0% found this document useful (0 votes)
76 views18 pages

Belimo EV..R2 BAC Datasheet En-Gb

Uploaded by

abhisharma021
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
76 views18 pages

Belimo EV..R2 BAC Datasheet En-Gb

Uploaded by

abhisharma021
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

Technical data sheet EV..

R2+BAC

Characterised control valve with thermal energy


meter, sensor-operated flow or power control,
power and energy monitoring function, 2-way,
internal and external thread, PN 25

• Nominal voltage AC/DC 24 V


• Control modulating, communicative, hybrid
• For closed chilled and hot water systems
• For modulating control of air-handling and
heating systems on the water side
• Ethernet 10/100 Mbit/s, TCP/IP, integrated
web server
• Communication via BACnet, Modbus, Belimo
MP-Bus or conventional control
• PoE (Power over Ethernet) Power supply
possible
• Conversion of sensor signals
• Glycol monitoring
• Power control, flow control, position control
and differential pressure control

Type Overview

Type DN Rp G V'nom V'nom V'nom Kvs theor. PN


["] ["] [l/s] [l/min] [m³/h] [m³/h]
EV015R2+BAC 15 1/2 3/4 0.42 25 1.5 3.2 25
EV020R2+BAC 20 3/4 1 0.69 41.7 2.5 5.3 25
EV025R2+BAC 25 1 1 1/4 0.97 58.3 3.5 8.8 25
EV032R2+BAC 32 1 1/4 1 1/2 1.67 100 6 14.1 25
EV040R2+BAC 40 1 1/2 2 2.78 166.7 10 19.2 25
EV050R2+BAC 50 2 2 1/2 4.17 250 15 30.4 25
Kvs theor.: theoretical Kvs value for pressure drop calculation

Structure

Components The Belimo Energy Valve consists of a characterised control valve, an actuator and a thermal
energy meter with a logic and a sensor module.
The logic module provides the power supply, the communication interface and the NFC
connection of the energy meter. All relevant data are measured and recorded in the sensor
module.
This modular design of the energy meter means that the logic module can remain in the
system if the sensor module is replaced.

External temperature sensor T1


Integrated temperature sensor T2
Logic module 1
Sensor module 2
Characterised control valve with actuator 3

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 1 / 18


Technical data sheet EV..R2+BAC

Technical data

Electrical data Nominal voltage AC/DC 24 V


Nominal voltage frequency 50/60 Hz
Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V
Power consumption in operation 4 W (DN 15, 20, 25)
5 W (DN 32, 40, 50)
Power consumption in rest position 3.7 W (DN 15, 20, 25)
3.9 W (DN 32, 40, 50)
Power consumption for wire sizing 6.5 VA (DN 15, 20, 25)
7.5 VA (DN 32, 40, 50)
Connection supply / control Cable 1 m, 6x 0.75 mm²
Connection Ethernet RJ45 socket
Power over Ethernet PoE DC 37...57 V
11 W (PD13W)
IEEE 802.3af/at, Type 1, Class 3
Conductors, cables AC/DC 24 V, cable length <100 m, no shielding
or twisting required
Shielded cables are recommended for supply
via PoE

Data bus communication Communicative control BACnet/IP, BACnet MS/TP


Modbus TCP, Modbus RTU
MP-Bus
Cloud
Number of nodes BACnet / Modbus see interface description
MP-Bus max. 8

Functional data Operating range Y 2...10 V


Input impedance 100 kΩ
Operating range Y variable 0.5...10 V
Position feedback U 2...10 V
Position feedback U note Max. 1 mA
Position feedback U variable 0...10 V
0.5...10 V
Sound power level Motor 35 dB(A) (DN 15, 20, 25, 32, 40)
45 dB(A) (DN 50)
V'max adjustable 25...100% of V'nom
Control accuracy ±5% (of 25...100% V'nom)
Control accuracy note ±10% (of 25...100% V'nom) @ Glycol 0...60%
vol.
Min. controllable flow 1% of V'nom
Parametrisation via NFC, Belimo Assistant 2
via integrated web server
Fluid Chilled and hot water, water with glycol up to
max. 60% vol.
Fluid temperature -10...120°C [14...248°F]
Fluid temperature note At a fluid temperature of -10...2°C, a spindle
heater or a valve neck extension is
recommended.
The allowed fluid temperature can be limited,
depending on the type of actuator. Limitations
can be found in the respective data sheets of
the actuators.
Close-off pressure ∆ps 1400 kPa psi

