RD11 Series Frequency converter Manual
1 Overview
1.1 Safety Precautions
To ensure safe and reasonable use of this product, please use the product after fully understanding the safety precautions described in this manual.
Warning signs and meanings
The following symbols are used in this manual to indicate that it is an important part of safety. Failure to follow these precautions may result in personal
injury or death, damage to this product and associated systems.
DANGER: Death or major safety hazard can result from incorrect operation.
Operational qualification
This product must be operated by trained professionals. Moreover, the operator must be trained in professional skills, familiar with the installation,
wiring, operation and maintenance of the equipment, and properly respond to various emergencies in use.
Safety guidance
Warning signs are provided for your safety. They are measures to prevent injury to the operator and damage to the product and associated
systems. Please read this manual carefully before use and follow the safety rules and warnings in this manual strictly while operating.
●Proper transportation, storage, installation, and careful operation and maintenance are essential for the safe operation of the inverter. During
transmission and storage, ensure that the inverter is not subject to shock and vibration. It must also be stored in a dry, non-corrosive atmosphere,
non-conductive dust and ambient temperature less than 60 °C.
● This product has a dangerous voltage and it controls a potentially dangerous moving mechanism. Failure to follow these instructions or not
complying with the requirements of this manual may result in personal injury or death, damage to the product and associated systems.
● Do not perform wiring work while the power is on, otherwise there is a danger of death due to electric shock. When wiring, inspection,
maintenance, etc., please cut off the power of all related equipment and confirm that the DC voltage of the main circuit has dropped to Safety
level, wait 5 minutes before performing related work.
● The power cable, motor cable, and control cable must be tightly connected. The grounding terminal must be grounded reliably and the grounding
resistance is less than 10Ω.
● The static electricity of the human body will seriously damage the internal sensitive components. Before performing related operations, please
observe the measures and methods specified in the static electricity prevention measures (ESD), otherwise the inverter may be damaged.
●Since the output voltage of the inverter is a pulse waveform, if the output side is equipped with a capacitor with improved power factor or a
varistor for lightning protection, be sure to remove or modify it on the input side of the inverter.
● Do not add switching devices such as circuit breakers and contactors on the output side of the inverter (if the switching device must be
connected to the output side, the output current of the inverter must be zero when the switch is activated).
● No matter where the fault occurs in the control equipment, it may cause a shutdown and a major accident. Therefore, take the necessary
external protection measures or spare equipment.
● This product can only be used in accordance with the manufacturer's specified use. It may not be used in special fields such as emergency,
rescue, shipbuilding, medical, aviation, nuclear facilities, etc. without permission.
●The maintenance of this product can only be carried out by the company or by a professional authorized by the company. Unauthorized
modification and use of accessories not approved by the company may result in product failure. Any defective devices must be replaced in time
for maintenance.
● The company is not responsible for any damage or equipment damage caused by your company or your company's customers who fail to
comply with the contents of this manual
1.2 Before use
Upon receipt of the product you ordered, please check the outsourcing for damage and open the outer packaging after confirming the integrity, and
confirm that whether the inverter is damaged, scratched or dirty. (Damage caused during transportation does not belong to our company's
warranty). If the product you received is damaged, please contact the company or the shipping company immediately. After confirming that the
1
RD11 Series Frequency converter Manual
received product is intact, please confirm that the received inverter model is consistent with the product you ordered.
Inverter model description
Example RD11-T4-1720-LO-IP20-BU-DC
RD11 Product Series
T4 Voltage class 380-400V / S2 220V / T6 690V / T9 1140V
1720 Rated output current, A
LO Low-overload / HO – high-overload
IP20 Environmental protection class IP20 or IP54
BU Brake unit integrated
DC DC choke integrated
3
RD11 Series Frequency converter Manual
External output
1 relay output, 1 collector output, 1 AO output: 0~10V output or 4~20mA output
signal
Overvoltage, under-voltage, current limit, over-current, overload, electric thermal relay, overheat,
Protection function
overvoltage stall, data protection, rapid speed protection, input/output phase failure protection
Built-in keyboard: single line 5- digital tube display monitor 1 inverter status quantity
LED display
External keyboard: double line 5- digital tube display Monitor 2 inverter status quantities
Keyboard Parameter copy Upload and download function code information of the inverter for fast parameter copying
display Output frequency, given frequency, output current, input voltage, output voltage, motor speed, PID
Status monitor
feedback, PID given value, module temperature etc. monitor parameters.
Over-voltage, under-voltage, over-current, short circuit, phase failure, overload, overheat, overvoltage
Error alarm
stall, current limit, or Data protection compromised, current fault health, historical fault record
The altitude is less than 1000 meters, and the derating is more than 1000 meters. The derating is 1%
Install place for every 100 meters. No condensation, icing, rain, snow, hail, etc., solar radiation is less than
700W/m2, air pressure 70~106kPa
Temperature, -10 ~ +50°C, derating can be used above 40 °C, the maximum temperature is 60 °C (no-load
humidity operation), 5%~95%RH(no condensation)
Environment Vibration 5% to 95% RH (no condensation)
9~200Hz,5.9m/s2(0.6g)
Storage temperature 5%—95%RH
-30—+60℃ (no condensation)
Installation Wall hanging
Protection degree IP20
Cooling method Forced air cooling
2 Installation
In order to ensure the safe use of this product by users, maximize the performance of the inverter, and ensure the reliable operation of the
inverter, please strictly use the product in accordance with the environment, wiring, ventilation and other requirements described in this chapter.
4
RD11 Series Frequency converter Manual
Overall dimension(mm) Installation dimension(mm) Apertur
Model
W H H1 D D1 W1 W2 H2 A B e
AC310-S2-R75G-B
76 200 192 155 149 65 65 193 5.5 4 3-M4
AC310-S2-1R5G-B
AC310-S2-2R2G-B
100 242 231 155 149 84 86.5 231.5 8 5.5 3-M4
AC310-S2-004G-B
RD11-T4-0003-LO-IP20-BU
RD11-T4-0004-LO-IP20-BU
RD11-T4-0006-LO-IP20-BU
76 200 192 155 149 65 65 193 5.5 4 3-M4
RD11-T4-0003-HO-IP20-BU
RD11-T4-0004-HO-IP20-BU
RD11-T4-0006-HO-IP20-BU
RD11-T4-0013-LO-IP20-BU
RD11-T4-0017-LO-IP20-BU
100 242 231 155 149 84 86.5 231.5 8 5.5 3-M4
RD11-T4-0010-HO-IP20-BU
RD11-T4-0013-HO-IP20-BU
RD11-T4-0025-LO-IP20-BU
RD11-T4-0032-LO-IP20-BU
116 320 307.5 175 169 98 100 307.5 9 6 3-M5
RD11-T4-0017-HO-IP20-BU
RD11-T4-0025-HO-IP20-BU
5
RD11 Series Frequency converter Manual
RD11-T4-0038-LO-IP20-BU
RD11-T4-0045-LO-IP20-BU
RD11-T4-0060-LO-IP20-BU
142 383 372 225 219 125 100 372 6 4-M5
RD11-T4-0032-HO-IP20-BU
RD11-T4-0038-HO-IP20-BU
RD11-T4-0045-HO-IP20-BU
RD11-T4-0075-LO-IP20-N
RD11-T4-0090-LO-IP20-N
172 430 / 225 219 150 150 416.5 7.5 4-M5
RD11-T4-0060-HO-IP20-N
RD11-T4-0075-HO-IP20-N
6
RD11 Series Frequency converter Manual
RD11-T4-0380-LO-IP20-N-DC
RD11-T4-0415-LO-IP20-N-DC
RD11-T4-0470-LO-IP20-N-DC
RD11-T4-0340-HO-IP20-N-DC 360 940 850 480 200 910 4-M16
RD11-T4-0380-HO-IP20-N-DC
RD11-T4-0415-HO-IP20-N-DC
RD11-T4-0520-LO-IP20-N-DC
RD11-T4-0600-LO-IP20-N-DC
RD11-T4-0470-HO-IP20-N-DC 370 1140 1050 545 200 1110 4-M16
RD11-T4-0510-HO-IP20-N-DC
7
RD11 Series Frequency converter Manual
Inverter installation space requirements
150mm以上
通风方向
Ventilation direction
wind
direction
150mm以上
Ventilation
通风方向 direction
左右空间不设限
Left and right space is not limited Up and
上下空间
downdown space
Up and
space
External keyboard shape and opening size Note: LCD keyboard is fully compatible with LED keyboard size and opening size。
62 16
62 16
使用自攻钉ST3*6
Self-tapping Screw
使用自攻钉ST3*6
17.5
17.5
100
17.5
3.5
100
17.5
3.5
49.4
49.4
37.8
37.8
键盘安装开孔尺寸
35.6 49.4 键盘安装开孔尺寸
Keyboard Installation Size
35.6 49.4
AC300П µ
Б Р
Н в
Т э
ј ь
Е М
Н в
Р О
ј °
ї Є
ї Ч
і Я
ґ з
AC300П µ
Б Р
Н в
Т э
ј ь
Е М
Н в
Р О
ј °
ї Є
ї Ч
і Я
ґ з
77 20.8
70
77 20.8
70
119
119*70mm;
键盘兜开孔尺寸
132.8
119
119*70mm;
1.8
AC300П µ
Б Р
Н в
Т э
ј ь ¶ 1.8
Е М Ј Ё
µ 0.75KW-37KWЈ ©
Н в
Р О
ј °
ї Є
ї Ч
і Я
ґ з
Н ј
RD05 Series External keyboard pocket shape and opening size
AC300П µ
Б Р
Н в
Т э
ј ь
Е М
¶ µ
Ј Ё
0.75KW-37KWЈ ©
Н в
Р О
ј °
ї Є
ї Ч
і Я
ґ з
Н ј
8
RD11 Series Frequency converter Manual
Standard Connection Diagram
External Brake Unit
R External DC Reactor
External External DC Rector
Brake
Resistor Short Note1
Piece
MCCB Contactor Intput Reactor
Input Rector Output
OutputReactor
Rector
AC POWER INPUT
Passive contact
TA 3A/240VAC
(Forward) X1 Coil 5A/30VDC
output
TB
(Reverse) X2
Multi function contact input
TC
(FWD JOG) X3
AC0V
(REV JOG) X4
+24V
Open collector(OC)
(Free STOP) X5 Shielded cable
Coil
Y (the end close
state output
PUL
to VFD grounding)
COM
COM
A+ Note:
RS485 Differential 120¦ ё 1.MAX Output of +24V Port:DC24V/100mA
Communication 2.Max Output of Y Port :DC24V/50mA
B-
20
0
Analog monitoring
Analog Voltage/Current quantity input
signal output
AI1 + -
Analog Voltage/Current quantity input Shielded cable (the
AI2 A0
GND end close to VFD
grounding)
GND
Note: 1.MAX Output of +10V port :50mA
Note:When output type of AO port as
2.Inner resistance of AI1/AI2 Port frequency and Voltage,
Maximum Output:2mA
Legend: 1.Symbol represent main circuit terminals;
2.Symbol represent control circuit terminals.
