-SV
Position transmitter
Operating instruc-
tions
8155512
2021-09
[8155514]
Translation of the original instructions
Table of contents
1 About this document . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Applicable Documents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Intended use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Training of qualified personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.4 UL/CSA certification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Additional information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Product overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.1 Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.2 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.2.1 Analogue output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.2.2 Switching functions and switching logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.2.3 Switching output operating mode (SIO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.2.4 IO-Link operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1 Electrical installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2 Mechanical installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.1 Switch on the position transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.2 Setting Set-up mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.3 Scaling analogue signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6.4 Program switching output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.4.1 Set window comparator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.4.2 Adjusting proximity switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.4.3 Set hysteresis comparator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.4.4 Inverting switching logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.4.5 Block/unblock operating key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.4.6 Programming IO-Link output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
7.1 Magnetic direction detection and magnetic direction correction . . . . . . . . . . . . . . . . . . . 18
7.2 LED displays in normal operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7.3 Reset position transmitter to factory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.4 Analogue output and switching function operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
8 Malfunctions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.1 Diagnostics via LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.2 General malfunctions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
9 Disassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10.2 IO-Link. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10.3 I-Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
10.4 Technical data for UL/CSA certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2 Safety
2.1 General safety instructions
– Only use the product in its original condition without unauthorised modifications.
– Only use the product if it is in perfect technical condition.
– The product may generate high frequency interference, which may require interference suppression
measures in residential areas.
– Technical data and environmental conditions may be subject to change in order to comply with
Underwriters Laboratories Inc. (UL) certification requirements for the USA and Canada. è 10.4
Technical data for UL/CSA certification
– Only for connection to a NEC/CEC Class 2 supply.
– The device shall be supplied from an isolating transformer having a secondary listed fuse rated 1 A.
3 Additional information
– Contact the regional Festo contact if you have technical problems è www.festo.com.
– Accessories and spare parts è www.festo.com/catalogue.
4 Product overview
4.1 Design
6 1
2
5
4.2 Function
The position transmitter detects the magnetic field of the piston magnet and continuously senses the
piston movement in the sensing range.
10 V
1V
0.5 V
0 mm X mm
Fig. 2: Characteristic curve of the analogue output
0V – IO-Link operation –
– Error, e.g. cable break, parameter error
0.5 V – Piston is outside the sensing range after switching on A, C
the operating voltage
The analogue output is switched off during active IO-Link communication. The output voltage is 0 V.
10 V
1V
0.5 V
0 mm 60 mm 120 mm 160 mm
Analogue signal scaled
Analogue signal not scaled
Fig. 3: Scaling of the analogue signal using the SDAT-MHS-M160 as an example
1 2
OUT
IN
Switching travel
Hysteresis
Fig. 4: Window comparator
OUT
IN
Switching travel
Hysteresis
Fig. 5: Proximity switch
1 Teach-in point
The proximity switch function consists of a switching path and hysteresis. Hysteresis serves to sup-
press switching signals in the event of fluctuations around the switching point.
– The teach-in value is the centre of the switching path.
– The switching path and the hysteresis are not adjustable. Values for the switching path and the
hysteresis are stored that correspond to a typical electronic proximity switch on a typical drive.
2 1
OUT
IN
Switching travel
Fig. 6: Hysteresis comparator
Even if the analogue output has been scaled, the switching output can still be programmed over the
entire sensing range.
5 Mounting
5.1 Electrical installation
WARNING
Risk of injury due to electric shock.
• For the electrical power supply, use only PELV circuits in accordance with IEC 60204-1/EN 60204-1
(Protective Extra-Low Voltage, PELV).
• Observe the general requirements of IEC 60204-1/EN 60204-1 for PELV circuits.
• Only use voltage sources that ensure a reliable electric separation from the mains network in
accordance with IEC 60204-1/EN 60204-1.
2 Retaining screw
6 Commissioning
6.1 Switch on the position transmitter
• Switch on the operating voltage.
Ä The LEDs light depending on the position of the piston è Tab. 5 LED displays in normal
operation.
Ä The position transmitter is ready for operation.
If, after entering the Set-up mode, programming is not completed within 60 s, the position transmitter
automatically switches to the operating mode.
10 V
1V
0.5 V
0 mm 60 mm 120 mm 160 mm
Analogue signal scaled
Analogue signal not scaled
Fig. 9: Scaling the analogue signal using the SDAT-MHS-M160 as an example
To invert the direction of increase of the analogue signal: set teach point 2 (10 V) on the cylinder axis
before teach point 1 (0 V).
1 2
OUT
IN
Switching travel
Hysteresis
Fig. 10: Window comparator
OUT
IN
Switching travel
Hysteresis
Fig. 11: Proximity switch
1 Teach point
2 1
OUT
IN
Switching travel
Fig. 12: Set hysteresis comparator
An error during commissioning is displayed on the user interface of the IO-Link master and the
programming option is blocked.
7 Operation
7.1 Magnetic direction detection and magnetic direction correction
During initial commissioning or after a reset to factory settings, the position transmitter outputs the
signals directly using the currently detected magnetic direction.
