0% found this document useful (0 votes)
32 views64 pages

Contour Breton Vacuum Pump ELMO-RIETSCHLE

Uploaded by

Ahmed Slim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views64 pages

Contour Breton Vacuum Pump ELMO-RIETSCHLE

Uploaded by

Ahmed Slim
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 64

Edition: 04.2010 · 610.48060.40.

000 Original operating instructions · English

Operating Instructions L-BV7

2BV7 060
2BV7 061
2BV7 070
2BV7 071

L-Serie
L-Series
Flüssig-
keitsring
Liquid Ring
© 2010 Gardner Denver Deutschland GmbH · Industriestraße 26 · 97616 Bad Neustadt · Germany
Replication, distribution and / or editing of this document and the use and distribution of its content is
prohibited unless explicitly permitted. Violation obligates compensation for damages.
All rights reserved in case of the issue of a patent, utility patent or design patent.
Contents

Contents

1 Glossary ..............................................................................................................................................6
2 Safety ..................................................................................................................................................7
2.1 Definitions .................................................................................................................................7
2.1.1 Safety alert symbol.......................................................................................................7
2.1.2 Signal words.................................................................................................................7
2.1.3 Graphic symbols...........................................................................................................8
2.2 General safety precautions .......................................................................................................9
2.3 Residual risks..........................................................................................................................11
3 Intended Use .....................................................................................................................................12
4 Technical Data ..................................................................................................................................13
4.1 Mechanical data ......................................................................................................................13
4.2 Electrical data..........................................................................................................................16
4.3 Operating conditions ...............................................................................................................16
5 Description of Vacuum Pump/Compressor .......................................................................................18
5.1 Design .....................................................................................................................................18
5.2 Operating method ...................................................................................................................18
5.3 Operating modes.....................................................................................................................19
5.3.1 Self-priming operation ................................................................................................19
5.3.2 Operation with operating-liquid feed ..........................................................................19
6 Transport and Handling.....................................................................................................................20
7 Installation .........................................................................................................................................22
7.1 Installation ...............................................................................................................................22
7.2 Electrical connection (motor) ..................................................................................................24
7.3 Connecting pipes/hoses (vacuum pump/compressor)............................................................25
7.3.1 Inlet connection ..........................................................................................................26
7.3.2 Discharge connection.................................................................................................26
7.3.3 Operating-liquid port...................................................................................................26
7.3.4 Notes ..........................................................................................................................27
7.4 Accessories.............................................................................................................................27
8 Commissioning ..................................................................................................................................28
8.1 Preparation and start-up .........................................................................................................28
8.2 Self-priming operation .............................................................................................................30
8.3 Operation with operating-liquid feed .......................................................................................31
9 Operation...........................................................................................................................................33
9.1 Self-priming operation .............................................................................................................33
9.2 Operation with operating-liquid feed .......................................................................................33
10 Shut-Down and Longer Standstills ....................................................................................................34
10.1 Draining ...................................................................................................................................34
10.2 Preparing for longer standstill .................................................................................................34
10.3 Storage conditions ..................................................................................................................35
11 Servicing............................................................................................................................................36
11.1 Maintenance............................................................................................................................36
11.2 Repairs/troubleshooting ..........................................................................................................39
11.3 Spare parts..............................................................................................................................41
11.3.1 Ordering nash_elmo spare parts................................................................................41
11.3.2 Ordering standardized parts.......................................................................................41
11.4 Service/After-sales service......................................................................................................41
11.5 Decontamination and Declaration of Clearance .....................................................................42
12 Disposal.............................................................................................................................................43

© Gardner Denver Deutschland GmbH 3 / 64 610.48060.40.000


Contents

13 Accessories .......................................................................................................................................44
13.1 Flanges....................................................................................................................................44
13.2 Non-return valve......................................................................................................................44
13.3 Gas ejector..............................................................................................................................45
13.4 Liquid separator ......................................................................................................................46
13.5 Cavitation protection ...............................................................................................................49
14 Exploded View with Parts List ...........................................................................................................50
14.1 Parts list...................................................................................................................................50
14.2 Exploded view .........................................................................................................................51
EU declaration of conformity ..................................................................................................................54
Form for statement on safety .................................................................................................................55
Index .......................................................................................................................................................56

610.48060.40.000 4 / 64 © Gardner Denver Deutschland GmbH


List of Illustrations

List of Illustrations
Fig. 1: Dimensions .............................................................................................................................13
Fig. 2: Minimum inlet pressure/cavitation limit ...................................................................................17
Fig. 3: Design and operation of liquid-ring vacuum pumps/compressors (cross-section of operating
chamber) .................................................................................................................................18
Fig. 4: Attachment points ...................................................................................................................21
Fig. 5: Points for measuring the vibration speed................................................................................23
Fig. 6: Securing elements for bolting feet to supporting surface........................................................23
Fig. 7: Pipe/hose connection of vacuum pump/compressor ..............................................................25
Fig. 8: Self-priming operation .............................................................................................................30
Fig. 9: Setting the operating-liquid flow rate: Setting pre-pressure....................................................31
Fig. 10: Setting the operating-liquid flow rate: Measuring the volume with a graduated vessel ..........31
Fig. 11: Operation with operating-liquid feed: Non-automatic operation..............................................32
Fig. 12: Operation with operating-liquid feed: Automatic operation .....................................................32
Fig. 13: Maximum permissible quantity of water entrained via the inlet connection............................32
Fig. 14: Pour in preservative and turn shaft .........................................................................................34
Fig. 15: Removing vacuum pump/compressor housing.......................................................................38
Fig. 16: Pouring in decalcifying agent and freeing shaft by turning .....................................................38
Fig. 17: Flanges....................................................................................................................................44
Fig. 18: Non-return valve......................................................................................................................44
Fig. 19: Gas ejector..............................................................................................................................45
Fig. 20: Mounting liquid separator, Part 1 of 2 .....................................................................................47
Fig. 21: Mounting liquid separator, Part 2 of 2 .....................................................................................48
Fig. 22: Exploded view: vacuum pump/compressor section................................................................51
Fig. 23: Exploded view: motor section .................................................................................................52
Fig. 24: Exploded view: motor section .................................................................................................53

© Gardner Denver Deutschland GmbH 5 / 64 610.48060.40.000


Glossary

1 Glossary
In these instructions the following technical terms with the specified meaning are used:

Designation: Definition:

Vacuum pump Machine for generating a vacuum.

Compressor Machine for generating a gauge pressure.

Machine Here: Vacuum pump or compressor.


Unit for extracting, transporting and compressing gases and/or vapors, as well as
for generating vacuum and gauge pressure. Here the drive is not considered part
of the machine.

Pump-motor unit Unit consisting of a machine and a drive motor.

Machine set Two or more machines that are interconnected with couplings and mounted on a
common base frame.

Driving side; Side of the machine on which the drive is connected.


D side

Non-driving side; Side of the machine on which no drive is connected.


N side

Inlet pressure Pressure of the pumped gases/vapors on the inlet connection of the machine.

Discharge pressure; Pressure of the pumped gases/vapors at the discharge connection of the machine.
Compression pressure

Test pressure Pressure to which the machine is subjected when testing for leaks.

Qualified personnel Persons who, based on their training, experience and instruction, as well as their
knowledge of the pertinent standards, regulations, accident protection regulations
and operating conditions, are capable of carrying out certain tasks (e.g. start-up,
operation, maintenance, repair) and can recognize and avoid possible dangers in
the process. The required knowledge includes a knowledge of first aid and of the
on-site emergency equipment.
These persons must be authorized by the person responsible for system safety to
perform the required tasks.

610.48060.40.000 6 / 64 © Gardner Denver Deutschland GmbH


Safety

2 Safety
2.1 Definitions

To point out dangers and important


information, the following signal words and  WARNING
symbols are used in these operating
instructions: Danger of injuries.
Indicates a potentially hazardous
situation,
2.1.1 Safety alert symbol that could result in death or
serious injury
 The safety alert symbol is if the corresponding measures
located in the safety precautions are not taken.
in the highlighted heading field
on the left next to the signal word
(DANGER, WARNING,  CAUTION
CAUTION).
Danger of injuries.
Safety precautions with a safety
alert symbol indicate a danger of Indicates a potentially hazardous
injuries. situation,
that may result in minor or
Be sure to follow these safety moderate injury
precautions to protect against if the corresponding measures
injuries or death! are not taken.

Safety precautions without a


safety alert symbol indicate a CAUTION
danger of damage.
Danger of damage.
Indicates a potentially hazardous
2.1.2 Signal words situation
that may result in property
damage
DANGER The signal words are located in if the corresponding measures
the safety precautions in the are not taken.
WARNING
highlighted heading field.
CAUTION
They follow a certain hierarchy
NOTICE and indicate NOTICE
(in conjunction with the safety
NOTE alert symbol, see Chapter 2.1.1) Indicates a possible
the seriousness of the danger disadvantage,
and the type of warning. i.e. undesirable conditions or
consequences can occur
See the following explanations: if the corresponding measures
are not taken.

 DANGER NOTE
Danger of injuries. Indicates a possible advantage
Indicates an imminently if the corresponding measures
hazardous situation, are taken;
that will result in death or tip.
serious injury
if the corresponding measures
are not taken.

© Gardner Denver Deutschland GmbH 7 / 64 610.48060.40.000


Safety

2.1.3 Graphic symbols

The graphic symbol is located in safety


precautions in the left-hand field.
There are several types of graphic symbols:

Hazard alerting symbols Prohibition symbols


... for general dangers: ... for general prohibitions:

... for special dangers:


... for special prohibitions:

Mandatory action symbols Information


... for general instructions:

... for special instructions:

610.48060.40.000 8 / 64 © Gardner Denver Deutschland GmbH


Safety

2.2 General safety precautions

 WARNING  WARNING
Improper use of the unit can When working on the unit,
result in serious there is a danger of injury,
or even fatal injuries! e.g. in the form of cuts/cutting
off, crushing and burns!
These operating instructions During transport/handling as well
 must have been read as assembly and disassembly
completely and understood always wear personal protective
before beginning any work equipment (safety helmet,
with or at the pump-motor protective gloves, safety boots)!
unit,
 must be strictly observed,
 must be available at the
operating location of the
pump-motor unit.

 WARNING
 WARNING
Hair and clothing can be pulled
Improper use of the unit can into the unit or caught and
result in serious wound up
or even fatal injuries! moving parts!
Do not wear long, loose hair or
Only operate the pump-motor wide, loose clothes!
unit
Use a hair net!
 for the purposes indicated
under "Intended Use"!
 with the fluids indicated under  DANGER
'Intended Use'!
 with the values indicated Electrical danger!
under 'Technical Data'!
Before beginning work on the
unit or system, the following
 WARNING measures must be carried out:
 Deenergize.
Improper use of the unit can  Secure against being
result in serious switched on again.
or even fatal injuries!  Determine whether
deenergized.
Transport and handling as well  Ground and short-circuit.
as assembly and disassembly of  Cover or block off adjacent
the unit may be carried out by energized parts.
trained and responsible
personnel only!
 DANGER
Electrical danger!
Work on electrical installations
may be carried out by trained
and authorized electricians only!

