Fault Analysis Q1 For the positive sequence network data shown in table below, obtain ZBUS by building procedure
Sr . No p q (nodes) Pos. Sequence
in pu 1 0 1 0.25 2 0 3 0.20 3 1 2 0.08 4 2 3 0.06 Q1 Symmetrical Fault or Three Phase Fault Change in System Bus Voltages Assuming fault occurs at bus k. Before the fault the current injected into bus k is I K and due to fault the current that is delivered by bus to fault is If . Post-fault current is IK & If since both currents are opposite. Thus, change in current is IK = -If Before fault, the voltage at bus k is Vk and due to grounding it is reduced to 0. Thus, change in voltage is Vk = - Vk
Substituting the values
of IK & Vk Change in System Bus Voltages If the initial Bus voltage was Vj , new bus voltage is given by,
Change in voltage of Bus j is
Fault Current Due to fault the terminal voltage changes but we assume emf as constant due to constant excitation. Then, the current delivered by generator is, Q1 Q2 Q3