Note: 1. When installing the DC reactor, be sure to remove the shorting tab between the P1 and (+) terminals.
2. The terminal (X1~X5/PUL) can select the NPN or PNP transistor signal as the input, and the bias voltage can select the internal power
supply (+24V terminal) or external power supply (PLC terminal) of the inverter.
9
RD11 Series Frequency converter Manual
● Function Specification of Switch Terminals
10
RD11 Series Frequency converter Manual
●Key function
Enter the function menu interface during standby or running; press this button
C to exit the modification when the parameter is modified; press the button (1
second) during standby or running to enter the status interface directly.
Confirmation function: After modifying the value, press this key to confirm the
D modification value.
Shift function: long press this button (1 second) to move the operation bit, long
press is not loose, then cyclic shift
E The up key increases the operation value, and the down key decreases the
operation value.
When the run/stop is controlled by the keyboard, press this button to turn the
inverter forward. The status indicator is always on during forward run, and the
status indicator is blinking during reverse run.
F
When the command given channel is keyboard control, press this key to stop
the inverter; the parameter F11.03 [keyboard stop key setting] can be used to
define whether other command channels are valid; when the fault state is
pressed, the inverter resets.
Digital potentiometer: Use clockwise rotation as the upper key to increase the
operation value, counterclockwise rotation as the lower key to reduce the
G operation value.
Confirmation key: After modifying the value, press this key to confirm the
modified value.
11
RD11 Series Frequency converter Manual
The following is an example of setting F01.22 [acceleration time] = 10.00s to explain the basic operation of the LED operator.
PRG short press Up
PRG短按 上键
PRG短按 下键
PRG short press Down
PRG short
PRG短按 press SET
Down
下键 Up
上键
Up
上键 SET
下键 SET
Down
SET
Note: When modifying the ten, hundred and thousand digits of the parameter value, use the keyboard shift key function to quickly select.
● Run monitoring status view
SET SET
SET
Output frequency
输出频率 Output voltage
输出电流
Note: When using the external keyboard, use the left shift button to cycle through the first line of monitoring parameters, and use the right shift button to cycle through the
second line of monitoring parameters.
● Monitoring parameter view
The following is an example to illustrate the basic operation of the LED operator at at C02.05 [PLC Operation Phase
PRG long press
PRG长按 Up
上键
PRG短按 下键
Down
PRG short
PRG短按 press SET
Up
上键
SET
下键
SET Down
12
RD11 Series Frequency converter Manual
Icon Description
V/F Effective parameters in asynchronous motor V/F control mode
SVC Effective parameters of asynchronous motor open loop vector control
FVC Effective parameters of closed-loop vector control of asynchronous motor
PMVF Effective parameters in synchronous motor V/F control mode
PMSVC Effective parameters of synchronous motor open loop vector control mode
PMFVC Effective parameters of synchronous motor closed-loop vector control mode
Note: The control mode icon has no shadow to indicate that the parameter is invalid in this control mode.
Icons and terms that represent control modes
Icon Description
RUN Parameters that can be modified during operation
STOP Parameters that cannot be modified during operation
READ This parameter can only be read and cannot be modified (the LED shows 5 "-" when modified)
13
RD11 Series Frequency converter Manual
4.3 Environment application
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
V/F SVC FVC PMVF PMSVC PMFVC
Set the parameter access level based on the case of restricted
parameter access.
F00.00 Parameter access 0
0: standard parameter (Fxx.yy) RUN
(0x0000) level (0 ~ 3)
1: Common parameters (F00.00, Pxx.yy)
2: Monitoring parameters (F00.00, Cxx.yy)
3: Changed parameter(F00.00, Hxx.yy)
V/F SVC FVC PMVF PMSVC PMFVC
Set the inverter initialization method.
0: not initialized
F00.03 0
Initialization 11: Select the set value according to the purpose to perform the STOP
(0x0003) (0 ~ 33)
parameter (excluding the motor parameter)
22: All parameters are initialized
33: Clear the fault record
V/F SVC FVC PMVF PMSVC PMFVC
F00.04 Keyboard parameter 0: no function 0
STOP
(0x0004) copy 1: Upload parameters to the keyboard (0 ~ 9999)
2: Download parameters to the inverter
F00.05 V/F SVC FVC PMVF PMSVC PMFVC 0
User password STOP
(0x0005) Used to set the user password. (0 ~ 65355)
V/F SVC FVC PMVF PMSVC PMFVC
F00.06 LCD keyboard 0
Select the language displayed on the LCD operator. RUN
(0x0006) language selection (0 ~ 1)
0: Chinese 1: English
F00.07 V/F SVC FVC PMVF PMSVC PMFVC 0
Free parameter 1 When using multiple machines, use the machine number or usage RUN
(0x0007) (0 ~ 65535)
mode number.
V/F SVC FVC PMVF PMSVC PMFVC
F00.08 0
Free parameter 2 When using multiple machines, use the machine number or usage RUN
(0x0008) (0 ~ 65535)
mode number.
V/F SVC FVC PMVF PMSVC PMFVC
F00.10~F00.3
“0~00” digits: yy setting in function parameter number Fxx.yy
9 Common parameter 0102
00~99 RUN
(0x0010 ~ address setting (0000 ~ 3199)
“000~0000”digits: xx setting in function parameter number Fxx.yy
0x0027)
00~31
F01.0x:Basic command
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
V/F SVC FVC PMVF PMSVC PMFVC
The control mode of the motor.
Asynchronous motor control mode:
0: AM-VF; VF control
F01.00 1:AM-SVC; open loop vector control, current closed loop control 0
Motor control STOP
(0x0100) 2: AM-FVC; closed loop vector control (0 ~ 12)
Synchronous motor control mode:
10: PM-VF; VF control
11: PM-SVC; open loop vector control
12: PM-FVC; closed loop vector control
V/F SVC FVC PMVF PMSVC PMFVC
Used to select the channel that the drive accepts the run and stop
F01.01 Run command 0
commands and the direction of travel. RUN
(0x0101) channel (0 ~ 3)
0: keyboard control (external keyboard priority) 1: terminal control
2: RS485 communication control 3: Option card
V/F SVC FVC PMVF PMSVC PMFVC
The given source channel B of the frequency converter
F01.02 Frequency given 0
0: keyboard digital reference frequency 1: keyboard analog RUN
(0x0102) channel A (0 ~ 11)
potentiometer given
2: Current/voltage analog AI1 given
14
RD11 Series Frequency converter Manual
3: Current/voltage analog AI2 given
4: Reserved 5: Terminal pulse PUL given
6: RS485 communication reference 7: Terminal UP/DW control
8: PID control given 9: Program control (PLC) given
10: Optional card 11: Multi-speed speed given
F01.03 Frequency reference V/F SVC FVC PMVF PMSVC PMFVC 100.0
STOP
(0x0103) source channel A gain Frequency reference source channel A gain (0.0 ~ 500.0%)
V/F SVC FVC PMVF PMSVC PMFVC 2
F01.04 Frequency given
The given source channel B of the frequency converter same RUN
(0x0104) channel B (0 ~ 11)
as[F01.02]
F01.05 Frequency reference V/F SVC FVC PMVF PMSVC PMFVC 100.0
STOP
(0x0105) source channel B gain Frequency reference source channel B gain (0.0 ~ 500.0%)
V/F SVC FVC PMVF PMSVC PMFVC
The reference source of frequency given channel B is selected by
F01.06 Frequency channel B 0
this parameter. RUN
(0x0106) reference source (0 ~ 1)
0: reference source with maximum output frequency
1: Use channel A to set the frequency as the reference source
V/F SVC FVC PMVF PMSVC PMFVC
It is used to select the combination mode of the inverter setting
frequency channel A and channel B.
F01.07 Frequency reference 0
0: channel A 1: channel B RUN
(0x0107) source selection (0 ~ 5)
2: Channel A + Channel B. 3: Channel A-channel B
4: Maximum value of channel A and channel B
5: the minimum of channel A and channel B
V/F SVC FVC PMVF PMSVC PMFVC
When this parameter is valid, it is used to set the channel source
frequency channel for each running command channel.
Units: Bundled with Keyboard command Ten
digits: Bundled with Terminal command Hundreds: Bundled
with communication command Thousands: Bundled with optional
Run command card command 0000
F01.08
bundled given 0: no binding 1: keyboard digital given frequency RUN
(0x0108) (0000 ~ DDDD)
frequency 2: Keyboard analog potentiometer given 3: current / voltage analog
AI1 given
4: Current/voltage analog AI2 given 5: Reserved
6: Terminal pulse PUL reference 7: Communication given
8: Terminal UP/DW control 9: PID control given
A: Program control given B: Option card
C: multi-speed reference D: reserved
50Hz
F01.09 Keyboard digital given V/F SVC FVC PMVF PMSVC PMFVC (0.00~upper limit RUN
(0x0109) frequency Used to set and modify the keyboard digital setting frequency.
frequency)
F01.1x:Frequency Command
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
50.00Hz
F01.10 V/F SVC FVC PMVF PMSVC PMFVC (Upper limit
Maximum frequency STOP
(0x010A) The maximum frequency that the frequency converter can set. frequency~
600.00Hz)
V/F SVC FVC PMVF PMSVC PMFVC
Select a given source for the upper limit frequency of the converter.
0: upper limit frequency digital reference 1: keyboard analog
F01.11 Upper frequency potentiometer given 0
RUN
(0x010B) source selection 2: Current/voltage analog AI1 given (0~7)
3: Current/voltage analog AI2 given
4: Reserved 5: Terminal pulse PUL given
6: RS485 communication reference 7: Option card
50.00Hz
F01.12 Upper limit frequency V/F SVC FVC PMVF PMSVC PMFVC (0~Max RUN
(0x010C) digital setting Upper limit frequency given channel when F01.11 is set to 0
frequency)
0.00Hz
F01.13 V/F SVC FVC PMVF PMSVC PMFVC (0~Upper limit
Lower limit frequency RUN
(0x010D) Given a lower frequency limit, the given frequency is limited.
frequency)
15
RD11 Series Frequency converter Manual
F01.2x-F01.3x: Acceleration and deceleration Time
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
V/F SVC FVC PMVF PMSVC PMFVC
F01.20 Acceleration/decelerati Set the reference frequency to calculate the 0
STOP
(0x0114) on time reference acceleration/deceleration time. (0 ~ 2)
0: Maximum frequency 1: Fixed frequency 50Hz 2: Set frequency
V/F SVC FVC PMVF PMSVC PMFVC 2
F01.21
Acceleration time unit The unit of acceleration time setting. STOP
(0x0115) (0 ~ 2)
0:1s 1:0.1s 2:0.01s
V/F SVC FVC PMVF PMSVC PMFVC
The time required for the output frequency to accelerate from 0.00 Hz
F01.22 to the reference frequency. Model related(0.01
Acceleration time 1 1~65000s(F01.21 = 0) RUN
(0x0116) ~ 650.00s)
0.1~6500.0s(F01.21 = 1)
0.01~650.00s(F01.21 = 2)
V/F SVC FVC PMVF PMSVC PMFVC
F01.23 Model related
Deceleration time 1 Time required for the output frequency to decelerate from the RUN
(0x0117) (0.01~650.00s)
reference frequency to 0.00 Hz.
