Five common steam line sizing errors _ Plant Engineering
Five common steam line sizing errors _ Plant Engineering
errors
When operating a boiler for process or building heat, engineers deal
with a dynamic system. Phase changes, mass and energy balances,
mixed-phase flows, non-Newtonian compressible gases, changes in
pressure and velocity, and production-based or seasonal load swings
are characteristics of this complex system.
BY VINCENT FERGUSON & ALAN STANDERWICK, SPIRAX SARCO, INC., BLYTHEWOOD,
SC MAY 1, 2005
Key Concepts
Improperly sized distribution piping can raise pressure drops or increase heat loss.
Undersized piping after pressure reducing valves can cause erosion of components.
Undersized piping after steam traps can cause water hammer.
When operating a boiler for process or building heat, engineers deal with a dynamic system. Phase
changes, mass and energy balances, mixed-phase flows, non-Newtonian compressible gases,
changes in pressure and velocity, and production-based or seasonal load swings are characteristics
of this complex system.
Across the breadth of steam systems field engineers encounter, most steam systems are far from
perfect. Some problems result from inadequate design and some developed in the course of
expansions or modifications. Many of the problems involve incorrect steam and condensate line pipe
sizing (see “Pipe friction data”).
The effects of these errors range from noise and erosion to equipment damage, erratic process
control, safety hazards, and higher fuel costs. Understanding the causes and effects of these errors
can go a long way to minimizing damage and improving the reliability of the system.
Noise is not the sole issue. Only where appreciable superheat (dry gas) is employed should velocities
exceed 120 ft/sec.
Problems can occur when it is decided that boiler pressure can be changed without consideration of
the existing pipe size. The most cost-effective method is to run the boiler at its design pressure and
reduce the pressure at the point of usage.
Assume it is planned to set a 3450 lb/hr (100 hp) rated boiler at the 50-psig requirements of the
process systems. The resulting steam would occupy a volume of 6.7 ft3/lb. For acceptable velocities
this pressure setting would require a 4-inch steam line (Sch. 40). However, if the same boiler is set at
200 psig, steam tables show the volume reduces to 2.14 ft3/lb, requiring only a 2-inch steam pipe.
Look at the economic impact. A 200-foot, 4-inch, Sch. 40 main steam line would cost three times
more than a 200-foot, 2-inch main line.
Velocity through the pressure reduction station must be considered when sizing fittings and
components. Designers sizing these lines often fail to properly consider the significant increase in
specific volume of steam with reduced pressure. If the designer had checked the specific volume at
the two pressures, he would have seen that the steam at reduced pressure occupies more volume,
and the outlet piping has to be a minimum of 4-inch to maintain reasonable velocity.
This error would result in much higher steam velocities downstream of the PRV and a high level of
noise. The high velocity could cause premature erosion of the outlet piping and downstream
components.
Pipe sizing for condensate recovery takes on a new dimension: two-phase flow brought about by the
larger effective volume and reduced pressure of the condensate system. When hot condensate under
pressure is released to a lower pressure, its temperature must drop very quickly to the boiling point
for the lower pressure. This sensible heat released from the liquid condensate causes some re-
evaporation into flash steam, and the two phases are present in the condensate system.
If the condensate pipes are undersized by neglecting the presence of flash steam, the result is
increased back pressure and velocity, this time with a liquid phase that could lead to water hammer.
Severe water hammer can cause damage to steam system pipes, equipment, and personnel.
Increased back-pressure can create problems with process equipment.
First, keep in mind which part of the steam system is being assessed:
Since steam is a compressible gas; pressure and volume are inversely proportional. As steam
pressure increases, the volume of space it occupies (specific volume) decreases. Steam tables and
pressure/specific volume graphs (Fig. 1) are useful in quantifying the relationship between steam
pressure and volume to size piping correctly.
Piping should be sized with consideration for fluid velocity and pressure drop. For velocity, the
relationships among the saturated steam velocity, specific volume, and pipe diameter is:
V = (2.4QVs)/A
where:
V = Velocity, ft/min
To size by pressure drop, make use of a variation of the D’Arcy Equation that calculates pressure loss
due to friction for straight pipe of constant diameter for fluids of reasonably constant density.
dP = (pfLv 2 )/(144D2g)
where:
L = Length of pipe, ft
Since the values for ‘f’ are complex, they are generally obtained from tables.
Constant velocity after PRVs
Downstream piping cross-sectional area must be larger by the same ratio as the change in volume.
Consult steam tables for the specific volume of saturated steam for the two pressures, then calculate
the ratio of the downstream pressure to the upstream pressure (always greater than 1).
Use the velocity equation to solve for cross sectional area of the high-pressure side for the design
velocity and flow rate. Then multiply the cross sectional area by the ratio to figure what the cross
sectional area of the low-pressure side should be. Use pipe size tables to find a pipe diameter for the
pipe schedule being used.
Line velocity of no more than 50 to 66 ft/sec is recommended for condensate return lines and vent
pipes. Sizing programs and nomographs are available that combine sizing calculations for the size of
a flash vessel, condensate line, and flash steam vent line in one chart (Fig. 2). This can help to
correctly size all two-phase flow components.
Check the capacity of installed condensate pumps in relation to return line flow rates. Electric pumps
are usually sized with a pumping capability of 2
These sizing considerations underscore the importance of auditing a steam system periodically,
especially whenever process equipment is altered, or boiler ratings or operating conditions are
changed. This inexpensive process and the resulting optimization measures can preserve plant
efficiency, maintainability, and safety.
More Info:
Questions about steam line sizing should be directed to 800-833-3246. For more information on
allowing for flash steam in piping refer to Design of Fluid Systems-Hook-Ups, Spirax Sarco, Inc., 12th
edition. Article edited by Joseph L. Foszcz, Senior Editor, 630-288-8776, [email protected] .
Undersized piping downstream of pressure reducing valves, from failing to consider changes in steam
velocity and specific volume.
Undersized condensate piping downstream of traps, ignoring the presence of two-phase flow.
Improperly sized condensate return lines, from failure to differentiate between pressurized and
pumped condensate.