Position transmitter

Operating instruc-
tions

8155512
2021-09
[8155514]
Translation of the original instructions
Table of contents
1 About this document . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Applicable Documents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Intended use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Training of qualified personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.4 UL/CSA certification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Additional information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Product overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.1 Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.2 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.2.1 Analogue output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.2.2 Switching functions and switching logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.2.3 Switching output operating mode (SIO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.2.4 IO-Link operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1 Electrical installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2 Mechanical installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.1 Switch on the position transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.2 Setting Set-up mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.3 Scaling analogue signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6.4 Program switching output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.4.1 Set window comparator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.4.2 Adjusting proximity switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.4.3 Set hysteresis comparator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.4.4 Inverting switching logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.4.5 Block/unblock operating key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.4.6 Programming IO-Link output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7.1 Magnetic direction detection and magnetic direction correction . . . . . . . . . . . . . . . . . . . 18
7.2 LED displays in normal operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7.3 Reset position transmitter to factory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.4 Analogue output and switching function operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8 Malfunctions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.1 Diagnostics via LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.2 General malfunctions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
9 Disassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10.2 IO-Link. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10.3 I-Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
10.4 Technical data for UL/CSA certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Festo — SDAT-MHS-...-SV — 2021-09 3


Safety

1 About this document


1.1 Applicable Documents

All available documents for the product è www.festo.com/sp.

2 Safety
2.1 General safety instructions
– Only use the product in its original condition without unauthorised modifications.
– Only use the product if it is in perfect technical condition.
– The product may generate high frequency interference, which may require interference suppression
measures in residential areas.

2.2 Intended use


The position transmitter is intended for contactless detection of the piston position of magnetic
proximity sensing drives and grippers.
– Use the position transmitter only for suitable Festo drives and grippers.
– Do not place magnetic objects in the immediate vicinity of the position transmitter.

2.3 Training of qualified personnel


Work on the product may only be carried out by qualified personnel who can evaluate the work and
detect dangers. The qualified personnel have skills and experience in dealing with electropneumatic
(open-loop) control technology.

2.4 UL/CSA certification


In combination with the UL inspection mark on the product, the information in this section must also
be observed in order to comply with the certification conditions of Underwriters Laboratories Inc. (UL)
for USA and Canada.
UL approval information

Product category code NRKH, NRKH7


File number E232949
Considered standards UL 60947-1, UL 60947-5-2, CSA C22.2 No. 60947-1, CSA C22.2 No.
60947-5-2
UL mark

Ind. Cont. EQ. (Industrial Control Equipment)


2MD1
Tab. 1: UL/CSA approval information

4 Festo — SDAT-MHS-...-SV — 2021-09


Product overview

– Technical data and environmental conditions may be subject to change in order to comply with
Underwriters Laboratories Inc. (UL) certification requirements for the USA and Canada. è 10.4
Technical data for UL/CSA certification
– Only for connection to a NEC/CEC Class 2 supply.
– The device shall be supplied from an isolating transformer having a secondary listed fuse rated 1 A.

3 Additional information
– Contact the regional Festo contact if you have technical problems è www.festo.com.
– Accessories and spare parts è www.festo.com/catalogue.

4 Product overview
4.1 Design

6 1

2
5

Fig. 1: Design of SDAT-MHS


1 Connecting cable 5 Green LED: ready status display

2 Retaining screws 6 Yellow LED: switching status display

3 M8 plug, rotatable 7 Operating key

4 Red LED: status indicator

4.2 Function
The position transmitter detects the magnetic field of the piston magnet and continuously senses the
piston movement in the sensing range.

Festo — SDAT-MHS-...-SV — 2021-09 5


Product overview

The following output signals are available:


– analogue voltage signal: 0 … 10 V
– programmable switching output: 24 V
– IO-Link communication mode è 4.2.4 IO-Link operating mode
4.2.1 Analogue output
The analogue output provides an output signal 0 … 10 V.
– The output signal is proportional to the path of the piston stroke in the sensing range.
– The output signal can be scaled.
– The direction of increase of the analogue output signal can be inverted.
– The analogue output signal in the switching output operating mode is made available parallel and
independent of the position value output of the switching output.
– The analogue output is switched off in the IO-Link operating mode.

