Multi Vrf Ch
Multi Vrf Ch
Inverter
Multi VRF Modular
Owner's Manual
Air Conditioners
Models:
CHV-5S224NMX
CHV-5S280NMX
CHV-5S335NMX
CHV-5S400NMX
CHV-5S450NMX
CHV-5S504NMX
■
■
■
CHV-5S2460NMX
Thank you for choosing Cooper&Hunter Air Conditioners, please read this owner’s manual
carefully before operation and retain it for future reference. If you have lost the Owner’s
Manual, please contact the local agent or visit cooperandhunter.com for electronic version.
Cooper&Hunter reserves the right to interpret this manual which will be subject to any change
due to product improvement without further notice.
Cooper&Hunter International Corporation, Inc. of Zhuhai reserves the final right to interpret
this manual.
Preface
Cooper&Hunter DC Inverter Multi VRF System, with the most advanced technologies in the
world, uses eco-friendly refrigerant R410A as its cooling medium. For correct installation and
operation, please read this manual carefully. Before reading the manual, please note that:
(1) For safety operation, please strictly follow the instructions in this manual.
(2) During operation, the gross rated capacity of working IDU should be within the gross rated
capacity of ODU. Otherwise, IDU’s cooling/heating performance will be reduced.
(3) This manual must be in the hands of direct operators or maintenance men.
(4) In case of malfunction and operation failure, please examine the following items and
contact our authorized service centers as soon as possible.
1) Nameplate (model, cooling capacity, product code, ex-factory date).
2) Malfunction status (detail description of conditions before and after malfunction occurs)
(5) All units have been strictly tested and proved to be qualified before ex-factory. To avoid
unit damage or even operation failure which may be caused by improper disassembly,
please do not disassemble units by yourself. If disassembly is needed, please contact our
authorized serve centers for help.
(6) All graphics and information in this manual are only for reference. Manufacturer reserves
the right for changes in terms of sales or production at any time and without prior notice.
This appliance can be used by children aged from 8 years and above and persons with reduced
physical, sensory or mental capabilities or lack of experience and knowledge if they have been
given supervision or instruction concerning use of the appliance in a safe way and understand
the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children without supervision.
DISPOSAL:Do not dispose this product as unsorted municipal waste. Collection of such waste
separately for special treatment is necessary.
Contents
1 Safety Precautions ...................................................................................................................... 1
2 Product Introduction .................................................................................................................... 3
2.1 Names of Main Parts......................................................................................................... 3
2.2 Combinations of Outdoor Units . ........................................................................................ 4
2.3 Combinations of Indoor and Outdoor Units . ..................................................................... 5
2.4 The Range of Production Working Temperature ............................................................... 6
3 Preparation before Installation . ................................................................................................... 7
3.1 Standard Parts .................................................................................................................. 7
3.2 Installation Site .................................................................................................................. 7
3.3 Piping Work Requirements . ............................................................................................ 12
4 Installation Instruction................................................................................................................ 12
4.1 Physical Dimension of the Outdoor Unit and Mounting Hole . ......................................... 12
4.2 Connection Pipe .............................................................................................................. 14
4.3 Installation of the Connection Pipe . ................................................................................ 27
4.4 Air Purging and Refrigerant Charge. ............................................................................... 31
4.5 Electric Wiring ................................................................................................................. 32
4.6 System Communication . ................................................................................................. 38
4.7 Connection Method and Steps for System Communication ............................................ 42
4.8 External Electrical Wiring Diagram . ................................................................................ 47
5 Check Items after Installation and Trial Run . ............................................................................ 48
5.1 Check Items after Installation. ......................................................................................... 48
5.2 Trial Run .......................................................................................................................... 49
6 Common Malfunction and Troubleshooting . ............................................................................. 61
7 Error Indication .......................................................................................................................... 63
8 Maintenance and Care .............................................................................................................. 66
8.1 Outdoor Heat Exchanger . ............................................................................................... 66
8.2 Drain Pipe ....................................................................................................................... 66
8.3 Notice before Seasonal Use . .......................................................................................... 66
8.4 Maintenance after Seasonal Use . ................................................................................... 67
8.5 Parts Replacement. ......................................................................................................... 67
9 After-sales Service .................................................................................................................... 67
D.C. Inverter Multi VRF Modular
1 Safety Precautions
Means items that must be forbidden! Otherwise, it may lead to personal injury or death
or serious damage.
Refers to things that must be followed. Incorrect operation may cause personal injury or
death.
Installation should be
conducted by dealer or
Follow this instruction to
qualified personnel. Please do
complete the installation work.
not attempt to install the unit
Please carefully read this
by yourself. Improper handling
manual before unit startup and
may result in water leakage,
service.
electric shock or fire disaster
etc.
Make sure the unit can be
Before installation, please check earthed properly and soundly
if the power supply is in after plugging into the socket
accordance with the so as to avoid electric shock.
requirements specified on the Please do not connect the
nameplate. And also take care of ground wire to gas pipe, water
the power safety. pipe, lightning rod or
telephone line.
1
D.C. Inverter Multi VRF Modular
Turn off the unit or cut off the Never spray or flush water
power supply before cleaning towards unit, otherwise
the unit, otherwise electric shock malfunction or electric shock
or injury may happen. may happen.
2
D.C. Inverter Multi VRF Modular
2 Product Introduction
Cooper&Hunter Multi VRF Modular System adopts inverter compressor technology. According to
change the displacement of compressor, stepless capacity regulation within range of 10%-100%
can be realized. Various product lineup is provided with capacity range from 22.4kW to 246kW,
which can be widely used in working area and especially applicable to the place with variable
load change.Cooper&Hunter air conditioner is absolutely your best choice.
2.1 Names of Main Parts
Fig.1
3
D.C. Inverter Multi VRF Modular
NO. ① ② ③ ④ ⑤
Note: The picture is only used for reference and the actual product prevails.
Model(Single) CHV-5S2460NMX
CHV-5S615NMX+
CHV-5S615NMX+
Model(Combined)
CHV-5S615NMX+
CHV-5S615NMX
4
D.C. Inverter Multi VRF Modular
5
D.C. Inverter Multi VRF Modular
The total capacity of indoor units should be within 50%~135% of that of outdoor units.