© Gardner Denver Deutschland GmbH 9 / 64 610.48060.40.000


Safety

 DANGER  WARNING
Electrical danger! Danger due to gauge pressure
and vacuum!
Do not open the motor terminal
box unless absence of electricity Danger due to escaping fluid!
has been ensured!
Only operate the unit with the
pipes/hoses connected to the
 WARNING intake and discharge connection,
as well as to the operating-liquid
Danger due to gauge pressure port!
and vacuum!
Danger due to escaping fluid!  WARNING
Before beginning work on the
Danger from rotating impeller
unit or system:
of unit!
 Interrupt supply of operating
liquid. Only operate the unit with the
 Bleed lines and vacuum pipes/hoses connected to the
pump/compressor intake and discharge connection,
(depressurize). as well as to the operating-liquid
port!

 WARNING
 WARNING
Danger from rotating external
fan of unit! Danger in the form of cuts or
Only operate the unit with the fan cutting off extremities on the
guard mounted! impeller of the pump-motor
unit!
It is prohibited to remove the fan
guard! Do not reach into the unit through
open connections!
Do not insert objects into the unit
through the openings!
 WARNING
Danger from rotating impeller  WARNING
of unit!
Only operate the unit with the Danger due to gauge pressure
vacuum pump/compressor and vacuum!
housing mounted! Check the lines and containers
Do not remove the vacuum used for sufficient strength!
pump/compressor housing until
after the unit has been shut down  WARNING
and the impeller has come to a
complete stop! Danger due to gauge pressure
Consider that the impeller has a and vacuum!
certain run-out! Danger due to escaping fluid!
Check the connections of the
pipe/hose connections for leaks!

610.48060.40.000 10 / 64 © Gardner Denver Deutschland GmbH


Safety

2.3 Residual risks


 WARNING
 WARNING
Danger of burns and scalding
from hot surfaces of the pump-
Danger zone:
motor unit and from hot fluids!
Shaft exposed in gap between
Do not touch during operation!
drive motor and vacuum
Allow to cool after shut-down! A
pump/compressor.
Hazard:
 CAUTION
Possible entanglement of long,
Danger of unit tipping over! loose hair!
Secure the pump-motor unit on Protective measures:
the installation surface before
Wear hair net!
putting into operation!

 WARNING
Danger zone:
Fan guard
Hazard:
Long, loose hair can be drawn
into external fan through fan
guard grate, even with fan guard
mounted!
Protective measures:
Wear hair net!

 WARNING
Danger zone:
Hot surface.
Hazard:
Burns/scalding possible.
Protective measures:
Do not touch!
Wear protective gloves!

© Gardner Denver Deutschland GmbH 11 / 64 610.48060.40.000


Intended Use

3 Intended Use

These operating instructions When operating the L-BV7, the limits listed in
Chapter 4, "Technical Data", Pg. 13 ff. must
 apply to liquid-ring vacuum always be complied with.
pumps/compressors of the L-BV7 series,
types 2BV7 060, 2BV7 061, 2BV7 070 and
2BV7 071, Foreseeable Misuse
 contains instructions bearing on transport
and handling, installation, commissioning, It is prohibited
operation, shut-down, storage, servicing
and disposal of the L-BV7,  to use the L-BV7 in applications other than
 must be completely read and understood by industrial applications
all operating and servicing personnel before unless the necessary protection is provided
beginning to work with or on the L-BV7, on the system,
 must be strictly observed, e.g. guards suitable for children's fingers,
 must be available at the site of operation of  to use the device in rooms in which
the L-BV7. explosive gases can occur if the L-BV7 is
not expressly intended for this purpose;
About the operating and servicing personnel of  to extract, to deliver and to compress
the L-BV7: explosive, flammable, corrosive or toxic
fluids
 These persons must be trained and unless the L-BV7 is specifically designed
authorized for the work to be carried out. for this purpose,
 Work on electrical installations may be  to operate the L-BV7 with values other than
carried out by trained and authorized those specified in Chapter 4, "Technical
electricians only. Data", Pg. 13 ff.
 If necessary, the training/instruction on
using the L-BV7 can be carried out by the Any unauthorized modifications of the L-BV7
manufacturer/suppler on order of the are prohibited for safety reasons.
owner. any maintenance and repair work, such as
replacing worn or defective components, may
The L-BV7 only be carried out by companies authorized
 are pump-motor units for generating by the manufacturer (please contact service).
vacuum or gauge pressure.
 are used to extract, transport and compress
the following
pumped gases/vapors:
– all dry and humid gases,
which are not explosive or flammable,
– preferably air or air/vapor mixtures.
– In case of corrosive or toxic
gases/vapors contact service.
 are designed for operation with the
following
operating liquids:
– Water
with a pH of 6 to 9,
free of solid materials (such as sand).
– If the pH values or operating liquids
differ, it is necessary to contact service.
 are intended for industrial applications.
 are designed for continuous operation.

610.48060.40.000 12 / 64 © Gardner Denver Deutschland GmbH


Technical Data

4 Technical Data
4.1 Mechanical data

Dimensions

A
N3.0 G
W1
N2.0 W
d
N1.0 S5 S4
P2
H4

P3
H3

W3
H2

H1
H6

N8.7
S2 N4.2
R
B1 E M
B L

Fig. 1: Dimensions

N1.0 Inlet connection


N2.0 Discharge connection
N3.0 Operating-liquid port
N4.2 Emptying or drain opening
N8.7 Connection for cavitation protection

Specification in mm

Type 2BV7 060 2BV7 061 2BV7 070 2BV7 071


...-1 ...-2
...-3 ...-1 ...-2 ...-3 ...-1
...-2 ...-3

A 335 372 394 438 473 482 488 511

B 162 180 180 202 204 266 227 266

B1 125 140 140 160 160 216 190 216

E 100 100 100 140 140 140 140 140

G 186 218 218 231 266 266 252 266

H1 80 90 90 100 100 132 112 132

H2 107 117 117 134 134 166 146 166

H3 156 166 166 194 194 227 206 227

H4 180 190 190 222 222 260 234 260

H6 26 36 36 34 34 66 46 66

L 184 225 225 249 284 284 263 284

© Gardner Denver Deutschland GmbH 13 / 64 610.48060.40.000


Technical Data

Specification in mm

Type 2BV7 060 2BV7 061 2BV7 070 2BV7 071


...-1 ...-2
...-3 ...-1 ...-2 ...-3 ...-1
...-2 ...-3

M 72 68 68 89 89 99 96 99

P2 200 218 218 235 235 300 261 300

P3 161 180 180 201 202 265 225 265

R 59 55 55 71 71 81 78 81

S2 10 10 10 12 12 12 12 12

S4 M25 x 1.5 M32 x 1.5

S5 M16 x 1.5 M32 x 1.5

W 32 32 32 42 42 42 42 42

W1 110 110 110 120 120 120 120 120

W3 23 23 23 28 28 28 28 28

d G1 G1 G1 G 1½ G 1½ G 1½ G 1½ G 1½
N3.0,

4.2, 8.7

Specifications in inches

Type 2BV7 060 2BV7 061 2BV7 070 2BV7 071


...-1 ...-2
...-3 ...-1 ...-2 ...-3 ...-1
...-2 ...-3

A 13.2 14.6 15.5 17.2 18.6 19.0 19.2 20.1

B 6.38 7.09 7.09 7.95 8.03 10.5 8.94 10.5

B1 4.92 5.51 5.51 6.30 6.30 8.50 7.48 8.50

E 3.94 3.94 3.94 5.51 5.51 5.51 5.51 5.51

G 7.32 8.58 8.58 9.09 10.5 10.5 9.92 10.5

H1 3.15 3.54 3.54 3.94 3.94 5.20 4.41 5.20

H2 4.21 4.61 4.61 5.28 5.28 6.54 5.75 6.54

H3 6.14 6.54 6.54 7.64 7..4 8.94 8.11 8.94

H4 7.09 7.48 7.48 8.74 8.74 10.2 9.21 10.2

H6 1.02 1.42 1.42 1.34 1.34 2.60 1.81 2.60

L 7.24 8.86 8.86 9.80 11.2 11.2 10.4 11.2

M 2.83 2.68 2.68 3.50 3.50 3.90 3.78 3.90

610.48060.40.000 14 / 64 © Gardner Denver Deutschland GmbH


Technical Data

Specifications in inches

Type 2BV7 060 2BV7 061 2BV7 070 2BV7 071


...-1 ...-2
...-3 ...-1 ...-2 ...-3 ...-1
...-2 ...-3

P2 7.87 8.58 8.58 9.25 9.25 11.8 10.3 11.8

P3 6.34 7.09 7.09 7.91 7.95 10.4 8.86 10.4

R 2.32 2.17 2.17 2.80 2.80 3.19 3.07 3.19

S2 0.394 0.394 0.394 0.472 0.472 0.472 0.472 0.472

S4 M25 x 1.5 M32 x 1.5

S5 M16 x 1.5 M32 x 1.5

W 1.26 1.26 1.26 1.65 1.65 1.65 1.65 1.65

W1 4.33 4.33 4.33 4.72 4.72 4.72 4.72 4.72

W3 0.906 0.906 0.906 1.10 1.10 1.10 1.10 1.10

d G1 G1 G1 G 1½ G 1½ G 1½ G 1½ G 1½
N3.0,

4.2, 8.7

© Gardner Denver Deutschland GmbH 15 / 64 610.48060.40.000


Technical Data

Weight 4.3 Operating conditions


Type Weight Temperatures
[kg] [lbs] Temperature max. +80 °C [max. +176 °F]
2BV7 060-1A.0. approx. 16 approx. 35.3 of pumped At higher fluid temperatures,
2BV7 060-2A.0. approx. 17 approx. 37.5 gases/vapors: measures must be taken on
2BV7 060-3A.0. approx. 18 approx. 39.7 the system to prevent burns,
2BV7 061-1A.0. approx. 22 approx. 48.5 e.g. mount separating safety
device (cover).
2BV7 070-1A.0. approx. 31 approx. 68.3
Operating- max. +80 °C [max. +176 °F]
2BV7 070-2A.0. approx. 35 approx. 77.2
liquid min. +5 °C [min. +41 °F]
2BV7 070-3A.0. approx. 48 approx. 106 temperature:
2BV7 071-1A.0. approx. 39 approx. 86 Nominal
value:
2BV7 071-2A.0. approx. 50 approx. 110 +15 °C [+59 °F]
2BV7 071-3A.0. approx. 56 approx. 123
Ambient max. +40 °C [+104 °F]
temperature: min. +5 °C [+41 °F]
Minimum distances for heat dissipation
Type Minimum distance from
fan guard to adjacent surface Pressures
[mm] [inches]
Min. inlet Dependent on the operating
2BV7 060 34 1.34 pressure: liquid temperature
2BV7 061 34 1.34 (see Fig. 2, Pg. 17)
2BV7 070 53 2.09
2BV7 071 53 2.09 When this temperature is
dropped below, the hose of
the liquid separator
Noise level
(accessory) must be
Measuring-surface sound pressure level as per connected to the connection
EN ISO 3744, measured at distance of 1 m for cavitation protection
[3.28 ft] with medium throttling (100 mbar abs. (Fig. 7, Pg. 25, Item 4).
[1.45 psia]) and connected lines, tolerance 3 Max. 1.1 bar abs. [16.0 psia]
dB (A). discharge
Type 1-m measuring-surface sound pressure
pressure level L [dB (A)] during
at 50 Hz: at 60 Hz: vacuum-pump
2BV7 060 70 operation:
2BV7 061 70 Max. 8 bar abs. [116 psia]
70 permissible
2BV7 070 72 If higher pressures can occur
pressure in in the system, then
2BV7 071 76 pump-motor corresponding protective
unit: devices must be provided.
Limit speeds for supply by converter
Type n [rpm] Max. discharge pressure p2 max during
2BV706 4,800 compressor operation (at inlet pressure p1 =
1 bar abs. [14.5 psia]):
2BV707 4,000
Type p2 max