V/F SVC FVC PMVF PMSVC PMFVC
F01.24 Model related
Acceleration time 2 Time required for the output frequency to accelerate from 0.00Hz to RUN
(0x0118) (0.01~650.00s)
the reference frequency
V/F SVC FVC PMVF PMSVC PMFVC
F01.25 Model related
Deceleration time 2 Time required for the output frequency to decelerate from the RUN
(0x0119) (0.01~650.00s)
reference frequency to 0.00 Hz.
V/F SVC FVC PMVF PMSVC PMFVC
F01.26 Model related
Acceleration time 3 Time required for the output frequency to accelerate from 0.00Hz to RUN
(0x011A) (0.01~650.00s)
the reference frequency
F01.27 V/F SVC FVC PMVF PMSVC PMFVC Model related
Deceleration time 3 Time required for the output frequency to decelerate from the RUN
(0x011B) (0.01~650.00s)
reference frequency to 0.00 Hz.
V/F SVC FVC PMVF PMSVC PMFVC Model related
F01.28
Acceleration time 4 Time required for the output frequency to accelerate from 0.00Hz to RUN
(0x011C) (0.01~650.00s)
the reference frequency
V/F SVC FVC PMVF PMSVC PMFVC
F01.29 Model related
Deceleration time 4 Time required for the output frequency to decelerate from the RUN
(0x011D) (0.01~650.00s)
reference frequency to 0.00 Hz.
S curve acceleration V/F SVC FVC PMVF PMSVC PMFVC
F01.30 1
and deceleration S curve acceleration and deceleration selection is valid or invalid STOP
(0x011E) (0~1)
selection 0:invalid 1:valid
F01.31 S curve acceleration V/F SVC FVC PMVF PMSVC PMFVC 0.20s
STOP
(0x011F) start time Set the S curve acceleration start time. (0.00~10.00)
F01.32 S curve acceleration V/F SVC FVC PMVF PMSVC PMFVC 0.20s
STOP
(0x0120) end time Set the S curve acceleration end time (0.00~10.00)
F01.33 S curve deceleration V/F SVC FVC PMVF PMSVC PMFVC 0.20s
STOP
(0x0121) start time Set the S curve deceleration start time. (0.00~10.00)
F01.34 S curve deceleration V/F SVC FVC PMVF PMSVC PMFVC 0.20s
STOP
(0x0122) end time Set the S curve deceleration end time (0.00~10.00)
Switching frequency 0.00Hz
F01.35 between acceleration V/F SVC FVC PMVF PMSVC PMFVC (0.00~Max RUN
(0x0123) time 1 and acceleration Set the frequency switch between Acc time 1 and Acc time 2
frequency)
time 2
F01.4x:PWM Controlling
16
RD11 Series Frequency converter Manual
F01.43 Dead zone V/F SVC FVC PMVF PMSVC PMFVC 306
RUN
(0x012B) compensation gain Dead zone compensation gain (0 ~ 512)
F02.10 Asynchronous motor V/F SVC FVC PMVF PMSVC PMFVC Model related (0.1~
STOP
(0x020A) no-load current Set the size of the no-load current of the asynchronous motor. 3000.0A)
Model related
F02.11 Asynchronous motor V/F SVC FVC PMVF PMSVC PMFVC
(0.01mΩ ~ STOP
(0x020B) stator resistance Set the size of the asynchronous motor stator resistance.
60000mΩ)
Model related
F02.12 Asynchronous motor V/F SVC FVC PMVF PMSVC PMFVC
(0.01mΩ ~ STOP
(0x020C) rotor resistance Set the size of the asynchronous motor rotor resistance.
60000mΩ)
Asynchronous motor Model related
F02.13 V/F SVC FVC PMVF PMSVC PMFVC (0.01mH ~
stator leakage STOP
(0x020D) Set the stator leakage inductance of the asynchronous motor.
inductance 65535mH)
17
RD11 Series Frequency converter Manual
Model related
F02.14 Asynchronous motor V/F SVC FVC PMVF PMSVC PMFVC (0.01mH ~ STOP
(0x020E) stator inductance Set the stator inductance of the asynchronous motor.
65535mH)
Model related
F02.15 Stator resistance V/F SVC FVC PMVF PMSVC PMFVC (0.01 ~ READ
(0x020F) standard value Set the stator resistance value.
50.00%)
F02.16 Rotor resistance V/F SVC FVC PMVF PMSVC PMFVC Model related
READ
(0x0210) standard value Set the rotor resistance value. (0.01~50.00%)
F02.17 Stator leakage V/F SVC FVC PMVF PMSVC PMFVC Model related
READ
(0x0211) inductance Set the stator leakage inductance value。 (0.01~50.00%)
Model related
F02.18 Stator inductance V/F SVC FVC PMVF PMSVC PMFVC (0.1 ~ READ
(0x0212) value Set the stator inductance value
999.0%)
18
RD11 Series Frequency converter Manual
F02.36 Encoder gear ratio V/F SVC FVC PMVF PMSVC PMFVC 1
RUN
(0x0224) denominator Set the encoder driven ratio denominator. (1 ~ 32767)
Encoder speed
F02.37 V/F SVC FVC PMVF PMSVC PMFVC 1.0ms
measurement filter RUN
(0x0225) Set the encoder speed measurement filter time (0.0~ 100.0ms)
time
0.500s
F02.38 Encoder disconnection V/F SVC FVC PMVF PMSVC PMFVC (0.100~ RUN
(0x0226) detection time Set the encoder disconnection detection time.
60.000s)
F03.0x:Speed loop
F03.07 ASR (speed loop) V/F SVC FVC PMVF PMSVC PMFVC 0.100s
RUN
(0x0307) integration time 2 Set the ASR (speed loop) integration time 2. (0.000~6.000s)
F03.08 V/F SVC FVC PMVF PMSVC PMFVC 0.0ms
ASR filtering time 2 RUN
(0x0308) Set the ASR filter time 2. (0.0~100.0ms)
F03.09 ASR switching V/F SVC FVC PMVF PMSVC PMFVC 0.00Hz
RUN
(0x0309) frequency 2 Set the ASR switching frequency 2. (0.00~Max)
19
RD11 Series Frequency converter Manual
F03.11
Current loop D-axis V/F SVC FVC PMVF PMSVC PMFVC 1.00
(0x030B) RUN
integral gain Set the current loop D-axis integral gain (0.001 ~ 4.000)
RUN
F03.12 Current loop Q-axis V/F SVC FVC PMVF PMSVC PMFVC 1.00
RUN
(0x030C) proportional gain Set the current loop Q-axis proportional gain (0.001 ~ 4.000)
F03.13 Current loop Q-axis V/F SVC FVC PMVF PMSVC PMFVC 1.00
RUN
(0x030D) integral gain Set the current loop Q-axis integral gain (0.001 ~ 4.000)
F03.15 Electric state torque V/F SVC FVC PMVF PMSVC PMFVC 250.0%
RUN
(0x030E) limit Set the motor state torque limit. (0.0~400.0%)
F03.16 Power generation V/F SVC FVC PMVF PMSVC PMFVC 250.0%
RUN
(0x030F) torque limit Set the power generation torque limit (0.0~400.0%)
F03.17 Regenerative torque V/F SVC FVC PMVF PMSVC PMFVC 0.0%
RUN
(0x0312) limit at low speed Set the regenerative torque limit at low speed (0.0~400.0%)
Torque limit action
F03.18 V/F SVC FVC PMVF PMSVC PMFVC 6.00s
frequency amplitude at RUN
(0x0313) Set the torque limit action frequency amplitude at low speed (0.00~30.00s)
low speed
F03.24 Starting torque initial V/F SVC FVC PMVF PMSVC PMFVC 0.0%
RUN
(0x0318) value Set the initial value of the starting torque (0.0 ~ 250.0%)
20
RD11 Series Frequency converter Manual
21
RD11 Series Frequency converter Manual
V/F SVC FVC PMVF PMSVC PMFVC
High frequency
F03.62 The frequency range of the high frequency injection is relatively 10.0%
injection cutoff RUN
(0x033E) high, and the high frequency injection is effective when the motor (0.0 ~ 100.0%)
frequency
speed is less than this value.
