Siemens-LMG Fisa Tehnica 7422
Siemens-LMG Fisa Tehnica 7422
ro
7 422
Burner controls for the supervision of 1- or 2-stage gas or forced draft gas / oil
burners of small to medium capacity (typically up to 350 kW) in intermittent op-
eration.
The LMG… and this Data Sheet are intended for OEMs which integrate the burner
controls in their products.
Use
LMG... are designed for the startup and supervision of 1- or 2-stage gas or forced draft
gas / oil burners in intermittent operation. The flame is supervised with an ionization
probe or a UV flame detector QRA…. (with ancillary unit AGQ2 …A27). LMG21... /
LMG22... in the same housing replace burner controls LGB21... / LGB22... (refer to
«Type summary») and – with the help of the relevant adapters – burner controls LFI7...
and LFM1... (refer to «Ordering»).
CC1N7422en
Siemens Building Technologies
21.12.2004 HVAC Products
Warning notes
x All activities (mounting, installation and service work, etc.) must be carried out by
qualified staff
x Before performing any wiring changes in the connection area of the LMG…, com-
pletely isolate the burner control from the mains supply (all-polar disconnection)
x Ensure protection against electric shock hazard by providing adequate protection
for the burner control’s connection terminals
x Check to ensure that wiring is in an orderly state
x Check the connecting lines of the air pressure switch for short-circuits (connection
terminals 3, 6 and 11)
x Press the lockout reset button / operation button only manually (applying a force of
no more than 10 N), without using any tools or pointed objects
x Fall or shock can adversely affect the safety functions. Such units must not be put
into operation, even if they do not exhibit any damage
Engineering notes
x On applications with actuators, the actuator does not deliver a position feedback
signal to the burner control
x The actuator’s running times must be matched to the burner control’s program. An
additional safety check of the burner together with the actuator must be made
Mounting notes
x Ensure that the relevant national safety regulations are complied with
2/18
x Always run the high-voltage ignition cables separate from the unit and other cables
while observing the greatest possible distance
x Do not mix up live and neutral conductors
x Install switches, fuses, earthing, etc., in compliance with local regulations
x The connection diagrams shown apply to burner controls with an earthed neutral
conductor. In the case of ionization current supervision in networks with non-earthed
neutral conductor, terminal 2 must be connected to the earth conductor via an RC
unit (part no. ARC 4 668 90660). It must be made certain that local regulations are
complied with (e.g. protection against electric shock hazard) since AC 230 V / 50 Hz
mains voltage produces peak leakage currents of 2.7 mA
x Make certain that the maximum permissible current rating of the connection termi-
nals will not be exceeded
x Do not feed external mains voltage to the control outputs of the burner control.
When testing the devices controlled by the LMG... (fuel valves, etc.), the burner con-
trol must never be plugged in
x In the case of burners with no fan motor, an AGK25 must be connected to terminal
3 of the unit, or else the burner cannot reliably be started up
x For safety reasons, feed the neutral conductor to terminal 2. As shown below, the
burner components (fan, ignition transformer and gas valves) must be connected to
the neutral distributor. The connection between neutral distributor and terminal 2 is
prewired in the base of the unit
Example
2 3 7 4 5
Legend
Z BV2 BV... Fuel valve
M
BV1 M Fan motor
Z Ignition transformer
N
7422a01/0300
3/18
Type reference
LMG21.130B27 x x x x
LMG21.230B27 x x x x
LMG21.330B27 x x x x
LMG21.350B27 x x x x
LMG21.530B27 x x x ---
LMG21.550B27 x x x x
LMG22.130B27 x x x x
LMG22.230B27 x x x x
LMG22.233B27 x x x x
LMG22.330B27 x x x x
LMG25.230B27 x x x x
LMG25.330B27 x x x x
LMG25.350B27 x x x x
LMG49.030B27 --- --- x ---
LMG49.031B27 --- --- x ---
Service notes
x Every time a unit has been replaced, check to ensure that wiring is in an orderly
state and make the safety checks as specified in «Commissioning notes»
x Use service adapter KF8872 for short periods of time only
4/18
The unit contains electrical and electronic components and must not be disposed of
together with domestic waste.
Local and currently valid legislation must be observed.
Mechanical design
LMG... x Units of plug-in design like their predecessor types LGB2… (refer to «Dimensions»)
x Housing made of impact-proof and heat-resistant plastic
x The housing accommodates:
– The microcontroller with the PCB relay for load control
– The electronic flame signal amplifier (ionization)
– The lockout reset button with the integrated red signal lamp and the green flame
signal lamp
5/18
The type references given below refer to the LMG… with no plug-in base and with no flame detector.