4.2 Electrical data [bar abs.] [psia]


See drive motor rating plate. at at at at
50 Hz: 60 Hz: 50 Hz: 60 Hz:
2BV7 060 2 2 29.0 29.0
2BV7 061 2 2 29.0 29.0
2BV7 070 3 2.5 43.5 36.3
2BV7 071 3.5 2.5 50.8 36.3

610.48060.40.000 16 / 64 © Gardner Denver Deutschland GmbH


Technical Data

300

4.5
250 4
3.5
200
3
p 1 [mbar abs.]

p1 [psia]
2.5
150
2
1.5
100
1
0.5
50
0
0 50 100 150 200
0
f l [°F]
0 20 40 60 80
fl [°C]

Fig. 2: Minimum inlet pressure/cavitation limit

fl [°C, °F] = Temperature of operating liquid


p1 [mbar abs., psia] = Inlet pressure abs.

The minimum permissible inlet pressure of the pump-motor unit is dependent on the temperature of the operating
liquid.
During operation without cavitation protection, the minimum inlet pressure must be set above the shaded area.

Nominal operating-liquid flow rate


(with dry air extraction and with water at 15°C
[59 °F] as operating liquid)
Type Flow rate

[m³/h] [ft³/h]
at at at at
50 Hz: 60 Hz: 50 Hz: 60 Hz:
2BV7 060 0.20 0.20 7.06 7.06
2BV7 061 0.23 0.23 8.12 8.12
2BV7 070 0.28 0.34 9.89 12.0
2BV7 071 0.45 0.55 15.9 19.4

Operating-liquid filling amount for priming


Type Filling amount
[l] [gal (US)] [gal (UK)]
2BV7 060 0.40 0.106 0.088
2BV7 061 0.55 0.145 0.121
2BV7 070 0.80 0.211 0.176
2BV7 071 1.10 0.291 0.242

© Gardner Denver Deutschland GmbH 17 / 64 610.48060.40.000


Description of Vacuum Pump/Compressor

5 Description of Vacuum Pump/Compressor

Fig. 3: Design and operation of liquid-ring


2 vacuum pumps/compressors (cross-section of
operating chamber)
1 3
1 Discharge connection
2 Operating-liquid port
4 3 Inlet connection
4 Impeller
5 Housing
6 Discharge port
5 7 Inlet port
8 Operating liquid

6 7

5.1 Design 5.2 Operating method


The L-BV7 2BV7s are liquid-ring vacuum When the impeller turns, the operating liquid is
pumps compressors. They consist of the put into motion and accelerated. This forms a
vacuum pump/the compressor itself and an liquid ring that also rotates. Due to centrifugal
electric motor. For the detailed design, see force, this ring is arranged concentrically to the
Fig. 3, Pg. 18. housing and eccentrically to the impeller.

The pumped gases/vapors are sucked via the During a complete rotation of the impeller, the
inlet connection (3) into the pump-motor unit following occurs:
and pushed out via the discharge connection  The impeller cells are completely filled with
(1). operating liquid at the upper vertex.
 During the first half rotation, the liquid ring
The impeller (4) with the blades is located in lifts off the impeller hub. The space in the
the cylindrical housing (5). The impeller is cells increases so that the pumped
arranged eccentrically relative to the housing. gases/vapors are sucked in through the
In addition, the housing also contains the inlet port (7).
operating liquid (8). This liquid is fed in via the  The space in the cells is largest at the lower
operating-liquid port (2) and output together vertex, as these are virtually free of
with the pumped gases/vapors via the operating liquid.
discharge connection (1).  During the second half rotation, the liquid
ring approaches the hub again. The space
in the cells decreases so that the pumped
gases/vapors are compressed and pushed
out through the discharge port (6).

610.48060.40.000 18 / 64 © Gardner Denver Deutschland GmbH


Description of Vacuum Pump/Compressor

5.3 Operating modes Here the following additional distinctions are


made:
The pump-motor unit can function in several
different operating modes.
Non-automatic operation
These differ in how the pump-motor unit is
supplied with operating liquid: In this case the operating liquid feed is
switched on and off manually with a stop valve.
 Self-priming operation
See Fig. 11, Pg. 32.
 Operation with operating-liquid feed:

– Non-automatic operation Automatic operation


– Automatic operation In this case the operating liquid feed is
switched on and off by a solenoid valve. The
solenoid valve is dependent on the motor
5.3.1 Self-priming operation operating mode:
In this operating mode the pump-motor unit
automatically sucks in the operating liquid.  Motor/pump-motor unit switched on:
The operating-liquid flow rate is automatically Valve open.
adjusted.
 Motor/pump-motor unit switched off:
See Fig. 8, Pg. 30. Valve closed.

See Fig. 12, Pg. 32.


5.3.2 Operation with operating-liquid feed
In this operating mode the pump-motor unit
DOES NOT automatically suck in the operating NOTICE
liquid.
A certain volume flow ("nominal operating- The following is dependent on
liquid flow rate") or pre-pressure must be set the operating mode:
for the operating liquid.
 when and how the pump-
motor unit must be filled with
operating liquid the first time,
 how the pump-motor unit is
put into operation.
The specifications for this are
contained in Chapter 7,
"Installation", Pg. 22ff., and
Chapter 8, "Commissioning",
Pg. 28ff.

© Gardner Denver Deutschland GmbH 19 / 64 610.48060.40.000


Transport and Handling

6 Transport and Handling

Manual handling:
 WARNING
Danger from tipping or falling
 WARNING
loads!
Prior to transport and handling Danger from lifting heavy
make sure that all components loads!
are securely assembled and
Manual handling of the unit is
secure or remove all components
only permitted within the
the fasteners of which have been
following limits:
loosened!
 max. 30 kg [max. 66 lbs]
for men
 CAUTION  max. 10 kg [max. 22 lbs]
for women
Tipping or falling can lead to  max. 5 kg [max. 11 lbs]
crushing, broken bones etc.! for pregnant women
Sharp edges can cause cuts! For the weight of the pump-motor
unit, see Chapter 4.1,
Wear personal safety equipment
"Mechanical data",
(protective helmet, protective
Section "Weight", Pg. 16.
gloves, safety shoes) during
transport! For weights above the given
values use suitable lifting
appliances and handling
equipment!

Handling by means of lifting equipment:

Packing:  WARNING
On delivery the pump-motor unit is bolted to a
pallet and covered with a cardboard box. Danger from tipping or falling
To unpack, remove the cardboard box and loads!
unscrew the securing bolts on the feet of the When transporting with lifting
pump-motor unit. equipment, observe the following
basic rules:
 The lifting capacity of lifting
equipment and lifting gear
must be at least equal to the
unit's weight.

For the weight of the pump-


motor unit, see Chapter 4.1,
"Mechanical data",
Section "Weight", Pg. 16.

 The pump-motor unit must be


secured so that it cannot tip or
fall.

 Do not stand or walk under


suspended loads!

610.48060.40.000 20 / 64 © Gardner Denver Deutschland GmbH


Transport and Handling

Transport and handling by means of a crane Attach the strap belts as shown in Fig. 4,
and strap belts is advisable. Pg. 21:
 Use two strap belts, of which one is routed
under the vacuum pump/compressor
housing, and one under the fan guard.
 The strap belts should be seated securely
in the undercuts so that the unit cannot slip
out.
 The belts must be sufficiently long (spread
angle smaller than 90°).
 Make sure that no damage is caused to any
attached fittings.

 WARNING
Danger from tipping loads!
Be sure to observe the routing of
the strap belts as shown in
Fig. 4, S. 21, even if the motor is
provided with attachment points
such as transport eyes or eye
bolts.
These are solely designed for the
separate transport of the motor,
however not for the different
weight distribution that results for
the mounted vacuum
pump/mounted compressor, so
that the unit could tip!

Fig. 4: Attachment points

© Gardner Denver Deutschland GmbH 21 / 64 610.48060.40.000


Installation

7 Installation
7.1 Installation

 CAUTION CAUTION
Danger of crushing from unit Danger of damage to the
tipping over! pump-motor unit due to
overheating!
In the unmounted state, the unit
can easily tip due to its weight When installing the unit, make
distribution! sure that heat dissipation and
cooling are not obstructed. The
Wear gloves and safety shoes! minimum distances specified in
Handle the unit with the Chapter 4.1, "Mechanical data",
appropriate care! Section "Minimum distances for
heat dissipation", Pg. 16 must be
 CAUTION complied with.
Discharge air of other units may
Danger of tripping and falling! not be directly sucked in again!
Make sure the unit does not
present a danger of tripping! For the space requirement and arrangement of
the holes for installing and securing the pump-
motor unit, please see Fig. 1, Pg. 13.
 WARNING For minimum clearances for heat dissipation
and cooling, see Chapter 4.1, "Mechanical
Electrical danger! data", Section "Minimum distances for heat
The pump-motor unit must be dissipation", Pg. 16.
installed so that the electrical
device cannot be damaged by
external influences! The pump-motor unit must be installed as
follows:
In particular, the feed pipes must
be securely routed, e.g. in cable  on level surfaces,
ducts or in the floor.  with shaft in horizontal position,
 on stationary (fixed) surfaces or structures,
 at a maximum height of 1000 m [3280 ft]
 CAUTION above sea level.
Danger of injuries from flying
parts! Observe the following when installing the
Select installation so that parts pump-motor unit:
that are thrown out through the
 The load bearing capacity of the base
grate if the external fan breaks
plate or the foundation must be designed
cannot hit persons!
for at least the weight of the unit.