V/F SVC FVC PMVF PMSVC PMFVC
F03.70 Position compensation 0.0
Position compensation control under speed control for zero servo RUN
(0x0346) control (0 ~ 250.0)
or increased system rigidity
F03.71 V/F SVC FVC PMVF PMSVC PMFVC 1.0
Compensation gain RUN
(0x0347) Set compensation gain (0.0 ~ 100.0)
F03.72 Compensation V/F SVC FVC PMVF PMSVC PMFVC 0.0%
STOP
(0x0348) amplitude limit Set the compensation amplitude limit value. (0.0 ~ 100.0%)
F03.73 V/F SVC FVC PMVF PMSVC PMFVC 10.0%
Compensation range STOP
(0x0349) Set the compensation range. (0.0 ~ 100.0%)
F03.80 Synchronous motor V/F SVC FVC PMVF PMSVC PMFVC 100.0%
RUN
(0x0350) MTPA gain Set the synchronous motor MTPA gain. (0.0 ~ 400.0%)
F03.81 Synchronous motor V/F SVC FVC PMVF PMSVC PMFV 1.0ms
RUN
(0x0351) MTPA filter time Set the MTPA filter time of the synchronous motor. (0.0 ~ 100.0ms)
F04.0x:V/F Controlling
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
V/F SVC FVC PMVF PMSVC PMFVC
Used to select the type of V/F curve to meet different load
F04.00 Linear VF curve 0
characteristics. STOP
(0x0400) selection (0 ~ 11)
0: straight VF curve; 1-9: respectively, a power curve of 1.1-1.9 VF;
10: square VF curve; 11: customize VF curve;
F04.08 Output voltage V/F SVC FVC PMVF PMSVC PMFVC 100.0%s
STOP
(0x0408) percentage Set the output voltage percentage (25.0~120.0%)
22
RD11 Series Frequency converter Manual
F04.11 V/F SVC FVC PMVF PMSVC PMFVC 1.00Hz
Self-set frequency F1 STOP
(0x040B) Self-set frequency F1 (0.00~Max)
F04.12 V/F SVC FVC PMVF PMSVC PMFVC 28.0%
Self-setting voltage V2 STOP
(0x040C) Self-setting voltage V2 (0.0 ~ 100.0%)
F04.13 V/F SVC FVC PMVF PMSVC PMFVC 10.0Hz
Self-set frequency F2 STOP
(0x040D) Self-set frequency F2 (0.00~ Max)
F04.14 V/F SVC FVC PMVF PMSVC PMFVC 55.0%
Self-setting voltage V3 STOP
(0x040E) Self-setting voltage V3 (0.0 ~ 100.0%)
F04.15 V/F SVC FVC PMVF PMSVC PMFVC 25.00Hz
Self-set frequency F3 STOP
(0x040F) Self-set frequency F3 (0.00~ Max)
F04.16 V/F SVC FVC PMVF PMSVC PMFVC 78.0%
Self-setting voltage V4 STOP
(0x0410) Self-setting voltage V4 (0.0 ~ 900.0%)
F04.17 V/F SVC FVC PMVF PMSVC PMFVC 37.5Hz
Self-set frequency F4 STOP
(0x0411) Self-set frequency F4 (0.00~ Max)
F04.18 V/F SVC FVC PMVF PMSVC PMFVC 100.0%s
Self-setting voltage V5 STOP
(0x0412) Self-setting voltage V5 (0.0~100.0%)
F04.19 V/F SVC FVC PMVF PMSVC PMFVC 50.0Hz
Self-set frequency F5 STOP
(0x0413) Self-set frequency F5 (0.00~ Max)
F04.2x:Reserved
23
RD11 Series Frequency converter Manual
F05.07 Terminal X8 function V/F SVC FVC PMVF PMSVC PMFVC 0
selection STOP
(0x0507) See the function of the terminal for details. (0 ~ 95)
F05.08 Terminal X9 function V/F SVC FVC PMVF PMSVC PMFVC 0
selection STOP
(0x0508) See the function of the terminal for details. (0 ~ 95)
F05.09 Terminal X10 function V/F SVC FVC PMVF PMSVC PMFVC 0
selection STOP
(0x0509) See the function of the terminal for details. (0 ~ 95)
F05.1x:Detection Delay
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
V/F SVC FVC PMVF PMSVC PMFVC
F05.10 X1 effective detection 0.010
The delay time corresponding to the input terminal X1 transit from the RUN
(0x050A) delay (0.000 ~ 6.000s)
inactive state to the active state
V/F SVC FVC PMVF PMSVC PMFVC
F05.11 X1 invalid detection 0.010
The delay time corresponding to the input terminal X1 transit from the RUN
(0x050B) delay (0.000 ~ 6.000s)
active state to the inactive state
V/F SVC FVC PMVF PMSVC PMFVC
F05.12 X2 effective detection 0.010
The delay time corresponding to the input terminal X2 transit from the RUN
(0x050C) delay (0.000 ~ 6.000s)
inactive state to the active state
V/F SVC FVC PMVF PMSVC PMFVC
F05.13 X2 invalid detection 0.010
The delay time corresponding to the input terminal X2 transit from the RUN
(0x050D) delay (0.000 ~ 6.000s)
active state to the inactive state
V/F SVC FVC PMVF PMSVC PMFVC
F05.14 X3 effective detection 0.010
The delay time corresponding to the input terminal X3 transit from the RUN
(0x050E) delay (0.000 ~ 6.000s)
inactive state to the active state
V/F SVC FVC PMVF PMSVC PMFVC
F05.15 X3 invalid detection 0.010
The delay time corresponding to the input terminal X3 transit from the RUN
(0x050F) delay (0.000 ~ 6.000s)
active state to the inactive state
V/F SVC FVC PMVF PMSVC PMFVC
F05.16 X4 effective detection 0.010
The delay time corresponding to the input terminal X4 transit from the RUN
(0x0510) delay (0.000 ~ 6.000s)
inactive state to the active state
V/F SVC FVC PMVF PMSVC PMFVC
F05.17 X4 invalid detection 0.010
The delay time corresponding to the input terminal X4 transit from the RUN
(0x0511) delay (0.000 ~ 6.000s)
active state to the inactive state
V/F SVC FVC PMVF PMSVC PMFVC
F05.18 X5 effective detection 0.010
The delay time corresponding to the input terminal X5 transit from the RUN
(0x0512) delay (0.000 ~ 6.000s)
inactive state to the active state
V/F SVC FVC PMVF PMSVC PMFVC
F05.19 X5 invalid detection 0.010
The delay time corresponding to the input terminal X5 transit from the RUN
(0x0513) delay (0.000 ~ 6.000s)
active state to the inactive state
24
RD11 Series Frequency converter Manual
Terminal UP/DW
V/F SVC FVC PMVF PMSVC PMFVC
F05.26 controls frequency 0.50Hz/s
Set terminal UP/DW to control the frequency increase and decrease RUN
(0x051A) increase and decrease (0.01~50.00Hz/s)
rate
rate
F05.27 Terminal emergency V/F SVC FVC PMVF PMSVC PMFVC 1.00s
RUN
(0x051B) stop deceleration time Set terminal emergency stop deceleration time (0.01~650.00s)
F05.51 AI1 lower limit V/F SVC FVC PMVF PMSVC PMFVC 0.00%
RUN
(0x0533) corresponding setting Set the percentage of the corresponding set value (-100.00~100.00%)
F05.53 AI1 upper limit V/F SVC FVC PMVF PMSVC PMFVC 100.00%
RUN
(0x0535) corresponding setting Set the percentage of the corresponding set value (-100.00~100.00%)
V/F SVC FVC PMVF PMSVC PMFVC 0.010s
F05.54
AI1 filtering time Define the size of the analog signal to be used to eliminate interfering RUN
(0x0536) (0.000~6.000s)
signals.
25
RD11 Series Frequency converter Manual
V/F SVC FVC PMVF PMSVC PMFVC
F05.55 0.0%
AI2 lower limit Define the signal received by the AI2 terminal,The voltage signal RUN
(0x0537) (0.00~100.0%)
below this value is processed by the limit value.
F05.56 AI2 lower limit V/F SVC F VC PMVF PMSVC PMFVC 0.00%
RUN
(0x0538) corresponding setting Set the percentage of the corresponding set value (-100.00~100.00%)
V/F SVC FVC PMVF PMSVC PMFVC
F05.57 100.0%
AI2 upper limit Define the signal received by the AI2 terminal. The voltage signal RUN
(0x0539) (0.0~100.0%)
higher than this value is processed according to the upper limit value.
F05.58 AI2 upper limit V/F SVC FVC PMVF PMSVC PMFVC 100.00%
RUN
(0x053A) corresponding setting Set the percentage of the corresponding set value (-100.00~100.00%)
V/F SVC FVC PMVF PMSVC PMFVC
F05.59 0.010s
AI2 filter time Define the size of the analog signal to be used to eliminate interfering RUN
(0x053B) (0.000~6.000s)
signals.
F05.60 V/F SVC FVC PMVF PMSVC PMFVC 0.0%
Curve 1 lower limit RUN
(0x053C) Set the lower limit of curve 1 (0.0 ~ 100.0%)
F05.61 Curve 1 lower limit V/F SVC FVC PMVF PMSVC PMFVC 0.00%
RUN
(0x053D) corresponding setting Set the corresponding percentage (0.00 ~ 100.00%)
F05.62 Curve 1 inflection point V/F SVC FVC PMVF PMSVC PMFVC 30.0%
RUN
(0x053E) 1 input voltage Set curve 1 inflection point 1 input voltage (0.0 ~ 100.0%)
F05.63 Curve 1 inflection point V/F SVC FVC PMVF PMSVC PMFVC 30.00%
RUN
(0x053F) 1 corresponding setting Set the corresponding percentage (0.00~100.00%)
F05.64 Curve 1 inflection point V/F SVC FVC PMVF PMSVC PMFVC 60.0%
RUN
(0x0540) 2 input voltage Set curve 1 inflection point 2 input voltage (0.0 ~ 100.0%)
F05.65 Curve 1 inflection point V/F SVC FVC PMVF PMSVC PMFVC 60.00%
RUN
(0x0541) 2 corresponding setting Set the corresponding percentage (0.00~100.00%)
F05.66 V/F SVC FVC PMVF PMSVC PMFVC 100.0%
Curve 1 upper limit RUN
(0x0542) Set the upper limit of curve 1 (0.0~100.0%)
F05.67 Curve 1 upper limit V/F SVC FVC PMVF PMSVC PMFVC 100.00%
RUN
(0x0543) corresponding setting Set the corresponding percentage (0.00 ~ 100.00%)
F05.71 Curve 2 lower limit V/F SVC FVC PMVF PMSVC PMFVC 0.00%
RUN
(0x0547) corresponding setting Set the corresponding percentage (0.00 ~ 100.00%)
F05.72 Curve 2 inflection point V/F SVC FVC PMVF PMSVC PMFVC 30.0%
RUN
(0x0548) 1 input voltage Set curve 2 inflection point 1 input voltage (0.0 ~ 100.0%)
F05.73 Curve 2 inflection point V/F SVC FVC PMVF PMSVC PMFVC 30.00%
RUN
(0x0549) 1 corresponding setting Set the corresponding percentage (0.00~100.00%)
F05.74 Curve 2 inflection point V/F SVC FVC PMVF PMSVC PMFVC 60.0%
RUN
(0x054A) 2 input voltage Set curve 2 inflection point 1 input voltage (0.0 ~ 100.0%)
F05.75 Curve 2 inflection point V/F SVC FVC PMVF PMSVC PMFVC 60.00%
RUN
(0x054B) 2 corresponding setting Set the corresponding percentage (0.00~100.00%)
F05.76 V/F SVC FVC PMVF PMSVC PMFVC 100.0%
Curve 2 upper limit RUN
(0x054C) Set the upper limit of curve 2 (0.00~100.0%)
F05.77 Curve 2 upper limit V/F SVC FVC PMVF PMSVC PMFVC 100.00%
RUN
(0x054D) corresponding setting Set the corresponding percentage (0.00 ~ 100.00%)
V/F SVC FVC PMVF PMSVC PMFVC
F05.80 AI terminal for digital 0:valid at low level 1:valid at high level 0000
RUN
(0x0550) input (0000 ~ 1111)
Unit:AI1 Tens:AI2
F05.81 Terminal characteristics V/F SVC FVC PMVF PMSVC PMFVC 0
STOP
(0x0551) selection See the function of the terminal for details. (0~63)
AI terminal function V/F SVC FVC PMVF PMSVC PMFVC
F05.82 70.00%
selection (as X The input setting is higher than the high level setting, which is the RUN
(0x0552) (0.00~100.00%)
terminal) input high level.