10 V

1V
0.5 V
0 mm X mm
Fig. 2: Characteristic curve of the analogue output

X = maximum length of the sensing range


Signal Description Range1)

0V – IO-Link operation –
– Error, e.g. cable break, parameter error
0.5 V – Piston is outside the sensing range after switching on A, C
the operating voltage

6 Festo — SDAT-MHS-...-SV — 2021-09


Product overview

Signal Description Range1)

1V – The piston has left the sensing range in the direction of A


the falling output current
> 1 V … < 10 V – Piston is within the sensing range B
10 V – Piston has left the sensing range in the direction of the C
rising output voltage
1) Range Fig. 2, range A and C: red LED on
Tab. 2: Output signal of the analogue output

The analogue output is switched off during active IO-Link communication. The output voltage is 0 V.

Scaling of the analogue signal


The analogue output signal is assigned by default to the complete sensing range. If only a part of the
sensing range is to be used, the analogue value output can be scaled to the sensing range in use. The
resolution and the repetition accuracy are not improved by scaling.
1 2

10 V

1V
0.5 V

0 mm 60 mm 120 mm 160 mm
Analogue signal scaled
Analogue signal not scaled
Fig. 3: Scaling of the analogue signal using the SDAT-MHS-M160 as an example

1 Teach-in point 1 2 Teach-in point 2

Festo — SDAT-MHS-...-SV — 2021-09 7


Product overview

4.2.2 Switching functions and switching logic


4.2.2.1 Window comparator

1 2

OUT

IN
Switching travel
Hysteresis
Fig. 4: Window comparator

1 Teach-in point 1 2 Teach-in point 2

Teach-in points 1 and 2 are linked to the window comparator function.


– The position of the teach points determines the window width.
– Hysteresis is not selectable or preset.

8 Festo — SDAT-MHS-...-SV — 2021-09


Product overview

4.2.2.2 Proximity switch

OUT

IN
Switching travel
Hysteresis
Fig. 5: Proximity switch

1 Teach-in point

The proximity switch function consists of a switching path and hysteresis. Hysteresis serves to sup-
press switching signals in the event of fluctuations around the switching point.
– The teach-in value is the centre of the switching path.
– The switching path and the hysteresis are not adjustable. Values for the switching path and the
hysteresis are stored that correspond to a typical electronic proximity switch on a typical drive.

Festo — SDAT-MHS-...-SV — 2021-09 9


Product overview

4.2.2.3 Hysteresis comparator

2 1

OUT

IN
Switching travel
Fig. 6: Hysteresis comparator

1 Teach-in point 1 2 Teach-in point 2

Teach-in points 1 and 2 are linked to the hysteresis comparator function.


– Teach-in point 1 (ON) is the switch-on point, teach-in point 2 (OFF) is the reset point.
– Teach-in point 2 establishes the size of the hysteresis.
4.2.2.4 Switching logic
The switching logic normally open (NO) is set as the default. If the switching logic normally closed (NC)
is selected, the function of the switching output is inverted.
4.2.3 Switching output operating mode (SIO)
If the IO-Link/switching output is operated as a switching output, only 1 binary channel can be
programmed. The switching output operating mode must be programmed actively via the Set-up mode
è 6.2 Setting Set-up mode.
– The window comparator, the proximity switch or the hysteresis comparator function are program-
mable.
– The normally closed (NC) or the normally open (NO) switching logic can be selected.
– Programming via the IO-Link protocol (channel BDC1) or the operating key on the device.
– Display switching output ON: the yellow LED is on.
– Output signal 24 V DC (PNP).

Even if the analogue output has been scaled, the switching output can still be programmed over the
entire sensing range.

4.2.4 IO-Link operating mode


Programmed switching signals and the continuous position values (digitally coded analogue values)
are transferred in the IO-Link operating mode.