Fig.2
Fig.2 is the combination view of the ODU of Modular DC Inverter Multi VRF System and the
IDU of Multi VRF System. IDU can be cassette type, one-way cassette type, wall-mounted type,
duct type, etc. When any one IDU receives operation signal, ODU will start to work according to
the capacity; when all IDUs stop, ODU will also stop.
2.4 The Range of Production Working Temperature
Cooling Ambient temperature: -5~52
Heating Ambient temperature: -20~24
When the indoor units are all VRF fresh air processor, the unit operating range is as follows:
Cooling Ambient temperature: 16°C~45°C
Heating Ambient temperature: -7°C~16°C
If the temperature is beyond the range, the safety protection measure of the unit may take
effect, and the air conditioning unit will stop.
6
D.C. Inverter Multi VRF Modular
1 Owner's Manual 1
Install the unit at a place where Never expose the unit under
is adequate to withstand the direct sunshine and
weight of the unit and make sure rainfall.Install the unit at a
the unit would not shake or fall place where is against dust,
off. typhoon and earthquake.
7
D.C. Inverter Multi VRF Modular
3.2.1 When the outdoor unit is totally surrounded by walls, please refer to following
figures for space dimension.
3.2.1.1 Space dimension for single-module unit
Fig. 3
3.2.1.2 Space dimension for dual-module unit
Fig. 4
3.2.1.3 Space dimension for three-module unit
Fig.5
8
D.C. Inverter Multi VRF Modular
Fig.6
3.2.2 When there is wall (or similar obstruction) above the unit, keep the distance
between the unit top and the wall at least 300mm or above. When the unit is located in
a totally open space with no obstructions in four directions, keep the distance between
the unit top and wall at least 1500mm or above (See Fig.7). When space is limited
within 1500mm or the unit is not set in an open space, air return pipe is required to be
installed in order to keep good ventilation (See Fig.8).
Fig.7 Fig.8
9
D.C. Inverter Multi VRF Modular
Fig.9
Fig.10
3.2.4 Take seasonal wind into consideration when installing the outdoor unit
(1)Anti-monsoon installation requirements for unit not connecting exhaust duct:
10
D.C. Inverter Multi VRF Modular
Fig.11
(2)Anti-monsoon installation requirements for unit connecting exhaust duct:
Fig.12
3.2.5 Take snow into consideration when installing the outdoor unit
Fig.13
11
D.C. Inverter Multi VRF Modular
4 Installation Instruction
4.1 Physical Dimension of the Outdoor Unit and Mounting Hole
Fig.14
12
D.C. Inverter Multi VRF Modular
Fig.15
13
D.C. Inverter Multi VRF Modular
Fig.16
14
D.C. Inverter Multi VRF Modular
Fig.17
15
D.C. Inverter Multi VRF Modular
Fig.18
CHV-5S335NMX, CHV-5S400NMX and CHV-5S450NMX
Fig.19
16
D.C. Inverter Multi VRF Modular
Fig.20
4.2.3 Allowable pipe length and drop height among indoor and outdoor units
Y type branch joint is adopted to connect indoor and outdoor units. Connecting method is
shown in the figure below.
Remark: Equivalent length of one Y-type manifold is about 0.5m.
Fig.21
L10: Length from the first branch to the farthest IDU;
17
D.C. Inverter Multi VRF Modular
Notices:
(1)Normally, the pipe length from the first branch of IDU to the farthest IDU is 40m. When
those three conditions as below are satisfied, the length can reached 90cm.
1) Actual length of pipe in total: L1+L2x2+L3x2+L4x2+…+L9x2+a+b+…+i+j≤1000m;
2) Length between each IDU and its nearest branch a, b, c, d, e, f, g, h, i, j≤40m;
3) Difference between the pipe length from the first branch of IDU to the farthest IDU and
the pipe length from the first branch of IDU to the nearest IDU: L10-L11≤40m.
(2) When the maximum length of the main pipe from ODU to the first branch of IDU is≥90m,
then adjust the pipe size of the gas pipe and liquid pipe of main pipe according to the
following table.
Outdoor Model Gas pipe size(mm) Liquid pipe size(mm)
18
D.C. Inverter Multi VRF Modular
(3) If the length between an IDU and its nearest branch is above 10m, then increase the size
of the liquid pipe of IDU (only for the pipe size that is≤6.35mm).
19
D.C. Inverter Multi VRF Modular
Fig.22
Fig.23
Note: When the distance between outdoor units exceeds 2m, U-type oil trap should be added
at low-pressure gas pipe. A+B≤10m.
20
D.C. Inverter Multi VRF Modular
4.2.5 Fitting pipe between Outdoor Unit and the First Manifold
4.2.5.1 For single module system, pipe size (between outdoor unit and the first manifold)
is determined by that of outdoor unit.
Fig.24
Pipe size of basic outdoor module is shown as follows:
Pipe between ODU and the first branch of IDU
Basic Module
Gas Pipe(mm) Liquid Pipe(mm)
21
D.C. Inverter Multi VRF Modular
4.2.5.2 For multi-module unit, select appropriate manifold connected to oudoor module as per the
pipe size of basic module. Pipe size of basic outdoor module is shown as follows:
Fig.25
Pipe between module and branch of ODU
Basic Module
Gas Pipe(mm) Liquid Pipe(mm)
22
D.C. Inverter Multi VRF Modular
Fig.26
Total capacity of upstream modules Pipe size between manifolds
Q(kW) Gas Pipe(mm) Liquid Pipe(mm)
22.4≥ Q Φ19.05 Φ9.52
28.0≥Q>22.4 Φ22.2 Φ9.52
40.0≥Q>28.0 Φ25.4 Φ12.7
45.0≥Q>40.0 Φ28.6 Φ12.7
68.0≥Q>45.0 Φ28.6 Φ15.9
96.0≥Q>68.0 Φ31.8 Φ19.05
135.0≥Q>96.0 Φ38.1 Φ19.05
Q>135.0 Φ44.5 Φ22.2
4.2.5.4 Fitting pipe between the first manifold from indoor unit and the end manifold from outdoor
unit
Single module unit
Fig.27
23
D.C. Inverter Multi VRF Modular
For multiple modules, the piping from ODU to the first branch of IDU is based on the total
rated capacity of outdoor modules.