F05.83 V/F SVC FVC PMVF PMSVC PMFVC 30.00%
AI high level setting RUN
(0x0553) Less than the low level setting is low level. (0.00~100.00%)
F06.1x: AO Extension
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
V/F SVC FVC PMVF PMSVC PMFVC
F06.10 Extended AO output 0:0~10V 1:4.00~20.00mA 0
RUN
(0x060A) mode selection (0 ~ 3)
2:0.00~20.00mA 3:FM frequency pulse output
V/F SVC FVC PMVF PMSVC PMFVC
F06.11 Extended AO output 1
Corresponding to the extended AO output selection, the same as the RUN
(0x060B) selection (0 ~ 19)
F06.01 selection
F06.12 Extended AO output V/F SVC FVC PMVF PMSVC PMFVC 100.0%
RUN
(0x060C) gain Adjust the value of the analog output of the terminal. (0.0 ~ 200.0%)
F06.13 Extended AO output V/F SVC FVC PMVF PMSVC PMFVC 0.0%
RUN
(0x060D) offset Set the A0 output offset to adjust the zero point of the terminal output. (-10.0~10.0%)
F06.14 Extended AO output V/F SVC FVC PMVF PMSVC PMFVC 0.01s
RUN
(0x060E) filtering The size of the analog signal is filtered to eliminate interfering signals. (0.0 ~ 6.00s)
27
RD11 Series Frequency converter Manual
F06.29 Y output OFF delay V/F SVC FVC PMVF PMSVC PMFVC 0.010s
RUN
(0x061D) time Set the Y output OFF delay time. (0.000~60.000s)
F06.30 Relay 1 output OFF V/F SVC FVC PMVF PMSVC PMFVC 0.010s
RUN
(0x061E) delay time Set relay 1 output OFF delay time. (0.000~60.000s)
F06.31 Extended Y1 output V/F SVC FVC PMVF PMSVC PMFVC 0.010s
RUN
(0x061F) OFF delay time Set the extended Y1 output OFF delay time (0.000~60.000s)
F06.32 Extended relay 2 V/F SVC FVC PMVF PMSVC PMFVC 0.010s
RUN
(0x0620) output OFF delay time Set the extended relay 2 output OFF delay time. (0.000~60.000s)
F06.51 Comparator 1 upper V/F SVC FVC PMVF PMSVC PMFVC 3000
RUN
(0x0633) limit Set the upper limit of comparator 1 (0 ~ 65535)
F06.52 Comparator 1 lower V/F SVC FVC PMVF PMSVC PMFVC 0
RUN
(0x0634) limit Set the lower limit of comparator 1 (0 ~ 65535)
F06.53 V/F SVC FVC PMVF PMSVC PMFVC 0
Comparator 1 bias RUN
(0x0635) Set the comparator 1 offset value (0 ~ 1000)
V/F SVC FVC PMVF PMSVC PMFVC
F06.54 Action selection when 0:Continue running(digital terminal output only); 0
RUN
(0x0636) sending CP1 1:Warning and free stop;2:Warning and continue running; (0 ~ 3)
3:Forced stop
V/F SVC FVC PMVF PMSVC PMFVC
F06.55 Comparator 2 monitor Units and Tens digits: Set yy value of the Cxx.yy 00~63 0002
RUN
(0x0637) selection (0000 ~ 0763)
Hundreds and thousands: Set xx value of the Cxx.yy 00~07
F06.56 Comparator 2 upper V/F SVC FVC PMVF PMSVC PMFVC 30
RUN
(0x0638) limit Set the upper limit of comparator 2 (0 ~ 65535)
F06.57 Comparator 2 lower V/F SVC FVC PMVF PMSVC PMFVC 0
RUN
(0x0639) limit Set the lower limit of comparator 2 (0 ~ 65535)
F06.58 V/F SVC FVC PMVF PMSVC PMFVC 0
Comparator 2 bias RUN
(0x063A) Set the comparator 2 offset value (0 ~ 1000)
V/F SVC FVC PMVF PMSVC PMFVC
F06.59 Action selection when 0: Continue running (digital terminal output only) 0
RUN
(0x063B) sending CP2 1: Warning and free stop 2: Warning and continue to run 3: Forced (0 ~ 3)
stop
28
RD11 Series Frequency converter Manual
F06.6x:Virtual Input and Output Terminal
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
F06.60 Virtual vX1 terminal V/F SVC FVC PMVF PMSVC PMFVC 0
RUN
(0x063C) function selection See terminal X function (0 ~ 63)
F06.61
Virtual vX2 terminal V/F SVC FVC PMVF PMSVC PMFVC 0
(0x063D) RUN
function selection See terminal X function (0 ~ 63)
RUN
F06.62 Virtual vX3 terminal V/F SVC FVC PMVF PMSVC PMFVC 0
RUN
(0x063E) function selection See terminal X function (0 ~ 63)
F06.63 Virtual vX4 terminal V/F SVC FVC PMVF PMSVC PMFVC 0
RUN
(0x063F) function selection See terminal X function (0 ~ 63)
V/F SVC FVC PMVF PMSVC PMFVC
0: Internal connection with virtual vYn 1: Link with physical terminal
F06.64 vX terminal valid status Xn 0000
RUN
(0x0640) source 2:whether the function code setting is valid? (0000 ~ 2222)
Unit: Virtual vX1 Ten: Virtual vX2
Hundreds place: virtual vX3 thousand: virtual vX4
V/F SVC FVC PMVF PMSVC PMFVC
Virtual vX terminal
F06.65 0: invalid; 1: valid 0000
function code setting RUN
(0x0641) Unit: Virtual vX1 Ten: Virtual vX2 (0000 ~ 1111)
valid status
Hundreds place: virtual vX3 thousand: virtual vX4
F06.66 Virtual vY1 output V/F SVC FVC PMVF PMSVC PMFVC 0
RUN
(0x0642) selection See Y terminal function for details. (0~31)
F06.67 Virtual vY2 output V/F SVC FVC PMVF PMSVC PMFVC 0
RUN
(0x0643) selection See Y terminal function for details. (0~31)
F06.68 Virtual vY3 output V/F SVC FVC PMVF PMSVC PMFVC 0
RUN
(0x0644) selection See Y terminal function for details. (0~31)
F06.69 Virtual vY4 output V/F SVC FVC PMVF PMSVC PMFVC 0
RUN
(0x0645) selection See Y terminal function for details. (0~31)
F06.70 vY1 output ON delay V/F SVC FVC PMVF PMSVC PMFVC 0.010s
RUN
(0x0646) time Set vY1 output ON delay time (0.000~60.000s)
F06.71 vY2 output ON delay V/F SVC FVC PMVF PMSVC PMFVC 0.010s
RUN
(0x0647) time Set vY2 output ON delay time (0.000~60.000s)
F06.72 vY3 output ON delay V/F SVC FVC PMVF PMSVC PMFVC 0.010s
RUN
(0x0648) time Set vY3 output ON delay time (0.000~60.000s)
F06.73 vY4 output ON delay V/F SVC FVC PMVF PMSVC PMFVC 0.010s
RUN
(0x0649) time Set vY4 output ON delay time (0.000~60.000s)
F06.74 vY1 output OFF delay V/F SVC FVC PMVF PMSVC PMFVC 0.010s
RUN
(0x064A) time Set vY1 output OFF delay time (0.000~60.000s)
F06.75 vY2 output OFF delay V/F SVC FVC PMVF PMSVC PMFVC 0.010s
RUN
(0x064B) time Set vY2 output OFF delay time (0.000~60.000s)
F06.76 vY3 output OFF delay V/F SVC FVC PMVF PMSVC PMFVC 0.010s
RUN
(0x064C) time Set vY3 output OFF delay time (0.000~60.000s)
F06.77 vY4 output OFF delay V/F SVC FVC PMVF PMSVC PMFVC 0.010s
RUN
(0x064D) time Set vY4 output OFF delay time (0.000~60.000s)
29
RD11 Series Frequency converter Manual
F07.1x:Stop Control
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
F07.10 V/F SVC FVC PMVF PMSVC PMFVC 0
Stop mode RUN
(0x070A) 0: Deceleration stop 1: Free stop (0 ~ 1)
V/F SVC FVC PMVF PMSVC PMFVC 0.50Hz
F07.11 Shutdown detection
When decelerating to stop, when the inverter output frequency is less (0.00~upper limit RUN
(0x070B) frequency
than this value, it will enter the stop state. frequency setting)
F07.12 Stop and restart limit V/F SVC FVC PMVF PMSVC PMFVC 0.00s
STOP
(0x070C) time Waiting time after restarting after shutdown (0.00~60.00s)
V/F SVC FVC PMVF PMSVC PMFVC
Insufficient lower limit
F07.15 0 : Run according to frequency command 0
frequency action RUN
(0x070F) 1 : Free running stops, enters the pause state (0~3)
selection
2 : Run at the following limited frequency 3 : Zero speed operation
V/F SVC FVC PMVF PMSVC PMFVC
F07.16 Zero speed torque 60.0%
Set zero speed torque current, 100.0% corresponds to inverter rated RUN
(0x0710) retention factor (0.0~150.0%)
current
F07.17 Zero speed torque V/F SVC FVC PMVF PMSVC PMFVC 0.0s
RUN
(0x0711) holding time Set zero speed torque hold time (0.0~6000.0s)
F07.18 Positive reversal dead V/F SVC FVC PMVF PMSVC PMFVC 0.0s
STOP
(0x0712) time Fwd and Rev switching, zero frequency maintenance time (0.0~120.0s)
30
RD11 Series Frequency converter Manual
F07.20 Braking current before V/F SVC FVC PMVF PMSVC PMFVC 60.0%
STOP
(0x0714) starting Set the brake current before starting (0.0~150.0%)
F07.21 Braking time before V/F SVC FVC PMVF PMSVC PMFVC 0.0s
STOP
(0x0715) starting Set the brake time before starting (0.0~60.0s)
F07.22 DC braking start V/F SVC FVC PMVF PMSVC PMFVC 1.00Hz
STOP
(0x0716) frequency Set the DC brake start frequency (0.00~50.00Hz)
V/F SVC FVC PMVF PMSVC PMFVC
F07.23 60.0%
DC braking current Refer to rated current,because the internal limit current cannot STOP
(0x0717) (0.0~150.0%)
exceed the rated current
F07.24 DC braking time during V/F SVC FVC PMVF PMSVC PMFVC 0.0s
STOP
(0x0718) stopping Set the DC braking time during stopping (0.0~60.0s)
V/F SVC FVC PMVF PMSVC PMFVC
Units: Search method
0: Search from the maximum frequency 1: Search from the stop
F07.25 frequency 0000
Speed tracking mode Tens:Reverse search STOP
(0x0719) (0000~1111)
0:Off 1:On
Hundreds: Search source
0:Software search 1:Hardware search
F07.26 V/F SVC FVC PMVF PMSVC PMFVC 0.5s
Speed tracking speed STOP
(0x071A) Set the speed of tracking speed (0.0~60.0s)
F07.27 Speed tracking stop V/F SVC FVC PMVF PMSVC PMFVC 1.00s
STOP
(0x071B) delay Set speed tracking stop delay (0.0~60.0s)
F07.3x:Jog
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
5.00Hz
F07.30 Jog running frequency V/F SVC FVC PMVF PMSVC PMFVC
(0.00~Max RUN
(0x071E) setting Set jog running frequency
frequency)