The magnetic direction detection and, with it, the signal curve are corrected during continuing opera-
tion in the following cases:
– The position transmitter was placed in operation in a position in which it was not possible to detect
a correct magnetic direction, e.g. due to ferromagnetic materials near the sensor or within the drive
or gripper.
– The position transmitter was rotated 180° in the slot after the magnetic direction was detected as
stable.
Brief error signals may be detected at the sensor output if automatic correction of the magnetic
direction detection is required è 8.2 General malfunctions.
Query configuration
The currently set configuration can be queried in the Set-up mode.
1. Switch to the Set-up mode è 6.2 Setting Set-up mode.
2. Press the operating key 6 times.
Ä The yellow, green and red LEDs flash cyclically according to the current configuration
è Tab. 6 Status indicators in the Set-up mode.
3. To terminate the query, press the operating key once.
Ä The position transmitter switches to the operating mode.
If the operating key is not pressed, the device automatically switches to the operating mode after 60 s.
LED display Description
Green Function
No display Deactivated
flashes once Window comparator
8 Malfunctions
8.1 Diagnostics via LED
LED display Possible cause Remedy
Yellow Green Red
If the device detects an error during IO-Link operation, a status message is output at the IO-Link
master. The IO-Link/switching output is not blocked.
Incorrect or unexpected signals Magnetic object in the imme- Do not place magnetic objects
at the analogue output or with diate vicinity of the position in the immediate vicinity of the
the IO-Link process data. transmitter. position transmitter.
Sensor or drive was rotated Reset to factory setting using
180° after initial commis- the operating key or via IO-Link.
sioning.
Incorrect or unexpected signals On initial commissioning, move
during initial commissioning on gripper jaws or piston within
grippers or in attachments with the sensing range, e.g. to both
ferromagnetic components. end positions.
Switching output does not Short circuit or overload at the Eliminate short circuit or over-
switch in accordance with the switching output. load.
settings. Device is faulty. Replace device.
Settings cannot be edited. Access protection is active. Unblock operating key (only
possible via IO-Link).
Tab. 8: Possible malfunctions
9 Disassembly
1. Switch off the power supply.
2. Disconnect connections from the position transmitter.
3. Unscrew the retaining screws è Fig. 8.
4. Remove the position transmitter from the T-slot of the drive.
10 Technical data
10.1 General
SDAT-MHS-... 50 80 100 125 160
Conformity è www.festo.com/sp
Note on materials halogen-free
Input signal/measuring element
Sensing range1) [mm] 50 80 100 125 160
Signal processing
Sampling interval typ. [ms] 1
Max. traverse velocity [m/s] 3
Output, general
Resolution of travel [mm] 0.05
Switching output
Switching output PNP
Repetition accuracy of switching point [mm] 0.1
Hysteresis [mm] £ 0.3
Analogue output
Analogue output [V] 0 … 10
Sensitivity [mV/mm] 180 113 90 72 56
Typical linearity error [mm] ±0.25
Repetition accuracy [mm] 0.1
Min. load resistance of voltage output [kΩ] 20
Electronics
Operating voltage DC [V] 15 … 30
Typical signal running time [ms] <2
Electromechanics
Cable length [m] 0.3
Conductor nominal cross section [mm2] 0.1
Mechanical system
Max. tightening torque [Nm] 0.5
Information on materials – housing PA-reinforced, polyester, high-alloy
stainless steel, nickel-plated brass
Immission/emission
Ambient temperature [°C] -25 … +70
Ambient temperature with flexible cable [°C] -20 … +70
installation
Degree of protection (to EN 60529) IP65/IP68
Condition with IP68: test duration 24 h
1) Type-dependent
Tab. 9: Technical data SDAT-MHS
10.2 IO-Link
SDAT-MHS-... 50 80 100 125 160
Proces Process Data Variable (PDV)è Tab. 12 Range of BDC41) BDC31) BDC21) BDC11)
s data values of the process data variables (PDV) for the
device lengths è Process data with use of IODD
Data Position switch switch switch switch
4 3 2 1
Type Unsigned Integer Boolean
1) BDC = binary data channel (BinaryDataChannel)
Tab. 11: Process data content
Raw data
Device Nominal PDV PDV minimum PDV maximum PDV PDV OoR
length sensing min. value of nominal value of nominal max. after Power
range [mm] OoR1) sensing range sensing range OoR2) ON3)
Device Nominal PDV PDV minimum PDV maximum PDV PDV OoR
length sensing min. value of nominal value of nominal max. after Power
range [mm] OoR1) sensing range sensing range OoR2) ON3)
Device Nominal PDV PDV minimum PDV maximum PDV PDV OoR
length sensing min. value of nominal value of nominal max. after Power
range [mm] OoR1) sensing range sensing range OoR2) ON3)
BDC1
0x003C 1 Setpoint SP1 175 R R/W R/W 2 byte Unsigned
2 Setpoint SP2 250 2 byte Integer
Name Coding
10.3 I-Port
The IO-Link specification data generally apply è 10.2 IO-Link.
For information on the process data contents è è Tab. 11 Process data content.
Index Name Default value Access1) Length
Byte 1 2 3 4 5 6 7 8
Phone:
+49 711 347-0
Internet: