Audit Format edit
Audit Format edit
Annexure-A
INSTALLATION DETAILS
LOCATION: …………………………………………………………………
INSTALLATION INCHARGE:………………………………………………………………
AUDIT DETAILS
Annexure-B
Pre-Audit Format
Annexure-B1
Detail of MDB/LT Panel/Emergency Panel/DB
1 Sr. No. of MDB/LT Panel/Emergency
Panel/DB
2 Year of Commissioning
3 Wall Mounted or Floor Mounted
4 Height from floor
5 IP protection
6 Bus Bar Type (Copper/Aluminium)
7 Size of Bus Bar (Width x Thickness)
8 Detail of feeder as per below detail
Type Cable connected to circuit
(ACB/
Breakin If MCCB Installatio
MCCB Detail of
Ratin No. g than Typ n Method
Name of /MCB/ location of Approxim
g in of Capacit fixed/ e/ Si (to be
Feeder Fuse/ DB/FDB/ ately
Amp. Poles y (In variable Cor ze checked
Changeo Load Length
KA) type e as per
ver
switch) Vol.5
(i) Incoming
(ii) Bus Coupler
(iii) Change over
switch
(iv) Outgoing
Circuit
No.1(X1)
(v) Outgoing
Circuit No.2
(X2)
(vi) Outgoing
Circuit No.3
(X3)
(vii Outgoing
) Circuit No.4
(X4)
Annexure-B2
Detail of FDB/EmergencyFDB
1 Sr.No. of FDB/ Emergency
FDB
2 Year of Commissioning
3 IP protection
4 Type (Copper/Aluminium)
Bus Bar
5 Size of Bus Bar (Width
Thickness)
6 Detail of feeder as per
below detail
Name of Connecti Type Ratin No. Breakin Detail Wire connected to Load/MS
Feeder on load (MCCB g in of g of Box
(In KW) /MCB/ Amp. Pole Capacit locatio Typ Siz Length Installat
Fuse/) s y (In n of e e from ion
KA) Load feeder Method
to Load (to be
checked
as per
Vol.5
(i) Incoming
(ii) Circcuit-1
(iii) Circcuit-2
(iv) Circcuit-3
(v) Circcuit-4
Annexure-1.1
19
SAFETY IN ELECTRICAL LOW VOLTAGE INSTALLATIONS
20
SAFETY IN ELECTRICAL LOW VOLTAGE INSTALLATIONS
21
SAFETY IN ELECTRICAL LOW VOLTAGE INSTALLATIONS
Annexure-1.2
Visual Inspection of Room
Name or Sr.No of Room:-
22
SAFETY IN ELECTRICAL LOW VOLTAGE INSTALLATIONS
23
SAFETY IN ELECTRICAL LOW VOLTAGE INSTALLATIONS
24
SAFETY IN ELECTRICAL LOW VOLTAGE INSTALLATIONS
Annexure-1.3
Coordination between conductor & Protective Device for Over load
Protection
Name or Sr.No of MDB/DB:
S. Name of Circuit Tripping Conductor connected to circuit Observati Recomme
N Feeder protecti Current Detail Installation Current on ndation
on due to of Method (to be rating of
(MCCB/M overload conduc checked as conductor
CB/ (1.45x tor per after
FUSE) rating of (type/c Annexure- VII applying
(Type/Ra MCB or ore/ of Vol.5 all
ted 1.3 x Size) "Selection of reduction
Current) rating of power cable factors
MCCB) in LV
Installation"
1
2
10
11
12
13
14
15
16
17
18
19
20
21
22
Annexure-1.4
Coordination between Load & Protective Device
Name or Sr.No of FDB:
Name of Connected fixed load Type &Rating Observation Recommendat
Feeder (In watt/ Amp) of /MCB/Fuse ion
(i) Circcuit-1
(ii) Circcuit-2
(iii) Circcuit-3
(iv) Circcuit-4
(v) Circcuit-5
(vi) Circcuit-6
Note:-
Annexure-2.1
Continuity Test
Name or Sr. No of MDB/DB/FDB:
Tester Type:Clamp meter Sigma Make Sr.No. Of Tester-SG678TRMS
S.N. Circuit Detail of Protective conductor PE continuity Observati Recommendat
No. (type/core/Size)connected to on ion
Load
R1 (Protective
Conductor)
1 1
2 2
3 3
4 4
5 5
6 6
Note:
Annexure-2.2
Insulation Resistance Test
Name or Sr.No of MDB/DB/SDB:- 12 Way MCB Distribution Box
Test Voltage:- 500 Volt DC Sr.No. of Megger
2205102636
S. Circuit/ Size(Sq.mm)/ Insulation Resistance (M-Ohm) Observati Recommendat
N Outgoing No. Type(PVC/ on ion
For 1-ø (For 3ø P-P (for 3ø
XLPE)/
shoring all phase Only)
Core(1/2/3/3.