For ordering information on the plug-in bases and other accessories, refer to «Ordering».
Type of flame detector Type reference of tw t1 TSA t3n t3 t4 t10 t11 t12 Behavior in the event
burner control min. min. max. ap- ap- ap- min. max. max. of loss of flame during
¹) prox. prox. prox. ¹) ²) ²) operation
Burner controls for prepurging with low-fire air volume, without actuator control
Ionization probe (ION) LMG21.130B27 ³) 2.5 s 7s 3s 2s 2s 8s 5s --- --- Lockout
or UV flame detector LMG21.230B27 4) 2.5 s 20 s 3s 2s 2s 8s 5s --- --- Lockout
QRA…. (with ancillary LMG21.330B27 4) 2.5 s 30 s 3s 2s 2s 8s 5s --- --- Lockout
unit AGQ2 …A27) LMG21.350B27 4) 2.5 s 30 s 5s 4s 2s 10 s 5s --- --- Lockout
LMG21.530B27 2.5 s 50 s 3s 2s 2s 8s 5s --- --- Lockout
LMG21.550B27 4) 2.5 s 50 s 5s 4s 2s 10 s 5s --- --- Lockout
Burner controls for prepurging with nominal air volume, with actuator control
Ionization probe (ION) LMG22.130B27 ³) 2.5 s 7s 3s 2s 3s 8s 3s 12 s 12 s Lockout
4)
or UV flame detector LMG22.230B27 2.5 s 20 s 3s 2s 3s 8s 3s 16.5 s 16.5 s Lockout
QRA…. (with ancillary LMG22.233B27 2.5 s 20 s 3s 2s 3s 8s 3s 30 s 30 s Lockout
unit AGQ2 …A27) LMG22.330B27 4) 2.5 s 30 s 3s 2s 3s 8s 3s 12 s 11 s Lockout
Burner controls for prepurging with low-fire air volume, without actuator
Ionization probe (ION) LMG25.230B27 2.5 s 20 s 3s 2s 2s 8s 5s --- --- Max. 3 repetitions
or UV flame detector LMG25.330B27 2.5 s 30 s 3s 2s 2s 8s 5s --- --- Max. 3 repetitions
QRA…. (with ancillary LMG25.350B27 2.5 s 30 s 5s 4s 2s 10 s 5s --- --- Max. 3 repetitions
unit AGQ2 …A27)
Burner controls for atmospheric burners
Ionization probe (ION) LMG49.030B27 5) 3.5 s --- 3s 2s 0.5 s 0.5 s --- --- --- Lockout
or UV flame detector LMG49.031B27 3.5 s --- 3s 2s 0.5 s 1s --- --- --- Max. 1 repetition
QRA…. (with ancillary
unit AGQ2 …A27)
Legend TSA Ignition safety time t10 Specified time for air pressure signal
tw Waiting time t11 Programmed opening time for actuator «SA»
t1 Prepurge time t12 Programmed closing time for actuator «SA»
t3 Preignition time
t3n Postignition time
t4 Interval between release of «BV1» and release
of «BV2»
6/18
Connection accessories for small burner controls refer to Data Sheet N7201
- Plug-in base AGK11...
- Cable holders AGK65..., AGK66, and AGK67...
- Cable strain relief elements for AGK67...
Connection accessories for small burner controls refer to Data Sheet N7203
- Plug-in base AGK13...
- Plug-in housing AGK56...
- Cover AGK68...
Flame detectors
- Ionization probe supplied by thirds
- UV detectors QRA... refer to Data Sheet N7712
7/18
Note With the same quality of flame, the detector current with the LMG… may be lower
than that with the LGB2….
The flame signal amplifier only responds to the DC current component of the flame signal.
A short-circuit between ionization probe and ground causes the burner to initiate lockout.
8/18
At mains voltage UN
AC 220 V AC 240 V
Detector voltage at QRA... (with no load)
Until the end of «t10» and after controlled shutdown DC 400 V DC 400 V
From the start of «t1» DC 300 V DC 300 V
Detector voltage
Load by DC measuring instrument Ri > 10 M:
Until the end of «t10» and after controlled shutdown DC 380 V DC 380 V
From the start of «t1» DC 280 V DC 280 V
DC current detector signals with UV detector Min. required Max. possible
QRA...
Measurement at the UV detector 200 µA 500 µA
9/18
Ancillary unit In connection with burner controls LMG..., use of UV ancillary unit AGQ2...A27 is man-
AGQ2...A27 datory.
Using circuitry (A) or (B), the quench test on aging UV detectors can be made in 2 dif-
ferent ways:
1. (A) Operation with a permanent line.