10 Festo — SDAT-MHS-...-SV — 2021-09


Mounting

– Proximity switches, window comparators or hysteresis comparators can be programmed separately


on 4 binary channels.
– The continuous position values are always transferred parallel and independently of the position
value output of the binary channels.
– Every channel can be set to be normally closed (NC) or normally open (NO).
– The data transfer is serially and digitally coded in the IO-Link protocol.
– Process data: 12 bit for position data and 4 bit for binary channels è 10 Technical data.
– Unshielded standard cables up to 20 m in length can be used.
– The device description file IODD for every device length è www.festo.com/sp.
– Parameters and function in accordance with Smart-Sensor profile.
– The optional block parameterisation and Data Storage functions are supported.
– IO-Link operation display: the green LED flashes.
– The direction of the process data values (PDV) can be inverted.
The PDVs are minimum (standard) or maximum (inverted) and end of the sensor cable.

5 Mounting
5.1 Electrical installation
WARNING
Risk of injury due to electric shock.
• For the electrical power supply, use only PELV circuits in accordance with IEC 60204-1/EN 60204-1
(Protective Extra-Low Voltage, PELV).
• Observe the general requirements of IEC 60204-1/EN 60204-1 for PELV circuits.
• Only use voltage sources that ensure a reliable electric separation from the mains network in
accordance with IEC 60204-1/EN 60204-1.

1. Switch off the operating voltage.


2. Connect the M8 plug to the connecting cable of the higher-order controller.
– Max. tightening torque for the union nut of the plug: 0.3 Nm.

Fig. 7: Circuit diagram

Pin Allocation Plug

1 Operating voltage +24 V DC M8x1, 4-pin


2 Analogue output 0 … 10 V
3 0V
4 IO-Link/switching output (C/Q line)

Tab. 3: Pin allocation of plug connection

Festo — SDAT-MHS-...-SV — 2021-09 11


Mounting

5.2 Mechanical installation


Any mounting position can be used.

Fig. 8: Mechanical installation


1 Hexagon socket spanner 3 T-slot

2 Retaining screw

1. Push the position transmitter into the T-slot of the drive.


2. Move the piston to an end position of the application.
3. Push the position transmitter in the direction of the piston until the red LED goes out.
4. Hand-tighten the retaining screw.
– Max. tightening torque: 0.5 Nm
– Tool: internal hexagon socket key (size 1.5 mm).

12 Festo — SDAT-MHS-...-SV — 2021-09


Commissioning

6 Commissioning
6.1 Switch on the position transmitter
• Switch on the operating voltage.
Ä The LEDs light depending on the position of the piston è Tab. 5 LED displays in normal
operation.
Ä The position transmitter is ready for operation.

Parameters Factory setting

Switching function None


Switching logic Normally open contact (N/O)
Scaling Total sensing range
Tab. 4: Factory settings of the position transmitter

6.2 Setting Set-up mode


• Press the operating key 3 times within 3 s.
Ä Set-up mode active: the green LED and the yellow LED flash simultaneously.

If, after entering the Set-up mode, programming is not completed within 60 s, the position transmitter
automatically switches to the operating mode.

Festo — SDAT-MHS-...-SV — 2021-09 13


Commissioning

6.3 Scaling analogue signal


1 2

10 V

1V
0.5 V

0 mm 60 mm 120 mm 160 mm
Analogue signal scaled
Analogue signal not scaled
Fig. 9: Scaling the analogue signal using the SDAT-MHS-M160 as an example

1 Teach point 1 2 Teach point 2

Requirement: the piston is in the sensing range (red LED off ).


1. Switch to the Set-up mode .
2. Press the operating key 5 times in succession.
Ä The analogue output can be scaled: the green LED flashes 5 times in quick succession within
2 s.
3. Move the piston to the starting point of the sensing range.
4. Press the operating key.
Ä Teach point 1 is defined: the starting point of the sensing range at 0 V.
Ä The green LED continues flashing, the yellow LED flashes at 1 Hz.
5. Move the piston to the end point of the sensing range.
6. Press the operating key.
Ä Teach point 2 is defined: the end point of the sensing range at 10 V.
Ä The position transmitter switches to the operating mode.

To invert the direction of increase of the analogue signal: set teach point 2 (10 V) on the cylinder axis
before teach point 1 (0 V).

14 Festo — SDAT-MHS-...-SV — 2021-09


Commissioning

6.4 Program switching output


6.4.1 Set window comparator

1 2

OUT

IN
Switching travel
Hysteresis
Fig. 10: Window comparator

1 Teach point 1 2 Teach point 2

Requirement: the piston is in the sensing range (red LED off ).