Fig.28
Total rated capacity of outdoor modules Pipe between ODU and the first branch of IDU
(multi-modular system) Gas Pipe(mm) Liquid Pipe(mm)
24
D.C. Inverter Multi VRF Modular
25
D.C. Inverter Multi VRF Modular
Fig.29
C<20.0 CH020N
20.0≤C≤30.0 CH030N
Y-type Manifold 30.0<C≤70.0 CH070N
70.0<C≤135.0 CH135N
135.0<C CH270N
Fig.30
26
D.C. Inverter Multi VRF Modular
Fig.31
Pipe between indoor branch and IDU
Rated capacity of indoor unit C(kW)
Gas Pipe(mm) Liquid Pipe(mm)
C≤2.8 Φ9.52 Φ6.35
2.8<C≤5.0 Φ12.7 Φ6.35
5.0<C≤14.0 Φ15.9 Φ9.52
14.0<C≤16.0 Φ19.05 Φ9.52
16.0<C≤28.0 Φ22.2 Φ9.52
27
D.C. Inverter Multi VRF Modular
Fig.32
1) Align the expansion end of copper pipe with the center of threaded joint. Tighten the
flare nuts with your hands.
2) Tighten the flare nuts with torque wrench until you hear "click" sound.
3) Use sponge to wrap the connecting pipe and joints without thermal insulation and tie it
up with plastic tape.
4) A mounting support for the connection pipe is required.
5) The curvature degree of connection pipe should not be small, otherwise the pipe might
crack. Installation personnel should use tube bender when bending the pipe.
6) Don't forbibly stretch the pipe joint, otherwise indoor capillary or other pipes might be
damaged and lead to refrigerant leakage.
4.3.2 Y-type manifold
(1) Y-type manifold
Fig.33
(2) Y-type manifold has serveral pipe sections with different pipe size, which facilitates to
match with various copper pipe. Use pipe cutter to cut in the middle of the pipe section
with different pipe size and deburr as well. See Fig.34.
(3) Y-type manifold must be installed vertically or horizontally.
28
D.C. Inverter Multi VRF Modular
Fig.34
Total capacity of downstream indoor
Y-type manifold Model
unit(s) (X) (kW)
X<20.0 CH020N
20.0≤X≤30.0 CH030N
30.0<X≤70.0 CH070N
70.0<X≤135.0 CH135N
135.0<X CH270N
(4) Manifold is isolated by insulating material that can bear 120℃ or higher temperature.
Manifold attached foam can not be taken as insulating material.
4.3.3 Thermal insulation for pipeline
(1) For multi VRF system, every copper pipe should be labled so as to avoild misconnection.
(2) Manifolds can be laid in the following ways:
The length of a straight pipe between two manifolds cannot be less than 500 mm. The length
of a straight pipe before the main pipe port of the manifold cannot be less than 500 mm. The
length of a straight pipe between the branch of the manifold and the IDU cannot be less than 500
mm. See Fig.35
Fig.35
(3) There must be three fixing point for both horizontal and vertical installation of the Y-type
manifold. See Fig.36.
Fixing point 1: 100 mm on the main inlet manifold from the welding point
29
D.C. Inverter Multi VRF Modular
Fixing point 2: 200 mm on the main branched pipe from the welding point
Fixing point 3: 250 mm on the branched pipe from the welding point
Fig.36
(4) Thermal insulation for pipeline
1) To avoid condensate or water leakage on connecting pipe, the gas pipe and liquid pipe
must be wrapped with thermal insulating material and adhesive pipe for insulation from
the air.
2) For heat pump unit, liquid pipe should bear 70℃ or above, and gas pipe should bear
120℃ or above. For cooling only unit,both liquid pipe and gas pipe should bear 70℃
or above. Example: Polyethylene foam can bear 120℃ above and foaming
polyethylene can bear 100℃ above.
3) Joints at indoor and outdoor units should be wrapped with insulating material and leave
no clearance between pipe and wall. See Fig.37.
Fig.37
4) Manifold attached foam can not be taken as insulating material.
5) When wrapping the tape, the later circle should cover half of the former one. Don’t wrap
the tape so tightly, otherwise the insulation effect will be weakened.
6) After wrapping the pipe, adopt sealing material to completely fill the hole so as to
prevent wind and rain from entering the room.
4.3.4 Support and protection for pipeline
(1) Support should be made for hanging connection pipe. Distance between each support
can not be over 1m.
(2) Protection towards accidental damage should be made for outdoor pipeline. When the
pipeline exceeds 1m, a pinch board should be added for protection.
30
D.C. Inverter Multi VRF Modular
Fig.38 Fig.39
4.4.2 Additional refrigerant charging
Outdoor unit has been charged refrigerant before delivery.
Charge additional refrigerant for field-installed connecting pipe. If the pipeline is longer than
1m, please refer to the following table for charging amount of refrigerant. (Liquid pipe prevails)
How much additional refrigerant should be charged
Total refrigerant charging amount R= Pipeline charging amount A + ∑charging amount B of
every module
(1) Pipeline charging amount
Pipeline charging amount A= ∑Liquid pipe length×refrigerant charging amount of every 1m
liquid pipe
Diameter of liquid
Φ28.6 Φ25.4 Φ22.2 Φ19.05 Φ15.9 Φ12.7 Φ9.52 Φ6.35
pipe (mm)
31
D.C. Inverter Multi VRF Modular
Note:
① IDU/ODU rated capacity collocation ratio C = Sum of rated cooling capacity of indoor unit /
Sum of rated cooling capacity of outdoor unit
② If all of the indoor units are fresh air indoor units, the quantity of refrigerant added to each
module is 0kg.
③ If outdoor air processor is connected with normal VRF indoor unit, adopt the perfusion
method for normal indoor unit for perfusion.
For example 1:
Outdoor unit consists of one 28kW module and one 45kW module. Five 14kW duct type units
are used as indoor units.
IDU/ODU rated capacity collocation ratio C= 140×5/(280+450)=96%. The quantity of included
IDUs is more than 4 sets. Please refer to the above table.