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 2 / 18


Technical data sheet EV..R2+BAC

Functional data Differential pressure Δpmax 350kPa


Differential pressure note 200 kPa for low-noise operation
Flow characteristic equal percentage (VDI/VDE 2173), optimised
in the opening range
Flow characteristic note switchable to linear (VDI/VDE 2173)
Leakage rate air-bubble tight, leakage rate A (EN 12266-1)
Pipe connection Internal and external thread
Functional data Installation orientation upright to horizontal (in relation to the stem)
Servicing maintenance-free
Manual override with push-button, can be locked

Measuring data Measured values Flow


Fluid temperature supply
Fluid temperature return
Temperature sensor Pt1000 - EN 60751, 2-wire technology,
inseparably connected
Cable length external sensor T1: 3 m
T2 integrated in flow sensor

Temperature measurement Measuring accuracy absolute temperature ± 0.35°C @ 10°C (Pt1000 EN60751 Class B)
± 0.6°C @ 60°C (Pt1000 EN60751 Class B)
Measuring accuracy differential temperature ±0.22 K @ ΔT = 10 K
±0.32 K @ ΔT = 20 K

Flow measurement Measuring principle Ultrasonic volumetric flow measurement


Measuring accuracy flow ±2% (of 20...100% V'nom) @ 20°C / glycol 0%
vol.
Measuring accuracy flow note EN 1434 Class 2 @ 15…120°C
±5% (of 20...100% V'nom) @ glycol 0...60% vol.
Min. flow measurement 0.5% of V'nom

Glycol monitoring Measurement display glycol 0...60% or >60%


Measuring accuracy glycolmonitoring ±4% (0...60%)

Safety data Protection class IEC/EN III, Protective Extra-Low Voltage (PELV)
Degree of protection IEC/EN IP54
Logic module: IP54 (with grommet A-22PEM-
A04)
Sensor module: IP65
Measuring Instruments Directive CE according to 2014/32/EU
Pressure equipment directive CE according to 2014/68/EU
EMC CE according to 2014/30/EU
Certification IEC/EN IEC/EN 60730-1:11 and IEC/EN 60730-2-15:10
Quality Standard ISO 9001
Type of action Type 1
Rated impulse voltage supply / control 0.8 kV
Pollution degree 3
Ambient humidity Max. 95% RH, non-condensing
Ambient temperature -30...50°C [-22...122°F]
Storage temperature -40...80°C [-40...176°F]

Materials Valve body Brass


Flow measuring pipe Brass body nickel-plated
Closing element Stainless steel

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 3 / 18


Technical data sheet EV..R2+BAC

Technical data
Materials Spindle Stainless steel
Spindle seal EPDM O-ring
Immersion sleeve Stainless steel

Safety notes

• This device has been designed for use in stationary heating, ventilation and air-conditioning
systems and must not be used outside the specified field of application, especially in aircraft
or in any other airborne means of transport.
• Outdoor application: only possible in case that no (sea) water, snow, ice, insolation or
aggressive gases interfere directly with the device and that it is ensured that the ambient
conditions remain within the thresholds according to the data sheet at any time.
• Only authorised specialists may carry out installation. All applicable legal or institutional
installation regulations must be complied with during installation.
• The device contains electrical and electronic components and must not be disposed of as
household refuse. All locally valid regulations and requirements must be observed.

Product features

Operating mode The HVAC performance device is comprised of four components: characterised control valve
(CCV), measuring pipe with flow sensor, temperature sensors and the actuator itself. The
adjusted maximum flow (V'max) is assigned to the maximum control signal DDC (typically 10
V / 100%). Alternatively, the control signal DDC can be assigned to the valve opening angle or
to the power required on the heat exchanger (see power control). The HVAC performance
device can be controlled via communicative or analogue signals. The fluid is detected by the
sensor in the measuring pipe and is applied as the flow value. The measured value is
balanced with the setpoint. The actuator corrects the deviation by changing the valve
position. The angle of rotation α varies according to the differential pressure through the
control element (see flow curves).

Calibration certificate A calibration certificate is available in the Belimo Cloud for each thermal energy meter. If
required, this can be downloaded as a PDF with Belimo Assistant 2 or via the Belimo Cloud
frontend.

Power calculation The thermal energy meter calculates the current thermal power based on the current flow
rate and the measured temperature difference.