1. Switch to the Set-up mode è 6.2 Setting Set-up mode.
2. Press the operating key once.
Ä The green LED flashes once within 2 s.
3. Move the piston to the first switching point (teach point 1).
4. Press the operating key once.
Ä Switching point 1 is set.
Ä The green LED continues flashing, the yellow LED flashes at 1 Hz.
5. Move the piston to the second switching point (teach point 2).
6. Press the operating key once.
Ä Switching point 2 is set.
Ä The position transmitter switches to the operating mode.

Festo — SDAT-MHS-...-SV — 2021-09 15


Commissioning

6.4.2 Adjusting proximity switch

OUT

IN
Switching travel
Hysteresis
Fig. 11: Proximity switch

1 Teach point

Requirement: the piston is in the sensing range (red LED off ).


1. Switch to the Set-up mode è 6.2 Setting Set-up mode.
2. Press the operating key twice.
Ä The green LED flashes 2 times quickly within 2 s.
3. Move the piston to the first switching point (teach point 1).
4. Press the operating key once.
Ä Switching point 1 is set.
Ä The position transmitter switches to the operating mode.

16 Festo — SDAT-MHS-...-SV — 2021-09


Commissioning

6.4.3 Set hysteresis comparator

2 1

OUT

IN
Switching travel
Fig. 12: Set hysteresis comparator

1 Teach point 1 2 Teach point 2

Requirement: the piston is in the sensing range (red LED off ).


1. Switch to the Set-up mode è 6.2 Setting Set-up mode.
2. Press the operating key 3 times.
Ä The green LED flashes 3 times quickly within 2 s.
3. Move the piston to the switch-on point (teach point 1).
4. Press the operating key once.
Ä The switch-on point is established.
Ä The green LED continues flashing, the yellow LED flashes at 1 Hz.
5. Move the piston to the reset point (teach point 2).
6. Press the operating key once.
Ä The reset point is established.
Ä The position transmitter switches to the operating mode.

6.4.4 Inverting switching logic


The switching logic can be inverted from N/C to N/O and vice versa.
1. Switch to the Set-up mode è 6.2 Setting Set-up mode.
2. Press the operating key 4 times.
Ä The green LED flashes 4 times quickly within 2 s.
Ä The yellow LED lights: the currently set switching logic is N/C.
The yellow LED is off: the currently set switching logic is N/O.
3. Press the operating key once.
Ä The switching logic is inverted.
The position transmitter switches to the operating mode.

Festo — SDAT-MHS-...-SV — 2021-09 17


Operation

6.4.5 Block/unblock operating key


In IO-Link mode, the operating key is always blocked.
In the switching output operating mode, the operating key is unlocked by default. However, in the
IO-Link mode the operating key can be blocked for the switching output mode:
1. Start IO-Link communication.
2. Select key lock for switching output operating mode in the IO-Link parameter menu:
– Device access block
– Local user interface block
LED display with blocked operating key
– If the operating key is pressed, the green LED flashes for 3 s at 3 Hz.
– The yellow LED displays the current status of the switching output.
– The red LED only lights if the piston is outside the sensing range.
6.4.6 Programming IO-Link output
The IO-Link function cannot be set with the operating keys on the device. All settings for set-up,
commissioning and parameterisation are made in the higher-level controller of the IO-Link master.
1. Upload the IODD device description file belonging to the device to the interpreter of the IO-Link
master.
2. Connect the IO-Link/switching output to the IO-Link master.
3. Program the device è Operating instructions for the IO-Link master.

An error during commissioning is displayed on the user interface of the IO-Link master and the
programming option is blocked.

7 Operation
7.1 Magnetic direction detection and magnetic direction correction
During initial commissioning or after a reset to factory settings, the position transmitter outputs the
signals directly using the currently detected magnetic direction.
The magnetic direction detection and, with it, the signal curve are corrected during continuing opera-
tion in the following cases:
– The position transmitter was placed in operation in a position in which it was not possible to detect
a correct magnetic direction, e.g. due to ferromagnetic materials near the sensor or within the drive
or gripper.
– The position transmitter was rotated 180° in the slot after the magnetic direction was detected as
stable.