F07.31 V/F SVC FVC PMVF PMSVC PMFVC 10.0s
Jog acceleration time RUN
(0x071F) Set jog acceleration time (0.0~650.0s)
F07.32 V/F SVC FVC PMVF PMSVC PMFVC 10.0s
Jog deceleration time RUN
(0x0720) Set jog deceleration time (0.0~650.0s)
F07.33 V/F SVC FVC PMVF PMSVC PMFVC 0
Jog S curve selection RUN
(0x0721) 0:Invalid 1:Valid (0~1)
V/F SVC FVC PMVF PMSVC PMFVC
F07.34 Jog stop mode 0
Set stop mode STOP
(0x0722) selection (0~1)
0: According to F7.10 setting mode 1: Deceleration only
31
RD11 Series Frequency converter Manual
(0x072D) amplitude Set the amplitude of jump frequency 1 (0.00~Max
frequency)
0.00Hz
F07.46 V/F SVC FVC PMVF PMSVC PMFVC
Jump frequency 2 (0.00~Max RUN
(0x072E) Set the jump frequency 2
frequency)
0.00Hz
F07.47 Jump frequency 2 V/F SVC FVC PMVF PMSVC PMFVC
(0.00~Max RUN
(0x072F) amplitude Set the amplitude of jump frequency 2
frequency)
0.00Hz
yF08.32 Swing frequency V/F SVC FVC PMVF PMSVC PMFVC
(0~upper limit STOP
(0x0820) preset frequency Set the swing frequency preset frequency
frequency)
Swing frequency
F08.33 V/F SVC FVC PMVF PMSVC PMFVC 0.0s
preset frequency STOP
(0x0821) Set the swing frequency preset frequency waiting time (0.0~3600.0s)
waiting time
F08.34 Swing frequency V/F SVC FVC PMVF PMSVC PMFVC 10.0%
STOP
(0x0822) amplitude Set the swing frequency amplitude (0.0~50.0%)
F08.35 V/F SVC FVC PMVF PMSVC PMFVC 10.0%
Kick frequency STOP
(0x0823) Set the kick frequency (0.0~50.0%)
F08.36 V/F SVC FVC PMVF PMSVC PMFVC 5.00s
Triangle wave rise time STOP
(0x0824) Set the triangle wave rise time (0.1~999.9s)
32
RD11 Series Frequency converter Manual
4.12 F09:Reserved
F10.1x:Voltage Protection
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
V/F SVC FVC PMVF PMSVC PMFVC
F10.10 Bus overvoltage Set whether the bus overvoltage hardware protection function is 0
STOP
(0x0A0A) hardware protection enabled. (0 ~ 1)
0: off 1: on
V/F SVC FVC PMVF PMSVC PMFVC
When the bus voltage is greater than the overvoltage suppression
point, it will slow down or stop the acceleration and deceleration to
prevent overvoltage faults.
F10.11 Bus overvoltage 0012
Unit: Overvoltage suppression function STOP
(0x0A0B) suppression (0000 ~0012)
0: Off 1: Only enable during deceleration 2: Enable during both
acceleration and deceleration
Tens: overexcitation function
0: off 1: on
T3:780
S2:365
F10.12 Bus overvoltage V/F SVC FVC PMVF PMSVC PMFVC (0~ overvoltage point)
T3 overvoltage STOP
(0x0A0C) suppression point Set bus voltage value for trigger overvoltage suppression function
point:820V;S2
overvoltage
point:390V
F10.13 Bus overvoltage V/F SVC FVC PMVF PMSVC PMFVC 100.0%
RUN
(0x0A0D) suppression gain Set the response effect of overvoltage suppression (0.0~500.0%)
V/F SVC FVC PMVF PMSVC PMFVC
F10.14 Set whether the energy brake function is on 2
Energy brake enable RUN
(0x0A0E) 0: Off 1: On, but off overvoltage suppression (0 ~2)
2: Turn on, and turn on the overvoltage suppression function.
33
RD11 Series Frequency converter Manual
T3:735
S2:360
V/F SVC FVC PMVF PMSVC PMFVC
F10.15 Energy consuming Set the energy consuming braking action voltage, when the bus (0~ overvoltage point)
T3 overvoltage RUN
(0x0A0F) braking action voltage voltage is greater than this value, the energy consuming brake starts
to act point:820V;S2
overvoltage
point:390V
T3:430
S2:240
F10.17 Bus undervoltage V/F SVC FVC PMVF PMSVC PMFVC (0~ overvoltage point)
T3 overvoltage STOP
(0x0A11) suppression point Set bus voltage value for trigger undervoltage suppression function
point:820V;S2
overvoltage
point:390V
F10.18 Bus undervoltage V/F SVC FVC PMVF PMSVC PMFVC 100.0%
RUN
(0x0A12) suppression gain Set the response effect of undervoltage suppression (0.0~500.0%)
T3:350
S2:190
V/F SVC FVC PMVF PMSVC PMFVC (0~ overvoltage point)
F10.19 Bus undervoltage
Set the allowable lower limit of the bus voltage. Below this value, the T3 overvoltage STOP
(0x0A13) protection point
inverter reports undervoltage fault. point:820V;S2
overvoltage
point:390V
F10.2x:Auxiliary Protection
34
RD11 Series Frequency converter Manual
F10.3x:Load Protection
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
Motor overload V/F SVC FVC PMVF PMSVC PMFVC
F10.30 100.0%
protection curve Set the coefficient of overload protection for the load motor. STOP
(0x0A1E) (0 ~250.0%)
coefficient Increasing this value can increase the overload capacity of the motor.
Selection of inverter V/F SVC FVC PMVF PMSVC PMFVC
F10.31 overload 0
Set whether the overload protection function is valid when the speed STOP
(0x0A1F) characteristics at low (0 ~1)
is low (less than 5Hz)
speed
V/F SVC FVC PMVF PMSVC PMFVC
Set the inverter load warning detection mode and the early warning
mode at this time
Unit: Load warning checkout 1 setting
0: No detection 1: The detection load is too large
2: Excessive load detection only at constant speed 3: Insufficient
detection load
4: Insufficient load detection only at constant speed
F10.32 Load warning checkout 0000
Ten digits: warning setting when load warning is detected 1 STOP
(0x0A20) setting (0000 ~1414)
0: continue to run, report A.LD1 1: Free stop, report to E.LD1
Hundreds place: load warning checkout 2 setting
0: No detection 1: The detection load is too large
2: Excessive load detection only at constant speed 3: Insufficient
detection load
4: Insufficient load detection only at constant speed
Thousands: warning setting when load warning is detected 2
0: continue to run, report A.LD1 1: Free stop, report to E.LD1
V/F SVC FVC PMVF PMSVC PMFVC
Set the detection value of load warning 1
F10.33 Load warning detection Under VF control, this value 100% is corresponding to the rated 130.0%
STOP
(0x0A21) level 1 current of the motor. (0 ~200.0%)
Under vector control, this value 100% is corresponding to the rated
output torque of the motor.
V/F SVC FVC PMVF PMSVC PMFVC
F10.34 Load warning detection Set the duration of the detected load warning 1 and the load is greater 5.0s
STOP
(0x0A22) time 1 than the load warning detection level for the duration, and the load (0 ~60.0)
warning 1 is reported.
V/F SVC FVC PMVF PMSVC PMFVC
Set the detection value of load warning 1
F10.35 Load warning detection Under VF control, this value 100% is corresponding to the rated 130.0%
STOP
(0x0A23) level 2 current of the motor. (0 ~200.0%)
Under vector control, this value 100% is corresponding to the rated
output torque of the motor.
V/F SVC FVC PMVF PMSVC PMFVC
F10.36 Load warning detection Set the duration of the detected load warning 2 and the load is greater 5.0s
STOP
(0x0A24) time 2 than the load warning detection level for the duration, and the load (0 ~60.0)
warning 2 is reported.
F10.4x:Stall Protection
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
V/F SVC FVC PMVF PMSVC PMFVC
Set the warning detection mode selection and alarm mode selection
when deviation between the motor given speed and feedback speed
Speed deviation is excessive
F10.40 0000
excessive protection Unit: Check out the selection STOP
(0x0A28) (0000 ~0012)
action 0: No detection 1: Only at constant speed detection 2: Always
detected
Ten places: alarm selection
0: Free stop and report fault 1: Alarm and continue to run
Speed deviation V/F SVC FVC PMVF PMSVC PMFVC
F10.41 10.0%
excessive detection Set the detected value when speed deviation is excessive. This value STOP
(0x0A29) (0 ~60.0%)
threshold corresponds to F01.10 [maximum frequency].
35
RD11 Series Frequency converter Manual
V/F SVC FVC PMVF PMSVC PMFVC
Speed deviation
F10.42 Set the detection time of the excessive speed deviation, when the 2s
excessive detection STOP
(0x0A2A) speed deviation is excessive and the duration is longer than this time (0 ~60)
time
value the deviation warning reported
V/F SVC FVC PMVF PMSVC PMFVC
Set the alarm detection mode selection and alarm mode selection
when the motor is overspeed
F10.43 Speed protection Unit: Check out the selection 0002
STOP
(0x0A2B) action 0: No detection 1: Only at constant speed detection 2: Always (0000 ~0012)
detected
Ten places: alarm selection
0: Free stop and report fault 1: Alarm and continue to run
V/F SVC FVC PMVF PMSVC PMFVC
F10.44 Speed exceed 110.0%
Set the speed exceed warning detection value, which corresponds STOP
(0x0A2C) detection threshold (0 ~150.0%)
to F01.10 [maximum frequency]
V/F SVC FVC PMVF PMSVC PMFVC
F10.45 Speed exceed Set the duration of the detection of the flying speed, the feedback 0.010s
STOP
(0x0A2D) detection time speed is greater than F10.44 and continue for that time, and the (0 ~2.000)
speed warning is detected.