UV test with a higher supply voltage across the UV cell on startup and after the
controlled shutdown.
2. (B) Operation with a controlled line.
UV test with a higher supply voltage only on startup during the interval between
controlled startup and air pressure signal.
- No voltage at UV cell after the controlled shutdown
- No full substitute for mode (A) described above since an aged UV cell
can regenerate itself
7422a21/0702
LMG... AGQ2...A27
12 2 11 1 7422a02/0602 br bl rt sw
(B) sw bl
GP/SB
R/W
QRA
L br bl rt sw
L (A) sw bl AGQ2...A27
N
+
QRA
-
10/18
LMG21... Legend
7422d01/0700
SB / R / W / GP 12
B-B´ Interval for establishment of flame
AL 10
C Operating position of burner reached
M 3 C-D Burner operation (generation of heat)
Z 7 D Controlled shutdown by «R»
x Burner will immediately be shut down
BV1 4
x Burner control will immediately be ready for a new
BV2 5
startup
LP 11
A B B´ C
LP Air pressure switch
D
SB / R / W / GP 12
LR Load controller
M Fan motor
AL 10
I Cam I actuator
BV1 4
(LR) BV2 5
t1 Prepurge time
LP 11
t3 Preignition time
FS 1
t3n Postignition time
EK2 8
t4 Interval between establishment of flame and release of «BV2»
t10
tw t1 t3 t3n 400 ms t10 Specified time for air pressure signal
7422d03/0700
t12 TSA t4 t11 Programmed opening time for actuator «SA»
t11
t12 Programmed closing time for actuator «SA»
LMG49... TSA Ignition safety time
tw Waiting time
A B B´ C D
7422d06/0301
SB / R / W / GP 12
AL 10
Z 7
BV1 4
BV2 5
FS 1
EK2 8
tw + t1 t3 t3n 400 ms
TSA t4
11/18
Controlled intermittent After no more than 24 hours of continuous operation, the burner control will initiate
operation automatic safety shutdown followed by a restart.
Reversed polarity If the connections of line (terminal 12) and the neutral conductor (terminal 2) have been
protection mixed up, the burner control will initiate lockout at the end of «TSA».
Control program in the x If a fault occurs, all outputs will immediately be deactivated (< 1 second)
event of fault x On restoration of power, a restart will be made with the full control sequence
x If mains voltage drops below the undervoltage threshold (for threshold, refer to
«Functions»), a restart will be made with the full control sequence
x If there is a premature faulty flame signal during «t1», the burner control will initiate
lockout
x If the contacts of the air pressure switch «LP» have welded in their working posi-
tion, startup will be prevented and, after 65 seconds, lockout initiated
x If there is no air pressure on completion of «t10», the burner control will initiate
lockout
x If the burner does not ignite during «TSA», lockout will be initiated
x If the flame is lost during operation:
o LMG21... / LMG22... / LMG49.030B27 lockout
o LMG25... 3 repetitions
o LMG49.031B27 1 repetition
Lockout Lockout cannot be changed and takes place 10 seconds after safety shutdown.
A mains voltage failure during that period a time will lead to a restart.
Resetting the LMG... Whenever lockout occurs, the burner control can immediately be reset.
Press lockout reset button and keep it depressed for 0.5... 3 seconds.
The LMG... can be reset only when all contacts in the line are closed and when there is
no undervoltage.
12/18
GP/SB
AL M Z BV1 BV2
HS LP
7422a03/0404
EK2
0 I
Si
L
N
ON/OFF
Controlled pre-purging «t1» with low-fire air volume. Same low-fire actuator
position during startup and operation.
LR SA RV
For information about actuators «SA»:
SQN3... refer to Data Sheet N7808
SB/R/W
SQN7… refer to Data Sheet N7804 BV1 BV2
L
SQN9... refer to Data Sheet N7806
LMG21.../25... LMG21.../25...
12 2 10 8 3 6 11 9 7 4 5 1 12 2 10 8 3 6 11 9 7 4 5 1
(*)
ION ION
EK2 EK2 LP
LP
AL M Z AL M Z
BV1 BV1
GP/
GP/SB SB
LR R/W LR
R/W
HS HS BV2
BV2
(*)
*
0 I N 1 2 6 7 5 4 3 0 I N N 1 2 5 3 6 4
Si Si
B
7422a05/0404
b1 b2 K2
N L N L
+
III IV IV III
LKP
a b a b t1 a b D a b
A NL I
a3 RV - + K1
a2 C3
C31
II I V KL IV IV IV II I V
MS III III MS
a b a b a b Zu
t a b a b R32 R1 a b
LK II 7422d04/0300 LK
SA
7422a06/0404
LMG21.../25...
