MCS-Magnum Refr Manual Version 17 (1)
MCS-Magnum Refr Manual Version 17 (1)
www.mcscontrols.com
MCS Total
Solution
for all your
Control
Needs Energy Efficient and Storage Climate Controls
RoHS Compliant
MCS-REFRIG MANUAL
All information contained within this document is considered to be proprietary information of Micro Control Systems, Inc.
No information or data from this document shall be published, used, reproduced, transmitted, or disclosed to others out-
side your organization without the prior expressed written consent of Micro Control Systems, Inc. This document and the
information contained herein shall be treated as proprietary. Reasonable provisions shall be provided to ensure that this
information remains proprietary by your employees, agents, and other personnel that may have access to this document.
Copyright ©2020
2
MCS-REFRIG MANUAL
Table of Contents
Chapter - 1. Purpose of the REFR software ....................................................................................9
1.1. Compressor Control ....................................................................................................................................9
1.2. Defrost .........................................................................................................................................................9
Chapter - 2. Introduction to the Magnum .......................................................................................10
Magnum V17 Software Control Point Capacity..........................................................................................10
Magnum Hardware Supported by Magnum V17 Software.........................................................................10
Chapter - 3. MCS-MAGNUM-N and Expansion Boards .............................................................12
3.1. MCS-Magnum Revision 9.1........................................................................................................................12
3.2. MCS-SI16-A04- Version 1.3.......................................................................................................................13
3.3. MCS-RO10 - Version 1.2............................................................................................................................13
3.4. MCS-Magnum-N-12 Revision 9.2...............................................................................................................14
3.4.1 Optional Single Output Power Supply..............................................................................................14
3.5. MCS-IO-BASE and MCS-IO-EXT .............................15
3.6. MCS-RO-BASE and MCS-RO-EXT ..........................................................................................................18
3.7. MCS-SI-BASE and MCS-SI-EXT ..............................................................................................................19
Chapter - 4. Network Connection–MCS-485 ................................................................................20
4.1. MCS 485 Network......................................................................................................................................20
Chapter - 5. Network Connection–Ethernet ..................................................................................21
5.1. ETHERNET................................................................................................................................................21
5.1.1 RJ45 using a Crossover Ethernet Cable..........................................................................................21
Chapter - 6. Network Connection–Remote ....................................................................................22
6.1. Remote using Ethernet...............................................................................................................................22
Chapter - 7. PC Software for the Magnum .....................................................................................23
7.1. Requirements for PC Software...................................................................................................................23
Chapter - 8. Authorization Function ..................................................................................................24
8.1. Authorization Function ...............................................................................................................................24
Chapter - 9. Standard Control Options ............................................................................................26
9.1. General Options.........................................................................................................................................26
9.2. Variable Capacity Control Method..............................................................................................................26
9.2.1 Screw Compressor with slide piston.................................................................................................26
9.2.1.1. Force Digital Compressor Speed.........................................................................................27
9.2.2 Compressor with a Variable Frequency Drive (VFD)........................................................................27
9.2.3 Example of a system with 3 variable Step Compressors..................................................................27
9.2.4 Compressor Types............................................................................................................................27
9.2.5 Condenser Options...........................................................................................................................28
9.3. Target Reset (only if temperature control)..................................................................................................28
9.4. Oil Differential Calculation..........................................................................................................................28
9.5. On/Off Switches..........................................................................................................................................28
9.6. Low Suction Unloading & Holding..............................................................................................................29
9.7. High Discharge Pressure Unloading & Holding..........................................................................................29
9.8. High Discharge Temperature Unloading & Holding....................................................................................29
9.9. High Ampere Unloading & Holding.............................................................................................................30
9.10. Control Power Relay –No Stop...................................................................................................................30
9.11. Part Wind or Star Delta Starter...................................................................................................................30
9.12. English or Metric sensor readings..............................................................................................................31
9.13. Compressor Auto Rotation.........................................................................................................................31
9.14. Expanded Compressor Rotation to Check for Maximum Run Time...........................................................32
9.15. Run Hour Lockout.......................................................................................................................................32
9.16. Compressor Anti-Cycle Logic.....................................................................................................................32
9.17. Warning & Alarm Relay Outputs.................................................................................................................33
9.18. Operating Schedules..................................................................................................................................33
9.19. Modification to adjust approach values......................................................................................................33
Chapter - 10. Magnum Control Zone ...................................................................................................34
3
MCS-REFRIG MANUAL
4
MCS-REFRIG MANUAL
15.4.Outputs.......................................................................................................................................................51