Energy consumption The energy consumption data can be read out as follows:
- Bus
- Cloud API
- Belimo Cloud Account of the device owner
- Belimo Assistant 2
- Integrated web server

PoE (Power over Ethernet) If necessary, the thermal energy meter can be supplied with power via the Ethernet cable.
This function can be enabled via Belimo Assistant 2.
DC 24 V (max. 8 W) is available at wires 1 and 2 for power supply of external devices (e.g.
actuator or active sensor).
Caution: PoE may only be enabled if an external device is connected to wires 1 and 2 or if
wires 1 and 2 are insulated!

Spare parts Sensor module of the thermal energy meter consisting of:
- 1 x sensor module including integrated temperature sensor T2 and external temperature
sensor T1

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 4 / 18


Technical data sheet EV..R2+BAC

Flow rate curves

Transmission behaviour HE Heat exchanger transmission behaviour


Depending on the construction, temperature spread, fluid characteristics and hydronic circuit,
the power Q is not proportional to the water volumetric flow V' (Curve 1). With the classical
type of temperature control, an attempt is made to maintain the control signal Y proportional
to the power Q (Curve 2). This is achieved by means of an equal-percentage flow characteristic
(Curve 3).

Power control Alternatively, the control signal DDC can be assigned to the output power required at the heat
exchanger.
Depending on the water temperature and air conditions, the Energy Valve ensures the
amount of water V' required to achieve the desired power.

Maximum controllable power on heat exchanger in power control mode:

Control characteristics The specially configured control parameters in connection with the precise velocity sensor
ensure a stable quality of control. They are, however, not suitable for rapid control processes,
i.e. for domestic water control.

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 5 / 18


Technical data sheet EV..R2+BAC

Power control
Q'nom is the maximum possible power output on the heat exchanger.

Q'max is the maximum power output on the heat exchanger which has been set with the
highest control signal DDC. Q'max can be set between 1% and 100% of Q'nom.

Q'min 0% (non-variable).

Flow control
V'nom is the maximum possible flow.

V'max is the maximum flow rate which has been set with the highest control signal DDC.
V'max can be set between 25% and 100% of V'nom.

Position control
In this setting, the control signal is assigned to the opening angle of the valve (e.g. Y = 10 V α
= 90°).
The result is a pressure-dependent operation similar to that of a conventional valve.
Running time of the motor in this mode is 90 s for 90°.

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 6 / 18


Technical data sheet EV..R2+BAC

Differential pressure control In addition to power control, flow control and position control, the Energy Valve can be used
to control the differential pressure between two measuring points of a differential pressure
sensor (not included).

The following differential pressure sensors can be used:


- Belimo differential pressure sensor 22WDP-11..
The specifications listed in the sensor data sheet must be observed.

Energy Valve with accessories


Differential pressure sensor 22WDP-11..
Pipe connector EXT-EF-..F
T-piece with thermowell A-22PE-A0..
In the operating mode differential pressure control, no external setpoint is given to the
Energy Valve. The setpoint is set in the device. The setting is made via web server, Belimo
Assistant 2, communicative interface (BACnet, Modbus, MP-Bus) or via the Belimo Cloud. The
possible setting value depends on the selected differential pressure sensor and is between 10
and 400 kPa.
Further information on the differential pressure control mode can be found in the document
"Differential pressure control with the Belimo Energy Valve™".

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 7 / 18


Technical data sheet EV..R2+BAC

Creep flow suppression Given the very low flow speed in the opening point, this can no longer be measured by the
sensor within the required tolerance. This range is overridden electronically.

Opening valve
The valve remains closed until the flow required by the control signal DDC corresponds to 1%
of V'nom. The control along the flow characteristic is active after this value has been
exceeded.

Closing valve
The control along the flow characteristic is active up to the required flow rate of 1% of V'nom.
Once the level falls below this value, the flow rate is maintained at 1% of V'nom. If the level
falls below the flow rate of 0.5% of V'nom required by the control signal DDC, then the valve
will close.

Configurable actuators The factory settings cover the most common applications.
The parametrisation can be carried out through the integrated web server (RJ45 connection to
the web browser) or by communicative means.
Additional information regarding the integrated web server can be found in the separate
documentation.
Belimo Assistant 2 is required for parametrisation via Near Field Communication (NFC) and
simplifies commissioning. Moreover, Belimo Assistant 2 provides a variety of diagnostic
options.

Communication The parametrisation can be carried out through the integrated web server (RJ45 connection to
the web browser) or by communicative means.
Additional information regarding the integrated web server can be found in the separate
documentation.

