L 102-89L 103-89T 105-89T 107-89L 108-89L

101-89LE1 102-89LE1 103-89TE1 105-89TE1 107-89LE1 108-89LE1


D 132kV GIS D

101-PT 102-PT 107-PT 108-PT


132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 06

101-LA 102-LA 107-LA 108-LA


CopyRight (C) Siemens Limited, India All Rights Reserved.

BAY-101 BAY-102 BAY-107 BAY-108 ICT-3 SINGHIK SINGHIK


66kV SIDE ICT-1 66kV SIDE ICT-2
FUTURE FUTURE FUTURE
RANGPO(PG) D/C LINE BAY-103 BAY-105 DIKCHU POOL D/C LINE BAY-109 BAY-110 BAY-111

E E

132kV AIS

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 3/20/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. SYSTEM SLD SIK SS04 W10206
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 06 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <05 07>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 132kV MAIN BUS-1

A A
132kV MAIN BUS-2

102-89A 102-89B

102-89AE

P1
B S1 B
CORE-5 7SD52 87L
RATIO: 800-400/1A S2 Line Diff. Protn.
CLASS: PS

S1
CORE-4 7SJ66 67/67N
RATIO: 800-400/1A S2 DIR. OC & EF Protn.
CLASS: PS

S1
CORE-3 6MD85 BCU Premier300 EM**
RATIO: 800-400/1A S2 Bay Control Unit Energy Meter
CLASS: 02S

C C
Last Used by: z004cv6p

Time: 5:31:39 PM

102-52
Date: 7/18/2022

S1
CORE-2
RATIO: 800-400/1A SPARE
S2
CLASS: PS

S1 *
CORE-1 7VK61 50Z
RATIO: 800-400/1A S2 LBB Protection Relay
CLASS: PS
D D

102-89LE1
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 07

102-89L

102-89LE2
6MD85 BCU Premier300 EM**

CVT T3 Bay Control Unit Energy Meter


CopyRight (C) Siemens Limited, India All Rights Reserved.

T1 T1 7SJ66 67/67N
T2
DIR. OC & EF Protn.
E E
7SD52 87L*

LA Line Diff. Protn.

NOTE :**NOT IN SIEMENS SCOPE OF SUPPLY


DIKHU POOL D/C LINE-1
BAY-101 *BB relay shall be mounted in Busbar protection panel

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. PROTECTION SLD SIK SS04 W10207
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 07 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <06 09>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-0.1-1/10/2012
Sheet Version: 0.1
E-Base Version: 7.0.0.1257

A A

B B

C WIRING DIAGRAM C
Last Used by: z004cv6p

Time: 5:31:49 PM
Date: 7/18/2022

D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 09
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) 0000 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. Cover Sheet SIK SS04 W10209
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 09 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <07 10>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 132kV MAIN BUS-1

132kV MAIN BUS-2

A A

102-89A 102-89B

102-89AE

B B

LCC-102 102R

XTA 07 A111
/16.3
04
08 A131
/16.3
05 TO 87L CKT.

P2

P2

P2
CORE-5 1S3 1S3 1S3 09 A151
/16.3
C R-PH Y-PH B-PH C
Last Used by: z004cv6p

RATIO: 800-400/1A 1S1 1S1 1S1 01


CLASS: PS
Time: 5:32:06 PM
Date: 7/18/2022

P1

P1

P1
02 A171
/16.3

03

XTA 17 C111
/18.3
14
18 C131
/18.3
15
P2

P2

P2
TO 67/67N CKT.
CORE-4 1S3 1S3 1S3 19 C151
/18.3
R-PH Y-PH B-PH 16
D RATIO: 800-400/1A D
1S1 1S1 1S1 11
CLASS: PS
P1

P1

P1

12 C171
/18.3
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 10

13

XTA 27 D111
/26.3
24
CopyRight (C) Siemens Limited, India All Rights Reserved.

28 D131
/26.3
25
P2

P2

P2

TO BCU CKT.
CORE-3 1S2 1S2 1S2 29 D151
/26.3
E R-PH Y-PH B-PH 26 E
RATIO: 800-400/1A 1S1 1S1 1S1 21
CLASS: 0.2S
P1

P1

P1

22 D171
/26.3

23

LCC. DRG. NO. ZF40-145/T2500-40


R

B
Y

SHT. CR-L/T. 43
/11.3

/11.3

/11.4

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CT CORE DISTRIBUTION SIK SS04 W10210
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 10 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <09 11>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

/10.3

/10.3

/10.4
Y

B
R
A A

102-52
LCC-102

XTA 31

32
SPARE

P1

P1

P1
CORE-2 1S1 1S1 1S1 33
R-PH Y-PH B-PH
RATIO: 800-400/1A 1S2 1S3 1S3 37
B CLASS: PS B
34

P3

P2

P2
38
35
39
36
XTA 41 102R

42 B171
/20.3

P1

P1

P1
TO LBB PROTN. CKT.
CORE-1 1S1 1S1 1S1 43
R-PH Y-PH B-PH
RATIO: 800-400/1A 1S3 1S3 1S3 44 B111
CLASS: PS /20.3
C 47 C
Last Used by: z004cv6p

P2

P2

P2
45 B131
/20.3
Time: 5:32:33 PM

48
Date: 7/18/2022

46 B151
/20.3
49

LCC. DRG. NO. ZF40-145/T2500-40


SHT. CR-L/T. 44

D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 11

R
CopyRight (C) Siemens Limited, India All Rights Reserved.

/12.1

Y
/12.1

E B E
/12.1
LA

LA

LA

BAY-101
F DIKCHU POOL D/C LINE F
Unless otherwise specified, wires are PVC 1.5 GY
C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CT INPUT CIRCUIT SIK SS04 W10211
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 11 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <10 12>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

/11.4

/11.4

/11.4
A A

Y
R

B B

2S2

2S2

2S2

3S2

3S2

3S2
CVT CVT CVT CVT CVT CVT
WDG-2 WDG-2 WDG-2 WDG-3 WDG-3 WDG-3
1S2

1S2

1S2
CVT CVT CVT R-PH Y-PH B-PH R-PH Y-PH B-PH
WDG-1 WDG-1 WDG-1
R-PH Y-PH B-PH RATIO: 132kV/√3 / 110V/√3 RATIO: 132kV/√3 / 110V/√3
RATIO: 132kV/√3 / 110V/√3 CLASS: 3P CLASS: 0.2S

2S1

2S1

2S1

3S1

3S1

3S1
CLASS: 3P
1S1

1S1

1S1
C C
Last Used by: z004cv6p

Time: 5:33:10 PM
Date: 7/18/2022

PTMB
15

15

15
TB1 3 5 TB1 10 12 TB1 17 19 TB2 3 5 TB2 10 12 TB2 17 19 TB3 3 5 TB3 10 12 TB3 17 19
1

8
**

D D
102R 102R
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 12

10

11

12
1

9
X:CVT X:CVT X:CVT
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E
E111

E131

E151

E171

E211

E231

E251

E271

E311

E331

E351

E371
/16.3

/16.3

/16.3

/16.3

/18.3

/18.3

/18.3

/18.3

/26.2

/26.2

/26.2

/26.2
TO LINE DIFF. PROTN. TO DIR. O/C & E/F PROTN. TO BCU & EM CKT

** DETAILS NEED TO FINISH BY CUSTOMER.


F Unless otherwise specified, wires are PVC 1.5 GY F
C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CVT CORE DISTRIBUTION SIK SS04 W10212
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 12 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <11 13>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

103R 102R 101R

A A
BE511B1
/W101/13.2
BE511B1 XB:VT 1 E511B1
/W103/15.6 /29.2

BE531B1
/W101/13.2
BE531B1 XB:VT 2

CLASS: 0.2
/W103/15.6
Bus-1 VT
Core-3 TO VT SELECTION CKT.
BE551B1
/W101/13.2
BE551B1 XB:VT 3
/W103/15.6

BE571B1
/W101/13.2
BE571B1 XB:VT 4 E571B1
/W103/15.6 /29.2

B B

BE511B2
/W101/13.2
BE511B2 XB:VT 5 E511B2 /29.2
/W103/15.6

BE531B2
/W101/13.2
BE531B2 XB:VT 6
CLASS: 0.2

/W103/15.6
Bus-2 VT
Core-3

TO VT SELECTION CKT.
BE551B2
/W101/13.2
BE551B2 XB:VT 7
/W103/15.6
C C
Last Used by: z004cv6p

BE571B2
/W101/13.2
Time: 5:33:51 PM

BE571B2 XB:VT 8 E571B2


/W103/15.6 /29.2
Date: 7/18/2022

BE211
/W101/13.2
BE211 XB:VT 9 E211
/W103/15.6

BE231
/W101/13.2
BE231 XB:VT 10 E231
/W103/15.6 TO VT SELECTION CKT.
CLASS: 3P
Bus-1 VT
Core-2

BE251
D /W101/13.2 D
BE251 XB:VT 11 E251
/W103/15.6

BE271
/W101/13.2
BE271 XB:VT 12 E271
/W103/15.6
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 13

BE511
/W101/13.2
BE511 XB:VT 13 E511
/W103/15.6
CopyRight (C) Siemens Limited, India All Rights Reserved.

BE531
/W101/13.2
BE531 XB:VT 14 E531
/W103/15.6
TO VT SELECTION CKT.
CLASS: 3P
Bus-2 VT
Core-2

E BE551 E
/W101/13.2
BE551 XB:VT 15 E551
/W103/15.6

BE571
/W101/13.2
BE571 XB:VT 16 E571
/W103/15.6

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. BUS VT DISTRIBUTION SIK SS04 W10213
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 13 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <12 14>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257
+Unit 102R

X:DC1
-VE J102 XB:DC1 2

A 110V DC SUPPLY-1 2 A
J101 XB:DC1 1
+VE 1 LCC-102
X:C 2

2
FS1-LCC1

FS2-LCC1
FS1-86.1

FS2-86.1
FS1-DC1

FS2-DC1

FS1-TC1

FS2-TC1
FS1-87L

FS2-21
80.1

32A

32A

10A

10A

16A

16A
4A

4A

4A

4A
X:C 1 12 21
FOR FUTURE USE

1
11 13

1L+

1L-
K101

K102

K501

K502
K1T

K2T
X:C 3 X:C 4 16 15
/27.4
J103 17 TO BCU

1LKDCCO-1

1LKDCCO-2
/17.3

/17.3

/33.3

/33.3

/22.3

/22.4

2
LCC-102 26 25
/20.4
J104 X:ZL 01 X:ZL 09 27 TO 50Z RELAY
B B

1
TO DISTANCE TO CB TC-1 TO 86.1 RELAY
PROTN. CKT. CKT. CKT. DRG. NO. ZF40-145/T2
500-40-SHT. CR-L/T. 07

J105

DCCO
16 17
/14.6

J106

DCCO
26 27
/14.6
C C
Last Used by: z004cv6p

DCCO
Time: 5:34:23 PM

14 15 J11
Date: 7/18/2022

+Unit /14.6
DCCO
24 25 J12
-VE X:DC2 /14.6
J202 XB:DC2 2
2
110V DC SUPPLY-2
J201 XB:DC2 1 J206
+VE 1 LCC-102

2
X:C 6

FS1-BCU

FS2-BCU

FS1-50Z

FS2-50Z
Auxiliary Relay

4A

4A

4A

4A
DCCO
2

5 11 21

1
X:C J205
FS1-DC2

FS2-DC2
32A

32A

FOR FUTURE USE


D D
1

14 15
/14.5
24 25

K401

K402

K701

K702
/14.5
16 17
/14.5
26 27
/14.5

2LKDCCO-1

2LKDCCO-2
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 14

/25.2

/25.7

/20.3

/20.6
2

2
1

1
TO BCU & CB CKT. TO 50Z RELAY
CKT.
J203
CopyRight (C) Siemens Limited, India All Rights Reserved.

J204

E E
2

2
FS1-LCC2

FS2-LCC2

80.2
16A

16A
2

12 21
FS1-86.2

FS2-86.2
FS1-TC2

FS2-TC2
FS1-67

FS2-67

10A

10A
4A

4A

4A

4A

11 13
1

2L+

2L-

16 15
K51T

K52T
K201

K202

K601

K602

/27.4
X:C 7 X:C 8 17 TO BCU
LCC-102 26 25
/20.4
/19.3

/19.6

/34.3

/34.3

/23.2

/23.2

X:ZL 07 X:ZL 15 27 TO 50Z RELAY

DRG. NO. ZF40-145/T2


TO BACKUP TO CB TC-2 . CKT. TO 86.2 RELAY 500-40-SHT. CR-L/T. 07
PROTN. CKT. CKT.
F Unless otherwise specified, wires are PVC 1.5 GY F
C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. DC DISTRIBUTION CIRCUIT SIK SS04 W10214
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 14 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <13 15>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