15.5.Inputs..........................................................................................................................................................52
15.6.Alarms........................................................................................................................................................53
15.7.Graphs........................................................................................................................................................53
15.8.Set points ...................................................................................................................................................53
15.9.Service Tools..............................................................................................................................................57
Chapter - 16. Control Status Display ...................................................................................................58
16.1. From the MCS-Connect program...............................................................................................................58
16.1.1 Information displayed:.......................................................................................................................58
Chapter - 17. Magnum Control States ................................................................................................60
Chapter - 18. Capacity Control States (number) ...........................................................................61
18.1. UNIT IN POWER UP (0).............................................................................................................................61
18.2. POWER LOSS DELAY (1)..........................................................................................................................61
18.3. NO RUN- I/O LOST (2)...............................................................................................................................61
18.4. UNIT IN LOCKOUT (3)...............................................................................................................................61
18.5. UNIT IS OFF (4).........................................................................................................................................62
18.6. UNIT IS HOLDING (5)................................................................................................................................62
18.7. UNIT UNLOADING (6)...............................................................................................................................62
18.8. UNIT IS LOADING (7)................................................................................................................................62
18.9. CMP IN STARTU (8)...................................................................................................................................62
18.10. RUN/STOP SW OFF (9).............................................................................................................................62
18.11. SCHEDULED OFF (10)..............................................................................................................................62
18.12. OFF- NO FLOW(s) (11)..............................................................................................................................62
18.13. NOT USED (12)..........................................................................................................................................63
18.14. NOT USED (13)..........................................................................................................................................63
18.15. NOT USED (14)..........................................................................................................................................63
18.16. UNIT IS UNLOADED (15)..........................................................................................................................63
18.17. UNIT IS LOADED (16)................................................................................................................................63
18.18. NOT USED (17)..........................................................................................................................................63
18.19. NOT USED (18)..........................................................................................................................................63
18.20. NOT USED (19)..........................................................................................................................................63
18.21. DEF-STARTING CMP (20) (only used if not Air Normal Defrost)...............................................................63
18.22. DEFROSTING COILS (21) (only used if not Air Normal Defrost)...............................................................63
18.23. LO TEMP UNLOAD (22).............................................................................................................................63
Chapter - 19. Circuit Control States (number) ...............................................................................64
19.1. LOST IO LOCKED (0)................................................................................................................................64
19.2. CMP LOCKED OUT (1)..............................................................................................................................64
19.3. SWITCHED OFF (2)...................................................................................................................................64
19.4. UNLD & PMPDWN (3)................................................................................................................................64
19.5. CMP ANTICYCE (4)...................................................................................................................................64
19.6. CMP OFF/READY (5).................................................................................................................................64
19.7. NOT USED (6)............................................................................................................................................64
19.8. NOT USED (7)............................................................................................................................................64
19.9. CMP UNLOADED (8).................................................................................................................................65
19.10. CMP UNLD STEP1 (9)...............................................................................................................................65
19.11. CMP UNLD STEP2 (10).............................................................................................................................65
19.12. CMP IS HOLDING (11)...............................................................................................................................65
19.13. CMP IS LOADING (12)...............................................................................................................................65
19.14. CMP IS UNLDING (13)...............................................................................................................................65
19.15. CMP IS RUNNING (14)..............................................................................................................................65
19.16. FAST UNLOADING (15).............................................................................................................................65
19.17. LO SUCT UNLOAD (16).............................................................................................................................65
19.18. LO SUCT HOLD (17)..................................................................................................................................66
19.19. HI DISC UNLOAD (18)...............................................................................................................................66
19.20. HI DISC HOLD (19)....................................................................................................................................66
19.21. SAFETY TRIPPED (20).............................................................................................................................66
