Technical Specifications
Technical Specifications
A current transformer produces a reduced current accurately proportional to the current in the circuitis which is too high
to apply directly to metering and protecting instruments.
A current transformer isolates the measuring instruments from what may be very high voltage in the monitored circuit.
Current transformers are commonly used in metering and protective relays in the electrical power industry.
there are two main standards to which current transformers are designed. IEC 1-60044 (BSEN 1-60044) & IEEE C57.13 (ANSI)
Main Primary
Conductor
Hollow Core
Ammeter
Primary Is
Ip
Current
Construction
The burden, in a CT is the (largely resistive) impedance presented to its secondary winding. Typical burden ratings for IEC CTs
are 1.5 VA, 3 VA, 5 VA, 10 VA, 15 VA, 20 VA, 30 VA, 45 VA and 60 VA. As for ANSI/IEEE burden ratings are B0.1-, B0.2-, B0.5-, B1.0-,
B2.0- and B4.0-. Items that contribute to the burden of a current measurement circuit are switch-blocks, meters and intermediate
conductors. The most common source of excess burden is the conductor between the metering or protecting instruments and
the CT. The excessive length of wire creates a large resistance. This problem can be reduced by using CTs with lower ampere
secondaries, which will produce less voltage drop between a CT and the metering or protecting instruments.
Knee-point core-saturation voltage
The knee-point voltage of a current transformer is the voltage at which a 10% increase in applied voltage
increases the magnetizing current by 50%. At this point output current ceases to linearly follow the input
current within declared accuracy. The knee-point voltage is less applicable for metering current
transformers as their accuracy is generally much higher, but constrained within a very small range of the
current transformer rating, typically 1.2 to 1.5 times rated current. However, the concept of knee point
voltage is very pertinent to protection current transformers, since they are necessarily exposed to fault
currents of 20 to 30 times rated current.
Accuray class is the limit of the permisible percentage current error at the rated current,rating factor is
a factor by which the nominal full load current of a CT can be multiplied to determine its absolute
maximum measurable primary current. The rating factor of a CT is largely dependent upon ambient
temperature.
Ideally the secondary current of a current transformer should be perfectly in phase with the primary
current. In practice, this is impossible to achieve, but phase shifts as low as a few tenths of a degree for
well constructed transformers up to as much as six degrees for simpler designs may be encountered.
For the purposes of current measurement, any phase shift is immaterial as the indicating ammeter,
only displays the magnitude of the current However, if the current transformer is used in conjunction
with the current circuit of a wattmeter, energy meter or power factor meter, any phase shift in the
Technical Notices
Kind Class Current error in % at ... total error at Phase displacement in minutes at ...
1 5 20 50 100 120 150 200 n x IN 1 5 20 100 120 150 200
Percent of rated current in % Percent of rated current
Primary P1 -- P2
Primary with taps P1 -- P2 -- P3 .....
Secondary S1 -- S2
Connection diagrams:
Wound primary C.T. Window type C.T.
P1 S1 P1 S1
P2 S2 P2 S2
P1 S1 P1 S1
P2 S2
P3 S2 P2 S3
Technical Notices
Material numbers and placement of bars due to DIN 43670 / DIN 43671
20 5 320 550
20 10 500 820
30 5 450 780
30 10 620 1090
40 5 570 990
Aluminium