A A
101R 102R 103R

BH1
/W103/14.3
BH1 XB:AC 1 H1
/W101/15.6

BH2
/W103/14.3
BH2 2 H2
/W101/15.6

B AC SUPPLY B
X:AC 1

FS1-LCCAC

FS2-LCCAC
2

2
FS1-AC

FS2-AC
16A

16A

16A

16A
2

1
LCC-102

H21 X:C 9 X:JL 01


DRG. NO. ZF40-145/T
2500-40-SHT CR-L/T. 03
C H23 X:C 10 X:JL 04 C
Last Used by: z004cv6p

Time: 5:34:54 PM
Date: 7/18/2022

H12

H11

CFL
D CFLS D
21 22 H13 1 2
/41.4
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 15

HT
HTS TH
1 2 H15 1 2 H17 1 2
CopyRight (C) Siemens Limited, India All Rights Reserved.

PS
E 1 PSS 2 E
PE

E-BB

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. AC DISTRIBUTION CIRCUIT SIK SS04 W10215
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 15 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <14 16>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 102R

87L

A A
BLKA-87L IL1
A111 X:CT 1 A112 S1 R1 A113 Q1 * Q2
/10.6
2 /41.2 /43.1

A175A
IL2
A131 3 A132 S3 R3 A133 Q3 * Q4
/10.6
4 /41.2 /43.1
+Unit ADJACENT BAY
CT CORE-5
IL3
A151 5 A152 S5 R5 A153 Q5 * Q6 X:CT 10

B
A
/10.6 A B
/43.1

B
6 /41.2
NEUTRAL CURRENT

A
TO PARALLEL LINE
B A A
FOR MUTUAL CURRENT
B
COMPENSATION

A179
B B

B
A171 7 A172 S7 R7 A175D 11

B
A
/10.6 A B

B
8 /41.2
E-BB
PE1
ETL-1
2 1 A179E PE
I4
Q7 * Q8 A175C 12 A175A

B
A
A B
/43.1

B
14
NEUTRAL CURRENT

A
A A
TO PARALLEL LINE
FOR MUTUAL CURRENT
B B
COMPENSATION

B
C C
Last Used by: z004cv6p

A175D 13 A175E

B
A
A B

B
Time: 5:35:19 PM
Date: 7/18/2022

FS-87L-R BLKA-87L UL1


E111 2 1 E112 S4 R4 E113 R15 *
/12.2
2A /41.2 /43.1

FS-87L-Y UL2
E131 2 1 E132 S6 R6 E133 R17 *
/12.2
2A /41.2 /43.1
LINE CVT
D CORE-1 D
FS-87L-B UL3
E151 2 1 E152 S8 R8 E153 R18 * R16
/12.3
2A /41.2 /43.1
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 16

LK-87L-N
E171 2 1 E172 S10 R10 E173
/12.3
/41.2
CopyRight (C) Siemens Limited, India All Rights Reserved.

FS-BVT1-R BLKB-87L U4
E511 2 1 E513 S6 R6 E514 R13 * R14
/26.3
E 2A /41.3 /43.1 E
BUS-1 & BUS-2
SELECTED VT LK-BVT1-N BLKB-87L
E571 2 1 E573 S7 R7 E574
/26.3
/41.3

** AND * SHORTING TO BE REMOVED FOR PARALLEL LINE MUTUAL COMPENSATION


* SHORTING TO BE MADE BETWEEN X:CT-25 & 28 AND X:CT-26 & 29 & REMOVE LINK IN
TB’S X:CT-27 & 30 WHEN MUTUAL COMPENSATION IS NOT USED.
F Unless otherwise specified, wires are PVC 1.5 GY F
C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CT AND VT CIRCUIT FOR 87L SIK SS04 W10216
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 16 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <15 17>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

102R

A A

/14.4

/14.4
87L

K101

K102
87L
Power Supply
K101 K1 K2
+ - Run
86.1 /43.1
213 214
Error
/22.6
86.2 BI1
213 214 K103 K17 K18
A/R BLOCK LED 1 R-PH TRIP
/23.5 /43.1
B 96 B
213 214
LED 2 Y-PH TRIP
/24.5
LCCX BI2
12 13 K105 J1 J2 GAS COMPT. ZONE TRIP
BELOW CB GAS COMPT. LED 3 B-PH TRIP
/19.5 /43.1

LED 4 ZONE-1
LCC-102 BI6
52B
12 13 K113 J7 J8
CB CLOSE COMMAND LED 5 ZONE-2
/25.5 /43.1
** X:CB 1
LED 6 ZONE-3

BI7 LED 7 Z.COM TRIP


XS-52 XS-52 2 K115 J9 J10
CB OPEN
/43.1
C 31 32 C
Last Used by: z004cv6p

LED 8 PSB DETECTED


,
BCU
Time: 5:35:46 PM

BI8
Date: 7/18/2022

BO 2.2 LED 9 FFR


LCC. DRG. NO. ZF40-145/T2500-40 2B5 2B8 K117 J11 J12
CB READY
SHT. CR-L/T. 13 /47.1 2B6 /43.1
LED 10 SOTF OPTD.

LED 11 O/V STG-1 OPTD.

LED 12
K101

K102

LED 13
/40.3

/40.3

D LED 14 D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 17
CopyRight (C) Siemens Limited, India All Rights Reserved.

GOOSE SIGNALS

E E

1.LBB OPTD.(FROM 67/67N)


2.O/C OPTD.(FROM 67/67N)
3. E/F OPTD.(FROM 67/67N)
4. BUSBAR OPTD.(FROM 67/67N)
5. MANUAL TRIP(FROM 67/67N)

NOTE:This is asssumed that all gas compt. Have 4 set of potential free contact to wire for Gas compt. Zone trip.

**Details shall be furnished by customer. NOTE: FO17, Optical 1300 nm, Duplex LC Connector, For Distances Up To 24km, Via Monomode FO Cable For Direct FO Connection.

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. BINARY INPUT CIRCUIT 87L SIK SS04 W10217
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 17 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <16 18>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 102R

67/67N

A A
BLK-67/67N IA
C111 X:CT 15 C112 S1 R1 C113 Q1 • Q2
/10.6
16 /41.4 /44.1

C175
IB
C131 17 C132 S3 R3 C133 Q3 • Q4
/10.6
18 /41.4 /44.1

CT CORE-4 IC
C151 19 C152 S5 R5 C153 Q5 • Q6
/10.6
20 /41.4 /44.1

B B

IN/INs
C171 21 C172 S7 R7 C173 Q7 • Q8
/10.6
22 /41.4 /44.1
E-BB
PE2
ETL-2
C179 2 1C179E PE

C C
Last Used by: z004cv6p

Time: 5:36:00 PM
Date: 7/18/2022

FS-67/67N-R BLK-67/67N VA
E211 2 1 E212 S4 R4 E213 R1 •
/12.4
2A /41.4 /44.1

FS-67/67N-Y VB
E231 2 1 E232 S6 R6 E233 R2 •
/12.5
LINE CVT 2A /41.4 /44.1
CORE-2

D FS-67/67N-B VC D
E251 2 1 E252 S8 R8 E253 R3 • R4
/12.5
2A /41.4 /44.1

LK-67/67N-N
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 18

E271 2 1 E272 E272


/12.6

VL4
R5 • R6
CopyRight (C) Siemens Limited, India All Rights Reserved.

/44.1

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CT AND VT CIRCUIT FOR 67/67N SIK SS04 W10218
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 18 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <17 19>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257
102R

/14.2

/14.3
A 67/67N
A

K201

K202
67/67N P1 P2
+ - Power Supply
LED Configuration
/44.1
LED-1 GEN. TRIP
BI2
F3 F4
LED-2 O/C TRIP SPARE
/44.1
BI5
F8 F9
LED-3 E/F TRIP SPARE
/44.1
BI4
F7
LED-4 Spare SPARE
B /44.1 B
LED-5 Spare 52A BI9
22 23 K219 K2
MANUAL TRIP
/25.5 /44.1
LED-6 Spare
96 BI10
227 228 K221 K3
LED-7 Spare BUSBAR OPTD.
/24.5 /44.1

87L
Life Status Contact BI11
K4 K3 K223 K4
87L RELAY UNHEALTHY
/43.1 /44.1
BCU
LC
C 2B10 2B9 C
Last Used by: z004cv6p

BI12
/47.1 2B7 K225 K5
BCU UNHEALTHY
/44.1
Time: 5:36:22 PM
Date: 7/18/2022

LCCX BI13
14 15 K227 K6
GAS COMPT. ZONE TRIP
/19.5 /44.1

50ZX BI14
16 17 K229 K7
LBB OPTD.
LCC-102 /21.5 /44.1

BI15
X:LCC 58 XS-52 XS-52 X:LCC 59 K231 K8
D CB OPEN D
37 38 /44.1
LCC. DRG. NO. ZF40-145/T2500-40
SHT. CR-L/T. 13
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 19

87L
BO12 BI16
R5 R6 K233 K9 K10
AUTO RECLOSURE OPTD.
/43.1 /44.1
87L
BI1
CopyRight (C) Siemens Limited, India All Rights Reserved.

