06.-introduction-to-life-safety-dampers
06.-introduction-to-life-safety-dampers
Dampers
Michael Bulzomi, product manager, commercial
dampers, Greenheck
Participation Guidelines
To receive PDH credit:
◦ You must be present for the entire session and complete a
post-course online evaluation.
◦ Credit cannot be issued to anyone who does not complete the
evaluation.
◦ A link to the evaluation will be provided at the end of the
session and e-mailed in the weeks following the 2024 AHR
Expo.
2
AMCA International has met the standards and requirements of
Registered Continuing Education Program (RCEP). Credit earned upon
completion of this program will be reported to RCEP at RCEP.net. A
certificate of completion will be issued to each participant. As such, it
does not include content that may be deemed or construed to be an
approval or endorsement by RCEP.
4
COPYRIGHT MATERIALS
This educational activity is protected by U.S. and
International copyright laws. Reproduction, distribution,
display and use of the educational activity without written
permission of the presenter is prohibited.
5
Michael J. Bulzomi
Product Manager – Commercial Dampers,
AMCA Member Company
• Over 16 years experience in the HVAC industry
• Has held positions in sales, marketing and
application engineering across the U.S. for HVAC
product manufacturers and Sales Reps
• Holds an MBA, and a Bachelors in Earth Science
and Atmospheric Science
• Active member of ASHRAE, NFPA, and AMCA,
serving on multiple committees
Learning Objectives
Smoke Dampers
Life-Safety
Damper Combination Fire/Smoke Dampers
Types
Corridor Dampers
Lessons Learned…
Major U.S. fire incidents shaped modern-day code
requirements:
• MGM Grand Hotel Fire (1980)
MGM Grand Hotel Fire
Nov. 21, 1980
85 people died, more than 700 injured
~$223 million in legal settlements
• Area of origin was “The Deli,” an area that was vacant
and closed. Faulty wiring in a display case caused the
initial fire.
• Fire spread rapidly because of the ignition of
wallpaper, PVC piping, glue, and plastic mirrors.
• Toxic fumes/smoke spread because of faulty smoke
dampers within the ventilation ductwork and
throughout the air-circulation system.
“Dampers in the main unit over the
casino were … bolted in such a manner as
to make them inoperable.”
Mounting Position
Vertical
Static or Dynamic (Walls/Partitions)
Hourly Rating Installation
or Horizontal
1-1/2 hr. or 3 hr. (Ceilings/Floors) “In Wall” or “Out
of Wall”
Fire Dampers: Static vs. Dynamic
Compartmentalize the building into individual zones, each of which establishes a passive barrier to
smoke.
◦ Shutdown fans
◦ Close smoke dampers and smoke doors
◦ Prevents the circulation of air and smoke through the HVAC system.
Engineered Smoke-Control System
Combination Fire/Smoke Dampers
“A device that meets both the fire damper and smoke damper requirements.” (NFPA 80/105)
Purpose of Fire/Smoke Damper
• Provide the same level of
protection as individual fire
and smoke dampers
• Fire rating – UL 555
• Leakage rating – UL 555S
• Always supplied with factory-
mounted actuator
• Always dynamically rated
Fire/Smoke Dampers:
UL Rating Qualifications
Mounting Position
Vertical
Static or Dynamic Installation
Hourly Rating (Walls/Partitions)
or Horizontal “In Wall” or “Out
1-1/2 hr. or 3 hr.
(Ceilings/Floors) of Wall”
• First published in 2000, combo of 3 legacy codes: BOCA National Building Code
(BOCA/NBC), Uniform Building Code (UBC) & Standard Building Code (SBC)
• IBC – design of building; IMC – design of mechanical systems; IFC – regulate fire
hazards, testing, maintenance in existing buildings
International Building Code (IBC)
à Ch. 7 – Fire & Smoke Protection Features
• Dynamic
• To be used in applications where fans will be on
during a fire incident. Air-Transfer Opening
Periodic
Testing &
Inspection
Requirements
Periodic Testing & Inspection Requirements
International Fire Code (IFC)
Requires fire dampers to be maintained
in accordance with NFPA 80 and
smoke dampers to be maintained in
accordance with NFPA 105.
National Fire Protection Association
Installation, testing, and maintenance:
◦ NFPA 80 Standard for Fire Doors
5D 6D
Fig. 5.3
(Ducted Inlet & Outlet)
Damper Pressure Drop
• Example Pressure-Drop Specification:
Pressure drop shall not exceed 0.08” wc at 2,000-fpm velocity for a 12” x 12”
damper tested to AMCA Figure 5.3. Dampers shall bear the AMCA Certified
Ratings Program seal for Air Performance in accordance with AMCA 511.
Damper
Installation
Required Elements of an
“Approved” Life-Safety-Damper Installation
1. Rated barrier
2. Listed product
3. Installation requirements
Square Opening
Framing Requirements
Framing of Opening
◦ Vertical studs must run floor to ceiling
◦ Double vertical over 36 in. x 36 in.
◦ Wood studs must be covered with sheet
rock
◦ Steel studs do not need to be covered with
sheet rock
Typical Installation – Fire Damper
① UL-Classified Fire Damper - Dynamic or Static
1-1/2-hr label—for fire separations up to 2 hr
3-hr label—for fire separations up to 4 hr
② Fire Separation
③ Retaining Angles
④ Breakaway Joint
⑤ Sleeve (duct gauge min. SMACNA/NFPA 90A spec.)
⑥ Expansion Clearance
⑦ UL-Listed Heat-Responsive Device (fusible link)
⑧ Duct
⑨ Access Door
Typical Installation – Fire/Smoke Damper
1. UL-classified as both a dynamic fire damper and a
leakage-rated smoke damper
2. UL-qualified damper/actuator assembly
Pneumatic or Electric Actuators
3. Fire separation and smoke barrier
4. Retaining angles
5. Expansion clearance
6. Sleeve
7. Breakaway joint
8. Steel duct
9. Access door
10. UL-listed heat-responsive device
Retaining Angle
Two sided
◦ Attached to the damper sleeve on both
sides
Single sided
◦ Attached to the damper sleeve and
wall/floor
◦ 80 x 50 or 50 x 80 or
40 x 100 on vertical mount
◦ 144 x 96 on horizontal mount
Typical Installation – Smoke Damper
① UL-classified leakage-rated smoke damper
② UL-qualified actuator/damper assembly
Pneumatic or Electric Actuators
③ Smoke barrier
④ Duct
DFDR-510 FSDR-510
True Round True Round
Dynamic Fire Damper Fire Smoke Damper
Retaining Plate The Opening in the Wall
Included with the Damper Does Not Have to be
Round!
Installation Books & QR codes
Questions
To receive PDH credit, you must complete
the post-course evaluation