19.22. NOT USED (21)..........................................................................................................................................66
19.23. HI AMP UNLDING (22)...............................................................................................................................66
5
MCS-REFRIG MANUAL
22.1.2
EXV Maximum Operating Pressure..................................................................................................95
22.1.3
EXV control methods for Step Loading Compressors......................................................................95
Chapter - 23. EXV Control SSH, SSH2 ................................................................................................96
23.1. Fast Suction Superheat (Fast SSH) ..........................................................................................................96
23.2. Fast Suction Superheat 2 (Fast SSH2) .....................................................................................................96
23.3. Selecting Fast SSH or Fast SSH2 in MCS-Config.....................................................................................96
23.4. Circuit Base ...............................................................................................................................................96
23.4.1 Selecting the ‘EXV Control’ tab you are prompted with the following:..............................................97
23.4.2 Selection Options..............................................................................................................................97
23.4.3 Compressor EXV Results.................................................................................................................98
23.4.4 MCS EXV Factory Default Set Point.................................................................................................99
23.4.4.1. Fast SSH2, Suction Superheat, Plate HX............................................................................99
23.4.4.2. Fast SSH2, Suction Superheat, DX Coil..............................................................................99
23.4.4.3. Fast SSH, Suction Superheat, DX Barrel.............................................................................99
23.4.4.4. Fast SSH2, Discharge Superheat, DX Barrel.......................................................................99
23.4.4.5. Fast SSH, Suction Superheat, DX Barrel...........................................................................100
23.4.4.6. Suct Spht, Suction Superheat, DX Barrel...........................................................................100
23.5. Set Point Descriptions (Fast SSH & Fast SSH2)......................................................................................100
23.5.1 Set Point Adjustments.....................................................................................................................102
23.5.2 Low Suction Multiplier-SP 13 .........................................................................................................102
23.5.2.1. Low Superheat Adjustment-SP 15 .....................................................................................102
23.5.2.2. EXV Startup Time-SP 20 ...................................................................................................102
23.5.2.3. EXV Compressor Start Delay-SP 20 .................................................................................102
23.5.2.4. EXV Target & EXV Fast Zone-SP 9 ...................................................................................102
23.6. Fast SSH States ......................................................................................................................................103
23.6.1 FAST SSH2 State Format...............................................................................................................103
Chapter - 24. General Introduction to EXV PID ...........................................................................104
24.1. MCS PID REQUIREMENTS.....................................................................................................................104
24.2. Calculations for the adjustment to EXV valve...........................................................................................104
24.3. EXV PID Firmware ..................................................................................................................................104
24.4. MCS PID REQUIREMENTS.....................................................................................................................105
24.5. Selecting PID in MCS-CONFIG................................................................................................................105
24.6. Circuit Base..............................................................................................................................................105
24.7. Selecting the ‘EXV Control’ tab you are prompted with the following:......................................................106
24.8. Selection Options.....................................................................................................................................106
24.9. Compressor EXV Results.........................................................................................................................107
24.10. Set Point Descriptions (PID).....................................................................................................................107
24.11. PID Example Setpoint Defaults................................................................................................................109
24.12. Logic to Determine which K Multipliers to Use.........................................................................................110
24.12.1.1. Switching to Fast K multipliers is based on:.......................................................................110
24.12.1.2. Switching to Slow K multipliers is based on: .....................................................................110
24.12.1 Rate of Change - Moving too Fast..................................................................................................111
24.12.2 Rate of Change - Moving Slow Enough..........................................................................................111
24.13. MCS-Connect Evaporator EXV PID Status..............................................................................................112
24.14. Allowing an Adjustments to the EXV Valve...............................................................................................112
Chapter - 25. EXV Level Control using PID ...................................................................................113
25.1. Setting up EXV Level Control...................................................................................................................113
25.1.1 Setting up EXV Level Control – User Defined................................................................................113
25.1.2 Circuit Base Setup..........................................................................................................................115
25.1.3 Setup using EXV CONTROL WIZARD...........................................................................................115
25.1.4 Low Discharge Superheat EXV Target Adjust Logic.......................................................................116
25.1.4.1. The Low Discharge Superheat logic:..................................................................................116
Chapter - 26. Analog Output Control using PID ..........................................................................118
Chapter - 27. Hardware & Software support information ......................................................120
27.1. OEM Factory Checkout Procedure...........................................................................................................120
27.2. Hardware Trouble Shooting......................................................................................................................120
27.3. The MCS Trouble Shooting Quick Reference Sheet................................................................................120
7
MCS-REFRIG MANUAL
8
MCS-REFRIG MANUAL
1.2. Defrost
This is a procedure, performed periodically to maintain the systems operating efficiency by removing any ice
build-up in the evaporators. A number of defrost methods are supported, refer to documentation on the following
pages.