BO11
R4 K203 F1 F2
DISTANCE PROTN. OPTD.
/43.1 /44.1

E E
LCC-102 GAS COMPT. ZONE TRIP MUX.
LCCX
56 ZONETRIP 3 ZONETRIP 4 57 11 21
X:LCC X:LCC K201A
5 6
7 8 12 13
/17.4 TO 87L RELAY
9 10 14 15
/19.4 TO 67/67N RELAY
16 17
/37.5 TO BCU
22 23
TO 96 RELAY
24 25
K201

K202
NOTE: ** DETAILS TO BE CONFIRMED BY THE CUSTOMER 26 27
/27.5

/27.5
F Unless otherwise specified, wires are PVC 1.5 GY F
C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. BINARY INPUT CIRCUIT FOR 67/67N SIK SS04 W10219
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 19 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <18 20>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 102R

50Z

A A
BLK-50Z IL1
B111 X:CT 23 B112 S1 R1 B113 Q1 • Q2
/11.6
24 /41.5 /45.1

IL2
B131 25 B132 S3 R3 B133 Q3 • Q4
/11.6
26 /41.5 /45.1

CT CORE-1 IL3
B151 27 B152 S5 R5 B153 Q5 • Q6
/11.6
28 /41.5 /45.1

B B

I4
B171 29 B172 S7 R7 B173 Q7 • Q8 B174
/11.6
30 /41.5 /45.1
E-BB
PE6
ETL-4
B179 2 1 B179E PE

/14.7

/14.8
50Z
K701

K702
C C
Last Used by: z004cv6p

F1 F2
+ - Power Supply
Time: 5:36:39 PM
Date: 7/18/2022

86.1 /45.1
123 124
/22.6
86.2 BI1
123 124 K703 F5
LBB 3-PH INITIATION
/23.5 /45.1
96
123 124
/24.5

LCC-102

BI2
X:LCC 1 ZONETRIP 1 ZONETRIP 2 X:LCC 2 K705 F6
CB GAS COMPT. ZONE TRIP
/45.1
D D
BI3
X:LCC 3 XS-52 33 XS-52 34 X:LCC 4 K707 F7
CB OPEN
/45.1

LCC. DRG. NO. ZF40-145/T2500-40


132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 20

SHT. CR-L/T. 13

80.1
26 25 BI4
/14.7 27 K709 F8
DC-1 UNHEALTHY
/45.1
CopyRight (C) Siemens Limited, India All Rights Reserved.

80.2
26 25 BI5
/14.6 27 K711 F9 F10
DC-2 UNHEALTHY
/45.1
E E
BI6
X:SP 2 X:SP 3 K713 R9 R10
Spare
/45.1

87L
BO13 BI7
R8 R7 K715 R11 R12
ZONE-1/LINE DIFF. PROTN OPTD.
/43.1 /45.1
K701

K702
/21.3

/21.6
F Unless otherwise specified, wires are PVC 1.5 GY F
C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CT AND BI CIRCUIT FOR 50Z SIK SS04 W10220
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 20 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <19 21>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 102R

A A

/20.3

/20.6
K701

K702
LBB MUX. RELAY
50Z 50ZX
BO3
R4 R3 K721 11 21
B /45.1 B
12 13
/39.4 TO BUSBAR RELAY
14 15
/40.4 DIRECT TRIP SEND CH-1/2
16 17
/19.4 TO 87L RELAY (LBB OPTD.)
22 23
24 25
26 27

C C
Last Used by: z004cv6p

Time: 5:36:48 PM
Date: 7/18/2022

K701

K702
/24.2

/24.2
D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 21
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. 50Z MULTI. CKT. SIK SS04 W10221
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 21 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <20 22>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 102R

/14.5

/14.5
A A

K501

K502
RXTMA

21
22
23
24
RU.1
Trip Relay
4X150Ω/5W
86.1

12
13
11

21
K505 212 211 K502A
O
B 221 B
PB.86.1

1-3 1-4 K503 122 121


R
/41.4
BCU 113 114
BO 3.1 /27.4 TO BCU CKT.
3B12 3B11 115 116
/33.4 TO TC-1 CKT.
/47.1 117 118
/34.4 TO TC-2 CKT.
123 124
/20.4 TO INITIATE LBB
87L 213 214
BLKB-87L BO4 /17.4 TO 87L RELAY (A/R BLOCK)
S1 R1 K509 K10 K9 227 228
/41.3 /43.1 225 226
67/67N 223 224
BLK-67/67N BO1 /35.5 TO CB CLOSING CKT.
C S2 R2 K511 P4 P3 C
Last Used by: z004cv6p

/41.4 /44.1
Time: 5:37:00 PM
Date: 7/18/2022

D D
Supervision Relay
95.1
12 21 K557
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 22

11 13

16 15
/27.4
17 TO BCU
26 25
CopyRight (C) Siemens Limited, India All Rights Reserved.

27

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. GR-A 3-PH TRIP RELAY SIK SS04 W10222
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 22 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <21 23>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 102R

/14.4

/14.4
A A

K601

K602
RXTMA

21
22
23
24
RU.2
Trip Relay
4X150Ω/5W
86.2

12
13
11

21
K605 212 211 K602A
O
B 221 B
PB.86.2

1-3 1-4 K603 122 121


R
/41.4
BCU 113 114
BO 3.2 /27.4 TO BCU CKT.
3B14 3B13 115 116
/33.4 TO TC-1 CKT.
/47.1 117 118
/34.4 TO TC-2 CKT.
123 124
/20.4 TO INITIATE LBB
87L 213 214
BLKB-87L BO5 /17.4 TO 87L RELAY (A/R BLOCK)
S3 R3 K609 K12 K11 227 228
/41.3 /43.1 225 226
223 224
/35.4 TO CB CLOSING CKT.
C 67/67N C
Last Used by: z004cv6p

BLK-67/67N BO2
S9 R9 K611 P6 P5
/44.1
Time: 5:37:10 PM

/41.4
Date: 7/18/2022

D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 23

Supervision Relay
95.2
12 21 K657

11 13
CopyRight (C) Siemens Limited, India All Rights Reserved.

16 15
/27.4
17 TO BCU
E 26 25 E
27

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. GR-B 3-PH TRIP RELAY SIK SS04 W10223
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 23 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <22 24>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 102R

/21.3

/21.6
A A

K701

K702
RXTMA

21
22
23
24
RU.3
Trip Relay
4X150Ω/5W
96

12
13
11

21
K759 212 211 K702A
O
B 221 B
PB.96

1-3 1-4 K751 122 121


R
/41.4
113 114
/27.4 TO BCU CKT.
BCU 115 116
BO 3.3 /33.4 TO TC-1 CKT.
3C2 3C1 117 118
/34.4 TO TC-2 CKT.
/47.1 123 124
/20.4 TO INITIATE LBB
213 214
/17.4 A/R BLOCK
227 228
/19.4 TO 67/67N RELAY
225 226
/40.4 TO DIRECT TRIP SEND
223 224
/35.3 TO CB CLOSING CKT.
C C
Last Used by: z004cv6p

Time: 5:37:26 PM
Date: 7/18/2022

FROM BUSBAR PANEL


+Unit

XB:BB 1 BK701 BK759 XB:BB 2


/W100/22.5 /W100/22.5

D Supervision Relay D
95.3
12 21 K757

11 13
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 24

16 15
/27.4
17 TO BCU
26 25
27
CopyRight (C) Siemens Limited, India All Rights Reserved.

K702
E E
K701

/27.5
/27.5

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. 96 TRIP RELAY SIK SS04 W10224
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 24 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <23 25>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 102R

A A

/14.7

/14.7
K401

K402
CB TRIP MUX. RELAY
BCU 52A
BO 1.6
1C10 1C7 K441 11 21
/46.1

12 13
/33.4 TO TC-1 CKT.
14 15
/34.4 TO TC-2 CKT.
B CS52 16 17 B
TNC /40.4 DIRECT TRIP SEND CH-1/2
17 18 22 23
/19.4 TO 67/67N (MANUAL TRIP)
/41.3 24 25
26 27

C C
Last Used by: z004cv6p

CB CLOSE MUX. RELAY


BCU
Time: 5:37:35 PM

52B
Date: 7/18/2022

BO 2.1
2B4 2B3 K443 11 21
/47.1

12 13
/17.4 TO 21 RELAY(SOTF)
14 15
/35.3 TO CB CLOSING CKT.
16 17
/39.4 TO BUSBAR PROTN. RELAY
22 23
24 25
26 27

D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 25
CopyRight (C) Siemens Limited, India All Rights Reserved.

K401

K402
E E
/27.4

/27.6
F Unless otherwise specified, wires are PVC 1.5 GY F
C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CB CLOSE & TRIP CONTACT MULTI. SIK SS04 W10225
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 25 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <24 26>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 102R

A A
BCU

I M 1A1
D111 X:CT 35 D112 1A1 * 1A2 D113
/10.6 /29.4
36 /46.1

I M 1A2
D131 37 D132 1A3 * 1A4 D133
/10.6 /29.4
38 /46.1
CT CORE-3

TO ENERGY METER CKT.


I M 1A3
D151 39 D152 1A5 * 1A6 D153
/10.6 /29.4
B 40 /46.1 B

D179
D171 41 D173 D173
/10.6 /29.4
42
E-BB
PE3
ETL-3
2 1 D179E PE
I M 1A4
1A7 * 1A8
/46.1

C C
Last Used by: z004cv6p

RU
1 R1 2
Time: 5:37:54 PM

RU
Date: 7/18/2022

3 R2 4

RU
5 R3 6

FS-BCU-R V 1.1
E311 2 1 E312 1B1 1B2
/12.6
2A /46.1

FS-BCU-Y V 1.2
E331 2 1 E332 1B3 1B4
/12.7
2A /46.1
D D
LINE CVTP
CORE-3 FS-BCU-B V 1.3
E351 2 1 E352 1B5 1B6
/12.8
2A /46.1
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 26

LK-BCU-N
E371 2 1 E372
/12.8
CopyRight (C) Siemens Limited, India All Rights Reserved.

E311
E331
E351
E371

E E
/29.4
/29.4
/29.4
/29.4

FS-BVT-R V 1.4
E511 E511 2 1 E512 1B7 1B8
/29.5
2A /46.1

LK-BVT-N
E571 E571 2 1 E572
/29.5
E511

E571

RU
7 R4 8
/16.3

/16.3

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CT AND VT CIRCUIT FOR BCU SIK SS04 W10226
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 26 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <25 27>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
102R

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

/25.2

/25.7
BCU

K401

K402
PS
A A
2B1 2B2
+ - Power Supply
95.A /47.1
7 9 BI 2.1
/33.4 8 2K403 2B12
TC-1 FAULTY
/47.1
95.B
7 9 BI 2.2
/34.4 8 2K405 2B14
TC-2 FAULTY
/47.1
80.1
16 15 BI 2.3
/14.7 17 2K407 2B13 2B11
DC-1 FAIL
/47.1

86.1 BI 3.1
B 113 114 3K403 3A1 3A3 B
TO 86.1 RELAY OPTD.
/22.6 /47.1
95.1
16 15 BI 3.2
/22.4 17 3K405 3A2 3A4
TO 86.1 RELAY FAULTY
/47.1

86.2 BI 3.3
113 114 3K407 3A7 3A5
TO 86.2 RELAY OPTD.
/23.5 /47.1
95.2
16 15 BI 3.4
/23.3 17 3K409 3A8 3A6
TO 86.2 RELAY FAULTY
/47.1
CSS
IN OUT BI 3.5
C 11 12 3K411 3A9 3A11 C
Last Used by: z004cv6p

CARRIER PROTN. OUT


/41.1 /47.1
80.2
Time: 5:38:17 PM

16 15 BI 3.12
Date: 7/18/2022

/14.6 17 3K425 3B10 3B8


DC-2 FAIL
/47.1
CS52
TNC BI 3.6
1 2 3K413 3A10 3A12
MANUAL OPEN
/41.3 /47.1
CS52
TNC BI 3.7
7 8 3K415 3B1 3A13
MANUAL CLOSE
/41.3 /47.1
67/67N
Live BI 3.8
K16 K15 3K417 3B2 3A14
D 67/67N UNHEALTHY D
/44.1 /47.1

BI 1.3
1D5 1D3
SPARE
/46.1
96 BI 3.9
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 27

113 114 3K419 3B3 3B5


96 RELAY OPTD.
/24.5 /47.1
95.3
16 15 BI 3.10
/24.3 17 3K421 3B4 3B6
96 RELAY FAULTY
/47.1
CopyRight (C) Siemens Limited, India All Rights Reserved.