F11.0x:Button Operation
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
V/F SVC FVC PMVF PMSVC PMFVC
F11.00 0: No lock 1: Keyboard function parameter modification lock 0
Key lock selection RUN
(0x0B00) 2: Function parameters and non-start and stop button lock 3: function (0 ~ 3)
parameters and button full lock
F11.01 V/F SVC FVC PMVF PMSVC PMFVC 0
Key lock password RUN
(0x0B01) Set the key lock password (0 ~ 65535)
V/F SVC FVC PMVF PMSVC PMFVC
0: Invalid 1: Reverse run key
2: Forward jog run key 3: Reverse jog run key
4: Keyboard command channel and terminal naming channel switch
F11.02 Keyboard multi- 5: Keyboard command channel and communication naming channel 0
STOP
(0x0B02) function key selection switch (0 ~ 7)
6: Terminal command channel and communication naming channel
switch
7: keyboard, terminal, communication command channel cycle
switching
V/F SVC FVC PMVF PMSVC PMFVC
F11.03 Keyboard STOP 0: Non-keyboard control mode is invalid 0
STOP
(0x0B03) button settings 1: Non-keyboard control mode stops according to stop mode (0 ~ 2)
2: Non-keyboard control mode stops in free mode
V/F SVC FVC PMVF PMSVC PMFVC
Unit keyboard up and down keys to modify the selection
Status interface up and
F11.04 0: Invalid 1: Used to adjust the frequency keyboard given F01.09 0011
down keys (knob) STOP
(0x0B04) 2: used to adjust the PID keyboard given F13.01 (0000~0213)
function selection
3: Keyboard up and down keys to modify the parameter number
setting
36
RD11 Series Frequency converter Manual
Ten place: power down storage
0: frequency power down is not stored 1: frequency power down
storage
Hundreds: Action Limit
0: Run stop adjustable 1: Only adjustable during operation, stop and
keep
2: Adjustable during operation, stop and clear
V/F SVC FVC PMVF PMSVC PMFVC
Up and down keys to
F11.05 Ten digits: yy setting in function parameter number Fxx.yy 00~99 0109
quickly change the RUN
(0x0B05) Hundreds of thousands: xx setting in function parameter number (0000 ~ 1563)
parameter code setting
Fxx.yy 00~15
37
RD11 Series Frequency converter Manual
F11.2x:Monitoring Parameter
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
V/F SVC FVC PMVF PMSVC PMFVC
Unit digit: Output frequency display selection
0: Target frequency 1: Operating frequency >=2: Target frequency,
F11.20 Keyboard display item the filtering depth increases with this value 0002
RUN
(0x0B14) settings Ten: reserved (0000 ~ 111F)
Hundreds: Power Display Dimensions
0: Power display percentage (%) 1: Power display kilowatt (KW)
Thousands: reserved
38
RD11 Series Frequency converter Manual
Modbus
F12.05 V/F SVC FVC PMVF PMSVC PMFVC 0ms
communication RUN
(0x0C05) Set the time of Modbus communication response delay (0 ~ 500ms)
response delay
Modbus
F12.06 V/F SVC FVC PMVF PMSVC PMFVC 1.0s
communication timeout RUN
(0x0C06) Set the time of Modbus communication timeout failure (0.1 ~ 100.0s)
failure time
Communication V/F SVC FVC PMVF PMSVC PMFVC
F12.07 0
disconnection 0: Do not detect timeout failure 1: Fault and free stop RUN
(0x0C07) (0 ~ 3)
processing 2: Warning and continue to run 3: Forced stop
F12.08 Receive data (address V/F SVC FVC PMVF PMSVC PMFVC 0.00
RUN
(0x0C08) 0x3000) zero bias Offset correction communication data for address 0x3000. (-100.00-100.00)
F12.09 Receive data (address V/F SVC FVC PMVF PMSVC PMFVC 100.0%
RUN
(0x0C09) 0x3000) gain Linearly correct communication data of the address 0x3000. (0.0~500.0%)
F12.3x:Profibus-DP
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
F12.30 V/F SVC FVC PMVF PMSVC PMFVC 1
DP card address RUN
(0x0C1E) Set the address of DP card (1 ~ 247)
F12.4x:CAN Mode
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
F12.40 V/F SVC FVC PMVF PMSVC PMFVC 1
CAN mode selection RUN
(0x0C28) 0:Slave 1:Host station of VEDA-IN (0 ~ 1)
F12.41 Communication V/F SVC FVC PMVF PMSVC PMFVC 1
RUN
(0x0C29) address Set the address of the slave (1 ~ 247)
V/F SVC FVC PMVF PMSVC PMFVC
F12.42 Communication baud 0:20 kbps 1:50 kbps 2:100kbps 3
RUN
(0x0C2A) rate selection (0 ~ 6)
3:125kbps 4:250kbps 5:500kbps
39
RD11 Series Frequency converter Manual
6:1Mbps
F13.01 Keyboard digital PID V/F SVC FVC PMVF PMSVC PMFVC 50.0%
RUN
(0x0D01) given / feedback Set keyboard digital PID given / feedback value (0.00~100.0%)
40
RD11 Series Frequency converter Manual
V/F SVC FVC PMVF PMSVC PMFVC
0: keyboard digital PID feedback 1: keyboard analog potentiometer
feedback
F13.03 PID controller feedback 2: Current/voltage analog AI1 feedback 2
RUN
(0x0D03) signal source 3: Current/voltage analog AI2 feedback (0 ~ 9)
4: Reserved 5: Terminal pulse PUL feedback
6: RS485 communication feedback 7: Option card
8: Terminal selection 9: Local active current
F13.04 Feedback signal low V/F SVC FVC PMVF PMSVC PMFVC 0.010s
RUN
(0x0D04) pass filtering time Set the feedback signal low pass filter time (0.000~6.000s)
F13.05 V/F SVC FVC PMVF PMSVC PMFVC 1.00
Feedback signal gain RUN
(0x0D05) Set feedback signal gain (0.00~10.00)
F13.06 V/F SVC FVC PMVF PMSVC PMFVC 100.0
Feedback signal range RUN
(0x0D06) Set the feedback signal range (0~100.0)
41
RD11 Series Frequency converter Manual
F13.25-F13.28: PID Feedback Disconnection judgment
Parameter Factory default Adjustable
Name Content
(Address) (range) properly
V/F SVC FVC PMVF PMSVC PMFVC
V/F SVC FVC PMVF PMSVC PMFVC
Feedback
F13.25 0: Continue PID operation without reporting fault 1: Stop and report 0
disconnection action STOP
(0x0D19) fault (0 ~ 3)
selection
2: Continue PID operation and output alarm signal
3: Run at the current frequency, output alarm signal
F13.26 Feedback V/F SVC FVC PMVF PMSVC PMFVC 1.0s
disconnection RUN
(0x0D1A) Set feedback disconnection detection time (0.0~120.0s)
detection time
F13.27 Wire break alarm V/F SVC FVC PMVF PMSVC PMFVC 100.0
RUN
(0x0D1B) upper limit Set the upper limit of the disconnection alarm (0.0~100.0%)
F13.28 Wire break alarm lower V/F SVC FVC PMVF PMSVC PMFVC 0.0%
RUN
(0x0D1C) limit Set the upper limit of the disconnection alarm (0.0~100.0%)
42
RD11 Series Frequency converter Manual
20.00Hz
F14.07 V/F SVC FVC PMVF PMSVC PMFVC
Multi-speed 8 (0.00~ Max RUN
(0x0E07) Set PLC multi-speed 8
frequency)
10.00Hz
F14.08 V/F SVC FVC PMVF PMSVC PMFVC
Multi-speed 9 (0.00~Max RUN
(0x0E08) Set PLC multi-speed 9
frequency)
20.00Hz
F14.09 V/F SVC FVC PMVF PMSVC PMFVC
Multi-speed 10 (0.00~ Max RUN
(0x0E09) Set PLC multi-speed 10
frequency)
30.00Hz
F14.10 V/F SVC FVC PMVF PMSVC PMFVC
Multi-speed 11 (0.00~ Max RUN
(0x0E0A) Set PLC multi-speed 11
frequency)
40.00Hz
F14.11 V/F SVC FVC PMVF PMSVC PMFVC
Multi-speed 12 (0.00~Max RUN
(0x0E0B) Set PLC multi-speed 12
frequency)
50.00Hz
F14.12 V/F SVC FVC PMVF PMSVC PMFVC
Multi-speed 12 (0.00~Max RUN
(0x0E0C) Set PLC multi-speed 12
frequency)
40.00Hz
F14.13 V/F SVC FVC PMVF PMSVC PMFVC
Multi-speed 14 (0.00~Max RUN
(0x0E0D) Set PLC multi-speed 14
frequency)
30.00Hz
F14.14 V/F SVC FVC PMVF PMSVC PMFVC
Multi-speed 15 (0.00~ Max RUN
(0x0E0E) Set PLC multi-speed 15
frequency)
43
RD11 Series Frequency converter Manual
10.0
F14.23 PLC 8th stage running V/F SVC FVC PMVF PMSVC PMFVC
(0.0~ RUN
(0x0E17) time Set PLC 8h stage running time
6500.0(s/m/h))
10.0
F14.24 PLC 9th stage running V/F SVC FVC PMVF PMSVC PMFVC
(0.0~ RUN
(0x0E18) time Set PLC 9th stage running time
6500.0(s/m/h))
10.0
F14.25 PLC 10th stage V/F SVC FVC PMVF PMSVC PMFVC
(0.0~ RUN
(0x0E19) running time Set PLC 10th stage running time
6500.0(s/m/h))
10.0
F14.26 PLC11th stage running V/F SVC FVC PMVF PMSVC PMFVC
(0.0~ RUN
(0x0E1A) time Set PLC 11th stage running time
6500.0(s/m/h))
10.0
F14.27 PLC 12th stage V/F SVC FVC PMVF PMSVC PMFVC
(0.0~ RUN
(0x0E1B) running time Set PLC 12th stage running time
6500.0(s/m/h))
10.0
F14.28 PLC 13th stage V/F SVC FVC PMVF PMSVC PMFVC
(0.0~ RUN
(0x0E1C) running time Set PLC 13th stage running time
6500.0(s/m/h))
F14.29 PLC 14th stage V/F SVC FVC PMVF PMSVC PMFVC 10.0
RUN
(0x0E1D) running time Set PLC 14th stage running time (0.0~6500.0(s/m/h))
10.0
F14.30 PLC 15th stage V/F SVC FVC PMVF PMSVC PMFVC
(0.0~ RUN
(0x0E1E) running time Set PLC 15th stage running time
6500.0(s/m/h))
44
RD11 Series Frequency converter Manual
deceleration time of 9h
stage
PLC direction and
F14.40 acceleration and V/F SVC FVC PMVF PMSVC PMFVC 0000
RUN
(0x0E28) deceleration time of The same settings as F14.31 (0000~0031)
10th stage
PLC direction and
F14.41 acceleration and V/F SVC FVC PMVF PMSVC PMFVC 0000
RUN
(0x0E29) deceleration time of The same settings as F14.31 (0000~0031)
11th stage
PLC direction and
F14.42 acceleration and V/F SVC FVC PMVF PMSVC PMFVC 0000
RUN
(0x0E2A) deceleration time of The same settings as F14.31 (0000~0031)
12th stage
PLC direction and
F14.43 acceleration and V/F SVC FVC PMVF PMSVC PMFVC 0000
RUN
(0x0E2B) deceleration time of The same settings as F14.31 (0000~0031)
13th stage
PLC direction and
F14.44 acceleration and V/F SVC FVC PMVF PMSVC PMFVC 0000
RUN
(0x0E2C) deceleration time of The same settings as F14.31 (0000~0031)
14th stage
PLC direction and
F14.45 acceleration and V/F SVC FVC PMVF PMSVC PMFVC 0000
RUN
(0x0E2D) deceleration time of The same settings as F14.31 (0000~0031)