and test
5/4) of
between :-
conductor
(i) Shorting phase
(P) & Neutral(N)
(ii) Shorting phase
(P) & Earth (E)3
P-N P-E N-E R-Y Y-B B-R
1 1
2 2
3 3
4 4
5 5
6 6
Note:-
1. Testing method given in Para 3 of volume-4 on “Testing of Electrical LV Installations” under the
under the series “Safety in Electrical Low Voltage Installations.
2. For 3-phase circuit at first all 3-phase (R/Y/B) will be shorted and the insulation resistance to be
checked between Shorting phase (P) to Neutral(N) and Shorting phase (P) to Earth (E).If value of
insulation resistance not as per table in S.N.1, than insulation resistance to be checked individually
(R-N/Y-N/B-N).
Annexure-2.3
Fault Loop Impedance and Prospective Fault Current
Name or Sr.No of MDB/DB/SDB: N/A
Tester Type:- Sr.No. Of Tester
S Circ Circuit Conductor Fault Fault Observation Recommendation
. uit protect connected to Loop Loop
N No. ion Load Impeda Current
. (MCCB/ nce
MCB/ Detail of Detail L-N L- L- L- Regardin Regardin Regardi Regardin
FUSE) Line of PE N PE g tripping g short ng g short
(Type/R conduct Protecti of circuit tripping circuit
ated or ve Protectiv capacity of capacity
Current (type/co conduct e Device of Line & Protecti of Line &
) re/ Size) or (MCCB/M Protectiv ve Protectiv
CB/ FUSE) e Device e
Conducto (MCCB/ Conducto
r MCB/ r
FUSE)
Note:-
1. Testing method for fault loop impedance & prospective Fault Loop Current given in Para 5.1 of
volume-4 on “Testing of Electrical LV Installations” under the under the series “Safety in
Electrical Low Voltage Installations.
2. Checking of type and capacity of MCB for particular fault loop impedance are given in para 5.3.2
of volume-2 on “Selection and Application of LV Protective Devices” under the under the series
“Safety in Electrical Low Voltage Installations.
3. Instantaneous Tripping current of MCCB under short circuit & earth fault condition can be find
out from the time-current characteristic graph of MCCB, which may be received from the
catalogue/Manufacturer of MCCB. This tripping current may be compared with the testing fault
loop impedance/current for checking of tripping of MCCB.
4. Checking of Size of line & protective conductor are suitable for short circuit /Earth fault current
are given in Anneure-5 of volume-3 on “Inspection of Electrical LV Installations”& Para 3.2.8 of
volume-5 on “Selection of Power Cables in Electrical LV Installations” under the series “Safety in
Electrical Low Voltage Installations.
Annexure-2.4
Note:-
1. Testing method for RCD testing given in Para 6 of volume-4 on “Testing of Electrical LV
Installations” under the under the series “Safety in Electrical Low Voltage Installations.
Annexure-2.5
Polarity Test
Name or Sr.No of MDB/DB/SDB:- 12 Way MCB distribution Box
3 03
4 04
5 05
6 06
Note:-
1. Detail of Polarity Test given in Para 7 of volume-4 on “Testing of Electrical LV Installations” under
the under the series “Safety in Electrical Low Voltage Installations.
Note:-
1. Load unbalancing test may be checked any tongue tester. It may be also checked from 3-phase
measuring instrument (Ammeter), (If 3-phase measuring instrument are available on MDB/DB/FDB)