Panel - check list
Panel - check list
FORMAT NO. :
PROJECT NAME:- Data center
REPORT NO:
PRINCIPAL CONSULTANT FIRM :- M/S BLOCK NO:
LOCATION:
CONTRACTOR :- ENTERPRISE
DATE:
PANEL TAG NO:
NAME OF WORK : ELECTRICAL WORKS
PANEL TYPE:
SERIAL NO: VOLTAGE RATING:
CURRENT RATING: SOR NO:
MANUFACTURER: FREQUANCY: 50HZ
Records to
SI. be
Contr Remarks
No Activity Submitted/
actor
. CAT CAT
Format
A. B. No.
Incoming Material inspection at site NA
1
a) Owners Supply
b) Contractors supply WC Note-1 Format E2
a. Calibration certificate of measuring & testing
2 equipment’s/instruments
WC RW RW Format E1
b. Field calibration, if any WC W S Format E1
Check the layout of base channels/frames and ensure the
Format
3 correct provisions for grouting/welding and cable entry WC S --
E8,E9
openings.
Ensure level and centre lines are within the prescribed limits
Format
4 and they match with the requirements of incoming Bus-ducts, WC S --
E8,E9
if any
Format
5 Ensure proper grouting/welding of the base channels/frames WC S --
E8,E9
Format
6 Ensure proper handling of panels WC S --
E8,E9
Check sequence wise (starting from centre or Bus-duct panel)
7 installation, final leveling and bolting up
WC S -- --
INSPECTION & TEST PLAN FOR ELECTRICAL WORKS
FOR INSTALLATION/ ERECTION & TESTING OF SWITCH GEARS/ PCC/ MCC/
EMCCNFD's/ASB/LIGHTING PANELS/ HEATER PANELS / CONTROL PANLES OF
FILED EQUTS
ITP NO.: 3515 (Sheet 2 of
3)
Records to
SI. be
Contr Remarks
No Activity Submitted/
actor
. Format
CAT CAT
No.
A B
Check main bus bar connection at all shipping sections and
shrouding at all tap-off points. Measure contact resistance of Format E8,
8 each bus bar joints. Checking the tightness of down comers
WC S -- E9
(feeding each feeders)
Check inter panel wiring after fixing of loose accessories and Format E8,
9 wiring
WC S -- E9
Ensure the level of flooring for smooth opening of panel
10 doors and drawing out & in operation of Breaker Trolleys
WC S -- --
Check interchangeabilities of circuit breakers, MCC Feeder Format E8,
11 Modules
WC S -- E9
NOTE : 1) For Incoming material Inspection please refer ITP no: 6-82-1010
CAT A: HT Switch Gears / PCC Control Panels VFD's
CAT B: MCC / EMCC/ASB/lighting panels.