BI 3.11
K101 3B9 3B7
/40.3 87L RELAY DC SUPPLY HEALTHY
/47.1
E K102 E
/40.3
BI 4.11
K701 4B9 4B7
/24.2 50Z RELAY DC SUPPLY HEALTHY
/48.1

K702
/24.7
BI 4.12
K201 4B10 4B8
K401

K402
/19.3 67/67N RELAY DC SUPPLY HEALTHY
/48.1

K202
/19.6
/31.6

/31.6
F Unless otherwise specified, wires are PVC 1.5 GY F
C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. BINARY INPUT CIRCUIT FOR BCU SIK SS04 W10227
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 27 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <26 28>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

A A

ISOLATOR-10189A 101-BCU

B 10189A B
AND 101-89A OPEN

01 SELECT BUS-1
XOR AND
10189A VT SUPPLY
AND 101-89A CLOSE
BCU-BO
01

TO SELECT BUS-1

VT SUPPLY

BCU-BO

C C
Last Used by: z004cv6p

Time: 5:38:24 PM

SELECT BUS-2
AND
Date: 7/18/2022

VT SUPPLY

BCU-BO
ISOLATOR-10189B

10189B
TO SELECT BUS-2
AND 101-89B OPEN VT SUPPLY

01
XOR
BCU-BO
10189B
AND 101-89B CLOSE
D D
01
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 28
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. VT SELCTION LOGIC SIK SS04 W10228
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 28 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <27 29>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

102R

E311 E311
A /26.3 A

E331 E331
/26.3

E351 E351
/26.3

E371 E371
/26.3

TTB-EM Energy Meter EM**


B R1 VR R2 E314 R B
1 1 D117 1S
D113 D113 2 2
/26.6 R
3 3 D171B 1L
Y1 VY Y2 E334 Y
4 4 D137 2S
D133 D133 5 5
/26.6 Y
6 6 D171C 2L
B1 VB B2 E354 B
7 7 D157 3S
D153 D153 8 8
/26.6 B
D173 D173 9 9 D171D 3L
/26.6
C N1 VN N2 E374 N C
Last Used by: z004cv6p

Time: 5:38:36 PM
Date: 7/18/2022

BCU
BO 3.4
E511B1 3C4 3C3 E511
/13.4 /26.2
METERING CORE-3

/47.1
TO BCU CKT.
(BUS-1 VT)

BCU SELECTED BUS VT


BO 3.5
E571B1 3C6 3C5 E571
/13.4 /26.2
/47.1

D D
BCU
BO 3.6
METERING CORE-3

E511B2 3C8 3C7


/13.4
/47.1
(BUS-2 VT)
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 29

BCU
BO 3.7
E571B2 3C10 3C9
/13.4
/47.1
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

NOTE: EM** NOT IN SIEMENS SCOPE OF SUPPLY


NOTE: * WIRE (OF SUFFICIENT LENGTH) SHALL BE KEPT AS LOOSE,
CRIMPED WITH LUGS WITHOUT CONNECTING BOTH ENDS.

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. VT SELECTION & ENERGY METER CKT SIK SS04 W10229
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 29 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <28 30>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

A A

B B

NOTE:- ALL ISOLATOR, EARTH SWITCH INTERLOCKS SHALL BE AS PER LCC DRAWING.

C C
Last Used by: z004cv6p

Time: 5:38:49 PM
Date: 7/18/2022

D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 30
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. ISOL. INTERLOCK LOGIC SIK SS04 W10230
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 30 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <29 31>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 LCC-102 102R

/27.4

/27.6
X1.D1 X:ISL 1 K401
1

K401

K402
2 K402
A A
3
BCU
COMMON X1.D1 3 KC403
2
BO 4.1
4 KC405 4B12 4B11
ISO OPEN /48.1
8
BO 4.2
5 KC407 4B14 4B13
ISOL. CLOSE /48.1
7
6 KC409
COMMON 12
BO 4.3
7 KC411 4C2 4C1 BCU
TO INTERLOCKING 18 /48.1
B B
8 K401

BI 4.1
XS.D1 XS.D1 9 4K403 4A1 4A3
ISO 89A OPEN
21 22 /48.1

BI 4.2
XS.D1 XS.D1 10 4K405 4A2 4A4
ISO 89A CLOSE
1 2 BCU /48.1

11 KC417

X1.D1 BO 4.4
12 KC419 4C4 4C3
10 /48.1
BO 4.5
C 13 KC421 4C6 4C5 C
Last Used by: z004cv6p

9 /48.1
Time: 5:39:15 PM

14 KC423
Date: 7/18/2022

20
BO 4.6
15 KC425 4C8 4C7
19 /48.1

16 K401

BI 4.3
XS.E1 XS.E1 17 4K407 4A7 4A5
E/SW 89AE OPEN
21 22 /48.1

BI 4.4
XS.E1 XS.E1 18 4K409 4A8 4A6
E/SW 89AE CLOSE
1 2 /48.1
D D
X1.D2 19 K401
1
20 K402
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 31

3 BCU
X1.D2 21 KC431
COMMON 2
BO 1.1
22 KC433 1B10 1B9
ISO OPEN 8 /46.1
CopyRight (C) Siemens Limited, India All Rights Reserved.

BO 1.2
23 KC435 1B12 1B11
ISOL. CLOSE 7 /46.1

24 KC437
E COMMON 12 E
BO 1.3
25 KC439 1B13 1B14
TO INTERLOCKING 18 /46.1

26 K401

BI 1.1
XS.D2 XS.D2 27 1K403 1C13 1D1
ISO 89B OPEN
21 22 /46.1

BI 1.2
XS.D2 XS.D2 28 1K405 1C14 1D2

K401

K402
ISO 89B CLOSE
1 2 /46.1

DRG. NO. ZF40-145/T2

/32.6

/32.6
500-40-SHT. CR-L/T. 18

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. ISOL & E/SW CONTROL CKT SIK SS04 W10231
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 31 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <30 32>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 LCC-102 102R

/31.6

/31.6
K401

K402
A X1.D3
A
X:ISL 29 K401
1
30 K402
3
BCU
X1.D3 31 KC445
COMMON 2
BO 4.7
32 KC447 4C10 4C9
ISO OPEN 8 /48.1
BO 4.8
33 KC449 4C12 4C11
ISOL. CLOSE 7 /48.1

34 KC451
B COMMON 12 BCU B
BO 4.9
35 KC453 4C14 4C13
TO INTERLOCKING 18 /48.1

36 K401

BI 4.5
XS.D3 XS.D3 37 4K411 4A9 4A11
ISO 89L OPEN
21 22 /48.1

BI 4.6
XS.D3 XS.D3 38 4K413 4A10 4A12
ISO 89L CLOSE
1 2 /48.1

BCU
39 KC459
C C
Last Used by: z004cv6p

X1.D3 BO 4.10
40 KC461 4D2 4D1
/48.1
Time: 5:40:01 PM

10
Date: 7/18/2022

BO 4.11
41 KC463 4D4 4D3
9 /48.1

42 KC465
20
BO 4.12
43 KC467 4D6 4D5
19 /48.1

44 K401

BI 4.7
XS.E3 XS.E3 45 4K415 4B1 4A13
E/SW 89LE1 OPEN
21 22 /48.1
D D
BI 4.8
XS.E3 XS.E3 46 4K417 4B2 4A14
E/SW 89LE1 CLOSE
1 2 /48.1

BCU
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 32

47 KC473

BO 4.13
48 KC475 4D8 4D7
/48.1
BO 4.14
49 KC477 4D10 4D9
CopyRight (C) Siemens Limited, India All Rights Reserved.

/48.1

50 KC479

BO 4.15
E 51 KC481 4D12 4D11 E
/48.1
52 K401
BI 4.9
XS.E4 XS.E4 53 4K419 4B3 4B5
E/SW 89LE2 OPEN
21 22 /48.1

BI 4.10
XS.E4 XS.E4 54 4K421 4B4 4B6
E/SW 89LE2 CLOSE
1 2 /48.1

K401

K402
DRG. NO. ZF40-145/T2

/35.6

/35.6
500-40-SHT. CR-L/T. 23

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. ISOL & E/SW CONTROL CKT SIK SS04 W10232
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 32 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <31 33>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 102R LCC-102

A A
K1T X:TC1 1 X1.S2
/33.3
3

K2T 2 X1.S2
/33.3
5

K1TA X:TC1 3

87L
BLKB-87L BO14 X1.S2
S4 R4 K1TB R10 R9 K3T 4
REMOTE/PROTN. TRIP
B /41.3 /43.1 9 B
86.1
115 116
/22.6

86.2
115 116
/23.5

50Z
BLK-50Z BO4
S4 R4 K1TC R6 R5
/41.5 /45.1

C CS52 C
Last Used by: z004cv6p

TNC
3 4
/41.3
Time: 5:40:31 PM
Date: 7/18/2022

52A
12 13
/25.5

96
115 116
/24.5

TC-1 Supervision Relay


95.A

K2-1 K2-2

TS1
D D
K79T K1-4
E-BB
PE

PE4 K2-4 K2-5 K7T 5 X1.S2


TS2 PRE CLOSE SUPERVISION
19
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 33

K1T K1-1 TS1


SMPS

/14.4

TS3
K2T K1-2 TS2
/14.4

7 9
/27.4
8 TO BCU CKT.
CopyRight (C) Siemens Limited, India All Rights Reserved.

K1T

K2T

10 12
11 SPARE
6 X1.S2
/33.6

/33.6

K5T
POST CLOSE SUPERVISION
E 18 E

DRG. NO. ZF40-145/T2


500-40-SHT. CR-L/T. 11

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CB TC-1 CKT SIK SS04 W10233
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 33 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <32 34>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 102R LCC-102

A A

K51T X:TC2 1 X1.S2


/34.3
23

K52T 2 X1.S2
/34.3
27

K51TA X:TC2 3

87L
B BLKB-87L BO15 X1.S2 B
S5 R5 K51TB R12 R11 K53T 4
PROTN. REMOTE/TRIP
/41.3 /43.1 21

86.1
117 118
/22.6

86.2
117 118
/23.5

50Z
BLK-50Z BO5
S8 R8 K51TC R8 R7
/41.5 /45.1

C C
Last Used by: z004cv6p

CS52
TNC
Time: 5:40:42 PM

5 6
Date: 7/18/2022

/41.3

52A
14 15
/25.5

96
117 118
/24.5

D D
TC-2 Supervision Relay
95.B

K2-1 K2-2
TS1
K55T K1-4
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 34

E-BB
PE

PE5 K2-4 K2-5 K57T 5 X1.S2


TS2

PRE CLOSE SUPERVISION


10
K51T K1-1 TS1
SMPS

/14.3
TS3

K52T K1-2 TS2


CopyRight (C) Siemens Limited, India All Rights Reserved.