 The vibration behavior at the operating


location must be taken into account.
The total vibrations of the unit are
dependent on the following factors:
– the characteristic vibrations of the unit,
– the alignment and installation,
– the condition (vibration behavior) of the
load-bearing surface,
– the influences by vibrations of other
parts and system components (external
vibrations).
The maximum permissible value for
vibrations is veff = 4.5 mm/s.
To ensure proper operation and a long

610.48060.40.000 22 / 64 © Gardner Denver Deutschland GmbH


Installation

service life of the unit, this value may not be Bolt the feet of the unit to the supporting
exceeded. surface with suitable securing elements, as
Generally, this value can be adhered to shown in Fig. 6, Pg. 23.
without a special foundation or a special
base plate.
The points on the unit for measuring the
vibration speed are shown in Fig. 5, Pg. 23.

Fig. 6: Securing elements for bolting feet to


supporting surface
Fig. 5: Points for measuring the vibration
2BV7 06: M = 4 x M8-6.8
speed
2BV7 07: M = 4 x M10-6.8

Different installation, e.g. with the shaft in the


vertical position, requires consultation with
service.

© Gardner Denver Deutschland GmbH 23 / 64 610.48060.40.000


Installation

7.2 Electrical connection (motor)


CAUTION
The electrical connection must be carried out
as follows: Incorrect connection of the motor
 according to the applicable national and can lead to serious damage to
local laws and regulations, the unit!
 according to the applicable system-
dependent prescriptions and requirements,
 according to the applicable regulations of
the utility company. Observe the motor rating plate.
It is imperative that the operating conditions
correspond to the data given on the rating
 DANGER plate!
Electrical danger! Deviations permissible without reduction in
Malpractice can result in severe performance:
injuries and material damage!
 ±5 % voltage deviation
 ±2 % frequency deviation
 DANGER
Electrical danger! Make the connection in accordance with the
circuit diagram in the terminal box.
The electrical connection may be Connect the protective conductor.
carried out by trained and
authorized electricians only!  Use suitable cable lugs when doing so.
 The electrical connection must be
 DANGER permanently safe.
 Tightening torques for terminal plate
Electrical danger! connections:

Before beginning work on the Thread M4 M5


unit or system, the following
measures must be carried out: [Nm] 0.8 ... 1.2 1.8 ... 2.5
Tightening
 Deenergize. torque 0.590 ... 1.33 ...
[ft lbs]
 Secure against being 0.885 1.84
switched on again.
 Determine whether
deenergized.  WARNING
 Ground and short-circuit.
Electrical danger!
 Cover or block off adjacent
energized parts. Clearance between bare live
parts and between bare live parts
and ground:
 WARNING
at least 5.5 mm [0.217"] (at a
Danger due to gauge pressure nominal voltage of Vn ≤ 690V)
and vacuum! Make sure there are no
Danger due to escaping fluid! protruding pieces of wire!
Before beginning work on the
unit or system:
 Interrupt supply of operating
liquid.
 Bleed lines and vacuum
pump/compressor
(depressurize).

610.48060.40.000 24 / 64 © Gardner Denver Deutschland GmbH


Installation

7.3 Connecting pipes/hoses (vacuum


 WARNING pump/compressor)

Electrical danger!
The terminal box must be free
from
 foreign bodies,
 dirt,
 humidity.
Terminal box cover and cable
entries must be tightly closed so
as to make them dustproof and
waterproof.
Check for tightness at regular
intervals.

For motor overload protection:


 Use motor circuit breakers.
 Set the motor circuit breakers to the
nominal current specified on the rating
plate.
Fig. 7: Pipe/hose connection of vacuum
pump/compressor
For supply by converter:
 High-frequency current and voltage 1 Operating-liquid port G ¼"
harmonics in the motor supply cables can 2 Discharge connection
3 Inlet connection
lead to emitted electromagnetic
4 Connection for cavitation protection G ¼"
interference. 5 Drain opening G ¼"
 Use shielded supply cables,
whereby the shield must be installed on
both sides. To prevent foreign bodies from entering the
 Limit speed: unit, all connections are sealed off when
see Chapter 4.2, "Electrical data", Pg. 16. delivered.
Do not remove the sealing plugs until
immediately before connecting the
CAUTION pipes/hoses.
If the unit is run dry, the
For the arrangement of the pipe/hose
mechanical seal will be
connection, see Fig. 7, Pg. 25.
destroyed in a matter of seconds!
DO NOT switch on as long as the The pumped gases/vapors are sucked in via
unit is not filled with operating the inlet connection (see Chapter 7.3.1,
liquid! Pg. 26) and discharged via the discharge
connection (see Chapter 7.3.2, Pg. 26).
For operation the unit must be continuously
supplied with operating liquid.
This is fed in via the operating-liquid port (see
Chapter 7.3.3, Pg. 26) and discharged
together with the pumped gases/vapors
through the discharge connection.

© Gardner Denver Deutschland GmbH 25 / 64 610.48060.40.000


Installation

Fill with operating liquid: 7.3.1 Inlet connection


When and how the pump-motor unit must be The inlet connection (Fig. 7, Pg. 25, Item 3) is
filled with operating liquid the first time is marked with an arrow pointing downward (↓).
dependent on the operating mode: Connect the inlet pipe here. The pumped
 For self-priming operation: gases/vapors are sucked in via this.
During installation.
 For operation with operating-liquid feed:
After completing installation. CAUTION

For self-priming operation you now pour The tightening torque for pipe
operating liquid into the working space of the connections on intake and
pump-motor unit before you connect the discharge connections may not
pipes/hoses to the unit. exceed 100 Nm [73.8 ft lbs]!
To do this, pour operating liquid into the open
inlet connection, discharge connection or
operating-liquid port. 7.3.2 Discharge connection
For proper filling quantities, see Chapter 4.3,
"Operating conditions", Section "Operating- The discharge connection (Fig. 7, Pg. 25,
liquid filling amount for priming", Pg. 17. Item 2) is marked with an arrow pointing
upward (↑).
Then attach the pipes/hoses to the unit as Connect the discharge pipe here. Both the
described in the following. pumped gases/vapors and the operating liquid
are discharged via this pipe.

 WARNING
CAUTION
Danger due to gauge pressure
The tightening torque for pipe
and vacuum!
connections on intake and
Danger due to escaping fluid! discharge connections may not
exceed 100 Nm [73.8 ft lbs]!
During operation, connected
pipes and vessels are
pressurized or vacuumized!
7.3.3 Operating-liquid port
Make sure that all connections
are sufficiently tight! Use only The operating-liquid port (Fig. 7, Pg. 25,
pipes and vessels of sufficient Item 1) is located between the discharge and
strength! inlet connection.

Connect the feed pipe for the operating liquid


NOTICE here.
Attach pipes/hoses free of
mechanical tensions.
Support the weight of the
pipes/hoses.

610.48060.40.000 26 / 64 © Gardner Denver Deutschland GmbH


Installation

7.3.4 Notes

NOTICE
For operating liquid with
impurities:
 Install a filter, screen or
separator in the supply line if
necessary.

NOTICE
In case of operating liquid with
a high lime content:
 Soften operating liquid
OR
 Decalcify pump-motor unit
regularly (see Chapter 11.1,
"Maintenance", Pg. 36).

NOTICE
To prevent installation residues
(e.g. welding spatter) from
entering the unit,
a start-up screen should be
installed in the inlet pipe for the
first 100 operating hours.

7.4 Accessories
The following accessories are available
according to our catalogue:
 Liquid separator
 Non-return valve
 Connecting and counter flange
 Gas ejector.
See Chapter 13, "Accessories", Pg. 44.

© Gardner Denver Deutschland GmbH 27 / 64 610.48060.40.000


Commissioning

8 Commissioning

8.1 Preparation and start-up


 WARNING
Danger due to gauge pressure
CAUTION
and vacuum! If the pumped gases/vapors
Danger due to escaping fluid! discharged on the pressure side
are passed on,
Danger due to rotating parts! then it must be ensured that the
The pump-motor unit may only maximum discharge pressure of
be put into operation when the 1.1 bar abs. [16.0 psia] is not
following conditions are met: exceeded!
 Fan guard and vacuum
pump/compressor housing NOTICE
are mounted.
 The lines to the discharge Maximum permissible quantity of
connection, inlet connection water entrained via the inlet
and operating-liquid port are connection:
attached. See Fig. 13, Pg. 32.
 The lines and connections
have been tested for strength
and leaks. If a shut-off device is installed in the discharge
pipe:
CAUTION Make sure that the unit CANNOT be operated
with the shut-off device closed.
If the unit is run dry, the
mechanical seal will be
destroyed in a matter of seconds! Fill with operating liquid:
DO NOT switch on as long as the When and how the pump-motor unit must be
unit is not filled with operating filled with operating liquid the first time is
liquid! dependent on the operating mode:
 For self-priming operation:
During installation.
 For operation with operating-liquid feed:
After completing installation.

For operation with operating-liquid feed,


you now fill the working area of the unit with
operating liquid.
To do this, open the respective stop valve for
approx. 20 sec.:
 For non-automatic operation:
Stop valve (Fig. 11, Pg. 32, Item 4).
 For automatic operation:
Stop valve in the bypass pipe (Fig. 12,
Pg. 32, Item 4a).

Then proceed with commissioning as


described in the following.

610.48060.40.000 28 / 64 © Gardner Denver Deutschland GmbH


Commissioning

Check connections of the pipes/hoses for


leaks.  WARNING

Check direction of rotation: Danger due to gauge pressure


and vacuum!
 The direction of flow of the pumped
gases/vapors is marked with arrows on the Danger due to escaping fluid!
intake and discharge connection. Before beginning work on the
unit or system:
 The intended direction of shaft rotation is
marked with an arrow on the motor  Interrupt supply of operating
mounting adapter between the intake and liquid.
discharge connection, as well as with an  Bleed lines and vacuum
arrow on the fan guard. pump/compressor
(depressurize).
 The pump-motor unit may not be allowed to
run dry!
Have you filled it with operating liquid The further procedure is again dependent
beforehand (during or after installation)? on the unit operating mode:

See sections "Fill with operating liquid",


Pg. 26 and Pg. 28.

 Briefly switch on pump-motor unit.

 Compare the actual direction of rotation of


the external fan with the intended direction
of shaft rotation as indicated with the
arrows.

 Switch off pump-motor unit again.

 If necessary, reverse the direction of


rotation of the motor.

 DANGER
Electrical danger!
The electrical connection may be
carried out by trained and
authorized electricians only!

 DANGER
Electrical danger!
Before beginning work on the
unit or system, the following
measures must be carried out:
 Deenergize.
 Secure against being
switched on again.
 Determine whether
deenergized.
 Ground and short-circuit.
 Cover or block off adjacent
energized parts.