32
D.C. Inverter Multi VRF Modular
Fig.40
Please refer to the following table for circuit breaker and circuit breaker for modular outdoor
units. 5-core cable is used and the wire size unit is mm2.
Circuit Circuit breaker
Wire size of
breaker capacity for Wire size of
Model Basic models power supply
capacity combined combined uni (mm2)
(mm2)
(A) units (A)
CHV-5S224NMX CHV-5S224NMX 20 20 2.5 2.5×5
CHV-5S280NMX CHV-5S280NMX 25 25 2.5 2.5×5
CHV-5S335NMX CHV-5S335NMX 32 32 4.0 4.0×5
CHV-5S400NMX CHV-5S400NMX 40 40 6.0 6.0×5
CHV-5S450NMX CHV-5S450NMX 40 40 6.0 6.0×5
CHV-5S504NMX CHV-5S504NMX 50 50 10 10×5
CHV-5S560NMX CHV-5S560NMX 63 63 10 10×5
CHV-5S615NMX CHV-5S615NMX 63 63 10 10×5
CHV-5S680NMX 280+400 63 25 + 40 2.5 + 6.0 2.5×5 + 6.0×5
CHV-5S730NMX 280+450 63 25 + 40 2.5 + 6.0 2.5×5 + 6.0×5
CHV-5S785NMX 280+504 80 25 + 50 2.5 + 10 2.5×5 + 10×5
CHV-5S850NMX 280+560 80 25 + 63 2.5 + 10 2.5×5 + 10×5
CHV-5S900NMX 280+615 80 25 + 63 2.5 + 10 2.5×5 + 10×5
CHV-5S950NMX 335+615 80 32 + 63 4.0 + 10 4.0×5 + 10×5
CHV-5S1010NMX 400+615 100 40 + 63 6.0 + 10 6.0×5 + 10×5
CHV-5S1065NMX 450+615 100 40 + 63 6.0 + 10 6.0×5 + 10×5
33
D.C. Inverter Multi VRF Modular
34
D.C. Inverter Multi VRF Modular
Total capacity of indoor Capacity of circuit breaker Min. sectional area of Min. sectional area of
units (A) power cord (mm2) grounding wire (mm2)
Below10A 10 1.0 1.0
16~10A 16 1.5 1.5
20~16A 20 2.5 2.5
32~20A 32 4.0 4.0
40~32A 40 6.0 6.0
50~40A 50 10.0 10.0
63~50A 63 16.0 16.0
80~63A 80 25.0 16.0
100~80A 100 35.0 16.0
125~100A 125 50.0 25.0
Breaker capacity and power cord specification for every indoor unit
Capacity of circuit breaker Min. sectional area of Min. sectional area of
Indoor unit
(A) grounding wire (mm2) power cord (mm2)
If indoor unit is equipped with auxiliary electric heater, select capacity of circuit breaker as per
auxiliary electric heater, which requires special setting.
Indoor unit models (with auxiliary Capacity of circuit Min. sectional area of Min. sectional area of
electric heater) breaker (A) grounding wire (mm2) power cord (mm2)
Note:
①Specification of circuit breaker and power cord is selected on the basis of unit’s maximum
power (max. current).
②Specification of power cord is based on the working condition where ambient temperature
is 40℃ and multi-core cable with copper conductor(working temperature is 90℃, e.g.
power cable with YJV cross-linked copper, insulated PE and PVC sheath) is lying on the
surface of slot. If working condition is different, please adjust the specification according to
national standard.
③Copper-core cable must be used.
④The above sectional area is suitable for a maximum distance of 15m. If it’s over 15m,
sectional area must be expanded to prevent overload current from burning the wire or
causing fire hazard.
35
D.C. Inverter Multi VRF Modular
⑤Specification of circuit breaker is based on the working condition where the ambient
temperature of circuit breaker is 40℃. If working condition is different, please adjust the
specification according to national standard.
⑥The circuit breaker should include magnetic trip function and thermal trip function so that
system can be protected from short circuit and overload.
⑦An all-pole disconnection switch having a contact separation of at least 3mm in all poles
should be connected in fixed wiring
4.5.3 Connection of power cord
Warning: before obtaining access to terminals, all supply circuits must be disconnected.
Note:
(1) If units are type I electrical appliances, they must be reliably grounded.
(2) Ground resistance must be in accord with requirements of local standard.
(3) The green-yellow wire within units are ground wire. Do not use it for other purposes. Nor
should it be cut off or secured by tapping screws. Otherwise, it may cause electric shock.
(4) Power supply at user side must have reliable ground terminal. Do not connect ground wire
to the following places:
1) water pipe, 2) gas pipe, 3) drainage pipe, 4)other places that are considered by
professionals as unreliable.
(5) Power cord and communication wire should be separated, with a distance of more than
20cm. Otherwise, system’s communication may not work well.
Steps and graphic of power cord connection:
(1) Knock off the cross-through opening that’s used for leading the external power cord, with
the cross-through rubber ring on the opening. Then lead the cable through the opening.
Connect L1, L2, L3, N of power cord and ground wire separately to the positions on wiring
board (for power supply) that are marked with L1, L2, L3, N and the ground screw nearby.
(2) Use cable ties to tie the cable securely,
(3) Lead the power cord as instructed in the graphic below:
Wiring method for the power cord of CHV-5S224NMX ,CHV-5S280NMX ,CHV-5S335NMX ,
CHV-5S400NMX and CHV-5S450NMX
36
D.C. Inverter Multi VRF Modular
Fig.41
37
D.C. Inverter Multi VRF Modular
Fig.42
38
D.C. Inverter Multi VRF Modular
Fig.43
4.6.2 Communication mode of CHV5 Modular DC Inverter Units
CAN bus mode is taken for communication between IDU and ODU and communication
among IDUs.
4.6.3 Selection and connection mode of CHV5 communication material
4.6.3.1 Select communication material
Note: if air conditioners are installed at places where there’s strong electromagnetic
interference, the communication wire of IDU and wired controller must use shielded wire and the
communication wire between IDU and IDU/ODU must use shielded twisted pair.