/14.3

7 9
/27.4
8 TO BCU CKT.
K51T

K52T

E 10 12 E
11 SPARE
/34.6

/34.6

K55T 6 X1.S2
POST CLOSE SUPERVISION
20

DRG. NO. ZF40-145/T2


500-40-SHT. CR-L/T. 11

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CB TC-2 CKT SIK SS04 W10234
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 34 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <33 35>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257
102R LCC-102

K401 X:CB 3 X1.S2


/32.6 +VE
1
A A
K402 X:CB 4 X1.S2
/32.6 -VE
4

K401

K402
/36.5

/36.7
96 86.2 86.1
223 224 K46 223 224 K42 223 224 K41 X:CB 5
/24.5 /23.5 /22.6
B B
52B X1.S2
14 15 K43 X:CB 6 CB REMOTE CLOSE
/25.5
7

87L
BO7 X1.S2
K44 K16 K15 K45 X:CB 7 AUTORECLOSE
/43.1
8

DRG. NO. ZF40-145/T2


500-40-SHT. CR-L/T. 10

C C
Last Used by: z004cv6p

Time: 5:40:57 PM
Date: 7/18/2022

D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 35
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CB MANUAL TRIP & CLOSE CKT SIK SS04 W10235
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 35 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <34 36>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
LCC-102 102R

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

/35.6

/35.6
K401

K402
A BCU A
X:LCC 5

BI 5.1
XS XS
X:LCC 6 5K403 5A1
CB LOCAL MODE
/48.1
01 21
BI 5.2
XS
X:LCC 7 5K405 5A2
CB REMOTE MODE
/48.1
22
BI 5.3
XS XS
X:LCC 8 5K407 5A3
CB UNLOCK
/48.1
05 25
BI 5.4
XS
X:LCC 9 5K409 5A4
CB INTERLOCK
B 26
/48.1 B
BI 5.5
XS XS
X:LCC 10 5K411 5A7
SPRING CHARGEGING MOTOR FOR CB (FAULT)
/48.1
07 27
BI 5.6
XS XS
X:LCC 11 5K413 5A8
SPRING CHARGEGING MOTOR FOR CB (RUN)
/48.1
08 28
BI 5.7
XS XS
X:LCC 12 5K415 5A9
SPRING CHARGEGING MOTOR FOR CB (UNCHARGED)
/48.1
09 29
BI 5.8
XS XS
X:LCC 13 5K417 5A10
SPRING CHARGEGING MOTOR FOR CB (CHARGED)
/48.1
C 10 30 5A5 C
Last Used by: z004cv6p

5A6
5.COM 1-8 /48.1
Time: 5:41:22 PM

BI 5.9
Date: 7/18/2022

XS XS
X:LCC 14 5K419 5C1
SF6 GAS IN CB CHAMBER (ALARM)
/48.1
11 31
BI 5.10
XS XS
X:LCC 15 5K421 5C2
SF6 GAS IN CB CHAMBER (LOCKOUT)
/48.1
12 32
BI 5.11
XS XS
X:LCC 16 5K423 5C3
SF6 GAS IN DES1 CHAMBER (ALARM)
/48.1
13 33
BI 5.12
XS XS
X:LCC 17 5K425 5C4
D SF6 GAS IN DES2 CHAMBER (ALARM) D
/48.1
15 35
BI 5.13
XS XS
X:LCC 18 5K427 5C7
SF6 GAS IN DES3 CHAMBER (ALARM)
/48.1
17 37
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 36

BI 5.14
XS XS
X:LCC 19 5K429 5C8
SF6 GAS IN BUS DUCT CHAMBER (ALARM)
/48.1
19 38
BI 5.15
XS XS
X:LCC 20 5K431 5C9
CB CHARGING MOTOR MCB TRIP
CopyRight (C) Siemens Limited, India All Rights Reserved.

/48.1
06 39
BI 5.16
XS
X:LCC 21 5K433 5C10
DE S1 MOTOR MCB TRIP
E 40
/48.1 5C5 E
K401 5C6
5.COM 9-16 /48.1
BI 1.6
XS-52 XS-52 X:CB 8 1K413 1D8 1D10
CB OPEN
35 36 /46.1

BI 1.7
XS-52 XS-52 X:CB 9 1K415 1D13 1D11
CB CLOSE
11 12 /46.1

K402
K401

NOTE: All signal details are tentative,

/37.7
shall be changed after receiving of
/37.5

LCC drawing.
NOTE: X MARK TO BE CONFIRMED AT SITE
F Unless otherwise specified, wires are PVC 1.5 GY F
C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. BCU INPUT CKT. FOR LCC SIK SS04 W10236
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 36 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <35 37>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
102R

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

/36.5

/36.7
LCC-102

K401

K402
BCU
A A
X:LCC 22

BI 5.17
XS
X:LCC 23 5K435 5D1
DS S2 MOTOR MCB TRIP
/48.1
41
BI 5.18
XS
X:LCC 24 5K437 5D2
FES MOTOR MCB TRIP
/48.1
42
BI 5.19
XS
X:LCC 25 5K439 5D3
DES MOTOR MCB TRIP
/48.1
43
BI 5.20
XS
X:LCC 26 5K441 5D4
SIGNAL POWER MCB TRIP
B 44
/48.1 B
BI 5.21
XS
X:LCC 27 5K443 5D7
DES3 MOTOR MCB TRIP
/48.1
45
BI 5.22
XS
X:LCC 28 5K445 5D8
ILLUMINATION HEATER MCB TRIP
/48.1
46
BI 5.23
XS XS
X:LCC 29 5K447 5D9
DC POWER SINGAL
/48.1
14 48

LCCX BI 5.24
16 17 5K449 5D10 GAS COMP. ZONE TRIP
/19.5 /48.1 (BELOW CB GAS COMP.)
C C
Last Used by: z004cv6p

5D5
Time: 5:42:12 PM

5D6
Date: 7/18/2022

5.COM 17-24 /48.1


BI 5.25
X:LCC 31 5K451 5E1
GAS TIGHT SIGNAL
/49.1

BI 5.26
X:LCC 32 5K453 5E2
GAS REFIL SIGNAL IN CB CHAMBER
/49.1

BI 5.27
X:LCC 33 5K455 5E3
GAS REFIL SIGNAL IN DES1 CHAMBER
/49.1

D BI 5.28 D
X:LCC 34 5K457 5E4
GAS REFIL SIGNAL IN DES2 CHAMBER
/49.1

BI 5.29
X:LCC 35 5K459 5E7
GAS REFIL SIGNAL IN DES3 CHAMBER
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 37

/49.1

BI 5.30
X:LCC 36 5K461 5E8
GAS REFIL SIGNAL IN BUS DUCT CHAMBER
/49.1

BI 5.31
CopyRight (C) Siemens Limited, India All Rights Reserved.

X:LCC 37 5K463 5E9


SPARE
/49.1

BI 5.32
E X:LCC 38 5K465 5E10 E
SPARE
/49.1

5E5
5E6
5.COM 25-32 /49.1
K401

K402
/38.5

/38.7
NOTE: X MARK TO BE CONFIRMED AT SITE

NOTE: All signal details are tentative, shall be changed after receiving of
LCC drawing.

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. BCU INPUT CKT. FOR LCC SIK SS04 W10237
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 37 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <36 38>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
102R

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

/37.5

/37.7
LCC-102

K401

K402
A BCU A
X:LCC 39

BI 5.33
X:LCC 40 5K467 5G1
ZONE TRIPPING IN CB CHAMBER
/49.1

BI 5.34
X:LCC 41 5K469 5G2
ZONE TRIPPING IN DES1
/49.1

BI 5.35
X:LCC 42 5K471 5G3
ZONE TRIPPING IN DES2
/49.1

BI 5.36
X:LCC 43 5K473 5G4
ZONE TRIPPING IN DES3
B /49.1 B
BI 5.37
X:LCC 44 5K475 5G7
ZONE TRIPPING IN BUS DUCT CHAMBER
/49.1

BI 5.38
X:LCC 45 5K477 5G8
SPARE
/49.1

BI 5.39
X:LCC 46 5K479 5G9
SPARE
/49.1

BI 5.40
X:LCC 47 5K481 5G10
SPARE
/49.1
C C
Last Used by: z004cv6p

5G5
Time: 5:42:59 PM

5G6
Date: 7/18/2022

5.COM 33-40 /49.1


BI 5.41
X:LCC 48 5K483 5H1
SPARE
/49.1

BI 5.42
X:LCC 49 5K485 5H2
SPARE
/49.1

BI 5.43
X:LCC 50 5K487 5H3
SPARE
/49.1

D BI 5.44 D
X:LCC 51 5K489 5H4
SPARE
/49.1

BI 5.45
5H7
SPARE
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 38

X:LCC 52 5K491 /49.1

BI 5.46
X:LCC 53 5K493 5H8
SPARE
/49.1
CopyRight (C) Siemens Limited, India All Rights Reserved.

BI 5.47
X:LCC 54 5K495 5H9
SPARE
/49.1
E BI 5.48
E
X:LCC 55 5K497 5H10
SPARE
/49.1

5H5
5H6
5.COM 41-48 /49.1
K401

K402
NOTE: X MARK TO BE CONFIRMED AT SITE

NOTE: All signal details are tentative, shall be changed after receiving of
LCC drawing.
F Unless otherwise specified, wires are PVC 1.5 GY F
C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. BCU INPUT CKT. FOR LCC SIK SS04 W10238
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 38 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <37 39>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

A A

B 102R 100R B

K161 XB:BB 3 BK101


/W100/18.3
TO BUSBAR INITIATION FROM
50ZX BAY LBB OPTD.
12 13 K163 XB:BB 4 B2K111
/W100/18.4
/21.5

52B
16 17 K165 XB:BB 5 B2K113
/W100/18.4
/25.5 END FAULT PROTN.
C C
Last Used by: z004cv6p

Time: 5:43:26 PM
Date: 7/18/2022

D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 39
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. BB INTERFACING CKT. SIK SS04 W10239
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 39 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <38 40>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 102R DPC SW1-3000

/17.3

/17.3
K101

K102
A A
X:DPC 1

CSS
IN OUT
1 2 K175 X:DPC 2
/41.1
K177 X:DPC 3 XX XX
X CARRIER FAIL X

87L
3 4 K179 4
B /41.1 B
BI3
J3
/43.1 CARRIER RECIEVE CH-1/2 K181 5 XX XX
BI4
J4 X CARRIER RECEIVE CH-1/2 X
/43.1 DIRECT TRIP RECIEVE CH-1/2 K183 6 XX XX

X DIRECT TRIP RECEIVE CH-1/2 X


67/67N
67/67N
BI6
F11
CARRIER RECIEVE
/44.1
67/67N
BI7 DIRECT TRIP RECIEVE
F12 F10
/44.1
C C
Last Used by: z004cv6p

67/67N
Time: 5:43:42 PM

BI3
Date: 7/18/2022

/44.1 Carrier Fail

87L
BI5
J6 J5
/43.1 DIRECT TRIP SEND CH-1/2 K191 7 XX XX

X X
CSS DIRECT TRIP SEND CH-1/2
BLKB-87L BO3 IN OUT XX XX
S8 R8 K197 K5 K8 K188 5 6 K187 8
/41.3 /43.1 /41.1 X X
D CSS CARRIER SEND CH-1/2 D
BO2 IN OUT
OV STG-1/ZONE TRIP OPTD. K7 K193 7 8 K191
/43.1 /41.1

52A
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 40

MAIN CB TRIP COMMAND 16 17


/25.5
67/67N
BLK-67/67N BO4
S10 R10 K195 P9 P8
/41.4 /44.1
CopyRight (C) Siemens Limited, India All Rights Reserved.