© Gardner Denver Deutschland GmbH 29 / 64 610.48060.40.000


Commissioning

8.2 Self-priming operation


See Fig. 8, Pg. 30.

Here the following must be watched: Starting the pump-motor unit:


 The pump-motor unit must be pre-throttled  Switch on the unit.
on the inlet side. This means a vacuum of  The operating liquid is sucked in.
at least 900 mbar abs. [13.1 psia] must be
present in the inlet pipe (Item B) at switch-
on.

 During switch-on, the liquid level in the feed


pipe (Item A) and in the reservoir (Item C)
respectively must be at the same level as
the center of the unit shaft (Item 1).

 During operation the liquid level in the


reservoir (Item C) may not drop below
approx. 1 m [3.28 ft] below the center of
the unit shaft (Item 1).

A 900 mbar abs B


13.1 psia

1m
 3.28 ft 2

Fig. 8: Self-priming operation

A Feed pipe for operating liquid


B Inlet pipe
C Reservoir for operating liquid

1 Required liquid level when switching on


2 Min. liquid level during operation

610.48060.40.000 30 / 64 © Gardner Denver Deutschland GmbH


Commissioning

8.3 Operation with operating-liquid feed


See Fig. 9, Pg. 31; and Fig. 10, Pg. 31, as well as Fig. 11, Pg. 32 and Fig. 12, Pg. 32.

Proceed as follows here:

Method A: Method B:
1) Set pre-pressure of operating liquid (Fig. 9, 1) Start up the unit:
Pg. 31):
For non-automatic operation (Fig. 11, Pg. 32):
 Set a pre-pressure pA in the feed pipe for  Open the stop valve (Item 4) manually.
the operating liquid (Item A) around The operating liquid is fed in.
approx. 1 bar [14.5 psi] above the inlet  Switch on the unit.
pressure pB in the inlet pipe (Item B).
For automatic operation (Fig. 12, Pg. 32):
2) Start up the unit:  Switch on the unit.
For non-automatic operation (Fig. 11, Pg. 32):  The solenoid valve (Item 4) opens
 Open the stop valve (Item 4) manually. and the operating liquid is fed in.
The operating liquid is fed in.
2) Check the operating-liquid flow rate:
 Switch on the unit.
 with the flow meter (Fig. 11, Pg. 32, and
For automatic operation (Fig. 12, Pg. 32): Fig. 12, Pg. 32, Item 2)
 Switch on the unit. OR
 The solenoid valve (Item 4) opens  by measuring the volume of operating liquid
and the operating liquid is fed in. per unit of time that exits at the discharge
connection with a graduated vessel
(Fig. 10, Pg. 31)

3) Set/correct the operating-liquid flow rate:


 via the control valve (Fig. 11, Pg. 32, and
Fig. 12, Pg. 32, Item 3)
 Nominal operating-liquid flow rate:
For nominal values, see Chapter 4.3,
"Operating conditions", Section "Nominal
operating-liquid flow rate", Pg. 17.

pA = pB + 1 bar
pA = pB + 14.5 psi B A
A

Fig. 9: Setting the operating-liquid flow rate: Fig. 10: Setting the operating-liquid flow rate:
Setting pre-pressure Measuring the volume with a graduated vessel

A Feed pipe for operating liquid A Feed pipe for operating liquid
B Inlet pipe B Drain pipe for operating liquid

© Gardner Denver Deutschland GmbH 31 / 64 610.48060.40.000


Commissioning

2 3 4 5 6

Fig. 11: Operation with operating-liquid feed: Non-automatic operation

1 Pump-motor unit 4 Stop valve


2 Flow meter 5 Filter
3 Control valve 6 Feed pipe for operating liquid

2 3 4 5 6

4a

Fig. 12: Operation with operating-liquid feed: Automatic operation

1 Pump-motor unit 4a Bypass with stop valve (for priming)


2 Flow meter 5 Filter
3 Control valve 6 Feed pipe for operating liquid
4 Solenoid valve, connected to motor

4x 3x t= A

8x 7x t=2s B

Fig. 13: Maximum permissible quantity of water entrained via the inlet connection

A During continuous operation: 3x quantity of operating-liquid flow rate


B Briefly (up to 2 sec.): 7x quantity of operating-liquid flow rate

610.48060.40.000 32 / 64 © Gardner Denver Deutschland GmbH


Operation

9 Operation

9.1 Self-priming operation


 WARNING
Follow the instructions contained in
Danger due to gauge pressure Chapter 8.2, "Self-priming operation", Pg. 30
and vacuum! for this operating mode.

Danger due to escaping fluid!


Danger due to rotating parts! 9.2 Operation with operating-liquid feed

The pump-motor unit may only


be put into operation when the Start-up
following conditions are met: For non-automatic operation (Fig. 11, Pg. 32):
 Fan guard and vacuum  Open the stop valve (Item 4) manually.
pump/compressor housing The operating liquid is fed in.
are mounted.
 Switch on the unit.
 The lines to the discharge
connection, inlet connection For automatic operation (Fig. 12, Pg. 32):
and operating-liquid port are
attached.  Switch on the unit.
 The lines and connections  The solenoid valve (Item 4) opens
have been tested for strength and the operating liquid is fed in.
and leaks.

Shut down:
CAUTION
For non-automatic operation (Fig. 11, Pg. 32):
If the unit is run dry, the
 Switch off the pump-motor unit.
mechanical seal will be
destroyed in a matter of seconds!  Close the stop valve (Item 4) manually.
Feeding of the operating liquid is cut off.
DO NOT switch on as long as the  The following applies for the control valve
unit is not filled with operating (Item 3) for setting the operating-liquid flow
liquid! rate:
In case of an interruption in operation, the
valve setting (i.e. the valve position or the
 WARNING
open valve cross-section) is not changed.
Danger of burns and scalding
For automatic operation (Fig. 12, Pg. 32):
from hot surfaces of the pump-
motor unit and from hot fluids!  Switch off the pump-motor unit.
Do not touch during operation!  The solenoid valve (Item 4) closes,
Allow to cool after shut-down! and feeding of the operating liquid is cut off.
 The following applies for the control valve
(Item 3) for setting the operating-liquid flow
NOTICE rate:
In case of an interruption in operation, the
Maximum permissible quantity of valve setting (i.e. the valve position or the
water entrained via the inlet open valve cross-section) is not changed.
connection:
See Fig. 13, Pg. 32.

© Gardner Denver Deutschland GmbH 33 / 64 610.48060.40.000


Shut-Down and Longer Standstills

10 Shut-Down and Longer Standstills

10.1 Draining 10.2 Preparing for longer standstill


Before a longer standstill (from approx.
4 weeks) or when there is danger of frost,
 DANGER proceed as follows:

Electrical danger!  Drain pump-motor unit as described in


Chapter 10.1, "Draining", Pg. 34.
Before beginning work on the  Remove the pipe/hose from the intake or
unit or system, the following discharge connection.
measures must be carried out:  Pour ½ l [0.132 gal (US); 0.110 gal (UK)] of
 Deenergize. preservative (rust protection oil, e.g.
 Secure against being Mobilarma 247 form Mobil Oil)
switched on again. into the open intake or discharge
 Determine whether connection.
deenergized.  Close the intake and discharge connection,
 Ground and short-circuit. as well as the operating-liquid port and
 Cover or block off adjacent remount the disconnected pipes/hoses.
energized parts.  Guide a M6 or M8 bolt (depending on the
type) with a sufficient shank length through
the center opening into the fan guard and
 WARNING screw into the shaft end on the external fan
side (see Fig. 14, Pg. 34).
Danger due to gauge pressure  Turn the shaft by hand using the bolt.
and vacuum!  Remove the M6 or M8 bolt again.
Danger due to escaping fluid!  You have two options for the standstill:
Either the pump-motor unit remains
Before beginning work on the connected in the system,
unit or system: or the unit is removed for storage.
 Interrupt supply of operating
liquid.
 Bleed lines and vacuum
pump/compressor
(depressurize).

 Switch off the pump-motor unit.


 The above safety precautions apply when
working on the unit or system.
 Provide suitable catch containers below the
vacuum pump/compressor housing.
 Open the screw plug (Fig. 7, Pg. 25,
Item 5).
 Allow the liquid to drain out.
 Close the screw plug again,
tightening torque Tt = 2 ... 3 Nm
[1.48 ... 2.21 ft lbs].

Fig. 14: Pour in preservative and turn shaft

610.48060.40.000 34 / 64 © Gardner Denver Deutschland GmbH


Shut-Down and Longer Standstills

10.3 Storage conditions


 DANGER
This chapter applies in the following cases:
 new pump-motor units, Electrical danger!
 pump-motor unit that are already installed Work on electrical installations
in a system and were prepared for a longer may be carried out by trained
standstill, as described in Chapter 10.2, and authorized electricians only!
"Preparing for longer standstill", Pg. 34.

To prevent standstill damage during storage,


the environment must provide the following
conditions:
 dry,
 dust-free,
 low-vibration (effective value of vibration
speed veff ≤ 0.2 mm/s [0.008"/sec]).

Take the following measures for


commissioning following a longer
standstill:

 Measure the insulation resistance of the


motor.
In case of values ≤ 1kΩ per volt of nominal
voltage, dry winding.

 Drain off preservative, as described in


Chapter 10.1, "Draining", Pg. 34.
Subsequent cleaning of the pump-motor
unit is not required.
Dispose of preservative in accordance with
the manufacturer's specifications.

 For new pump-motor units:


Install pump-motor unit as described in
Chapter 7, "Installation", Pg. 22.
Commission the pump-motor unit as
described in Chapter 8, "Commissioning",
Pg. 28.

For pump-motor unit that are already


installed in a system:
Commission the pump-motor unit as
described in Chapter 8, "Commissioning",
Pg. 28.

© Gardner Denver Deutschland GmbH 35 / 64 610.48060.40.000


Servicing

11 Servicing

 DANGER  WARNING
Electrical danger! Danger of burns and scalding
from hot surfaces of the pump-
Before beginning work on the
motor unit and from hot fluids!
unit or system, the following
measures must be carried out: Do not touch during operation!
 Deenergize. Allow to cool after shut-down!
 Secure against being
switched on again.  WARNING
 Determine whether
deenergized. When working on the unit,
 Ground and short-circuit. there is a danger of injury,
 Cover or block off adjacent e.g. in the form of cuts/cutting
energized parts. off, crushing and burns!
During transport/handling as well
 WARNING as assembly and disassembly
always wear personal protective
Danger due to gauge pressure equipment (safety helmet,
and vacuum! protective gloves, safety boots)!
Danger due to escaping fluid!
Before beginning work on the
unit or system:
 Interrupt supply of operating
liquid.
 Bleed lines and vacuum
pump/compressor 11.1 Maintenance
(depressurize). The pump-motor unit is largely maintenance-
free.
 WARNING
However, if dirt or solid matter (e.g. sand) or
lime deposits get into the unit through the
Danger from rotating external
operating liquid and/or the pumped
fan of unit!
gases/vapors, then it is necessary to clean the
It is prohibited to remove the fan unit at regular intervals to prevent the impeller
guard! from jamming up and to avoid wearing of the
impeller and the vacuum pump/compressor
housing.