"Peer to Peer" connection


https://169.254.1.1
The Notebook must be set to "DHCP".
Make sure that only one network connection
is active.

Standard IP address:
https://192.168.0.10
Static IP address

Password (read-only):
User name: «guest»
Password: «guest»

Control signal inversion This can be inverted in cases of control with an analogue control signal DDC. The inversion
causes the reversal of the standard behaviour, i.e. at a control signal DDC of 0%, regulation is
to V'max or Q'max, and the valve is closed at a control signal DDC of 100%.

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 8 / 18


Technical data sheet EV..R2+BAC

Hydronic balancing Via the integrated web server, the maximum flow rate (equivalent to 100% requirement) can
be adjusted on the device itself, simply and reliably, in a few steps. If the device is integrated
in the management system, then the balancing can be handled directly by the management
system.

Delta-T manager If a heating or cooling coil is operated with a flow rate that is too high and thus with a
differential temperature that is too low, this will not result in an increased power output.

Low differential temperatures result in heat generators or chillers providing energy at a lower
efficiency. At the same time, too much water is circulated by the pumps, which unnecessarily
increases energy consumption.

With the aid of the Energy Valve, it is easy to identify operation that deviates from the design
case and to locate energy that is being used inefficiently.

The integrated delta T manager offers the user the possibility to define a delta T limit value.
Falling below this value is automatically avoided by the Energy Valve by limiting the flow rate.

The delta T manager can be activated in the operating modes power control, flow control and
position control. The delta T manager is not available in the differential pressure control
operating mode.

Power output of the heating or cooling


registers 1
Diff. temperature between supply and return
2
Loss zone (heating or cooling register
saturation) 3
Adjustable minimum differential temperature
4

Combination analogue - communicative With conventional control by means of an analogue control signal DDC, the integrated web
(hybrid mode) server, BACnet, Modbus or MP-Bus can be used for the communicative position feedback.

Power and energy monitoring function The HVAC performance device is equipped with two temperature sensors. A sensor (T2) is
already installed at the thermal energy meter and the second sensor (T1) must be installed
on-site on the other side of the water circuit. The two sensors are enclosed with the system
already wired. The sensors are used to record the fluid temperature of the supply and return
lines of the consumer (heating/cooling coil). As the water quantity is also known, thanks to
the flow measurement integrated in the system, the power released from the consumer can
be calculated. Furthermore, the heating/cooling energy is also determined automatically by
means of the evaluation of the power over time.
The current data, e.g. temperatures, volumetric flow volumes, exchanger energy
consumption etc. can be recorded and accessed at any time by means of web browsers or
communication.

Data recording The recorded data (integrated data recording for 13 months) can be used for the optimisation
of the overall system and for the determination of the performance of the consumer (heating/
cooling coil).
Download csv files through web browser.

Belimo Cloud Additional services are available if the Energy Valve is connected to the Belimo Cloud: for
instance, several devices may be managed via Internet. Also, Belimo experts may help analyse
the delta-T behaviour or provide written reports about the Energy Valve performance. Under
certain conditions, the product warranty according to the applicable Terms and Conditions of
Sale may be prolonged. The "Terms of Use for Belimo Cloud Services" in their currently valid
version apply to the use of Belimo Cloud services. Further details may be found under
[www.belimo.com/ext-warranty]

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 9 / 18


Technical data sheet EV..R2+BAC

Product features
Glycol monitoring Glycol monitoring measures the actual glycol content, which is necessary for safe operation
and optimised heat exchange.

Error readout with analogue position If the sensor cannot measure the flow due to a sensor error, this is indicated by 0.3 V at the
feedback position feedback U. This is only the case if the analogue position feedback U is set to flow
and the lower value of the signal range is 0.5 V or more.

Manual override Manual override with push-button possible (the gear train is disengaged for as long as the
button is pressed or remains locked).

High functional safety The actuator is overload protected, requires no limit switches and automatically stops when
the end stop is reached.