50ZX
LBB OPTD. 14 15
/21.5
E E
96
BB OPTD. 225 226
/24.5
K101

K102
/27.5

/27.5

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. PLCC CH-1/2 CIRCUIT SIK SS04 W10240
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 40 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <39 41>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257
102R

A A
CSS CS52
IN OUT TNC PB.86.1

1 2 1 2 1-3 1-4
/40.3 /27.4 /22.5
2-3 2-4
3 4 3 4
/40.3 /33.4
5 6 5 6
/40.6 /34.4
PB.86.2
7 8 7 8 1-3 1-4
/40.6 /27.4 /23.3
9 10 9 10 2-3 2-4

11 12 11 12
/27.4
13 14 13 14
B PB.96 B
15 16 15 16 1-3 1-4
/24.3
17 18 17 18 2-3 2-4
/25.3
19 20 19 20

21 22
CFLS
23 24 21 22
/15.4
25 26 31 32
13 14
27 28

29 30
C C
Last Used by: z004cv6p

Time: 5:44:01 PM
Date: 7/18/2022

D BLKA-87L BLKB-87L BLK-67/67N BLK-50Z D


S1 R1 S1 R1 S1 R1 S1 R1
/16.4 /22.4 /18.5 /20.5
S2 R2 S2 R2 S2 R2 S2 R2
/22.4
S3 R3 S3 R3 S3 R3 S3 R3
/16.4 /23.2 /18.5 /20.5
S4 R4 S4 R4 S4 R4 S4 R4
/16.4 /33.3 /18.5 /33.3
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 41

S5 R5 S5 R5 S5 R5 S5 R5
/16.4 /34.3 /18.5 /20.5
S6 R6 S6 R6 S6 R6 S6 R6
/16.4 /16.4 /18.5
S7 R7 S7 R7 S7 R7 S7 R7
/16.4 /16.4 /18.5 /20.5
S8 R8 S8 R8 S8 R8 S8 R8
/16.4 /40.3 /18.5 /34.3
S9 R9 S9 R9 S9 R9 S9 R9
CopyRight (C) Siemens Limited, India All Rights Reserved.

/23.2
S10 R10 S10 R10 S10 R10 S10 R10
/16.4 /40.3

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. SWITCH & BLOCK CONTACT DISTRIBUTION SIK SS04 W10241
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 41 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <40 42>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-0.1-1/10/2012
Sheet Version: 0.1
E-Base Version: 7.0.0.1257

A A

B B

C CONNECTION DIAGRAM C
Last Used by: z004cv6p

Time: 5:44:21 PM
Date: 7/18/2022

D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 42
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) 0000 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. Cover Sheet SIK SS04 W10242
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 42 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <41 43>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
: Case Size: 1/2 19”, 4xI, 4xV, 8 BI, 15 BO, 1 Live Status, 14 LED, Flush Mounting

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257 Designation Technical Specifications:
Type : 7SD52 Region World, 50/60 Hz, IEC/ANSI, Language English (UK) (Language Can Be Changed)
Manufacturer : Siemens, Germany IEC61850, Optical EN100, Double, LC Connector
Order No. : 7SD5221-5AB99-9EN0+L0S+M0G+N5G FO17, Optical 1300 nm, Duplex LC Connector, For Distances Up To 24km, Via Monomode FO Cable for Direct FO Connection
Product Code : 7SD5221-5AB99-9EN0+L0S+M0G+N5G Only Three-Pole Tripping, With Automatic Reclosure, With Synchro-Check
Current : Iph = 1A, Ie = 1A Overcurrent Time Protection / Circuit Breaker Failure Protection (CBF), +Pickup Z<, Polygon, With Power Swing Option, With Parallel Line Compensation
A Voltage : DC 110-250V, AC 115V, Binary Input Threshold 88V 4 Remote Commands / 24 Remote Indications, +Transformer Expansions, +Fault Locator - 1 Side A
Add. Info. 1 : CT Sec: 1A, PT Sec: 110V AC, Aux Supply: 110-250V DC, 115V AC, BI Threshold 88V Without Additional Functions
Add. Info. 2 : IEC61850, Optical EN100, Double, LC Connector

Comment Remarks Location Equipment Function


Line Diff. Protn. 250 87L

A: Time Synchronization

F: Front Operator Panel


Life Status

D: Optical 1300nm

E: Optical 1300nm
Power Supply Contact

Optical EN100
B: IEC61850,
2 3

1
X40
+

2
B B

PE
K1

K2

K3
K4

D
A

F
/17.5 /19.4

IL1 IL2 IL3 I4


*

*
Current Inputs

C C
Last Used by: z004cv6p

Q1
Q2

Q3
Q4

Q5
Q6

Q7
Q8
87L /16.5 /16.5 /16.5 /16.5
Time: 5:44:39 PM
Date: 7/18/2022

UL1 UL2 UL3 U4


*

*
Voltage Inputs
R15

R17

R18
R16

R13
R14

87L /16.5 /16.5 /16.5 /16.5

D BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 D


L+

L+

L+

L+

L+

L+

L+

L+
Input 1-8
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 43

K17
K18

J10

J11
J12
J1
J2

J3

J4

J6
J5

J7
J8

J9
87L /17.5 /17.5 /40.4 /40.4 /40.4 /17.5 /17.5 /17.5
CopyRight (C) Siemens Limited, India All Rights Reserved.

BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 BO15

2 3

1
X41

2
E Output (4x BO, 12x Fast)
E

R10

R11
R12
K10

K11
K12

K13
K14

K15
K16

R1

R2

R3

R4

R6
R5

R7
R8

R9
K6

K7

K8
K5

K9

87L /40.4 /40.4 /22.5 /23.3 /35.4 /19.4 /19.4 /20.4 /33.4 /34.4

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CONNECTION DIAGRAM FOR 87L SIK SS04 W10243
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 43 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <42 44>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257
Designation : Case Size: 1/3 19”, 4xI, 4xV, 16 BI, 7 BO, 1 Live Status, 7 LED, Flush Mounting Technical Specifications:
Type : 7SJ66
Manufacturer : Siemens, India
Order No. : 7SJ6611-5DB90-1FC0+L0S
Product Code :
A Current :
A
Voltage :
Add. Info. 1 : CT Sec: 1A, PT Sec: 110V AC, Aux Supply: 110-250V DC, 115-230V AC, BI Threshold: 69V
Add. Info. 2 : IEC 61850, Ethernet With 100Mbit/s Fiber Optic Port

Comment Remarks Location Function Function


DIR. OC & EF Protn. 250 67/67N

Time Synchronization
Live

System Interface
3

1
B B

FP
K15
K16
PE
P1

P2

B
/19.6 /27.4

IA IB IC IN/INs


C C
Last Used by: z004cv6p

Current Inputs
Time: 5:45:14 PM

Q1
Q2

Q3
Q4

Q5
Q6

Q7
Q8
Date: 7/18/2022

67/67N /18.5 /18.5 /18.5 /18.5

VA VB VC VL4

Voltage Inputs

D D
R1

R2

R3
R4

R5
R6

67/67N /18.5 /18.5 /18.5 /18.5


132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 44

BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16
CopyRight (C) Siemens Limited, India All Rights Reserved.

Input 1-16

K10
F11

F12
F10

K1

K2

K3

K4

K5

K6

K7

K8

K9
F1
F2

F3
F4

F6
F5

F7

F8
F9

E E
67/67N /19.6 /19.6 /40.4 /19.6 /19.6 /40.4 /40.4 /19.6 /19.6 /19.6 /19.6 /19.6 /19.6 /19.6 /19.6

BO1 BO2 BO3 BO4 BO5 BO6 BO7

Output 1-7
P11

P12
P10

K12
K11
K13
P3
P4

P5
P6

P7

P8
P9

67/67N /22.5 /23.3 /40.4


F Unless otherwise specified, wires are PVC 1.5 GY F
C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CONNECTION DIAGRAM FOR 67/67N SIK SS04 W10244
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 44 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <43 45>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257
Designation : Case Size: 1/3 19”, 4xI, 4xV, 7 BI, 5 BO, 1 Live Status, 7 LED, Flush Mounting Technical Specifications:
Type : 7VK61
Manufacturer : Siemens, Germany
Order No. : 7VK6101-5AB91-4YC0+L0S
Product Code :
A Current :
A
Voltage :
Add. Info. 1 : CT Sec: 1A, PT Sec: 110V AC, Aux Supply: 110-250V DC, BI Threshold 88V
Add. Info. 2 : IEC 61850, Optical, Double, LC Connector

Comment Remarks Location Function Function


LBB Protection Relay 250 50Z

Time Synchronization
Live

System Interface

System Interface
Front Interface

Digsi, Modem
3

1
B B

2
PE
F1

F2

F3
F4

C
A

B
/20.5

IL1 IL2 IL3 I4



C C
Last Used by: z004cv6p

Current Inputs
Time: 5:45:45 PM

Q1
Q2

Q3
Q4

Q5
Q6

Q7
Q8
Date: 7/18/2022

50Z /20.5 /20.5 /20.5 /20.5

VL1 VL2 VL3 V4


Voltage Inputs

D D
R15

R17

R18
R16

R13
R14

50Z
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 45

BI1 BI2 BI3 BI4 BI5 BI6 BI7


CopyRight (C) Siemens Limited, India All Rights Reserved.

Input 1-7
R10

R11
R12
F10

R9
F5

F6

F7

F8

F9

E E
50Z /20.5 /20.5 /20.5 /20.5 /20.5 /20.5 /20.5

BO1 BO2 BO3 BO4 BO5

Output 1-5
R1

R2

R3
R4

R5
R6

R7
R8

50Z /21.3 /33.4 /34.4


F Unless otherwise specified, wires are PVC 1.5 GY F
C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CONNECTION DIAGRAM FOR 50Z SIK SS04 W10245
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 45 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <44 46>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

Designation : Case Size: 5/6 19", 4xI, 4xV, 83 BI, 40 BO, 1 Live Status, 16 LED, Flush Mounting Technical Specifications
Type : 6MD85 Integrated Operation Panel
Manufacturer : Siemens, Germany Small Display
A : Without Key Operated Switch A
Voltage : DC 60 V - 250 V, AC 100 V - 230 V 16 LED
Add. Info. 1 : CT Sec: 1A, PT Sec: 110V AC, Aux Supply: 60-250V DC, 100-230V AC DIGSI Via Ethernet (Port J)
Add. Info. 2 : 2 x Optical Ethernet, LC Duplex Connector, 100 Mbit/s, Integrated Switch Port E: 2 x Optical Ethernet, LC Duplex Connector, 100 Mbit/s, Integrated Switch
Product Code : No Module Plugged in Port F
Port M: Not Available
Port N: Not Available
Port P: Not Available

Comment Remarks Location Equipment Function


Bay Control Unit 250 BCU

Designation : Input and Output Module IO202


1:IO202 Type : Part of 6MD85
Manufacturer : Siemens, Germany
Add. Info. 1 : 4 x Current Transformer (4 x Measure); 4 x Voltage Transformer
B BCU Add. Info. 2 : 8 x Binary Inputs DC 24 - 250V; 6 x Relay (6 x Fast), 250V AC DC, 5A B
I M 1A1 I M 1A2 I M 1A3 I M 1A4

1IL *

*
1A1
1A2

1A3
1A4

1A5
1A6

1A7
1A8
BCU /26.5 /26.5 /26.5 /26.5

V 1.1 V 1.2 V 1.3 V 1.4

C C
Last Used by: z004cv6p

1UL
Time: 5:46:11 PM
Date: 7/18/2022

1B1
1B2

1B3
1B4

1B5
1B6

1B7
1B8
BCU /26.5 /26.5 /26.5 /26.5

BI 1.1 BI 1.2 BI 1.3 BI 1.4 BI 1.5 BI 1.6 BI 1.7 BI 1.8


*

*
1BI

D D
1C13

1C14

1D10

1D13
1D11

1D14
1D12
1D1

1D2

1D5
1D3

1D6
1D4

1D7
1D9

1D8
BCU /31.6 /31.6 /27.5 /36.6 /36.6

BO 1.1 BO 1.2 BO 1.3 BO 1.4 BO 1.5 BO 1.6


132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 46

1B10

1B12

1B13

1C10
1C1

1C4
1C6

1C8

1BO
F

F
CopyRight (C) Siemens Limited, India All Rights Reserved.