The type that best suits the installation is selected via the MCS-CONFIG program.
9
MCS-REFRIG MANUAL
The versatility of the Magnum offers the user much flexibility in configuring the controls in an
economical way. The limitation is not the number of boards but the total number of set points.
10
MCS-REFRIG MANUAL
MCS-MAGNUM HARDWARE
REV. 9.1
MCS-MAGNUM hardware has been modified and its new revision number is - 9.1
Hardware modification - Ethernet PHY chip was replaced due to obsolescent of the old
Ethernet PHY chip by the manufacturer.
V7: V17:
HVAC 07.03-V HVAC 17.26-A or greater
CENT 07.03-V CENT 17.26-A or greater
REFR 07.03-V REFR
RTUM 17.26-A or greater
V9: PAO 17.26-A or greater
HVAC 09.14-P ACU 17.26-A or greater
CENT 09.14-P
REFR 09.14-P
RTUM 09.14-P
PAO 09.14-P
ACU 09.14-P
V16:
HVAC 16.11-G
CENT 16.11-G
REFR 16.11-G
RTUM 16.11-G
PAO 16.11-G
ACU 16.11-G
11
MCS-REFRIG MANUAL
MCS-MAGNUM-N
115-230vac-Selectable Power
Keypad 10 Relay Outputs Power
Display Input
Selectable
Power
4 Analog Outputs
Reset Button
4 Digital Outputs
12 Sensor Inputs
Power Green LED Light Communications
12
MCS-REFRIG MANUAL
Address Jumper
Spare Fuse
Keypad Display
10 Relay Outputs 12vdc Power
Input
4 Analog Outputs
Reset Button
4 Digital Outputs
Communications
Power Green LED Light 12 Sensor Inputs
Power Supply is based on number of expansion boards that are being used in the system.
14
MCS-REFRIG MANUAL
15
MCS-REFRIG MANUAL
23
78
4 56
MCS-IO-EXT
MCS-IO-Base - Set to #1
Mount a MCS-IO-EXT
address automatically
is assigned #2
2. Adding MCS-RO-BASE, MCS-RO-EXT
0
9 1
23
78
4 56
MCS-RO-EXT
MCS-RO-Base - Set to #3
Mount a MCS-RO-EXT
address automatically
is assigned #4
4 56
MCS-SI-Base - Set to #3
MCS-SI-EXT
Mount a MCS-SI-EXT
address automatically
is assigned #4
16
MCS-REFRIG MANUAL
23
78
4 56
MCS-IO-EXT
MCS-IO-Base - Set to #1
Mount a MCS-IO-EXT
address automatically
is assigned #2
MCS-IO-BASE #1
23
78
4 56
MCS-IO-Base - Set to #3
MCS-IO-BASE #2
17
MCS-REFRIG MANUAL
18
MCS-REFRIG MANUAL
19
MCS-REFRIG MANUAL
RS-485
MCS-USB-RS485 CABLE
USB PORT
PC with
Windows & MCS-CONNECT
NNECT
20
MCS-REFRIG MANUAL
Ethernet
Port
MCS-Ethernet
Switch
Ethernet Network
etwork
Windows & MCS-CONNECT
S-CONNECT
MCS-Ethernet-Cable
21
MCS-REFRIG MANUAL
able
tC
erne
Eth
Cr
os
so
ve
rE
the
rne
tC
ab
le
22
MCS-REFRIG MANUAL
MCS-CONFIG
SETUP SCREEN
23
MCS-REFRIG MANUAL
From the Keypad/Display the following changes can be made based upon the authorization level:
* Setpoints may have individual authorization levels; you must have the proper authorization to view or edit
them.