Refer to the following table:


 WARNING
Danger from rotating impeller
of unit!
Do not remove the vacuum
pump/compressor housing until
after the unit has been shut down
and the impeller has come to a
complete stop!
Consider that the impeller has a
certain run-out!

610.48060.40.000 36 / 64 © Gardner Denver Deutschland GmbH


Servicing

Contamination/Problem Remedy

Dirt collects in the motor  Clean the motor cooling fins at regular intervals.
cooling fins.

Fine-grain dirt (e.g. sand) get Install a liquid separator, filter or screen in the feed pipe.
into the vacuum
pump/compressor with the OR
operating liquid or pumped
gases/vapors. Regularly dismantle and clean the vacuum pump/compressor housing as
follows:
 Shut unit down.
 Drain the pump-motor unit as described in Chapter 10.1, "Draining",
Pg. 34.
 Unscrew the housing with a 36 mm [3/8"] wrench (in direction of arrow
shown on housing) (see Fig. 15, Pg. 38).
 Remove the housing.
 Dirt has collected in the housing. Rinse out the housing.
 Screw on the housing again (opposite direction of arrow shown on
housing) and tighten with a tightening torque of 50 Nm [36.9 ft lbs].
 When commissioning the pump-motor unit, proceed as described in
Chapter 8, "Commissioning", Pg. 28.

Impeller is jammed.  Shut unit down.


 Guide a M6 or M8 bolt (depending on the type) with a sufficient shank
length through the center opening into the fan guard and screw into the
shaft end on the external fan side (see Fig. 16, Pg. 38).
 Free the shaft using the bolt.
 Remove the bolt again.

Extremely hard water used Soften operating liquid.


as operating liquid
Lime content > 15°dH). OR

Decalcify the pump-motor unit at intervals of 3 months as follows (also see


Fig. 16, Pg. 38):
 Wear personal protective equipment (protective gloves and safety
goggles),
 Shut unit down.
 Drain the pump-motor unit as described in Chapter 10.1, "Draining",
Pg. 34.
 Remove pipes/hoses.
 Fill the unit with decalcifying liquid through one of the connection
openings. Use 10% solution of acetic acid or another commercially
available decalcifying agent.
 Allow the decalcifying liquid to soak for at least 30 minutes.
 Turn the shaft occasionally during this time. To do this, guide a M6 or M8
bolt (depending on the type) with a sufficient shank length through the
center opening into the fan guard and screw into the shaft end on the
external fan side (see Fig. 16, Pg. 38).
 Turn the shaft using the bolt.
 Remove the bolt again.
 Drain the decalcifying liquid out of the unit. To do this, proceed as
described in Chapter 10.1, "Draining", Pg. 34.
 Mount pipes/hoses.
 When commissioning the pump-motor unit, proceed as described in
Chapter 8, "Commissioning", Pg. 28.
 The decalcifying liquid can be disposed of in the sewer system.

© Gardner Denver Deutschland GmbH 37 / 64 610.48060.40.000


Servicing

Contamination/Problem Remedy

Dirt gets into the air Clean the motor air passages regularly. To do so, proceed as follows:
passages (fan guard,  Carry out protective measures for the use of compressed air:
external fan, cooling fins) of Wear personal protective equipment (protective gloves and safety
the motor. goggles),
secure surroundings. Remove objects lying around.
 Blow in compressed air through the fan guard grate.
 It is prohibited to remove the fan guard!

1 2

Fig. 15: Removing vacuum pump/compressor housing


Carry out with 36 mm [3/8"] open-end wrench.

Fig. 16: Pouring in decalcifying agent and freeing shaft by turning

610.48060.40.000 38 / 64 © Gardner Denver Deutschland GmbH


Servicing

11.2 Repairs/troubleshooting

Fault Cause Remedy Carried out by

Motor does At least two Check fuses, terminals and cables for open Electrician
not start, power supply circuit. Eliminate open circuit.
no motor leads interrupted.
noise.

Motor does One power Check fuses, terminals and cables for open Electrician
not start, supply lead circuit. Eliminate open circuit.
humming interrupted.
noise..
Impeller is Free shaft by turning. Operator
jammed. See Chapter 11.1, "Maintenance", Pg. 36.

Decalcify vacuum pump/compressor. Operator


See Chapter 11.1, "Maintenance", Pg. 36.

Drain and clean vacuum pump/compressor if Operator


necessary.
See Chapter 11.1, "Maintenance", Pg. 36.

Check and correct impeller gap setting if Service


necessary.

Impeller Replace impeller. Service


defective.

Motor bearings Replace motor bearings. Service


defective.

Protective Winding short- Have winding checked. Electrician


motor switch circuit.
trips when
motor is Motor Throttle operating-liquid flow rate. Operator
switched on. overloaded. See Chapter 8.2, "Self-priming operation", Pg. 30
or 8.3, "Operation with operating-liquid feed",
Pg. 31.

Counter-pressure Reduce counter-pressure. Operator


at discharge
connection too
high.

Share of liquid Reduce share of liquid also fed. Operator


also fed too high.

Impeller is See "Motor does not start, Service


jammed. humming noise."

Power Lime or other Decalcify vacuum pump/compressor. Operator


consumption deposits. See Chapter 11.1, "Maintenance", Pg. 36.
too high.
Clean vacuum pump/compressor. Operator
See Chapter 11.1, "Maintenance", Pg. 36.

Unit does not No operating Ensure proper operating-liquid flow rate. Operator
generate liquid. See Chapter 8.2, "Self-priming operation", Pg. 30
vacuum. or Chapter 8.3, "Operation with operating-liquid
feed", Pg. 31.

Severe leak in the Seal leak in the system. Operator


system.

Wrong direction Reverse direction of rotation by interchanging two Electrician


of rotation. connecting leads.

© Gardner Denver Deutschland GmbH 39 / 64 610.48060.40.000


Servicing

Fault Cause Remedy Carried out by

Unit Unit too small. Use larger unit. Operator


generates
insufficient Operating-liquid Increase operating-liquid flow rate to up to 2x the Operator
vacuum. flow too low. nominal flow rate.
See Chapter 8.2, "Self-priming operation", Pg. 30
or Chapter 8.3, "Operation with operating-liquid
feed", Pg. 31.

Operating liquid Cool or increase operating-liquid flow, Operator


too warm See Chapter 8.2, "Self-priming operation", Pg. 30
(nominal or 8.3, "Operation with operating-liquid feed",
temperature: Pg. 31.
15°C [59 °F]).

Erosion. Inspect impeller. To do so, proceed as follows: Operator


 Shut unit down.
 Drain the pump-motor unit as described in
Chapter 10.1, "Draining", Pg. 34.
 Unscrew the housing with a 36 mm [3/8"]
wrench (in direction of arrow shown on
housing) (see Fig. 15, Pg. 38).
 Remove the housing.
 Examine the impeller for erosion.
 Have the impeller replaced by Service if
necessary.
 Screw on the housing again (opposite
direction of arrow shown on housing) and
tighten with a tightening torque of 50 Nm [36.9
ft lbs].
 When commissioning the pump-motor unit,
proceed as described in Chapter 8,
"Commissioning", Pg. 28.

Replace affected components. Service

Slight leak in the Seal leak in the system. Operator


system.

Mechanical seal Replace mechanical seal. Service


leaky.

Abnormal Cavitation of Connect cavitation-protection hose of liquid Operator


screeching vacuum separator (see Chapter 13.5, "Cavitation
noise. pump/compressor protection", Pg. 49) or clean cavitation-protection
. equipment.

Operating-liquid Check operating-liquid flow rate and reduce if Operator


flow rate too high. necessary. See Chapter 8.3, "Operation with
operating-liquid feed", Pg. 31.

Unit leaky. Seals defective. Check seals. Service

610.48060.40.000 40 / 64 © Gardner Denver Deutschland GmbH


Servicing

11.3 Spare parts – Clean the unit on the inside and outside,
as described in Chapter 11.1,
"Maintenance", Pg. 36.
11.3.1 Ordering nash_elmo spare parts
 The pump-motor unit must be delivered
When ordering nash_elmo spare parts, always complete, i.e. not dismantled.
indicate the following:  Only the original packing should be used for
shipment.
 Type designation ("2BV...", "2BH..." or  A declaration of clearance must be included
"2BL..."), complete with all additions with the shipment,
(as per rating plate) as described in Chapter 11.5,
 Serial number ("No E"), 13-digit "Decontamination and Declaration of
(as per rating plate) Clearance", Pg. 42.
 Part item number, 4-digit  The original rating plate of the pump-motor
(as per parts list for exploded view, unit must be properly mounted, intact and
Chapter 14, "Exploded View with Parts legible.
List", Pg. 50) All warranty claims are voided for pump-
motor units delivered for a damage
Example of an order: expertise without the original rating plate or
with a destroyed original rating plate.
2BV7071-1AH08S(-Z) = Type
designation
No E F2 7 45688 70 010 = Serial number
047 = Part item #
Impeller = Part
designation

All parts of the parts list for the exploded view


are available from the manufacturer under the
corresponding item number.
See Chapter 14, "Exploded View with Parts
List", Pg. 50.

In case of inquiries, the serial number (No E)


of the pump-motor unit must be specified in
accordance with the rating plate.

11.3.2 Ordering standardized parts


Commercially available standardized parts can
be purchased on the open market.
When doing so, observe the information in the
parts list exactly, especially the design,
dimensions, property class etc.

11.4 Service/After-sales service


Our Service is available for work (in particular
the installation of spare parts, as well as
maintenance and repair work), not described in
these operating instructions (see front page of
these operating instructions).

Observe the following when returning pump-


motor unit:
 Before shipping:
– Drain the pump-motor unit so that it is
residue-free,
as described in Chapter 10.1, "Draining",
Pg. 34.

© Gardner Denver Deutschland GmbH 41 / 64 610.48060.40.000


Servicing

11.5 Decontamination and Declaration of


Clearance NOTICE
The inspection/maintenance/
repair of the unit at the workshop
 WARNING will not be begun
until the declaration of clearance
Danger from flammable, has been received!
caustic or toxic substances!
If the declaration of clearance is
To protect the environment and not included with the shipment,
persons, the following applies: delays may result!
Pump-motor unit which have
come into contact with
dangerous substances must
always be decontaminated
before being passed on to a
workshop!

A so-called Declaration of Clearance must be


included with each pump-motor unit that is
given to a workshop for inspection,
maintenance or repair.

