NH 100 DN - 6997
NH 100 DN - 6997
NH-100(A) Series
Intelligent Addressable Thermal
Detectors for FireWarden Series
Addressable
General
The NOTIFIER NH-100(A) Series thermal detectors are
addressable sensors that use a state-of-the-art thermistor
sensing circuit for fast response. These sensors provide open-
area protection and are intended for use with FireWarden
Series (FireWarden-100-2 and FireWarden-50) and Spartan
(NSP-25) addressable Fire Alarm Control Panels (FACPs).
The NH-100(A) and NH-100R(A) sensors provide fixed tem-
perature alarm detection at 135°F (57°C). The NH-100R(A)
sensor also responds to rate-of-rise conditions of greater than
15°F (8.3°C) per minute. The NH-100H(A) is a fixed high-tem-
B210-2251.jpg
perature detector that activates at 190°F (88°C). These ther-
mal detectors provide addressable property protection in a
variety of applications.
NH-100(A) in B210LP(A) Base
Two LEDs on each sensor light to provide a local, visible sen-
sor indication. Remote LED annunciator capability is available
using an optional accessory, the RA100Z. • Low standby current.
• 94-5V plastic flammability rating.
Features Options:
SLC loop: • Remote LED output connection to optional RA100Z remote
LED annunciator.
• Two-wire SLC loop connection.
• Flanged surface mounting kit.
• Unit uses base for wiring.
Addressing:
Installation
• Addressable by device.
NH-100(A) Series plug-in intelligent thermal detectors use a
• Rotary, decimal addressing: 01 – 99 with FireWarden-100- detachable base to simplify installation, service and mainte-
2, NSP-25, 01 – 50 with FireWarden-50. nance. Installation instructions are shipped with each detector.
Architecture:
Mount base (all base types) on an electrical backbox which is
• Sleek, low-profile, stylish design. at least 1.5" (3.81 cm) deep. For a chart of compatible junction
• State-of-the-art thermistor technology for fast response. boxes, see DN-60054.
• Integral communications and built-in device-type identifica- NOTE: Because of the inherent supervision provided by the SLC
tion. loop, end-of-line resistors are not required. Wiring “T-taps” or
branches are permitted for Style 4 (Class “B”) wiring only.
• Built-in tamper resistant feature.
• Built-in functional test switch activated by external magnet.
Applications
Operation:
Use thermal detectors for protection of property.
• Factory preset at 135°F (57°C) for the NH-100(A) and NH-
100R(A); 190°F (88°C) for the NH-100H(A).
Construction
• Rate-of-rise triggers at 15°F (8.3°C) per minute for the NH-
100R(A). These detectors are constructed of off-white fire-resistant
• 360°-field viewing angle of the visual alarm indicators (two plastic. The NH-100(A) Series plug-in intelligent thermal
bicolor LEDs). LEDs blink red in Normal condition and turn detectors are designed to commercial standards and offer an
on steady red in Alarm. attractive appearance.
• Visible LEDs “blink” every time the unit is addressed.
Mechanicals:
Operation
Each NH-100(A) Series detector uses one of 99 (FireWarden-
• Sealed against back pressure.
100-2, NSP-25) or 50 (FireWarden-50) possible addresses on
• SEMS screws for wiring of the separate base. a control panel SLC loop. It responds to regular polls from the
• Designed for direct-surface or electrical-box mounting. control panel and reports its type and the status. If it receives a
• Plugs into separate base for ease of installation and main- test command from the panel (or a local magnet test), it stimu-
tenance. lates its electronics and reports an alarm. It blinks its LEDs
when polled and turns the LEDs on when commanded by the
• Separate base allows interchange of photoelectric, ioniza-
panel. The NH-100(A) Series offers features and performance
tion and thermal sensors.
that represent the latest in thermal detector technology.
Other system features:
• Remote test feature from the panel.
• Walk test with address display.