**See the Setup screen of the configuration for authorization level(s) that are allowed unlimited resets per
day. Authorization levels below ‘Auth Level Bypass’ are allowed only a limited number of resets. Authori-
zation levels at and above ‘Auth Level Bypass’ are allowed unlimited lockout resets.
***Firmware Version 17.62M, ‘Change RS485 network settings - SERVICE or greater.’
To get authorized through the Keypad/Display do the following:
1. Press ‘Menu’
2. Using , , or keys, move cursor to ‘Passwords’
3. Press key.
4. Enter 4 digit password and press
24
MCS-REFRIG MANUAL
2. Click button.
3. Enter the 4 digit code into the pop-up box and click ok (or press the enter key).
4. Depending on the authorization level, the button will change to one of the following displays, indicating if
the code was accepted or not.
25
MCS-REFRIG MANUAL
26
MCS-REFRIG MANUAL
The Magnum will control the compressor speed in the same matter as the compressor slide. The same
Setpoints will be used. This allows a fixed staged compressor’s capacity to be varied. See previous section for
Setpoints associated with variable capacity control logic.
STAGE 2
Compressor 2’s startup procedure has begun. Once on, the system capacity will be changed to the calculated
% and compressor 1 will be unloaded until it matches the calculated system capacity. Both compressors will
be varied from the calculated to the maximum. All other compressors will be off. The steps Wanted On / Actual
On will be 2 / 2. If the system capacity has been reduced to 45%, or the calculated % (whichever is larger)
and less capacity is needed, a compressor will be turned off and the system capacity will be set to the 90% or
the maximum and the system will return to Stage 1.
STAGE 3
Compressor 3’s startup procedure has begun. Once on, the system capacity will be changed to the calculated
% and compressors 1 and 2 will be unloaded until they equal the required capacity. All compressors will be
varied from the calculated to 100%. The steps Wanted On / Actual On will be 3 / 3. If the system capacity has
been reduced to 60%, and less capacity is needed, a compressor will be turned off and the system capacity
will be set 90% and the system will return to Stage 2.
28
MCS-REFRIG MANUAL
Pump down switch, if on and the compressor is off, will not start the compressor. If the compressor is
on, the system moves to the pump down state to begin the process of turning off the compressor(s) in
normal steps.
Run/Stop, if off the system will not run. This is usually wired to a RUN/STOP switch that is manually
positioned. If the system is running, the system moves all circuits (compressor) to off in normal steps.
Network Run/Stop, if off the system will not run. This input is provided by another system that resides
on the network. It functions in the same matter as the Run/Stop switch.
Emergency Stop switch, if on, the system will be shut down immediately and will remain disabled until
the switch is off.
This option is activated when the set point #70, LO SUCT UNLD, is active. The purpose of this option is to take
corrective action prior to a safety being tripped. When the suction pressure is below the value calculated by
adding the value of this set point to the value of the LOW SUCTION set point for the time specified, the system
will turn on the WARNING relay output if specified in the MCS-Config and take the following action:
For a fixed step compressor, the system will turn off one step of capacity associated with that com-
pressor until that circuit is in an UNLOADED state, which all steps except one are unloaded. The
circuit (compressor) state will be LO SUCT HOLD. The circuit will remain in that state until the capacity
control indicates that another step is to be unloaded or if after 5 minutes the suction pressure has
turned to normal.
For an infinite step compressor, the system will begin unloading that compressor until the suction
pressure rises above the calculated value. During this time the circuit (compressor) state is LO SUCT
UNLOAD. Once this pressure has been reached, the circuit (compressor) state will be LO SUCT
HOLD. The circuit will remain in that state until the capacity control indicates that less capacity is
needed or if after 5 minutes the suction pressure has turned to normal.
Normal pressure is the value calculated by adding the value of the LO SUCT RELD set point #71 to the value of
the LOW SUCTION set point #69.