Brief error signals may be detected at the sensor output if automatic correction of the magnetic
direction detection is required è 8.2 General malfunctions.

18 Festo — SDAT-MHS-...-SV — 2021-09


Operation

7.2 LED displays in normal operation


LED display Description
Yellow Green Red

Ready for operation:


– Analogue output function or switching output operating mode.
Green LED: on – Piston within the sensing range.
Red LED: off
Ready for operation:
– IO-Link operating mode.
Green LED: flashing at 1 Hz
Ready for operation:
– Switching output switched.
Yellow LED: on – Piston in the range of a programmed function.
Green LED: on
Red LED: off
Status indicator:
– Operating key blocked.
Green LED: flashes 3 s at
3 Hz when the operating key is
pressed
Status indicator:
– Piston outside the sensing range.
Red LED: on
Tab. 5: LED displays in normal operation

Query configuration
The currently set configuration can be queried in the Set-up mode.
1. Switch to the Set-up mode è 6.2 Setting Set-up mode.
2. Press the operating key 6 times.
Ä The yellow, green and red LEDs flash cyclically according to the current configuration
è Tab. 6 Status indicators in the Set-up mode.
3. To terminate the query, press the operating key once.
Ä The position transmitter switches to the operating mode.
If the operating key is not pressed, the device automatically switches to the operating mode after 60 s.
LED display Description

Green Function
No display Deactivated
flashes once Window comparator

Festo — SDAT-MHS-...-SV — 2021-09 19


Operation

LED display Description

2 flashes Proximity switch function


3 flashes Hysteresis comparator
Yellow Switching logic
flashes once Normally closed (N/C contact)
2 flashes Normally open contact (N/O)
Red Scaling
flashes once User-configured
2 flashes Total sensing range
Tab. 6: Status indicators in the Set-up mode

7.3 Reset position transmitter to factory setting


1. Switch to the Set-up mode è 6.2 Setting Set-up mode.
2. Press the operating key 10 times.
Ä The yellow, green and red LEDs flash at 1 Hz.
3. Press the operating key.
Ä The position transmitter is reset to the factory settings.
Ä The position transmitter switches to the operating mode.

20 Festo — SDAT-MHS-...-SV — 2021-09


Operation

7.4 Analogue output and switching function operation

Fig. 13: Settings using the operating key (menu structure)

Festo — SDAT-MHS-...-SV — 2021-09 21


Malfunctions

8 Malfunctions
8.1 Diagnostics via LED
LED display Possible cause Remedy
Yellow Green Red

Fault in power supply. Connect power supply.


Fault in connecting cable. Replace connecting cable.
All LEDs are off. Device is faulty. Replace device.
Hardware error. Switch power supply on/off.
Replace device.
Yellow LED is off.
Green LED is off.
Red LED is flashing.
Short circuit or overload at the Eliminate short circuit or over-
switching output. load.
Yellow LED flashes at 3 Hz. Parameter error. Reset device to factory setting
è 7.3 Reset position trans-
mitter to factory setting.
Communication error in IO-Link Check IO-Link master.
mode. Restart communication.
Yellow LED flashes at 3 Hz Check C/Q line.

Green LED flashing at 1 Hz


Tab. 7: LED displays in case of malfunctions

If the device detects an error during IO-Link operation, a status message is output at the IO-Link
master. The IO-Link/switching output is not blocked.

8.2 General malfunctions


Malfunction Cause Remedy

Incorrect or unexpected signals Drive is not suitable. Use a suitable drive.


at the analogue output or with Device is faulty. Replace device.
the IO-Link process data.
No power supply or impermis- Maintain operating voltage
sible operating voltage. range.
Short circuit or overload at the Eliminate short circuit or over-
switching output. load.