The declaration of clearance


 is provided as a pre-printed form for
photocopying on Pg. Fehler! Textmarke
nicht definiert.,
 is legally binding,
 must be filled out and signed by authorized,
qualified personnel,
 must be issued for each unit sent in (i.e. a
separate declaration for each unit),
 must be attached outside on the packing of
the unit,
 should be sent to as a copy by fax the
workshop conducting the work prior to
shipment.

This ensures
 that the unit has not come into contact with
dangerous substances,
 that a unit that has come into contact with
dangerous substances has been sufficiently
decontaminated,
 that the inspection, maintenance or repair
personnel can take the required protective
measures if necessary.

610.48060.40.000 42 / 64 © Gardner Denver Deutschland GmbH


Disposal

12 Disposal
Have the entire pump-motor unit scrapped by a suitable disposal company. No special measures are
required when doing so.

For additional information on disposing of the unit, ask service.

© Gardner Denver Deutschland GmbH 43 / 64 610.48060.40.000


Accessories

13 Accessories
13.1 Flanges 13.2 Non-return valve
The pipes on the intake and discharge side are The non-return valve is basically a valve with a
connected to intake and discharge connections plate seat. Its function is to prevent the
via the flanges. pumped gases/vapors as well as the operating
liquid from flowing back out of the pump in
See Fig. 17, Pg. 44. case the operation of the pump-motor unit is
interrupted. It is mounted on the inlet
connection of the unit for this purpose.
2BV7 06: G1
2BV7 07: G1½ See Fig. 18, Pg. 44.

2BV7 06: 30 Nm (22.13 ft lb)


2BV7 07: 50 Nm (36.88 ft lb)
2BV7 06: G1
2BV7 07: G1½

Fig. 18: Non-return valve

Mounting
Fig. 17: Flanges
The non-return valve is mounted when
connecting the pipes/hoses, as described in
Mounting Chapter 7.3, "Connecting pipes/hoses
(vacuum pump/compressor)", Pg. 25.
The flanges are mounted when connecting the
pipes/hoses, as described in Chapter 7.3,
Proceed as follows:
"Connecting pipes/hoses (vacuum
pump/compressor)", Pg. 25.  Screw on the non-return valve with the
arrow pointing downward on the inlet
Proceed as follows: connection.
Use commercially available liquid sealant
 Screwing flanges onto intake and discharge
(e.g. Loctite) when doing so.
connections.
Tightening torque: dependent on the
Use commercially available liquid sealant
sealant.
(e.g. Loctite) when doing so.
Tightening torque: dependent on the  Screw the inlet pipe onto the non-return
sealant. valve.
Use commercially available liquid sealant
 Screw intake and discharge connections
(e.g. Loctite) when doing so.
onto flanges.
Tightening torque: dependent on the
Use commercially available liquid sealant
sealant.
(e.g. Loctite) when doing so.
Tightening torque: dependent on the
sealant.

610.48060.40.000 44 / 64 © Gardner Denver Deutschland GmbH


Accessories

13.3 Gas ejector Mounting


The gas ejector is used when an inlet The gas ejector is mounted when connecting
pressure of the unit in the range from the pipes/hoses, as described in Chapter 7.3,
40 mbar [0.580 psi] to 10 mbar [0.145 psi] is "Connecting pipes/hoses (vacuum
to be achieved. pump/compressor)", Pg. 25.
The gas ejector compresses the pumped
gases/vapors sucked in to the inlet pressure of Proceed as follows:
the pump-motor unit.
Ambient air at 20°C [68 °F] and 1013 mbar  Screw the gas ejector onto the inlet
[14.7 psi] is used as a propellant. This air may connection.
not contain any liquid droplets. Use commercially available liquid sealant
(e.g. Loctite) when doing so.
See Fig. 19, Pg. 45. Tightening torque: dependent on the
sealant.
 Screw the inlet pipe onto the gas ejector.
Use commercially available liquid sealant
(e.g. Loctite) when doing so.
Tightening torque: dependent on the
sealant.
 With soiled ambient air:
Screw a propellant line onto the gas ejector.

When evacuating containers, the gas ejector


operates as a throttle in the range from
1000 mbar [14.5 psi] to approx. 100 mbar
[1.45 psi]. To achieve fast venting times here,
the gas ejector can be bypassed with a bypass
pipe. The bypass pipe must be closed if the
gas ejector is to be effective. The best point for
switching over to operation with the gas ejector
is at approx. 40 mbar [0.580 psi].

Fig. 19: Gas ejector

© Gardner Denver Deutschland GmbH 45 / 64 610.48060.40.000


Accessories

13.4 Liquid separator 3) Screw the hose nipple into the hole
provided on the pump-motor unit. Use
The liquid separator is mounted on the
commercially available liquid sealant
discharge connection. Its functions consists of
(e.g. Loctite) when doing so.
separating the discharged operating liquid form
 Operating-liquid port:
the pumped gases/vapors. Part of this
Angled hose nipple, directed toward
separated operating liquid can be fed back to
the front.
the pump-motor unit via the operating-liquid
port. The rest is drained off and replaced with  Connection for cavitation protection:
fresh operating liquid. Angled hose nipple, directed upward.

Operation with a liquid separator and operating 4) Mount the "T" hose nipple on the angled
water return is the operating mode hose nipple on the operating-liquid port
recommended for the pump-motor unit. with the hose clamp.

The procedure for mounting the liquid 5) Place the liquid separator on the
separator on the pump-motor unit is shown in discharge connection and tighten it by
Fig. 20, Pg. 47, and Fig. 21, Pg. 48. Here the hand. Use commercially available liquid
following applies: sealant (e.g. Loctite) when doing so.

1) Remove the plug at the top and bottom 6) Mount the hose for returning the
on the liquid separator. operating liquid (see arrow) with hose
clamps.
2) Screw the hose nipple into the holes on  On the liquid separator:
the liquid separator. Use commercially Mount the hose on the lower hose
available liquid sealant (e.g. Loctite) nipple.
when doing so.  On the pump-motor unit:
 Top hole: Mount the hose on the side
Angled hose nipple. connection of the "T" hose nipple
 Bottom hole: (operating-liquid port).
Straight hose nipple.
7) Mount the cavitation-protection hose
For L-BV7 2BV7 060 and 2BV7 061: (see arrow) with hose clamps.
The premounted reducer on the liquid  On the liquid separator:
separator is required. Therefore: Mount the hose on the upper hose
 Remove the reducer from the liquid nipple.
separator.  On the pump-motor unit:
 Seal off thread. Use commercially Mount the hose on the hose nipple of
available liquid sealant (e.g. Loctite) the cavitation protection connection.
when doing so.
8) Side view of the mounted liquid
 Screw the reducer into the liquid
separator.
separator again.
A = Connection for feed pipe for fresh
operating liquid.
For L-BV7 2BV7 070 and 2BV7 071:
B = Connection for draining off
The premounted reducer on the liquid
separated operating liquid.
separator is not required. Therefore:
 Remove the reducer from the liquid
separator and dispose of it.

610.48060.40.000 46 / 64 © Gardner Denver Deutschland GmbH


Accessories

1 2

3 4

Fig. 20: Mounting liquid separator, Part 1 of 2

© Gardner Denver Deutschland GmbH 47 / 64 610.48060.40.000


Accessories

5 6

7 8

Fig. 21: Mounting liquid separator, Part 2 of 2

610.48060.40.000 48 / 64 © Gardner Denver Deutschland GmbH


Accessories

13.5 Cavitation protection


Cavitation is understood to be the production
and sudden implosion of gas bubbles in the
liquid being fed. If the pressure in the vacuum
pump/compressor drops below the evaporation
pressure of the liquid (on the intake side or in
constricted areas), gas bubbles form. When
the pressure increases above the evaporation
pressure again (on the discharge side or at
points with a larger cross-section), these gas
bubbles collapse while forming high pressure
peaks, which may lead to particles being torn
out of the housing wall and impeller. Noise is
radiated. Material destruction of the pump-
motor unit is possible. To prevent this,
measures should be taken for cavitation
protection.

To protect the unit from cavitation, connect the


cavitation-protection hose of the liquid
separator to the connection for cavitation
protection (Fig. 7, Pg. 25, Item 4).

© Gardner Denver Deutschland GmbH 49 / 64 610.48060.40.000


Exploded View with Parts List

14 Exploded View with Parts List


14.1 Parts list

Part Part Designation Part Part Designation Part Part Designation


Item Item Item
No. No. No.
001 Motor casing, 050 Valve plate 500 Fan guard
complete
051 Intercepting plate 501 External fan
002 Vacuum
pump/compressor 053 Special screw 503 Special screw
housing
058 O-ring 505 Feather key
005 Motor rotor
068 Screw plug 506 Circlip
006 Feather key
069 Sealing ring 640 Terminal-box upper
007 Deep-groove ball section
bearing 072 Washer for cavitation
protection 641 Gasket
008 Deep-groove ball
bearing 079 Screw plug 642 Screw
025 Screw 080 Sealing ring 650 Terminal board,
026 Motor mounting complete
095 Cover
adapter 651 Screw
027 Circlip 125 Screw
661 Clamping strap
033 Shaft sealing/CD ring 127 Retaining ring
662 Lock washer
035 Mechanical seal 405 End shield
663 Screw
036 Washer 409 Nut
675 Nut
037 Spring-type straight 410 O-ring
680 Terminal box lid
pin 451 Screw
042 Terminal box, 681 Gasket
complete 452 Shaft sealing/CD ring
682 Special screw
045 Screw 455 Spring strap*
690 Blind plug
047 Impeller 459 Nut
691 Blind plug
049 Port plate 467 Bearing screw-down
set

* NOTE:
Only with 2BV7 061, 2BV7 070 and 2BV7 071.

610.48060.40.000 50 / 64 © Gardner Denver Deutschland GmbH


Exploded View with Parts List

14.2 Exploded view

079 027
080 A
072

037
035
007
058
033
053
051 026
049 069
045 025

068
036
127
050

047

125

002 6104806001001

Fig. 22: Exploded view: vacuum pump/compressor section

(Example, delivered version may differ in some details)

© Gardner Denver Deutschland GmbH 51 / 64 610.48060.40.000


Exploded View with Parts List

682
680

681
651
650

642
042
640
690
641 691
503
663 500
662
661 501

095 452
451
450

455 *
467
005 008
006 001

Fig. 23: Exploded view: motor section

(Example, delivered version may differ in some details)

* NOTE:
Only with 2BV7 061.

610.48060.40.000 52 / 64 © Gardner Denver Deutschland GmbH


Exploded View with Parts List

Fig. 24: Exploded view: motor section

(Example, delivered version may differ in some details)

* NOTE:
Only with 2BV7 070 and 2BV7 071.

