VCB 3AE4 1
VCB 3AE4 1
I Circuit-breaker
Features
• According to IEC 62271‑100 and VDE 0671‑100 Vacuum circuit-breaker 3AE43
(for standards, see chapter 2)
• Application in hermetically welded switchgear vessel in
conformity with the system
• Climate-independent vacuum interrupter poles in the
SF6 ‑filled switchgear vessel
• Maintenance-free for indoor installation according to 1
IEC 62271‑1 and VDE 0671-1 7
3
• Individual secondary equipment
• A metal bellows is used for gasketless separation of the
SF6 insulation and the operating mechanism (already used
with success for over 5 million vacuum interrupters).
9
Trip-free mechanism 10
The vacuum circuit-breaker is fitted with a trip-free mecha-
R-HA3541-186 tif
5
nism according to IEC 62271 and VDE 0671. 4
2
Switching duties and operating mechanisms
The switching duties of the vacuum circuit-breaker are
dependent, among other factors, on its type of operating
mechanism. 11 6 8
2/7 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated Siemens HA 35.42 · 2020
Components
Circuit-breaker I
Section through the vacuum circuit-breaker Switching rate of the vacuum interrupter
77
13
AE43 24 kV, 25 kA, 630 A, 800 A with VSG 24-1-25-K4
3AE43 24 kV, 25 kA, 1000 A, 1250 A with VSG 24-1-25-K4
3AE43 24 kV, 25 kA, 1600 A, 2000 A with VSA 17-0-31
3 3AE43 17.5 kV, 31.5 kA, 1000 A, 1250 A with VSA 17-0-31-A1
3AE43 17.5 kV, 31.5 kA, 1600 A, 2000 A with VSA 17-0-31
+$HSV
43
AE43 24 kV, 25 kA, 2500 A with VSA 17-0-31
53
AE43 17.5 kV, 31.5 kA, 2500 A with VSA 17-0-31
O = OPEN operation
CO = C
LOSE operation with subsequent OPEN operation at the
shortest internal close-open time of the vacuum circuit-
breaker
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated Siemens HA 35.42 · 2020 3/7
Components
I Circuit-breaker
+$BHQHSV
LQDOOSROHV
3AH25 1st release: < 80 ms ,QLWLDWLRQRIFXUUHQWIORZ
LQWKHILUVWSROH
2nd release: < 65 ms ,QVWDQWZKHQFORVLQJ
LVUHOHDVHG
Minimum command Closing solenoid 45 ms
duration 1st release 40 ms
2nd release 20 ms Opening time
Pulse time for 1st release > 15 ms
circuit-breaker 2nd release > 10 ms &/26('SRVLWLRQ
Synchronism error
≤ 2 ms
between the poles &XUUHQWIORZ
7LPH
2SHQLQJWLPH 7RWDO Opening
DUFLQJ
WLPH
%UHDNWLPH
6HSDUDWLRQRI )LQDODUFH[WLQFWLRQ
+$BHQHSV
DUFLQJFRQWDFWV LQDOOSROHV
LQWKHSROH 6HSDUDWLRQRIDUFLQJFRQWDFWV
RSHQLQJILUVW LQDOOSROHV
,QVWDQWZKHQRSHQLQJ
LVUHOHDVHG
&/26('SRVLWLRQ
&RQWDFWPRYHPHQW
23(1 23(1
SRVLWLRQ SRVLWLRQ
&XUUHQWIORZ
7LPH
&/26(23(1FRQWDFWWLPH
'XUDWLRQRI&/26(23(1FXUUHQWIORZ
&RQWDFWV
WRXFKLQJWKH
SROHFORVLQJILUVW
&RQWDFWVWRXFKLQJ )LQDODUFH[WLQFWLRQ
+$BHQHSV
LQDOOSROHV LQDOOSROHV
%HJLQQLQJRIFXUUHQW 6HSDUDWLRQRIDUFLQJ
IORZLQILUVWSROH FRQWDFWVLQDOOSROHV
,QVWDQWZKHQFORVLQJ
LVUHOHDVHG
4/7 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated Siemens HA 35.42 · 2020
Components
Circuit-breaker I
Varistor module
• To limit overvoltages to approx. 500 V for protection devices
(when inductive components are mounted in the vacuum
circuit-breaker)
• For auxiliary voltages ≥ 60 V DC.
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated Siemens HA 35.42 · 2020 5/7
Components
I Circuit-breakers 3AE43, 3AE44, 3AH25 – Technical data
Circuit-breaker panel 27.6; 36; 38 20; 25; 26.3 630; 800 VSG 36-1-25
27.6; 36; 38 20; 25; 26.3 1000; 1250 VSG 36-1-25
Bus sectionalizer 27.6; 36; 38 20; 25; 26.3 1000; 1250 VSG 36-1-25
Circuit-breaker panel 7.2; 12; 15 8; 20; 25; 31.5 1000; 1250 VS17005
6/7 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated Siemens HA 35.42 · 2020
Components
Circuit-breakers 3AE43, 3AE44, 3AH25 – Technical data I
[%] [ms]
RMF 10,000 50 45, 75 23 no 3 A E 4 3 5 8 - 1
RMF 10,000 50 45, 75 23 no 3 A E 4 3 6 0 - 1
RMF 10,000 50 45, 75 23 yes* 3 A E 4 3 6 1 - 8
RMF 10,000 50 45, 75 23 yes* 3 A E 4 3 6 1 - 2
RMF 10,000 66 45, 75, 120 37 yes 3 A E 4 3 4 1 - 8
RMF 10,000 66 45, 75, 120 37 yes 3 A E 4 3 4 1 - 2
RMF 10,000 50 45, 75 23 yes 3 A E 4 3 6 1 - 4
RMF 10,000 50 45, 75 23 yes 3 A E 4 3 6 1 - 6
RMF 10,000 66 45, 75, 120 37 yes 3 A E 4 3 4 1 - 4
RMF 10,000 66 45, 75, 120 37 yes 3 A E 4 3 4 1 - 6
RMF 10,000 50 45, 75 23 no 3 A E 4 3 6 1 - 8
RMF 10,000 50 45, 75 23 no 3 A E 4 3 6 1 - 2
RMF 10,000 50 45, 75 23 no 3 A E 4 3 6 4 - 2 7
RMF 10,000 50 45, 75 23 no 3 A E 4 3 6 2 - 2
RMF 10,000 66 45, 75, 120 37 yes 3 A E 4 3 4 2 - 2
RMF 10,000 50 45, 75 23 yes 3 A E 4 3 6 2 - 4
RMF 10,000 50 45, 75 23 yes 3 A E 4 3 6 2 - 6
RMF 10,000 66 45, 75, 120 37 yes 3 A E 4 3 4 2 - 4
RMF 10,000 66 45, 75, 120 37 yes 3 A E 4 3 4 2 - 6
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated Siemens HA 35.42 · 2020 7/7
Components
I Electrical data
8/7 Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated Siemens HA 35.42 · 2020
Components
Electrical data I
Rated voltage of the motor Operating voltage Power consumption of the motor
V max. V min. V W / VA 7
24 DC 26 20 140
48 DC 53 41 140
60 DC 56 51 150
110 DC 121 93 280
220 DC 242 187 260
110 AC 121 93 280
230 AC 244 187 260
The inrush current in the drive motor can be neglected due to its very short presence.
1) Consumption at pickup current (90 % of the rated operating current) and open armature.
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated Siemens HA 35.42 · 2020 9/7