(1) Select communication wire between IDU and wired controller
Total length of
communication line Wire size Material
Material type Remarks
between IDU unit and (mm2) standard
wired controller L (m)
1. Total length of communication line
Light/Ordinary can't exceed 250m.
polyvinyl chloride 2. The cord shall be Circular cord (the
IEC
sheathed cord. L≤250 2×0.75~2×1.25 cores shall be twisted together).
60227-5:2007
(60227 IEC 52 3. If unit is installed in places with intense
/60227 IEC 53) magnetic field or strong interference, it is
necessary to use shielded wire.
39
D.C. Inverter Multi VRF Modular
Fig.44
(2) Select communication wire between ODU and IDU
Total Length L(m) of
Communication Cable Wire size Material
Material Type Remarks
between IDU Unit and (mm2) Standard
IDU (ODU ) Unit
Fig.45
4.6.3.2 Connection mode of communication
(1) All communication wires of CHV5 must be connected in series rather than in star.
Fig.46
40
D.C. Inverter Multi VRF Modular
Fig.47
Fig.48
(2) All communication wires of CHV5 are connected by screws.
Fig.49
(3) If a single communication wire is not long enough and needs to be connected, the
connected joint must be welded or pressure-welded. Do not simply twist the wires
together.
4.6.4 Communication address
Auto addressing technology is adopted for CHV5 IDU and ODU. No need to set address
41
D.C. Inverter Multi VRF Modular
codes manually. Only the addresses of master unit and central control are needed to be set
(address of central control is only needed when there are multiple refrigeration systems).
Note: When installing remote monitor or central controller, displacement on indoor units’
project codes must be made. Otherwise, there will be collision malfunction of the project codes.
For detail operation methods, please refer to the CHV5 Installation and Maintenance Manual.
42
D.C. Inverter Multi VRF Modular
43
D.C. Inverter Multi VRF Modular
Fig.52 One wired controller controls one IDU Fig.53 Two wired controllers control one IDU
When two wired controllers control multiple IDUs, the wired controller can be connected to
any one IDU, provided that the connected IDU is of the same series. Meanwhile, one and only one
of the wired controllers must be set as a slave controller. At most 16 IDUs can be controlled by
wired controllers and the connected IDUs shall be within a same IDU network.
No matter when unit is turned on or off, slave controller can be set.
How to set a slave controller: hold “function” button on the designated controller for 5s, and
temperature zone displays C00. Continue holding “function” button for 5s and setting screen of
controller parameter will come out. Default temperature zone displays P00.
Press button o button to select parameter code P13. Press “mode” button to switch to
setup of parameter values. Then the parameter value will blink. Press button or button to select
code 02. And then press “confirm/cancel” to finish setting.
Press “confirm/cancel” to return to the previous display until you exit from the setup of
parameter values.
Below are user’s parameter settings:
Parameter Parameter Default
Parameter scope Remark
code name value
4.7.3 Communication connection between duct type IDU and light board receiver
When the duct type IDU needs to be connected to light board remote receiver, it can be
connected via Dsp1 and Dsp2 on the IDU main board.
IDU type Connection wire Main board interface of corresponding IDU
Fig.56
Note:
①Wired controller and light board remote receiver can be used at the same time.
45
D.C. Inverter Multi VRF Modular
②When light board remote receiver is used, please use remote controller at the same time.
4.7.4 Communication connection of central controlling units
Note:The centralized controller can be installed when it is necessary.
Port connection G1 and G2 on the wiring board XT2 of master unit among each multi VRF
system (see below)
Fig.57
46
D.C. Inverter Multi VRF Modular
Each unit should be equipped with a circuit breaker for short circuit protection and exceptional
overload protection. Besides, a main circuit breaker shall be prepared for IDUs and ODUs in order
to connect or disconnect power of the entire system.
4.8.1 External wiring diagram of a single unit
Fig.58
Note: maximum number of IDU is based upon ODU capacity. For details, please refer to the
introduction of units’ combination.
47
D.C. Inverter Multi VRF Modular
Fig.59
Note: maximum number of ODU (N) and maximum number of IDU (n) are based upon the
combination type of ODU. For details, please refer to the introduction of units’ combination.
5 Check Items after Installation and Trial Run
5.1 Check Items after Installation
Check Items Conditions Might Happen Check
Has the unit been fixed firmly? The unit may drop, shake or emit noise.
It may cause insufficient cooling/heating
Have you done the gas leakage test?
capacity.
Is the unit get proper thermal insulation? It may cause condensation and dripping.
Does the unit drain well? It may cause condensation and dripping.
Is the voltage in accordance with the rated voltage
It may cause malfunction or damage the part.
specified on the nameplate?
Is the electric wiring and piping connection installed
It may cause malfunction or damage the part.
correctly and securely?
Has the unit been earthed securely? It may cause electrical leakage.
Is the power cord specified? It may cause malfunction or damage the part.
It may cause insufficient cooling/heating
Has the inlet and outlet been blocked?
capacity.
Has the pipe length and refrigerant charging amount
The refrigerant charging amount is not accurate.
been recorded?
48
D.C. Inverter Multi VRF Modular
Whether the engineering piping work and wiring Maybe there are mice biting the wires, which is
holes are sealed? the cause of malfunction.
Note: during debugging, one and only one module must be set as a master module.
During debugging, one and only one IDU must be set as a master IDU.
When no special requirement is needed, no need to set other functions. Unit can operate
according to ex-factory settings. When special requirement is needed, please read the Service
Manual or Debugging and Maintenance Manual.
5.2.1 Preparation before trial run
(1) The power supply should be turned on only after finishing all the installation.
(2) All the control wires and cables are connected correctly and safely.Completely open the
gas and liquid valves.
(3) All the objects like metal filing, thrum and clip should be cleared after installation.
(4) Check if the unit appearance and piping system is damaged or not due to transportation.
(5) Check if the terminals of electrical element is loose and the phase sequence is correct or
not.
(6) Check the valve: For single-module unit, fully open the gas and liquid valve and close oil
balance valve; For dual/three module unit, fully open the gas, liquid valve and oil balance
valve.