1B11

1B14

1C2

1C3

1C7
1B9

BCU /31.5 /31.5 /31.5 /25.3


E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CONNECTION DIAGRAM FOR BCU SIK SS04 W10246
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 46 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <45 47>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257
Designation : Power Supply Module PS201
2:PS201 Type : Part of 6MD85
Manufacturer : Siemens, Germany
Add. Info. 1 : 3 x Binary Inputs DC 24 - 250V
BCU Add. Info. 2 : 2 x Relay, 1 Live Status, 250V AC DC, 5A
A A

LC

2B7
2B9
2PS

H
E

K
J
2B10
2B2
2B1
B BCU /27.5 /19.4 B
BI 2.1 BI 2.2 BI 2.3

*
2BI 2B12

2B14

2B13
2B11
BCU /27.5 /27.5 /27.5

BO 2.1 BO 2.2
2B4

2B6
2B8

C C
Last Used by: z004cv6p

2BO
Time: 5:46:37 PM

S
Date: 7/18/2022

2B3

2B5

BCU /25.3 /17.4

Designation : Input and Output Module IO205


3:IO205 Type : Part of 6MD85
Manufacturer : Siemens, Germany
Add. Info. 1 : 12 x Binary Inputs DC 24 - 250V
BCU Add. Info. 2 : 16 x Relay , 250V AC DC, 5A
D D
BI 3.1 BI 3.2 BI 3.3 BI 3.4 BI 3.5 BI 3.6 BI 3.7 BI 3.8 BI 3.9 BI 3.10 BI 3.11 BI 3.12
*

*
3BI
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 47

3A11

3A10
3A12

3A13

3A14

3B10
3A1
3A3

3A2
3A4

3A7
3A5

3A8
3A6

3A9

3B1

3B2

3B3
3B5

3B4
3B6

3B9
3B7

3B8
BCU /27.5 /27.5 /27.5 /27.5 /27.5 /27.5 /27.5 /27.5 /27.5 /27.5 /27.5 /27.5
CopyRight (C) Siemens Limited, India All Rights Reserved.

BO 3.1 BO 3.2 BO 3.3 BO 3.4 BO 3.5 BO 3.6 BO 3.7 BO 3.8 BO 3.9 BO 3.10 BO 3.11 BO 3.12 BO 3.13 BO 3.14 BO 3.15 BO 3.16
3B12

3B14

3C10

3C12

3C14

3D10

3D12

3D14
3C2

3C4

3C6

3C8

3D2

3D4

3D6

3D8
E E
3BO
S

S
3C11

3C13

3D11

3D13
3B11

3B13

3C1

3C3

3C5

3C7

3C9

3D1

3D3

3D5

3D7

3D9
BCU /22.4 /23.3 /24.3 /29.3 /29.3 /29.3 /29.3

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CONNECTION DIAGRAM FOR BCU SIK SS04 W10247
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 47 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <46 48>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257
Designation : Input and Output Module IO205
4:IO205 Type : Part of 6MD85
Manufacturer : Siemens, Germany
Add. Info. 1 : 12 x Binary Inputs DC 24 - 250V
BCU Add. Info. 2 : 16 x Relay , 250V AC DC, 5A
A A
BI 4.1 BI 4.2 BI 4.3 BI 4.4 BI 4.5 BI 4.6 BI 4.7 BI 4.8 BI 4.9 BI 4.10 BI 4.11 BI 4.12

*
4BI

4A11

4A10
4A12

4A13

4A14

4B10
4A1
4A3

4A2
4A4

4A7
4A5

4A8
4A6

4A9

4B1

4B2

4B3
4B5

4B4
4B6

4B9
4B7

4B8
BCU /31.6 /31.6 /31.6 /31.6 /32.6 /32.6 /32.6 /32.6 /32.6 /32.6 /27.5 /27.5

BO 4.1 BO 4.2 BO 4.3 BO 4.4 BO 4.5 BO 4.6 BO 4.7 BO 4.8 BO 4.9 BO 4.10 BO 4.11 BO 4.12 BO 4.13 BO 4.14 BO 4.15 BO 4.16

4B12

4B14

4C2

4C4

4C6

4C8

4C10

4C12

4C14

4D2

4D4

4D6

4D8

4D10

4D12

4D14
B B
4BO

S
4C11

4C13

4D11

4D13
4B11

4B13

4C1

4C3

4C5

4C7

4C9

4D1

4D3

4D5

4D7

4D9
BCU /31.5 /31.5 /31.5 /31.5 /31.5 /31.5 /32.5 /32.5 /32.5 /32.5 /32.5 /32.5 /32.5 /32.5 /32.5

Designation : Input and Output Module IO230


5:IO230 Type : Part of 6MD85
Manufacturer : Siemens, Germany
Add. Info. 1 : 48 x Binary Inputs DC 24 - 250V
C BCU Add. Info. 2 : C
Last Used by: z004cv6p

BI 5.1 BI 5.2 BI 5.3 BI 5.4 BI 5.5 BI 5.6 BI 5.7 BI 5.8


Time: 5:47:10 PM
Date: 7/18/2022

+
5BI 1-8

5A10
5A1

5A2

5A3

5A4

5A7

5A8

5A9

5A5
5A6
BCU /36.6 /36.6 /36.6 /36.6 /36.6 /36.6 /36.6 /36.6 /36.6

BI 5.9 BI 5.10 BI 5.11 BI 5.12 BI 5.13 BI 5.14 BI 5.15 BI 5.16

D D
5BI 9-16

5C10
5C1

5C2

5C3

5C4

5C7

5C8

5C9

5C5
5C6
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 48

BCU /36.6 /36.6 /36.6 /36.6 /36.6 /36.6 /36.6 /36.6 /36.6

BI 5.17 BI 5.18 BI 5.19 BI 5.20 BI 5.21 BI 5.22 BI 5.23 BI 5.24


CopyRight (C) Siemens Limited, India All Rights Reserved.

+
5BI 17-24

5D10
E E
5D1

5D2

5D3

5D4

5D7

5D8

5D9

5D5
5D6
BCU /37.6 /37.6 /37.6 /37.6 /37.6 /37.6 /37.6 /37.6 /37.6

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CONNECTION DIAGRAM FOR BCU SIK SS04 W10248
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 48 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <47 49>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

A A
BI 5.25 BI 5.26 BI 5.27 BI 5.28 BI 5.29 BI 5.30 BI 5.31 BI 5.32

+
5BI 25-32

5E10
5E1

5E2

5E3

5E4

5E7

5E8

5E9

5E5
5E6
BCU /37.6 /37.6 /37.6 /37.6 /37.6 /37.6 /37.6 /37.6 /37.6

BI 5.33 BI 5.34 BI 5.35 BI 5.36 BI 5.37 BI 5.38 BI 5.39 BI 5.40

B B
5BI 33-40

5G10
5G1

5G2

5G3

5G4

5G7

5G8

5G9

5G5
5G6
BCU /38.6 /38.6 /38.6 /38.6 /38.6 /38.6 /38.6 /38.6 /38.6

BI 5.41 BI 5.42 BI 5.43 BI 5.44 BI 5.45 BI 5.46 BI 5.47 BI 5.48


+

+
5BI 41-48

5H10
C C
5H1

5H2

5H3

5H4

5H7

5H8

5H9

5H5
5H6
Last Used by: z004cv6p

BCU /38.6 /38.6 /38.6 /38.6 /38.6 /38.6 /38.6 /38.6 /38.6
Time: 5:47:39 PM
Date: 7/18/2022

D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 49
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. CONNECTION DIAGRAM FOR BCU SIK SS04 W10249
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 49 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <48 50>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257

87L 50Z 67/67N


Designation Comment Sheet Ref. Designation Comment Sheet Ref. Designation Comment Sheet Ref.

A BI1 A/R BLOCK /W102/17.5 BI1 LBB 3-PH INITIATION /W102/20.5 BI1 DISTANCE PROTN. OPTD. /W102/19.6 A
BI2 GAS COMPT. ZONE TRIP /W102/17.5 BI2 CB GAS COMPT. ZONE TRIP /W102/20.5 BI2 SPARE /W102/19.6
BI3 CARRIER RECIEVE CH-1/2 /W102/40.4 BI3 CB OPEN /W102/20.5 BI3 Carrier Fail /W102/40.4
BI4 DIRECT TRIP RECIEVE CH-1/2 /W102/40.4 BI4 DC-1 UNHEALTHY /W102/20.5 BI4 SPARE /W102/19.6
BI5 DIRECT TRIP SEND CH-1/2 /W102/40.4 BI5 DC-2 UNHEALTHY /W102/20.5 BI5 SPARE /W102/19.6
BI6 CB CLOSE COMMAND /W102/17.5 BI6 Spare /W102/20.5 BI6 CARRIER RECIEVE /W102/40.4
BI7 CB OPEN /W102/17.5 BI7 ZONE-1/LINE DIFF. PROTN OPTD. /W102/20.5 BI7 DIRECT TRIP RECIEVE /W102/40.4
BI8 CB READY /W102/17.5 BI8 DIRECT TRIP RECIEVE CH-1/2
BI9 MANUAL TRIP /W102/19.6
BI10 BUSBAR OPTD. /W102/19.6
BI11 87L RELAY UNHEALTHY /W102/19.6
B B
BI12 BCU UNHEALTHY /W102/19.6
BI13 GAS COMPT. ZONE TRIP /W102/19.6
BI14 LBB OPTD. /W102/19.6
BI15 CB OPEN /W102/19.6
BI16 AUTO RECLOSURE OPTD. /W102/19.6

Designation Comment Sheet Ref.


