1. Design of RCC Retaining Wall
1. Design of RCC Retaining Wall
0.25
Input Parameters
Retaining Height = 6.00 m
Height of Wall = 7.80 m
Height of Stem = 7.20 m
Depth of Footing = 0.60 m
6.00
Width of Footing = 5.60 m 7.20
Top thickness of stem = 0.25 m 7.80
Bottom thickness of stem = 0.70 m
Toe projection = 4.00 m 1.20
Heel projection = 0.90 m
Depth of soil at passive side = 1.20 m ( Upto the top of footing ) 0.60
Depth of soil at active side = 7.20 m ( Upto the top of footing )
Depth of Ground water = 0.00 m ( Not considered )
0.70
Width of Shear key = 0.35 m
Depth of Shear key = 1.20 m
4.00
0.90
5.60
7.80
12
3.00
2.60
1.00
7.80
7.80
2.60
3.00
Horizontal seismic coefficient, Kh = 0.2
Seismic coefficient for active earth pressure, KEa = Ko (1 + Kh) = 0.6 (AIJ Recommendation for Design
of Building Foundations,2019)
Seismic coefficient for passive earth pressure, KEp = 2.63 (Using Mononobe-Okabe Formula)
7.80
7.80
7.80
7.80
Sp = Ko × 3.00
= 0.50 × 3.00 × 1.00 = 1.50 kN/m
SN Component Horizontal Load, H (kN) Lever arm (m) Overturning moment, Mo (kNm)
1 W1 (rec) 8.64 4.200 36.29
2 W1 (tri) 7.78 3.000 23.33
3 W2 16.13 0.300 4.84
4 W3 23.33 3.600 83.98
∑H=55.87 ∑Mo=148.44
1.2 Stability Check
Summary of Forces
Sliding Resisting Downward Resisting Overturning
Upward Vertical Net Vertical
L/C Horizontal Force Horizontal Force Vertical Force Moment Moment (Mo),
Force (Vu), kN Force (V), kN
(Hs), kN (Hr), kN (Vd), kN (Mr), kNm kNm
111 285.48 217.53 0.00 375.84 375.84 1611.11 757.46
112 311.05 163.15 0.00 375.84 375.84 1556.16 823.30
For a structure to be safe in sliding, the factor of safety for sliding should be greater than 1.5 for long term and 1.3 for short term condition.
Factor of safety for sliding= Resisting Horizontal Force = µ*V+Hr
Sliding Horizontal Force Hs
For a structure to be safe in uplift, the factor of safety for uplift should be greater than 1.50.
Factor of safety for uplift= Downward Vertical Force = Vd
Upward Vertical Force Vu
For a structure to be safe in overturning, the factor of safety for overturning should be greater than 1.50.
Factor of safety for overturning= Resisting Moment = ∑Mr
Overturning Moment ∑Mo
The maximum soil pressure induced in the soil below foundation should be less than the bearing capacity of the soil.
Allowable Bearing Capacity of Soil = 120 kN/m2
Maximum pressure induced in the soil (qmax)
= α*∑V
A
where, ∑V = Net Vertical Force
A = Contact area
6ⅇ
1+ for e<B/6
𝐵
α =
2 for e>B/6
3 0 ⋅ 5 − ⅇൗ𝐵
e = (B/2)-x̄
x̄ = ∑(Mr-Mo)
∑V
Mr = Resiting Moment
Mo = Overturning Moment
B/6 = 0.93
Overturning Resisting
Net Vertical e=
L/C Moment, Moment, x̄ = (Mr-Mo)/V αmax αmin qmax=α*(V/A) qmin=α*(V/A) Remarks
Load, V(kN) (B/2)-x̄
Mo(kNm) Mr(kNm)
111 375.84 757.46 1611.11 2.27 0.53 1.57 0.43 105.13 29.10 OK
112 375.84 823.30 1556.16 1.95 0.85 1.91 0.09 128.24 5.99 OK
1.3 Structural Design
b) For Footing
5.99 128.24
Note:
L2 L1 - Shear check is done at a distance "d" (effective depth) from the
0.9m 4.0m face of retaining wall.
- Moment check is done at the face of retaining wall.
d d
0.53m 0.53m
At Toe side
2
Maximum Footing Pressure qtoe = 84.58 kN/m Note: Uniform distribution of qmax is considered
2
Self Weight = -13.13 kN/m to be in conservative side.
Soil Pressure = -21.60 kN/m2
2
49.85 kN/m
Vu = Wu . (L1 - d)
= 79.77 x 3.4750
= 277.19 kN
At Heel side
The pressures acting on the shear key is equivalent to the area (trapezoid) of the pressure
a. Design forces
Mu = 796.76 kN-m
Vu = 390.53 kN
b. Flexure Design
Section Properties Material Strength
2
b = 1000 mm fc' = 20 N/mm2 fs = 333 N/mm2 (𝑓s = 𝑓𝑦)
3
b. Outside reinforcement
a. Design forces
Mu = 638.13 kN-m
Mu, top = 638.13 kN-m
Vu = 277.19 kN
b. Flexure Design
Section Properties Material Strength
2
b = 1000 mm fc' = 20 N/mm2 fs = 333 N/mm2 (𝑓s = 𝑓𝑦)
3
b. Top reinforcement
Mu = 63.81 kN-m
Vu = 277.19 kN
cc = 56 mm : Concrete cover = (50+0.5d b )
d= 544 mm : Effective depth = (D-cc)
a. Design forces
Mu = 134.52 kN-m
Vu = 109.07 kN
b. Flexure Design
Section Properties Material Strength
2
b = 1000 mm fc' = 25 N/mm2 fs = 333 N/mm2 (𝑓s = 𝑓𝑦)
3