SDM630MCT_series_Datasheet_May22
SDM630MCT_series_Datasheet_May22
•T
hree Phase 1/5A Current • Configurable Pulsed output
Transformer operated (Import/ Export / Nett kWh)
• MID B+D Certified • Modbus (SDM630MCT) or
Mbus (SDM630MCT-Mbus)
• UL Registered
• Multi Parameter measurement
•A
ccuracy Class 1.0 (Active
Energy) or Accuracy Class 0.5 • Multi-Tariff
(SDM630MCT-MOD-MID-0.5)
• 0.333mV Current Transformer
•B
i-directional Measurement input option (NON MID)
for kW and kWh
• Free Configuration software
Specification table
Specification Accuracy
Nominal voltage(Un) 3x230/400 V ac Voltage,Current 1.0 % or 0.5% option available
Operational voltage 80% - 120% of Un. Frequency 0·2% of mid-frequency
Insulation capabilities Power factor 1% of unity (0.01)
- AC voltage withstand 4KV for 1 minute Active power , Apparent power ±1% of range maximum
- Impulse voltage withstand 6KV-1.2µS Reactive power ±1% of range maximum
Rated current (Ib) 5A CT or 333mV CT input Reactive energy(Varh) Class 2
Operational current range 0.4% Ib-Imax Active energy (Wh) Class 1
Over current withstand 20 Imax for 0.01s
Modbus
Operational frequency range 50 or 60Hz
Bus type RS485(semi-duplex)
Power consumption per phase ≤ 2W/10VA
Protocol Modbus RTU
Pulse output 1 Configurable
Baud rate 2400/4800/9600/19200/38400bps
Pulse output 2 3200 imp/kWh
Address range 1-247
Display LCD
Max. Bus loading 64pcs
Max reading 9999999.9 kWh/kVarh
Communication distance 1000M
Performance criteria Parity EVEN/ODD/NONE
Operating humidity ≤ 90% Data bit 8
Storage humidity ≤ 95% Stop bit 1
Operating temperature -25°C - +55°C
M-bus
Storage temperature -40°C - +70°C
Bus type M-bus
Reference temperature 23°C± 2°C
Protocol EN13757-3
International standard IEC 62053-21 / EN50470-1/3
Baud rate 300/600/1200/2400/4800/9600
Accuracy class Class1/Class B
Parity NONE/EVEN/ODD
Installation category CAT III
Stop bits 1 or 2
Mechanical environment M1
Primary Address 1 to 250
Electromagnetic environment E2
Secondary Address 00 00 00 01 to 99 99 99 99
Degree of pollution 2
Protection against penetration of dust and water IP51(indoor)
Insulating encased meter of protective class II
Electrostatic discharges 8kV contact / 15kV air gap
Radiated & conducted emissions EN 55022
Ordering options
Ordering
Meter Type
options
Description of Meter
SDM630MCT-Modbus 3PH-4W, 3PH-3W, 1PH-2W, 3x230(400)V, 1A or 5A CT input, Class 1.0 50/60Hz, backlighted LCD display, 2 pulse outputs,
RS485 Modbus RTU. Measures kWh, kVarh, W, Var, VA, V, A, PF, THD, Hz, Max.DMD, Imp_kWh, Exp_kWh etc.
SDM630MCT-MODBUS-0.5 3PH-4W, 3PH-3W, 1PH-2W, 3x230(400)V, 1A or 5A CT input, Class 0.5 50/60Hz, backlighted LCD display, 2 pulse outputs,
RS485 Modbus RTU. Measures kWh, kVarh, W, Var, VA, V, A, PF, THD, Hz, Max.DMD, Imp_kWh, Exp_kWh etc.
SDM630MCT-Mbus 3PH-4W, 3PH-3W, 1PH-2W,, 3x230(400)V, 1A or 5A CT input, 50/60Hz, backlighted LCD display, 2 pulse outputs,
M-Bus EN13757-3. Measures kWh, kVarh, W, Var, VA, V, A, PF, THD, Hz, Max.DMD, Imp_kWh, Exp_kWh etc
SDM630MCT-2T 3PH-4W, 3PH-3W, 1PH-2W,, 3x230(400)V, 1A or 5A CT input, 50/60Hz, backlighted LCD display, 2 pulse outputs,
Rs485 Modbus RTU, 2 Tariffs. Measures kWh, kVarh, W, Var, VA, V, A, PF, THD, Hz, Max.DMD, Imp kWh, Exp_kWh etc.
SDM630MCT-MV 3PH-4W, 3PH-3W, 1PH-2W, 3x230(400)V, 333mV CT input, 50/60Hz, backlighted LCD display, 2 pulse outputs,
RS485 Modbus RTU. Measures kWh, kVarh, W, Var, VA, V, A, PF, THD, Hz, Max.DMD, Imp_kWh, Exp_kWh etc.
Conformity References
Electromagnetic Compatibility: EN61326-1:2013 & EN61326-2-3:2013
Low Voltage Directive: EN61010-1-2010 & EN61010-2-30-2010
MID DIRECTIVE: 2014/32/EU