Parts included

Description Type
Grommet for RJ connection module with clamp A-22PEM-A04
Thermowell Stainless steel, 50 mm, G 1/4", SW17 A-22PE-A07
Insulation shell for EPIV / Belimo Energy Valve™ DN 15...25 Z-INSH15
Insulation shell for EPIV / Belimo Energy Valve™ DN 32...50 Z-INSH32
Insulation shell not included in Asia Pacific

Accessories

Replacement sensor modules Description Type


Sensor module thermal energy meter DN 15 R-22PE-0UC
Sensor module thermal energy meter DN 20 R-22PE-0UD
Sensor module thermal energy meter DN 25 R-22PE-0UE
Sensor module thermal energy meter DN 32 R-22PE-0UF
Sensor module thermal energy meter DN 40 R-22PE-0UG
Sensor module thermal energy meter DN 50 R-22PE-0UH
Tools Description Type
Service tool for wired and wireless setup, on-site operation, and Belimo Assistant 2
troubleshooting.
Converter Bluetooth / NFC ZIP-BT-NFC
Gateways Description Type
Converter M-Bus G-22PEM-A01
Mechanical accessories Description Type
T-piece with thermowell DN 15 A-22PE-A01
T-piece with thermowell DN 20 A-22PE-A02
T-piece with thermowell DN 25 A-22PE-A03
T-piece with thermowell DN 32 A-22PE-A04
T-piece with thermowell DN 40 A-22PE-A05
T-piece with thermowell DN 50 A-22PE-A06
Thermowell Stainless steel, 80 mm, G 1/2", SW27 A-22PE-A08
Pipe connector DN 15 Rp 1/2", G 3/4" EXT-EF-15F
Pipe connector DN 20 Rp 3/4", G 1" EXT-EF-20F
Pipe connector DN 25 Rp 1", G 1 1/4" EXT-EF-25F
Pipe connector DN 32 Rp 1 1/4", G 1 1/2" EXT-EF-32F
Pipe connector DN 40 Rp 1 1/2", G 2" EXT-EF-40F
Pipe connector DN 50 Rp 2", G 2 1/2" EXT-EF-50F
Valve neck extension for ball valve DN 15...50 ZR-EXT-01
Pipe connector for ball valve with internal thread DN 15 Rp 1/2" ZR2315
Pipe connector for ball valve with internal thread DN 20 Rp 3/4" ZR2320
Pipe connector for ball valve with internal thread DN 25 Rp 1" ZR2325
Pipe connector for ball valve with internal thread DN 32 Rp 1 1/4" ZR2332
Pipe connector for ball valve with internal thread DN 40 Rp 1 1/2" ZR2340

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 10 / 18


Technical data sheet EV..R2+BAC

Accessories
Description Type
Pipe connector for ball valve with internal thread DN 50 Rp 2" ZR2350

Electrical installation

Supply from isolating transformer.


Parallel connection of other actuators possible. Observe the performance data.
The wiring of the line for BACnet MS/TP / Modbus RTU is to be carried out in accordance with
applicable RS-485 regulations.
Modbus / BACnet: Supply and communication are not galvanically isolated. COM and ground
of the devices must be connected to each other.
Sensor connection: An additional sensor can optionally be connected to the thermal energy
meter. This can be a passive resistance sensor Pt1000, Ni1000, NTC10k (10k2), an active
sensor with output DC 0...10 V or a switching contact. Thus the analogue signal of the sensor
can be easily digitised with the thermal energy meter and transferred to the corresponding
bus system.
Analogue output: An analogue output (wire 5) is available on the thermal energy meter. It can
be selected as DC 0...10 V, DC 0.5...10 V or DC 2...10 V. For example, the flow rate or the
temperature of the temperature sensor T1/T2 can be output as an analogue value.

Wire colours: Functions:


1 = black C1 = D- = A (wire 6)
2 = red C2 = D+ = B (wire 7)
3 = white
5 = orange
6 = pink
7 = grey

BACnet MS/TP / Modbus RTU

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 11 / 18


Technical data sheet EV..R2+BAC

Electrical installation
BACnet/IP / Modbus TCP PoE with BACnet/IP / Modbus TCP

Optional connection via RJ45


(direct connection to notebook /
connection via Intranet or
Internet) for access to the
integrated web server

Converter for sensors


Connection with passive sensor Connection with switching contact Connection with active sensor

Further electrical installations

Functions with specific parameters (parametrisation necessary)


Override control and limiting with AC 24 V with relay contacts

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 12 / 18


Technical data sheet EV..R2+BAC

Functions with specific parameters (parametrisation necessary)


Override control and limiting with DC 24 V with relay contacts (with conventional control or hybrid mode)

1) Position control
2) Flow control
3) Power control

BACnet MS/TP / Modbus RTU with analogue setpoint (hybrid mode) BACnet/IP / Modbus TCP with analogue setpoint (hybrid mode)

MP-Bus, supply via 3-wire MP-Bus via 2-wire connection, MP-Bus with analogue setpoint (hybrid mode)
connection local power supply