12 2 10 8 3 6 11 7 4 5 1
LP ION
Z
EK2
GP/
AL M SB BV1
LR
R/W
BV2
HS N 3 6
8 4 1 5 2 7
0 I
Si
b2 LKP
N L a1 c1
NL I I
IV IV
b1 a2 III
KL
III
zu
B A C t
7422a07/0404
M II t1 TSA
I II III IV t4
LMG22... / LMG29...
12 2 10 8 3 6 11 7 4 5 9 1
R/W SA ION
GP/SB
AL M Z BV1 BV2
HS LP
7422a08/0404
EK2
0 I
Si
L
N
ION ION
GP EK2
LP Z EK2 LP
AL AL LR Z
S1)
R/W BV1
R/W M BV1
LR
GP/SB M
HS
* *
BV2 0 I
SB Si 6 8 10 2 1 3 7 9
N 1 8 2 7 5 6 3 4 9 2) R3
7422a11/0404
HS N L
R3 R1
R1
0 I t4 K2
Si
7422a22/0404
LKP TSA
B b1 b2
N L t1 K1
C2
A a1 a2 NL
+
I
D
KL III RV
- + C3
M LK III III
I II III V Zu R2 I II
5
1) t MS
RV II 7422d05/0300
C1
SA LK
12 2 10 8 3 6 11 5 9 7 4 1 12 2 10 8 3 6 11 9 5 7 4 1
R/W LP R/W LP
Z ION Z ION
EK2 EK2
LR LR
GP/SB AL GP/SB
M AL M 1 2
BV1 BV1
BV2 BV2
HS N 5 4 1 3 2 8 6 7 2
HS N 4 5 1 3 8 6 7
0 I b2 0 I
Si Si b2
L a1 c1 LKP
N a1
N L
NL I I
b1 a2
b1 a2 IV IV
KL III
A B
7422a12/0404
C A B III
7422a13/0404
M zu
t M
I II III IV II TSA
t1 I II III IV
t4
SQN7...454 / 2-stage control, 1-wire control SQN7...424 / 2-stage control, 2-wire control
14/18
LMG49...
LMG49...
12 2 10 8 3 6 11 7 9 4 5 1
ION
R/W
AGK25
GP/SB
AL Z BV1 BV2
HS
7422a19/0404
EK2
0 I
Si
L
N
Operating concept
- Wait > 10 s
- Press lockout reset button for > 3 s
- Read blink code of red signal lamp
AL
o «Error code table»
x Burner control in operation x Restart
o Green flame signal lamp Press lockout reset button for 0.5...3 s
illuminated
7422z02/0300
FS
15/18
7422z03e/0301
After lockout, the red signal lamp is steady on.
For reading the cause of fault, refer to the blink code given in the following table:
FS AL
Press lockout
Illuminated phase reset button
(waiting time > 10 s) for > 3 s Blink code Off Blink code
~
Fault Approx. 3 s 7422z04e/0902
During the time the cause of fault is diagnosed, the control outputs are deactivated.
- The burner remains shut down
- Exception: Error message «AL» at terminal 10
16/18
LMG21... / LMG25...
7422a17e/0404
Control of mircocontroller EK
NT
RESET
AL red FS green
K4 FSV
K3
K1 K2
AS
12 2 10 7 3 4 5 8 6 11 1
EK2 ION
R/W/ Z BV1 BV2
AL
GP/SB M
LP
H
Si
L
N
LMG22...
7422a18e/0404
Control of microcontroller EK
NT
RESET
AL red FS green
K4 FSV
K1 K2 K3
AS
12 2 10 7 3 9 4 5 8 6 11 1
R/W/ Z
AL
GP/SB M BV1 BV2
EK2
LP ION
H
LR
Si
SA
L
M
BV2
N
LMG49...
7422a20e/0404
Control of microcontroller EK
NT
RESET
AL red FS green
K4 FSV
K3
K1 K2
AS
12 2 10 7 3 4 5 8 6 11 1
EK2
ION
R/W/ Z BV1 BV2
AL
GP/SB
H AGK25
Si
L
N
17/18
Dimensions in mm
22
LMG...
5,5
62,5
7422m06/1204
Plug-in base AGK11... / AGK13...
9
41,5
88
91
47
62,5
Ancillary unit
27,5
AGQ2...A27
Type Dimensions
90,5
reference
60 A B
AGQ2.1A27 500 19
220 69 6
AGQ2.2A27 300 34
65,6
4
18
5,4 5,4
A B 6
13 7422m03/0400