22 Festo — SDAT-MHS-...-SV — 2021-09


Technical data

Malfunction Cause Remedy

Incorrect or unexpected signals Magnetic object in the imme- Do not place magnetic objects
at the analogue output or with diate vicinity of the position in the immediate vicinity of the
the IO-Link process data. transmitter. position transmitter.
Sensor or drive was rotated Reset to factory setting using
180° after initial commis- the operating key or via IO-Link.
sioning.
Incorrect or unexpected signals On initial commissioning, move
during initial commissioning on gripper jaws or piston within
grippers or in attachments with the sensing range, e.g. to both
ferromagnetic components. end positions.
Switching output does not Short circuit or overload at the Eliminate short circuit or over-
switch in accordance with the switching output. load.
settings. Device is faulty. Replace device.
Settings cannot be edited. Access protection is active. Unblock operating key (only
possible via IO-Link).
Tab. 8: Possible malfunctions

9 Disassembly
1. Switch off the power supply.
2. Disconnect connections from the position transmitter.
3. Unscrew the retaining screws è Fig. 8.
4. Remove the position transmitter from the T-slot of the drive.

10 Technical data
10.1 General
SDAT-MHS-... 50 80 100 125 160

Conformity è www.festo.com/sp
Note on materials halogen-free
Input signal/measuring element
Sensing range1) [mm] 50 80 100 125 160
Signal processing
Sampling interval typ. [ms] 1
Max. traverse velocity [m/s] 3

Festo — SDAT-MHS-...-SV — 2021-09 23


Technical data

SDAT-MHS-... 50 80 100 125 160

Output, general
Resolution of travel [mm] 0.05
Switching output
Switching output PNP
Repetition accuracy of switching point [mm] 0.1
Hysteresis [mm] £ 0.3
Analogue output
Analogue output [V] 0 … 10
Sensitivity [mV/mm] 180 113 90 72 56
Typical linearity error [mm] ±0.25
Repetition accuracy [mm] 0.1
Min. load resistance of voltage output [kΩ] 20
Electronics
Operating voltage DC [V] 15 … 30
Typical signal running time [ms] <2
Electromechanics
Cable length [m] 0.3
Conductor nominal cross section [mm2] 0.1
Mechanical system
Max. tightening torque [Nm] 0.5
Information on materials – housing PA-reinforced, polyester, high-alloy
stainless steel, nickel-plated brass
Immission/emission
Ambient temperature [°C] -25 … +70
Ambient temperature with flexible cable [°C] -20 … +70
installation
Degree of protection (to EN 60529) IP65/IP68
Condition with IP68: test duration 24 h
1) Type-dependent
Tab. 9: Technical data SDAT-MHS

24 Festo — SDAT-MHS-...-SV — 2021-09


Technical data

10.2 IO-Link
SDAT-MHS-... 50 80 100 125 160

Protocol version Device V1.1


Profile Smart Sensor Profile
Function classes 0x8000:Identification
0x8001:Binary Data Channel
0x8002:Process Data Variable
0x8003:Diagnosis
0x8004:Teach Channel
Communication mode COM3 (230.4 kbaud)
Process data length IN 2 byte
Port class A, 4-pin
Device ID 0x000010 0x000011 0x000012 0x000013 0x000014
Tab. 10: Physical layer

Process data record: 2 bytes


Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Proces Process Data Variable (PDV)è Tab. 12 Range of BDC41) BDC31) BDC21) BDC11)
s data values of the process data variables (PDV) for the
device lengths è Process data with use of IODD
Data Position switch switch switch switch
4 3 2 1
Type Unsigned Integer Boolean
1) BDC = binary data channel (BinaryDataChannel)
Tab. 11: Process data content

Raw data

Device Nominal PDV PDV minimum PDV maximum PDV PDV OoR
length sensing min. value of nominal value of nominal max. after Power
range [mm] OoR1) sensing range sensing range OoR2) ON3)

M50 0 … 50 0 21 1044 1064 4095


M80 0 … 80 0 21 1659 1679 4095
M100 0 … 100 0 21 2068 2088 4095

Festo — SDAT-MHS-...-SV — 2021-09 25


Technical data

Device Nominal PDV PDV minimum PDV maximum PDV PDV OoR
length sensing min. value of nominal value of nominal max. after Power
range [mm] OoR1) sensing range sensing range OoR2) ON3)

M125 0 … 125 0 21 2580 2600 4095


M160 0 … 160 0 21 3297 3317 4095
1) Min OoR (out of range): minimum value of the sensing range
2) Max OoR (out of range): maximum value of the sensing range
3) OoR after Power ON: outside the sensing range when operating voltage is applied
Tab. 12: Range of values of the process data variables (PDV) for the device lengths