154th stage
C00:Basic Monitoring
Parameter Name Parameter Name
(Address) (Address)
C00.00 (0x2100) Given frequency C00.20 (0x2114) Analog output AO
C00.01 (0x2101) Output frequency C00.21 (0x2115) Reserved
C00.02(0x2102) Output current C00.22 (0x2116) Counter count value
C00.03 (0x2103) Input voltage C00.23 (0x2117) Power-on running time
Accumulated running time of the
C00.04 (0x2104) The output voltage C00.24 (0x2118)
machine
C00.05 (0x2105) Mechanical speed C00.25 (0x2119) Inverter power level
C00.06 (0x2106) Given torque C00.26 (0x211A) Inverter rated voltage
C00.07 (0x2107) Output torque C00.27 (0x211B) Inverter rated current
C00.08 (0x2108) PID given C00.28 (0x211C) Software version
C00.09 (0x2109) PID feedback C00.29 (0x211D) PG feedback frequency
C00.10 (0x210A) Output Power C00.30 (0x211E) Timer timing
C00.11 (0x210B) bus voltage C00.31 (0x211F) PID output value
C00.12 (0x210C) Module temperature 1 C00.32 (0x2120) Inverter software subversion
C00.13 (0x210D) Module temperature 2 C00.33(0x2121) Encoder feedback angle
C00.14 (0x210E) Input terminal X is on (Note) C00.34 (0x2122) Z pulse cumulative error
C00.15 (0x210F) Output terminal Y is on (Note) C00.35 (0x2123) Z pulse count
C00.16(0x2110) Analog AI1 input value C00.36 (0x2124) Failure warning code
Cumulative power consumption
C00.17 (0x2111) Analog AI2 input value C00.37 (0x2125)
(low level)
Cumulative power consumption
C00.18 (0x2112) Keyboard potentiometer input value C00.38 (0x2126)
(high)
C00.19 (0x2113) Pulse signal PUL input value C00.39 (0x2127) Power factor angle
Note:For example, when terminals X1 and X2 are ON, C00.14 is displayed as ,When terminal Y and relay are ON, C00.15 is displayed
as 。
45
RD11 Series Frequency converter Manual
C01:Fault Monitoring
Parameter Name Parameter(Address) Name
(Address) The first fault operation
C01.00 (0x2200) Fault type C01.12 (0x220C)
frequency
C01.01 (0x2201) Troubleshooting information C01.13 (0x220D) Last fault output voltage
C01.02 (0x2202) Fault operating frequency C01.14 (0x220E) Last fault output current
C01.03 (0x2203) Fault output voltage C01.15 (0x220F) The first fault bus voltage
The first fault module
C01.04 (0x2204) Fault output current C01.16 (0x2210)
temperature
C01.05 (0x2205) Fault bus voltage C01.17 (0x2211) The first faulty inverter status
C01.06 (0x2206) Faulty module temperature C01.18 (0x2212) The first fault input terminal
status
C01.07 (0x2207) Faulty inverter status C01.19 (0x2213) The first fault output terminal
status
C01.08 (0x2208) Fault input terminal status C01.20 (0x2214) First 2 fault types
The first 2 troubleshooting
C01.09 (0x2209) Fault output terminal status C01.21 (0x2215)
information
C01.10 (0x220A) Previous failure type C01.22 (0x2216) Top 3 fault types
Previous troubleshooting The first 3 troubleshooting
C01.11 (0x220B) C01.23 (0x2217)
information information
C02:Application Monitoring
Parameter(Address) Name Parameter(Address) Name
C02.00 (0x2300) PID feedback C02.08 (0x2308) Fwd and Rev command given
46
RD11 Series Frequency converter Manual
Switch the frequency channel
14 35 Swing frequency input 56 Reserved
combination to A
Switch the frequency channel
15 36 Swing frequency pause 57 Zero servo command
combination to B
16 Multi-speed terminal 1 37 Swing frequency reset 58 Run output blocking
command
17 Multi-speed terminal 2 38 Keyboard button and display self- 59 Reserved
test selection
X5 or X10 (extended) frequency Speed torque control
18 Multi-speed terminal 3 39 60
measurement switching
19 Multi-speed terminal 4 40 Timer trigger terminal 61 Reserved
20 PID control canceled 41 Timer clear terminal 62 Reserved
3 The inverter is running in forward 17 PID feedback exceeds the upper 31 Inverter overheat warning
rotation limit
Fault trip alarm 1 (alarm during PID feedback is below the lower
4 18 32 Motor overheat alarm output
fault self-recovery) limit
Fault trip alarm 2 (no alarm during PID feedback sensor Frequency (speed) is
5 19 33
fault self-recovery) disconnection consistent 1
Any frequency (speed) is
6 External downtime 20 Meter length arrives 34
consistent 1
7 Inverter undervoltage 21 Timer time to 35 Frequency detection 1
8 The inverter is ready for operation 22 Counter reaches maximum 36 Frequency detection 2
Output frequency level detection 1 Frequency (speed) is
9 23 Counter reaches the set value 37
(FDT1) consistent 2
47
RD11 Series Frequency converter Manual
E.OL3(16) Inverter overload 2 continuous CBC Fault E.CP2(98) Monitor compare output 2 fault Fault
E.PG7(44) Spindle encoder Z pulse error fault Fault A.OH3(142) Motor over temperature warning Warning
E.PG8(44) Encoder Z pulse logic fault Fault A.RUN1(143) Run command conflict Warning
E.PG9(44) Spindle encoder Z pulse logic fault Fault A.RUN2(158) Jog terminal start protection Warning
E.PG10(44) Encoder Z pulse disconnection Fault A.RUN3(159) Terminal start protection Warning
External keyboard disconnection
E.BRU(50) Brake unit failure Fault A.PA2(144) Warning
warning
E.TExx(52) Motor parameter self-learning fault Fault A.COP(145) Parameter copy warning Warning
E.IAE1(71) Motor angle learning fault 1 Fault A.CP1(146) Monitor comparison output 1 warning Warning
E.IAE2(72) Motor angle learning fault 2 Fault A.CP2(147) Monitor comparison output 2 warning Warning
E.IAE3(73) Motor angle learning fault 3 Fault A.FA1(150) External extension reserve 1 Warning
E.PST1(74) Synchronous machine out of step fault 1 Fault A.FA2(151) External extension reserve 2 Warning
E.PST2(75) Synchronous machine out of step fault 2 Fault A.FA3(152) External extension reserve 3 Warning
E.PST3(76) Synchronous machine out of step fault 3 Fault A.FA4(153) External extension reserve 4 Warning
E.DEF(77) Speed deviation excessive Fault A.FA5(154) External extension reserve 5 Warning
E.SPD(78) Speed exceed fault Fault A.FA6(155) External extension reserve 6 Warning
: Do not perform related work while the power is on, otherwise there is a danger of death due to electric shock. When performing related work,
please cut off the power supply and confirm that the DC voltage of the main circuit has dropped to a safe level, and wait 5 minutes before performing related work.
49
RD11 Series Frequency converter Manual
5.2 Maintenance
All equipment and components have a service life. Proper maintenance can extend the life, but it cannot solve the damage of equipment and equipment. Please replace
the equipment according to requirements.
Item Service life Item Service life Item Service life
Fans 2~3 years Electrolytic capacitor 4~5 years PCB 8~10 years
The replacement of other devices is very strict with the maintenance technology and product familiarity, and must be strictly tested before being replaced before use.
Therefore, it is not recommended to replace other internal components. If you do need to replace it, please contact the agent where you purchased the product or the sales
department of the company.
50
RD11 Series Frequency converter Manual
Start Bit Bit1 Bit2 Bit3 Bit4 Bit5 Bit6 Bit7 Bit8 Check bit Stop bit
The information of a frame must be transmitted in a continuous stream. If the interval of more than 1.5 bytes before the end of the entire frame transmission, the receiving
device will clear the incomplete information and mistakenly believe that the next byte is the address field portion of a new frame. Similarly, if the interval between the start of a
new frame and the previous frame is less than 3.5 bytes, the receiving device will consider it to be the continuation of the previous frame. Due to the disorder of the frame, the
CRC check value is incorrect, resulting in communication error.
Standard structure of RTU frames:
mailing address:
Slave address
0 to 247 (decimal) (0 is the broadcast address)
03H: Read slave parameters
Command code 06H: Write slave parameters
08H: Loop self-test
Data area Parameter address, number of parameters, parameter value, etc.
51
RD11 Series Frequency converter Manual
Slave address 01H
Command code 83H
Fault code 04H
Low CRC CHK 40H
High CRC CHK F3H
52
RD11 Series Frequency converter Manual
RAM, won’t be stored when power down; if the function code parameter address field high nibble is D, written in the EEPROM, will be stored when power down.
For example, parameter F16.xx: 0x50xx (write in RAM) 0xD0xx (stored in EEPROM); parameter F17.xx: 0x51xx (write in RAM) 0xD1xx (stored in EEPROM), and so
on other group parameters. When reading the F16~F29 parameter group parameters, the address high nibble is 5, such as reading the parameter F18.xx: 0x52xx.
53
RD11 Series Frequency converter Manual
The operation is in one direction. This mode is the most commonly used two-wire mode. The factory default is to determine the forward and reverse running of the motor
by the X1 (forward running) and X2 (reverse running) terminal commands. As shown below:
X1 (forward rotation operation), and the direction is controlled by the reverse rotation operation terminal X2 (reverse rotation operation). The three-wire operation control
frequency inverter
SB1 SB2 X1
run order(run while on)
2: 3-line 1
54
RD11 Series Frequency converter Manual
55