5.2.2 Trial run
5.2.2.1 Notices
(1) Before test operation, make sure unit is power on and compressor has been preheated for
more than 8 hours. Touch the unit to check whether it’s normally preheated. Start test
operation after unit is normally preheated, otherwise compressor might be damaged.
Debugging must be performed by professional technicians or under the guide of
professional technicians.
49
D.C. Inverter Multi VRF Modular
Fig.60
(2) When debugging starts, system will operate according to the ambient temperature.
When outdoor temperature is above 20℃, debugging shall be in cooling mode.
When outdoor temperature is below 20℃, debugging shall be in heating mode.
(3) Before debugging, confirm again whether the cut-off valve of each basic module is fully
turned on.
(4) During debugging, front panel of the outdoor unit must be fully closed; otherwise,
debugging accuracy will be affected (see below).
Fig.61
(5) Before debugging, make sure the needed amount of refrigerant has been added to the
pipe or at least 70% of the needed refrigerant has been added.
(6) Description of each stage of debugging progress:
Description of each stage of debugging progress
Debugging
—— Progress code Status code
code
LED1 LED2 LED3 Meaning
progress Display Display Display
Code code Code
status status status
db light 01 light A0 light System is not debugged.
01_Set up
master unit System doesn’t have master unit. Reset
db light 01 light CC light
master unit.
50
D.C. Inverter Multi VRF Modular
51
D.C. Inverter Multi VRF Modular
Debugging
—— Progress code Status code
code
LED1 LED2 LED3 Meaning
progress Display Display Display
Code code Code
status status status
Calculate the refrigerant quantity
11_Calculate
manually and confirm the perfusion
refrigerant
db light 11 light AE light status of refrigerant (the quantity of
quantity
refrigerant added into the system must
manually
be recorded accurately).
13_ —— —— —— —— —— —— no meaning.
14_ —— —— —— —— —— —— no meaning.
52
D.C. Inverter Multi VRF Modular
According to the above errors, reset the master unit as instructed in Master Unit Setup
53
D.C. Inverter Multi VRF Modular
At this time, all buttons are ineffective. Set master IDU in 1min via debugging software. If
master IDU is not set in 1min, system will set up a master IDU randomly. After that, system will
start next progress.
Step 7: in progress 03, the quantity of modules needs to be confirmed manually. Main board
of each module will display:
Debugging code Progress code Status code
LED1 LED2 LED3
Progress Display Display Display
Code Code Code
status status status
03_Quantity of Quantity of
db light 03 light blink
modules modules
If the quantity displayed is the same with actual quantity, then press SW7 confirmation button
on the master unit to confirm it. Unit will start next progress:
Debugging code Progress code Status code
LED1 LED2 LED3
Progress Display Display Display
Code Code Code
status status status
03_Confirm the
quantity of db light 03 light OC light
modules
If the quantity displayed is different from actual quantity, then disconnect power and check
whether communication wire among each module is correctly connected. After the check, start
debugging again.
Step 8: in progress 04, the quantity of IDUs needs to be confirmed manually. Main board of
each module will display:
Debugging code Progress code Status code
LED1 LED2 LED3
Progress Display Display Display
Code Code Code
status status status
Quantity of
04_Confirm the
db Light 04 Light connected blink
quantity of IDUs
IDUs
If the quantity displayed is the same with actual quantity, then press SW7 confirmation button
on the master unit to confirm it. Unit will start next progress:
Debugging code Progress code Status code
LED1 LED2 LED3
Progress Display Display Display
Code Code Code
status status status
04_Confirm the
db Light 04 Light OC Light
quantity of IDUs
54
D.C. Inverter Multi VRF Modular
If no error is detected, system will display as below and then start next progress.
—— Debugging code Progress code Status code
LED1 LED2 LED3
Meaning
progress Display Display Display
Code code Code
status status status
05_Detect
internal db Light 05 Light OC Light Detection is finished. Start next progress.
communication
If error is detected, system will stay at current progress. Error has to be solved manually.
Below are relevant errors:
—— Debugging code Progress code Status code
LED1 LED2 LED3 Meaning
progress Display Display Display
Code code Code
status status status
System detects “driven communication
db Light 05 Light C2 Light error between master unit and inverter
compressor”.
System detects “driven communication
05_Detect
db Light 05 Light C3 Light error between master unit and inverter
internal
fan”.
communication
IDU/ODU “high proportion of rated
db Light 05 Light CH Light
capacity”.
IDU/ODU “low proportion of rated
db Light 05 Light CL Light
capacity”.
If error is detected, system will stay at current progress. Error has to be solved manually.
Below is relevant error:
—— Debugging code Progress code Status code
LED1 LED2 LED3
Meaning
progress Display Display Display
Code code Code
status status status
06_Detect
Error System detects error in outdoor
outdoor db Light 06 Light Light
code components.
components
55
D.C. Inverter Multi VRF Modular
If error is detected, system will stay at current progress. Error has to be solved manually.
Below is relevant error:
—— Debugging code Progress code Status code
LED1 LED2 LED3
Meaning
progress Display Display Display
Code code Code
status status status
XXXXor
07_Detect indoor System detects error in indoor
db Light 07 Light Error Light
components components.
code
XXXX is the project no. of the faulted IDU. 3s later, relevant error code is displayed. For
example, IDU no. 100 has d5 error, then LED3 displays like this: 01 (2s later) 00 (2s later) d5, and
repeat again.
Elimination methods of above error can be found in Troubleshooting.
Step 12: progress 08 is “Confirm preheated compressor”
If more than 8h of preheat time is detected, system will display as below and start next
progress.
—— Debugging code Progress code Status code
LED1 LED2 LED3
Meaning
progress Display Display Display
Code code Code
status status status
08_Confirm
Preheat time for compressor is 8h. Start
preheated db Light 08 Light OC Light
next progress.
compressor
If less than 8h of preheat time is detected, system will give error alarm and display as below.
Then press SW7 confirmation button to skip the wait time and start next progress. But this will
cause force start of the compressor, which may damage the compressor.