Process data with use of IODD

Device Nominal PDV PDV minimum PDV maximum PDV PDV OoR
length sensing min. value of nominal value of nominal max. after Power
range [mm] OoR1) sensing range sensing range OoR2) ON3)

M50 0 … 50 0 103 5099 5196 19999


M80 0 … 80 0 103 8102 8200 19999
M100 0 … 100 0 103 10100 10198 19999
M125 0 … 125 0 103 12600 12698 19999
M160 0 … 160 0 103 16102 16200 19999
1) Min OoR (out of range): minimum value of the sensing range
2) Max OoR (out of range): maximum value of the sensing range
3) OoR after Power ON: outside the sensing range when operating voltage is applied
Tab. 13: Range of values of the process data variables with use of IODD for the device lengths

Index Su Name Default value Access1) Length Format


bin (example M50) U M S
de
x

0x0002 0 System Com- è Tab. 15 System — W W 1 byte Unsigne


mand commands d
Integer
0x000C 0 Device Access 0 = unlocked R R/W R/W 2 byte Record
Locks2) 1 = locked
0x0010 0 Vendor Name Festo SE & Co. KG R R R 64 byte String
0x0011 0 Vendor Text http:// R R R 64 byte String
www.festo.com
0x0012 0 Product Name SDAT-MHSM50-1L- R R R 64 byte String
SA-E-0.3-M8
0x0013 0 Product ID3) 1531265 R R R 64 byte String

26 Festo — SDAT-MHS-...-SV — 2021-09


Technical data

Index Su Name Default value Access1) Length Format


bin (example M50) U M S
de
x

0x0014 0 Product Text Position trans- R R R 64 byte String


mitter
0x0015 0 Serial- 12345678901 R R R 16 byte String
Number
0x0016 0 Hardware REVxy R R R 64 byte String
Revision
0x0017 0 Firmware REVxy R R R 64 byte String
Revision
0x0018 0 Application *** R/ R/W R/W 32 byte String
Specific Tag4) W
0x0028 0 Process Data è Tab. 11 Process R R R 2 byte Record
Input data content
1) Authorisation group U = user, M = maintenance, S = specialist; access W = write, R = read, R/W = read and write, – = no access
2) Bit 0: lock parameter write access; Bit1: lock data storage; Bit3: lock local user interface (operating key)
3) Festo part number
4) Value defined by user
Tab. 14: Service data

Value Access1)2) Length Format Format


U M S

128 — — W 1 byte Unsigned Integer Reset Device


130 — — W Restore Factory Settings
176 — — W Reset Warnings
160 — W W Teach SP1 BDC13)
161 — W W Teach SP2 BDC13)
162 — W W Teach SP1 BDC23)
163 — W W Teach SP2 BDC23)
164 — W W Teach SP1 BDC33)
165 — W W Teach SP2 BDC33)
166 — W W Teach SP1 BDC43)
167 — W W Teach SP2 BDC43)

Festo — SDAT-MHS-...-SV — 2021-09 27


Technical data

Value Access1)2) Length Format Format


U M S

168 — W W 1 byte Unsigned Integer Teach Scale Start analogue


output
169 — W W Teach Scale End analogue
output
1) Authorisation group U = user, M = maintenance, S = specialist; access W = write, – = no access
2) If access = write, an attempted read access will return error code 0x8101.
3) Access also possible via the standard function class 0x8004 “Teach Channel” of the Smart Sensor Profile.
Tab. 15: System commands

Index Sub- Name Default Access2) Length Format3)


inde value U M S
x (example
M50)1)

BDC1
0x003C 1 Setpoint SP1 175 R R/W R/W 2 byte Unsigned
2 Setpoint SP2 250 2 byte Integer

0x003D 1 Switchpoint logic 0 1 byte


2 Switchpoint mode 0 1 byte
3 Switchpoint hyste- 5 2 byte
resis
BDC2
0x003E 1 Setpoint SP1 275 R R/W R/W 2 byte Unsigned
2 Setpoint SP2 350 2 byte Integer

0x003F 1 Switchpoint logic 0 1 byte


2 Switchpoint mode 0 1 byte
3 Switchpoint hyste- 5 2 byte
resis
Analogue current output
0x3000 1 Scale Start 1 R R/W R/W 2 byte Unsigned
2 Scale End 1063 2 byte Integer