BO1
BO2 DIRECTR TRIP SEND CH-1/2 /W102/40.4
BO3 CARRIER SEND CH-1/2 /W102/40.4
Designation Comment Sheet Ref.
BO4 TO 86.1 RELAY /W102/22.5
C BO1 Spare C
Last Used by: z004cv6p

BO5 TO 86.2 RELAY /W102/23.3


BO2 Spare
Time: 5:48:06 PM

BO6
Date: 7/18/2022

BO3 TO MUX. RELAY /W102/21.3


BO7 TO AUTO RECLOSURE /W102/35.4
BO4 TO TC-1 CKT. /W102/33.4
BO8
BO5 TO TC-2 CKT. /W102/34.4 Designation Comment Sheet Ref.
BO9
Live Live Status BO1 TO 86.1 RELAY /W102/22.5
BO10
BO2 TO 86.2 RELAY /W102/23.3
BO11 /W102/19.4
BO3 Spare
BO12 /W102/19.4
BO4 TO DT SEND CH-1/2 /W102/40.4
BO13 ZONE-1 OPTD. /W102/20.4
BO5 Spare
BO14 TO TC-1 CKT. /W102/33.4
BO6 SPARE
D D
BO15 TO TC-2 CKT. /W102/34.4
BO7 SPARE
Live Live Status /W102/27.4
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 50
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. BI & BO LIST FOR 87L,50Z & 67/67N SIK SS04 W10250
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 50 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <49 51>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257
BCU

Designation Comment Sheet Ref. Designation Comment Sheet Ref. Designation Comment Sheet Ref.

A BI 1.1 ISO 89B OPEN /W102/31.6 BI 3.1 TO 86.1 RELAY OPTD. /W102/27.5 BI 4.1 ISO 89A OPEN /W102/31.6 A
BI 1.2 ISO 89B CLOSE /W102/31.6 BI 3.2 TO 86.1 RELAY FAULTY /W102/27.5 BI 4.2 ISO 89A CLOSE /W102/31.6
BI 1.3 SPARE /W102/27.5 BI 3.3 TO 86.2 RELAY OPTD. /W102/27.5 BI 4.3 E/SW 89AE OPEN /W102/31.6
BI 1.4 BI 3.4 TO 86.2 RELAY FAULTY /W102/27.5 BI 4.4 E/SW 89AE CLOSE /W102/31.6
BI 1.5 BI 3.5 CARRIER PROTN. OUT /W102/27.5 BI 4.5 ISO 89L OPEN /W102/32.6
BI 1.6 CB OPEN /W102/36.6 BI 3.6 MANUAL OPEN /W102/27.5 BI 4.6 ISO 89L CLOSE /W102/32.6
BI 1.7 CB CLOSE /W102/36.6 BI 3.7 MANUAL CLOSE /W102/27.5 BI 4.7 E/SW 89LE1 OPEN /W102/32.6
BI 1.8 BI 3.8 67/67N UNHEALTHY /W102/27.5 BI 4.8 E/SW 89LE1 CLOSE /W102/32.6
BI 3.9 96 RELAY OPTD. /W102/27.5 BI 4.9 E/SW 89LE2 OPEN /W102/32.6

Designation Comment Sheet Ref. BI 3.10 96 RELAY FAULTY /W102/27.5 BI 4.10 E/SW 89LE2 CLOSE /W102/32.6

BO 1.1 ISO 89B OPEN /W102/31.5 BI 3.11 87L RELAY DC SUPPLY HEALTHY /W102/27.5 BI 4.11 50Z RELAY DC SUPPLY HEALTHY /W102/27.5
B BI 3.12 DC-2 FAIL /W102/27.5 BI 4.12 67/67N RELAY DC SUPPLY HEALTHY /W102/27.5
B
BO 1.2 ISO 89B CLOSE /W102/31.5
BO 1.3 ISO 89B I/L /W102/31.5
Designation Comment Sheet Ref. Designation Comment Sheet Ref.
BO 1.4
BO 3.1 TO 86.1 RESET /W102/22.4 BO 4.1 ISO 89A OPEN /W102/31.5
BO 1.5
BO 3.2 TO 86.2 RESET /W102/23.3 BO 4.2 ISO 89A CLOSE /W102/31.5
BO 1.6 CB TRIP /W102/25.3
BO 3.3 TO 96 RESET /W102/24.3 BO 4.3 ISO 89A I/L /W102/31.5
BO 3.4 VT SELECTION CIRCUIT /W102/29.3 BO 4.4 E/SW 89AE OPEN /W102/31.5
BO 3.5 VT SELECTION CIRCUIT /W102/29.3 BO 4.5 E/SW 89AE CLOSE /W102/31.5
BO 3.6 VT SELECTION CIRCUIT /W102/29.3 BO 4.6 E/SW 89AE I/L /W102/31.5
BO 3.7 VT SELECTION CIRCUIT /W102/29.3 BO 4.7 ISO 89L OPEN /W102/32.5
BO 3.8 SPARE BO 4.8 ISO 89L CLOSE /W102/32.5
C Designation Comment Sheet Ref. C
Last Used by: z004cv6p

BO 3.9 SPARE BO 4.9 ISO 89L I/L /W102/32.5


BI 2.1 TC-1 FAULTY /W102/27.5
BO 3.10 SPARE BO 4.10 E/SW 89LE1 OPEN /W102/32.5
Time: 5:48:37 PM

BI 2.2 TC-2 FAULTY /W102/27.5


Date: 7/18/2022

BO 3.11 SPARE BO 4.11 E/SW 89LE1 CLOSE /W102/32.5


BI 2.3 DC-1 FAIL /W102/27.5
BO 3.12 SPARE BO 4.12 E/SW 89LE1 I/L /W102/32.5
BO 3.13 SPARE BO 4.13 E/SW 89LE2 OPEN /W102/32.5
Designation Comment Sheet Ref.
BO 3.14 SPARE BO 4.14 E/SW 89LE2 CLOSE /W102/32.5
BO 2.1 CB CLOSE /W102/25.3
BO 3.15 SPARE BO 4.15 E/SW 89LE2 I/L /W102/32.5
BO 2.2 CB READY /W102/17.4
BO 3.16 SPARE BO 4.16 SPARE

D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 51
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. BI & BO LIST FOR BCU SIK SS04 W10251
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 51 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <50 52>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet Version: 0
DB Version: SL-0-7/1/2015
E-Base Version: 7.0.0.1257
BCU

Designation Comment Sheet Ref. Designation Comment Sheet Ref. Designation Comment Sheet Ref.
BI 5.1 CB LOCAL MODE /W102/36.6 BI 5.17 DS S2 MOTOR MCB TRIP /W102/37.6 BI 5.33 ZONE TRIPPING IN CB CHAMBER /W102/38.6
A BI 5.2 CB REMOTE MODE /W102/36.6 BI 5.18 FES MOTOR MCB TRIP /W102/37.6 BI 5.34 ZONE TRIPPING IN DES1 /W102/38.6 A
BI 5.3 CB UNLOCK /W102/36.6 BI 5.19 DES MOTOR MCB TRIP /W102/37.6 BI 5.35 ZONE TRIPPING IN DES2 /W102/38.6
BI 5.4 CB INTERLOCK /W102/36.6 BI 5.20 SIGNAL POWER MCB TRIP /W102/37.6 BI 5.36 ZONE TRIPPING IN DES3 /W102/38.6
BI 5.5 SPRING CHARGEGING MOTOR FOR… /W102/36.6 BI 5.21 DES3 MOTOR MCB TRIP /W102/37.6 BI 5.37 ZONE TRIPPING IN BUS DUCT CHA… /W102/38.6
BI 5.6 SPRING CHARGEGING MOTOR FOR… /W102/36.6 BI 5.22 ILLUMINATION HEATER MCB TRIP /W102/37.6 BI 5.38 SPARE /W102/38.6
BI 5.7 SPRING CHARGEGING MOTOR FOR… /W102/36.6 BI 5.23 DC POWER SINGAL /W102/37.6 BI 5.39 SPARE /W102/38.6
BI 5.8 SPRING CHARGEGING MOTOR FOR… /W102/36.6 BI 5.24 GAS COMP. ZONE TRIP /W102/37.6 BI 5.40 SPARE /W102/38.6

Designation Comment Sheet Ref. Designation Comment Sheet Ref. Designation Comment Sheet Ref.
B BI 5.9 SF6 GAS IN CB CHAMBER (ALARM) /W102/36.6 BI 5.25 GAS TIGHT SIGNAL /W102/37.6 BI 5.41 SPARE /W102/38.6 B
BI 5.10 SF6 GAS IN CB CHAMBER (LOCKOUT) /W102/36.6 BI 5.26 GAS REFIL SIGNAL IN CB CHAMBER /W102/37.6 BI 5.42 SPARE /W102/38.6
BI 5.11 SF6 GAS IN DES1 CHAMBER (ALARM) /W102/36.6 BI 5.27 GAS REFIL SIGNAL IN DES1 CHAMB… /W102/37.6 BI 5.43 SPARE /W102/38.6
BI 5.12 SF6 GAS IN DES2 CHAMBER (ALARM) /W102/36.6 BI 5.28 GAS REFIL SIGNAL IN DES2 CHAMB… /W102/37.6 BI 5.44 SPARE /W102/38.6
BI 5.13 SF6 GAS IN DES3 CHAMBER (ALARM) /W102/36.6 BI 5.29 GAS REFIL SIGNAL IN DES3 CHAMB… /W102/37.6 BI 5.45 SPARE /W102/38.6
BI 5.14 SF6 GAS IN BUS DUCT CHAMBER (A… /W102/36.6 BI 5.30 GAS REFIL SIGNAL IN BUS DUCT CH… /W102/37.6 BI 5.46 SPARE /W102/38.6
BI 5.15 CB CHARGING MOTOR MCB TRIP /W102/36.6 BI 5.31 SPARE /W102/37.6 BI 5.47 SPARE /W102/38.6
BI 5.16 DE S1 MOTOR MCB TRIP /W102/36.6 BI 5.32 SPARE /W102/37.6 BI 5.48 SPARE /W102/38.6

C C
Last Used by: z004cv6p

Time: 5:49:02 PM
Date: 7/18/2022

D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 52
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. BI & BO LIST FOR BCU SIK SS04 W10252
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 52 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <51 53>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-0.1-1/10/2012
Sheet Version: 0.1
E-Base Version: 7.0.0.1257

SIGNALS TAKEN AS GOOSE MESSAGES ARE SHOWN WITH TICK MARK.

DIST. RELAY BAY CONTROL UNIT


A 21 (LINE-1) BCU (LINE-1) A

CARRIER OUT

CARRIER CH-1/2 FAIL

CB READY

B B
LINE UNDER
VOLTAGE

C C
Last Used by: z004cv6p

Time: 5:49:13 PM
Date: 7/18/2022

D D
132/66kV SAMARDONG S/S 132kV BAY-102 (LINE-2) LINE-102 W102 53
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC 1.5 GY F


C QT Corrected 7/12/2022 HRD Date 4/27/2017 132/66kV SAMARDONG S/S BAY-102 (LINE-2) Customer Dwg No. P2 W 102R 1 mm. : 1 mm.
B Client Comments 1/20/2021 NR Drawn By PRT POWER GRID CORPORATION OF INDIA LTD. LIST OF GOOSE MESSAGE SIK SS04 W10253
A Customer Cmnts. 12/17/2021 BST Chkd By HEM Sh. 53 of 52
3005082555 (3)G719EA-JG9127-W102
Revision Remarks Date Name Appr GCB Orig.: Replaces: Replaced by: Wiring Schematics <52 ->
1 2 3 4 5 6 7 8