—— Debugging code Progress code Status code
LED1 LED2 LED3
Meaning
progress Display Display Display
Code code Code
status status status
08_Confirm
Preheat time for compressor is less than
preheated db Light 08 Light UO Light
8h.
compressor
56
D.C. Inverter Multi VRF Modular
If there’s no or not enough refrigerant in the system to meet the requirement of operation
startup, system will display U4 “refrigerant shortage protection” and fails to start next progress.
Then check if there’s any leakage or add refrigerant inside until error eliminated.
—— Debugging code Progress code Status code
LED1 LED2 LED3
Meaning
progress Display Display Display
Code code Code
status status status
If unit detects that valve status is not normal, it will display as below:
—— Debugging code Progress code Status code
LED1 LED2 LED3
Meaning
progress Display Display Display
Code code Code
status status status
10_Status
judgments of
db Light 10 Light U6 Light Outdoor valves are not fully turned on.
outdoor valves
before startup
Then check the big and small valves whether they are fully turned on. After the check, press
SW6 return button to restart the judgments.
If unit detects that valve status is normal, it will display as below and start next progress.
—— Debugging code Progress code Status code
LED1 LED2 LED3
Meaning
progress Display Display Display
Code code Code
status status status
10_Status
judgments of
db Light 10 Light OC Light Outdoor valves are turned on normally.
outdoor valves
before startup
57
D.C. Inverter Multi VRF Modular
If it’s confirmed, press SW7 confirmation button. Unit will display as below and start next
progress.
—— Debugging code Progress code Status code
LED1 LED2 LED3
Meaning
progress Display Display Display
Code code Code
status status status
12_Status
judgments of Manual calculation of refrigerant quantity
db Light 12 Light AE Light
outdoor valves is set up.
before startup
Step 17: after unit is confirmed to start debugging, system select cooling/heating mode
according to ambient temperature.
A If cooling mode is selected, relevant display is as below:
Debugging
—— Progress code Status code
code
LED1 LED2 LED3 Meaning
progress Display Display Display
Code code Code
status status status
58
D.C. Inverter Multi VRF Modular
Step 18: if there’s no error during operation for about 40min, system will automatically confirm
that debugging is finished and then stop. System resumes standby condition and displays as
below:
—— Debugging code Progress code Status code
LED1 LED2 LED3
Meaning
progress Display Display Display
Code code Code
status status status
Step 19: after debugging is finished, some functions can be set up according to project’s
actual needs. For specific details, please refer to System Functions Setup. If no special
requirements, skip this step.
Step 20: deliver the product to user and inform user about usage precautions.
59
D.C. Inverter Multi VRF Modular
IPM temp of inverter ●When ambient temp is lower than 35℃, IPM temp is below
12 ℃
compressor 1 80℃. Highest temp won’t be above 95℃.
Operating freq. of
14 Hz Varies from 30Hz to 100Hz
inverter compressor 2
Current of inverter ●According to different operating freq. and different load,
15 A
compressor 2 current will vary from 7A to 20A.
IPM temp of inverter ●When ambient temp is lower than 35℃, IPM temp is below
16 ℃
compressor 2 80℃. Highest temp won’t be above 95℃.
60
D.C. Inverter Multi VRF Modular
Communi
●Quantity of IDU and ODU detected by software is the same
26 -cation Communication data —
with actual quantity. No communication error.
parameter
61
D.C. Inverter Multi VRF Modular
Note:
①When installing remote monitor or central controller, displacement on indoor units’ project
codes must be made. Otherwise, there will be collision malfunction of the project codes.
For detail operation methods, please refer to the CHV5 Installation and Maintenance
Manual.
②If problem can not be solved after checking the above items, please contact
Cooper&Hunter service center and show phenomena and models.
Following circumstance are not malfunction.
“Malfunction” Reason
When unit is started immediately after it is just Overload protection switch makes it run
Unit doesn’t run turned off after 3 minutes delay
Slight cracking sound is heard when just turned It is noise when electronic expansion valve
on initialization
There is sound when unit starts or stops That's sound for gas refrigerant stops to flow
Noise is emitted
There is slight and consecutive sound when unit That's sound for operation of drainage
is running or after running system
Cracking sound is heard when unit is operating That’s sound caused by expansion of panel
and after operating and other parts due to temperature change
The unit blows out When unit runs after no operation for a long
Dust in indoor unit is blew out
duct period
Indoor unit still Indoor fan motor will keep running 20-70s so
After every indoor unit receive "stop" signal, fan
runs after switch as to take good use of excess cooling and
will keep running
off heating and prepare for next operation
62
D.C. Inverter Multi VRF Modular
7 Error Indication
Inquiry method of malfunction display: combine division number and content number to check
the corresponding malfunction.
For example, division number L and content number 4 together means power supply
over-current protection.