M-Bus with converter M-Bus parallel Modbus TCP or BACnet/IP with PoE

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 13 / 18


Technical data sheet EV..R2+BAC

Further electrical installations


Functions with specific parameters (parametrisation necessary)
M-Bus via Converter M-Bus M-Bus parallel Modbus RTU or BACnet MS/TP

M-Bus parallel Modbus TCP or BACnet/IP

Operating mode differential pressure control


Connection of differential pressure sensor 22WDP-11.. (sensor not
included)

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 14 / 18


Technical data sheet EV..R2+BAC

Operating controls and indicators

1 LED display green

On: Device starting up


Flashing: In operation (Power ok)
Off: No power

2 Flow direction

3 NFC interface

4 Manual override button

Press button: Gear train disengages, motor stops, manual override possible
Release button: Gear train engages, standard mode. Device performs synchronisation

Installation notes

Permissible installation orientation The ball valve can be installed upright to horizontal. The ball valve may not be installed in a
hanging position, i.e. with the spindle pointing downwards.

Installation location in return Installation in the return is recommended.

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 15 / 18


Technical data sheet EV..R2+BAC

Water quality requirements The water quality requirements specified in VDI 2035 must be adhered to.
Belimo valves are regulating devices. For the valves to function correctly in the long term, they
must be kept free from particle debris (e.g. welding beads during installation work). The
installation of a suitable strainer is recommended.

Servicing Ball valves, rotary actuators and sensors are maintenance-free.


Before any service work on the control element is carried out, it is essential to isolate the
rotary actuator from the power supply (by unplugging the electrical cable if necessary). Any
pumps in the part of the piping system concerned must also be switched off and the
appropriate slide valves closed (allow all components to cool down first if necessary and
always reduce the system pressure to ambient pressure level).
The system must not be returned to service until the ball valve and the rotary actuator have
been correctly reassembled in accordance with the instructions and the pipeline has been
refilled by professionally trained personnel.

Flow direction The direction of flow, specified by an arrow on the housing, is to be complied with, since
otherwise the flow rate will be measured incorrectly.

Cleaning of pipes Before installing the thermal energy meter, the circuit must be thoroughly rinsed to remove
impurities.

Prevention of stresses The thermal energy meter must not be subjected to excessive stress caused by pipes or
fittings.

Inlet section In order to achieve the specified measuring accuracy, a flow-calming section or inflow section
in the direction of the flow is to be provided upstream from the flow sensor. Its dimensions
should be at least 5x DN.

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 16 / 18


Technical data sheet EV..R2+BAC

Installation notes
Mounting of immersion sleeve and The valve is equipped with two fully-wired temperature sensors.
temperature sensor • T2: This sensor is installed in the thermal energy meter.
• T1: This sensor has to be installed on site ahead of the consumer (valve in the return line;
recommended) or after the consumer (valve in the supply line).

Note
The cables between valve unit and temperature sensors may not be shortened or extended.

Split installation The valve-actuator combination may be mounted separately from the flow sensor. The
direction of flow of both components must be observed.

General notes

Minimum differential pressure (pressure The minimum required differential pressure (pressure drop through the valve) for achieving
drop) the desired volumetric flow V'max can be calculated with the aid of the theoretical Kvs value
(see type overview) and the below-mentioned formula. The calculated value is dependent on
the required maximum volumetric flow V'max. Higher differential pressures are compensated
for automatically by the valve.

Formula

Example (DN 25 with the desired maximum flow rate = 50% V'nom)

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 17 / 18


Technical data sheet EV..R2+BAC

General notes
Behaviour in case of sensor failure In case of a flow sensor error, the Energy Valve will switch from either power or flow control
to position control (Delta-T manger will be deactivated).
Once the error disappears, the Energy Valve will switch back to the normal control setting
(Delta-T manager activated)

Dimensions

Dimensional drawings

Further documentation

• Data sheet thermal energy meter


• Overview MP Cooperation Partners
• Tool connections
• General notes for project planning
• Instruction Webserver
• Description Data-Pool Values
• BACnet Interface description
• Modbus Interface description
• Introduction to MP-Bus Technology
• Installation instructions for actuators and/or ball valves
• Differential pressure control with the Belimo Energy Valve™
• Quick Guide – Belimo Assistant 2

www.belimo.com EV..R2+BAC • en-gb • 2024-09-27 • Subject to change 18 / 18

You might also like