PDV 0: normal, 1: inverted, not for analogue current output


0x3010 0 PDV Invertierung 0 R R/W R/W 1 byte Unsigned
Integer
BDC3

28 Festo — SDAT-MHS-...-SV — 2021-09


Technical data

Index Sub- Name Default Access2) Length Format3)


inde value U M S
x (example
M50)1)

0x4000 1 Setpoint SP1 375 R R/W R/W 2 byte Unsigned


2 Setpoint SP2 450 2 byte Integer

0x4001 1 Switchpoint logic 0 1 byte


2 Switchpoint mode 0 1 byte
3 Switchpoint hyste- 5 2 byte
resis
BDC4
0x4002 1 Setpoint SP1 475 R R/W R/W 2 byte Unsigned
2 Setpoint SP2 550 2 byte Integer

0x4003 1 Switchpoint logic 0 1 byte


2 Switchpoint mode 0 1 byte
3 Switchpoint hyste- 5 2 byte
resis
1) Raw data without use of IODD
2) Authorisation group U = user, M = maintenance, S = specialist; access R = read, R/W = read and write
3) Coding BDC1… BDC4 è Tab. Tab. Coding switching point parameters
Tab. 16: parameter

Name Coding

Setpoint SP1/SP21) 12 bit position values


Switchpoint logic 0 = output signal not inverted; 1 = output signal inverted
Switchpoint mode 0 = deactivated; 1 = proximity switch, 2 = window comparator, 3
= hysteresis comparator
Switchpoint hysteresis Fix: 5
1) Value range è Tab. Value range of the process data variables (PDV) for the device lengths
Tab. 17: Coding switch point parameter

Error code Mode Type Comments

0x4000 (Dis)appear Error Temperature fault


0x5000 (Dis)appear Error Hardware defective
0x5111 (Dis)appear Warning Voltage too low
0x6320 (Dis)appear Error Parameter error

Festo — SDAT-MHS-...-SV — 2021-09 29


Technical data

Error code Mode Type Comments

0x8CA0 (Dis)appear Error Magnetic field too weak, unsuit-


able drive
0xFF91 (Dis)appear Notification Data Storage upload request
Tab. 18: Error Codes

10.3 I-Port
The IO-Link specification data generally apply è 10.2 IO-Link.
For information on the process data contents è è Tab. 11 Process data content.
Index Name Default value Access1) Length

0x0040 Device attributes 0x00 R/W 1 byte


0x0041 Extended parameters 0x0000 R/W 2 byte
0x0042 Diagnosis parameter 0x0000 R 2 byte
0x0043 Device specific parameters è Tab. 20 Device-spe- R/W 8 byte
cific parameters
0x00FE I-Port Revision 0x0101 R/W 2 byte
1) Access R = read, R/W = read and write
Tab. 19: Additionally supported parameters in accordance with I-Port specification

Byte 1 2 3 4 5 6 7 8

IO-Link index 0x003C 0x003D


Subindex 1 2 1 2 3
Function1) SP1 SP2 Logic Mode HY
Byte high low high low — — high low
Default value 0x00 0xAF 0x00 0xFA 0x00 0x00 0x00 0x05
1) Coding parameter è Tab. Coding switching point parameters
Tab. 20: Device-specific parameters

10.4 Technical data for UL/CSA certification


Electrical and environmental ratings UL/CSA

Input Voltage Max. 30 V DC, Class 2


Input current 160 mA/max. 4.8 W
Analog output 0 … 10 V
Transistor output Max. 30 V DC, 100 mA G.P.

30 Festo — SDAT-MHS-...-SV — 2021-09


Technical data

Electrical and environmental ratings UL/CSA

Maximum Ambient Temperature 70 °C/158 °F


NEMA enclosure type number Type 1
(Enclosure Type Rating)
Tab. 21: Electrical data and ambient conditions UL/CSA

Festo — SDAT-MHS-...-SV — 2021-09 31


Copyright:
Festo SE & Co. KG
73734 Esslingen
Ruiter Straße 82
Deutschland

Phone:
+49 711 347-0

Internet:
© 2022 all rights reserved to Festo SE & Co. KG www.festo.com