Content
symbol
Division 0 1 2 3 4 5
symbol
63
D.C. Inverter Multi VRF Modular
Content
symbol
Division 0 1 2 3 4 5
symbol
operation of
after-sales
Limit setting for Compulsory
SE operation
Compulsory max. excursion of
n setting of
defrosting capacity/output engineering
system
capacity code of IDU
Content
symbol
6 7 8 9 A H
Division
symbol
For single
For single control
control over Alarm due to
Power supply is over multiple
L No main IDU multiple units, bad air
insufficient units, IDU series
number of IDU quality
is inconsistent
Indoor is inconsistent
Malfunction of Malfunction of
Malfunction PCB of wired
exit-tube water Malfunction of Web address of
d of humidity controller is
temperature temperature jumper cap IDU is abnormal
sensor abnormal
sensor sensor
E
Malfunction
Malfunction of Malfunction of Malfunction of Malfunction of
of discharge Current
discharge discharge discharge discharge
temperature sensor of
F temperature temperature temperature temperature
sensor of compressor 1
sensor of sensor of sensor of sensor of
compressor is abnormal
compressor 2 compressor 4 compressor 5 compressor 6
3
Protection
Over-current Gas-mixing High pressure Low pressure
because of
J protection for protection of ratio protection of ratio protection
abnormal
compressor 6 4-way valve system of system
pressure
Malfunction
Malfunction of
Outdoor of exit tube Malfunction of Malfunction of
inlet tube Malfunction of Clock of
temperature gas temperature oil-return
b temperature outdoor humidity system is
sensor of sensor of heat temperature
sensor of vapor sensor abnormal
vapor liquid exchanger sensor 1
liquid separator
separator
Malfunction High-voltage
Drive IPM Drive IPM high Desynchronizin
of drive Malfunction of protection of
module temperature g protection of
P temperature drive storage chip compressor’s
protection of protection of inverter
sensor of of compressor drive DC bus
compressor compressor compressor
compressor bar
Malfunction Malfunction of High-voltage
Drive IPM Drive IPM high Desynchronizin
of drive drive storage chip protection of
H module temperature g protection of
temperature of inverter outdoor fan’s drive
protection of fan protection of fan inverter fan
sensor of fan fan DC bus bar
Alarm because
Malfunction of Malfunction of
U valve is
pipeline for IDU pipeline for ODU
abnormal
Debuggi
ng Abnormal
Alarm because Rated
communicati Emergency status Emergency Emergency status
C ODU quantity is capacity is
on of of compressor status of fan of module
inconsistent too high
converter
Heat pump Quiet mode Vacuum pump
A Heating
function setting setting mode
Status
Inquiry of Inquiry of Inquiry of project Check quantity Heating only
n Heat pump unit
malfunction parameters code of IDU of IDU on line unit
64
D.C. Inverter Multi VRF Modular
Content
symbol
C L E F J P
Division
symbol
IDU is not Rotation speed Setting of
Malfunction Malfunction Zero-crossing
matching of EC DC water functional DIP
L of water flow of shunt malfunction
with pump is switch code is
switch valve setting of PG motor
outdoor unit abnormal wrong
Malfunction
Indoor Setting Malfunction
Malfunction of upper Malfunction of
capacity of Malfunction of of inlet tube
of air outlet water backwater
d DIP switch indoor CO2 temperature
temperature temperature temperature
code is sensor sensor of
sensor sensor of sensor
abnormal generator
water tank
E
Current Current Current
Current
sensor of sensor of Current sensor sensor of
sensor of Malfunction
F compressor compressor of compressor compressor
compressor 6 of DC motor
2 is 3 is 4 is abnormal 5 is
is abnormal
abnormal abnormal abnormal
Protection
Water flow because Oil-return
Oil-return pipe
J switch high pipe is
is blocked
protection pressure is leaking
too low
Protection
Protection
because Malfunction High-pressure
because the Malfunction of Malfunction
the of outlet sensor and
temperature inlet tube of
temperature tube low-pressure
Outdoor b sensor at the temperature temperature
sensor at temperature sensor are
top of sensor of sensor of
the top of sensor of connected
compressor condenser oil-return 2
compressor condenser reversely
2 is loose
1 is loose
Malfunction
Low voltage Malfunction
of current AC current
protection for Phase-lacking of charging Failure startup
detection protection of
P DC bus bar of inverter loop of of inverter
circuit drive inverter
of drive of compressor driven of compressor
of compressor
compressor compressor
compressor
Malfunction
Low voltage Malfunction
of current AC current
protection of Phase-lacking of charging Failure startup
H detection protection of
bus bar of of inverter fan loop of fan of inverter fan
circuit of fan inverter fan
fan drive drive
drive
Emergency
Identification
operation
Setting of Charging of malfunction
DIP switch
U main IDU is refrigerant is of IDU of
code of
succeeded invalid mode
compressor
exchanger
is wrong
Debugging The
matching Communication
Malfunction Address DIP Malfunction
ratio of rated malfunction
No main of multiple switch code of of multiple
C capacity for between mode
unit main control system is wired
IDU and exchanger and
units shocking controller
ODU is too IDU
low
Debugging
Charge Charge Cleaning
confirmation
A Cooling refrigerant refrigerant Fan reminding of
when starting
automatically manually filter
up the unit
Status
High
Cooling temperature
n Negative code Fan model
only unit prevention
when heating
65
D.C. Inverter Multi VRF Modular
Content
symbol
U b d n y
Division
symbol
Indoor unit’s branch is
not inconsistent for
L
one-to-more unit of
heat recovery system
Indoor
Malfunction of
Malfunction of solar
drainage pipe Malfunction of
d Debugging status power temperature
temperature sensor of swing parts
sensor
generator
E
Malfunction of
Malfunction of casing Malfunction of casing Malfunction of exit
inlet tube
top temperature top temperature tube temperature
F temperature
sensor of compressor sensor of sensor of mode
sensor of mode
1 compressor 2 exchanger
exchanger
J
Outdoor
Malfunction of Malfunction of
b temperature sensor of temperature sensor
oil return 3 of oil return 4
AC input voltage of
P drive of inverter
compressor
AC input voltage of
H
drive of inverter fan
U
Communicati
Debuggi Communication Communication Malfunction of
on
ng malfunction between Overflow distribution malfunction between network for IDU
C malfunction
IDU and the receiving of IP address mode exchanger and and ODU of
of mode
lamp ODU mode exchanger
exchanger
Long-distance Emergency stop of Shielding
A Limit operation Child lock status
emergency stop operation status
Status Length
Eliminate the
modification of
n long-distance shielding Bar code inquiry
connection pipe
command of IDU
of ODU
Outdoor heat exchanger is required to be cleaned once every six months. Use vacuum
cleaner with nylon brush to clean up dust and sundries on the surface of heat exchanger. Blow
away dust by compressed air if it is available. Never use water to wash the heat exchanger.
8.2 Drain Pipe
Regularly check if the drain pipe is clogged in order to drain condensate smoothly.
8.3 Notice before Seasonal Use
(1) Check if the inlet/outlet of the indoor/outdoor unit is clogged.
66
D.C. Inverter Multi VRF Modular
9 After-sales Service
In case the air-conditioning unit you bought has any quality problem or you have any inquiry,
please contact the local after-sales service agency designated by Cooper&Hunter.
Warranty should meet the folowing requirements:
(1) First run of the unit should be operated by professional personnel from
Cooper&Hunter appointed service center.
(2) Only Cooper&Hunter manufactured accessories can be used on the machine.
(3) All the instructions listed in this manual should be followed.
(4) Warranty will be automatically invalid if fails to obey any item mentioned above.
67
COOPER AND HUNTER INTERNATIONAL CORPORATION