C-9201
C-9201
Technical Specifications
• Standard: EN54-part 11
• Approval: CE
• Protection rating: IP 40
• Operating voltage: 24Vdc Loop
• Operating current:
Standby current 0.8mA
Alarm Current 2mA
• Operating temperature: -10°C to
+50°C
• N/O Output contact: 60Vdc, 0.1A
• Contact resistance: 100mΩ
• Relative humidity: 95%
• Application: Indoor use
Features and Benefits • Visual Indicator: LED, Red ( lit
1. Re-settable (non-breaking glass) steady when alarm, 3 sec interval
2. Additional volt free contact blinking at normal state)
3. Friendly installation and test • Material and colour: ABS, red
• Wiring: 1 pair polarized
Description • Dimensions: 90x122x48.5mm
Designed for the purpose of raising an alarm
manually once verification of a fire or Mounting Base
emergency condition exists, by pressing the The location of manual call point should be
non breakable glass. Meets the standard installed in compliance with all local codes
requirement of EN 54 part 11, European and / or NFPA 72 National Fire Alarm Code,
Standard and approved by Loss Prevention NFPA 70 National Electrical Code. Surface
Certificate Board (LCPB). mount and it is installed onto a standard
The C-9201 constructed of high impact red
ABS with a modern pleasing appearance. The I−9201
WALL
terminating back box enables first fix
installation and termination leaving the fascia FIRE
ELECTRICAL
with integral electronics to be simply plugged BACK BOX
PANEL
1 2
Note: Specifications are subject to change without notice.
K1 K2
−
OR
ZONE
MONITOR
TO NEXT DETECTOR
MODULE
I+ I− O− 0+
4 3 OR
AEOL