© Gardner Denver Deutschland GmbH 53 / 64 610.48060.40.000


EU declaration of conformity

EU declaration of conformity

EU declaration of conformity
Manufacturer: Gardner Denver Deutschland GmbH
P.O. Box 1510
D-97605 Bad Neustadt / Saale

Responsible for documentation: Holger Krause


P.O. Box 1510
D-97605 Bad Neustadt / Saale

Designation: L Series Liquid ring vacuum pump/ compressor


L-BV7
Types 2BV7 060
2BV7 061
2BV7 070
2BV7 071
The liquid ring vacuum pump/compressor described above meets the following applicable Community
harmonisation legislation:
2006/42/EC Directive 2006/42/EC of the European Parliament and of the Council of 17 May 2006 on machinery,
and amending Directive 95/16/EC

The protection targets of the directive 2006/95/EC have been met

Harmonised standards applied:

EN 1012-2:1996 Compressors and vacuum pumps — Safety requirements — Part 2: Vacuum pumps
+A1:2009

Other technical standards and specifications used:

EN 1012-1:1996 Compressors and vacuum pumps — Safety requirements — Part 1: Compressors

Bad Neustadt/Saale, 23.04.2010


(Place and date of issue)
Thomas Kurth, Managing Director
(Name and function) (Signature)
664.48060.40.000

610.48060.40.000 54 / 64 © Gardner Denver Deutschland GmbH


Form for statement on safety

Form for statement on safety

Statement on health safety and on the protection of the environment


 For the safety of our employees and to comply with statutory requirements on handling substances harmful to the health and
the environment, this statement must be enclosed, fully completed, with each unit/system sent.
 Without the fully completed statement, repair/disposal is not possible and delays are unavoidable!
 The statement is to be completed and signed by suitably qualified, authorised personnel at the operating organisation.
 In the case of shipment to Germany, the statement is to be completed in German or English.
 The statement is to be attached to the outside of the packing on shipment.
 If necessary, the carrier is to be informed.
1. Product designation (type):

2. Serial number (no. BN):

3. Reason for sending:

4. The unit/system
has not come into contact with hazardous substances. There will be no hazards for personnel or the environment during
repair/disposal. Continue with "6. Legally binding statement“
has come into contact with hazardous substances. Continue with "5. Information on the contamination“
5. Information on the contamination (if necessary provide more information on an additional sheet)
The unit/system was used in the following application:

and has come into contact with the following classifiable substances or substances presenting a hazard to health/environment:
Hazardous Properties (e.g. toxic, inflammable,
Trade name: Chemical designation: substance class: caustic, radioactive):

The unit/system has been emptied in accordance with the operating instructions, flushed and cleaned externally.
Safety data sheets in accordance with the applicable regulations are enclosed ( sheet).
The following safety precautions are necessary for handling (e.g. personal protective equipment):

6. Legally binding statement


I herewith guarantee that the details specified are true and complete and that I, as signatory, am in a position to judge that this is
so.
We are aware that we are liable to the contractor for any damages arising from incomplete or incorrect specifications. We are
obliged to indemnify the contractor against claims for damages by third parties arising from incomplete or incorrect specifications.
We are aware that, irrespective of this statement, we are directly liable to third parties - in particular including the contractor's
employees tasked with repair/disposal.
Company/institute:

Name, position: Phone:

Street: Fax:

Post code, city:

Country: Stamp:

Date, signature:

© Gardner Denver Deutschland GmbH 610.00250.40.905


P.O. box 1510 Phone: +49 7622 392 0 E-mail: [email protected] 10.2009
97605 Bad Neustadt Fax: +49 7622 392 300 Internet: www.gd-elmorietschle.com English

© Gardner Denver Deutschland GmbH 55 / 64 610.48060.40.000


Index

Index

Definitions ....................................................... 7
A Design........................................................... 18
Accessories .............................................27, 44 Dimensions ................................................... 13
Cavitation protection.................................49 Direction of rotation....................................... 29
Flanges.....................................................44
Gas ejector ...............................................45 Discharge connection ................................... 26
Liquid separator........................................46 Discharge pressure......................................... 6
Non-return valve .......................................44
Disposal ........................................................ 43
After-Sales Service........................................41
Draining......................................................... 34
Attachment points..........................................21
Driving side ..................................................... 6
B
E
Burns .................................................11, 33, 36
Electrical connection (motor) ........................ 24
C Electrical data ............................................... 16
Electrical installations.................................... 35
CAUTION.........................................................7
Erosion.......................................................... 40
Cavitation.................................................40, 49
Exploded view............................................... 50
Cavitation protection......................................49
External fan................................................... 10
Commissioning ..............................................28
Commissioning after longer standstill............35
F
Compression pressure ....................................6
Fan guard................................................ 10, 11
Compressor .....................................................6
Filling amount:............................................... 17
Connection
Electrical connection (motor)....................24 Flanges ......................................................... 44
Pipes/hoses (vacuum pump/compressor) 25 Foreseeable misuse...................................... 12
Discharge connection..........................26
Inlet connection ...................................26 Frequency deviation...................................... 24
Operating-liquid port............................26
Contents ..........................................................3 G
Continuous operation ....................................12
Gas ejector.................................................... 45
Converter .......................................................25
Gases/vapors, to be transported .................. 12
Glossary.......................................................... 6
D
Graphic symbols ............................................. 8
D side...............................................................6 Hazard alerting symbols ............................ 8
Damage ...........................................................7 Information................................................. 8
Mandatory action symbols ......................... 8
DANGER .........................................................7 Prohibition symbols.................................... 8
Data, technical...............................................13
Data, electrical..........................................16 H
Data, mechanical......................................13
Operating conditions ................................16 Hair net ........................................................... 9
Declaration of clearance................................55 Hazard alerting symbols ................................. 8
Declaration of Clearance ...............................42 Heat dissipation ............................................ 16
Declaration of Conformity ..............................54 Housing......................................................... 10
Decontamination......................................42, 55 Humming noise ............................................. 39

610.48060.40.000 56 / 64 © Gardner Denver Deutschland GmbH


Index

I Feed............................................. 19, 31, 33


Filling amount: ......................................... 17
Information.......................................................8 Impurities ................................................. 27
Operating liquid with high lime content.... 27
Injuries .............................................................7 Priming............................................... 26, 28
Inlet connection .............................................26 Regenerative operation ............... 19, 30, 33
Operating method ......................................... 18
Inlet pressure...................................................6
Operating modes .................................... 19, 29
Installation .....................................................22
Operation with operating-liquid feed. 19, 31,
Insulation resistance......................................35 33
Intended Use .................................................12 Automatic operation............................ 19
Non-automatic operation .................... 19
Self-priming operation.................. 19, 30, 33
L Operating personnel ..................................... 12

Lifting equipment ...........................................20 Operating-liquid port ..................................... 26

Lime deposits ................................................39 Operation ...................................................... 33

Limit speeds ..................................................16 Ordering spare parts ..................................... 41


nash_elmo spare parts ............................ 41
Liquid separator.............................................46
Standardized parts................................... 41
List of Illustrations............................................5 Other deposits............................................... 39
Longer standstill ............................................34
P
M
Packing: ........................................................ 20
Machine ...........................................................6 Part item numbers......................................... 50
Machine set .....................................................6 Parts list ........................................................ 50
Maintenance ..................................................36 Personal safety equipment ............................. 9
Mandatory action symbols...............................8 Pipes/hoses (vacuum pump/compressor) .... 25
Mechanical data ............................................13 Preservative ............................................ 34, 35
Minimum distances........................................16 Pressure
Misuse, ..........................................................12 Compression pressure............................... 6
Discharge pressure.................................... 6
Motor circuit breaker......................................25 Inlet pressure ............................................. 6
Test pressure............................................. 6
N Pressure:......................................................... 6

N side...............................................................6 Pressures...................................................... 16

nash_elmo spare parts ..................................41 Prohibition symbols......................................... 8

Noise level .....................................................16 Protective gloves............................................. 9

Nominal operating-liquid flow rate ...........17, 19 pumped gases/vapors .................................. 12

Non-driving side...............................................6 Pump-motor unit ............................................. 6

Non-return valve ............................................44


Q
NOTE...............................................................7
NOTICE ...........................................................7 Qualified personnel ..................................... 6, 9

O R

Operating conditions......................................16 Repairs.......................................................... 39


Cavitation................................................. 40
Operating Instructions ...............................9, 12 Erosion..................................................... 40
Operating liquid .............................................12 Humming noise........................................ 39

© Gardner Denver Deutschland GmbH 57 / 64 610.48060.40.000


Index

Lime deposits ...........................................39 Standstill, longer ........................................... 34


Other deposits ..........................................39
Storage conditions ........................................ 35
Required space .............................................22
Residual risks ................................................11 T
Running dry ...................................................25
Technical data............................................... 13
Rust protection oil....................................34, 35
Temperatures................................................ 16

S Terminal box ................................................. 25


Test pressure .................................................. 6
Safety...............................................................7
Transport and handling
Safety alert symbol ..........................................7
Handling by means of lifting equipment... 20
Safety boots.....................................................9 Transport and Handling ................................ 20
Safety equipment, personal.............................9 Manual handling: ..................................... 20
Safety helmet...................................................9 Troubleshooting ............................................ 39

Safety precautions...........................................9
U
Scalding .............................................11, 33, 36
Securing.........................................................11 Use, intended................................................ 12
Service...........................................................41
V
Servicing ........................................................36
Servicing personnel .......................................12 Vacuum pump................................................. 6
Shaft ..............................................................29 Vacuum pump/compressor housing ............. 10
Shutting down................................................34 Voltage deviation .......................................... 24
Signal words ....................................................7
CAUTION ...................................................7 W
DANGER ....................................................7
NOTE..........................................................7 WARNING....................................................... 7
NOTICE ......................................................7 Weight........................................................... 16
WARNING ..................................................7
Standardized parts ........................................41

610.48060.40.000 58 / 64 © Gardner Denver Deutschland GmbH


© Gardner Denver Deutschland GmbH 59 / 64 610.48060.40.000
610.48060.40.000 60 / 64 © Gardner Denver Deutschland GmbH
© Gardner Denver Deutschland GmbH 61 / 64 610.48060.40.000
610.48060.40.000 62 / 64 © Gardner Denver Deutschland GmbH
© Gardner Denver Deutschland GmbH 63 / 64 610.48060.40.000
www.gd-elmorietschle.de
[email protected]

Gardner Denver Gardner Denver


Schopfheim GmbH Deutschland GmbH
Roggenbachstraße 58 Industriestraße 26
79650 Schopfheim · Deutschland 97616 Bad Neustadt · Deutschland
Tel. +49 7622 392-0 Tel. +49 9771 6888-0
Fax +49 7622 392-300 Fax +49 9771 6888-4000

Elmo Rietschle is a brand of


Gardner Denver‘s Industrial Products
Group and part of Blower Operations.

You might also like