This option is activated when the set point #74, HI DISC UNLD, is active. The purpose of this option is to take
corrective action prior to a safety being tripped. When the discharge pressure is above the value calculated by
subtracting the value of this set point from the value of the HI DISCH PSI set point for the time specified, the
system will turn on the WARNING relay output if specified in the MCS-Config and take the following action:
For a fixed step compressor, the system will turn off one step of capacity associated with that
compressor until that circuit is in an UNLOADED state, that is all steps except one are unloaded. The
circuit (compressor) state will be HI DISC HOLD. The circuit will remain in that state until the capacity
control indicates that another step is to be unloaded or if after 5 minutes the discharge pressure has
turned to normal.
For an infinite step compressor, the system will begin unloading that compressor until the discharge
pressure drops below the calculated value. During this time the circuit (compressor) state is HI DISC
UNLOAD. Once this pressure has been reached, the circuit (compressor) state will be HI DISC
HOLD. The circuit will remain in that state until the capacity control indicates that less capacity is
needed or if after 5 minutes the discharge pressure has turned to normal.
Normal pressure is the value calculated by subtracting the value of the HI DISC RELD set point #75 from the
value of the HI DISC PSI set point #73.
29
MCS-REFRIG MANUAL
This option is activated when the set point #80, HI DISC UNLD, is active. The purpose of this option is to take
corrective action prior to a safety being tripped. When the discharge temperature is above the value calculated
by subtracting the value of this set point from the value of the HI DISCH TMP set point for the time specified, the
system will turn on the WARNING relay output if specified in the MCS-Config and take the following action:
For a fixed step compressor, the system will turn off one step of capacity associated with that
compressor until that circuit is in an UNLOADED state, that is all steps except one are unloaded. The
circuit (compressor) state will be HI DISC HOLD. The circuit will remain in that state until the capacity
control indicates that another step is to be unloaded or if after 5 minutes the discharge temperature
has turned to normal.
For an infinite step compressor, the system will begin unloading that compressor until the discharge
temperature drops below the calculated value. During this time the circuit (compressor) state is HI
DISC UNLOAD. Once this temperature has been reached, the circuit (compressor) state will be HI
DISC HOLD. The circuit will remain in that state until the capacity control indicates that less capacity
is needed or if after 5 minutes the discharge temperature has turned to normal.
Normal pressure is the value calculated by subtracting the value of the DIS TMPRELD set point #81 from the
value of the HI DISC TMP set point #79.
This option is activated when the set point #67, HI AMPS %, is active. The purpose of this option is to take correc-
tive action prior to a safety being tripped. When the amp draw is within one-half of the calculated HI AMP safety
value, the system will turn on the WARNING relay output if specified in the MCS-Config and take the fol-
lowing action:
• For a fixed step compressor, the system will turn off one step of capacity associated with that compressor until
that circuit is in an UNLOADED state, that all steps except one are unloaded. The circuit (compressor) state will
be HI AMP HOLD. The circuit will remain in that state until the capacity control indicates that another step is to
be unloaded or if after 5 minutes the amp draw has turned to normal.
30
MCS-REFRIG MANUAL
When this option is enabled, the system will rotate the compressors based upon the value in set point # 93.
CMP ROTATION
If the value set point #93 is zero, rotation will occur with every complete capacity cycle and the next compres-
sor will be selected as the lead compressor.
92 LEAD COMP Enables the user to specify the lead compressor. The value of this setpoint will indicate
the lead compressor. If zero, then auto rotation is enabled.
If the ‘Time (sec)’ field is non-zero the compressor with the least amount of run time will
become the lead compressor upon rotation.
93 COMP ROTATION Specifies the number of days between rotations (setpoint #92 must be set to zero to en-
able auto rotation). If zero, then rotation will occur with every cycle.
If the value set point # 93 is zero, rotation will occur with every complete capacity cycle and the next compressor
will be selected as the lead compressor.
Else, the value is the number of days between rotations. At midnight the system will check if it is time to rotate
compressors. If yes, the system will check the run hours on each compressor and select the one with the least
amount of run hours to be the lead compressor.
If set point # 93 is set up as an ALARM type of set point, a compressor rotation message will be generated each
time a compressor is rotated.
31
MCS-REFRIG MANUAL
Run Hour Lockout- At midnight if any compressor has reached a set number of run hours, the unit will be
disabled until an authorized service call is performed.
Function 2: (Compressor lockout based on run time hours)
If this option has been enabled, at midnight if any single compressor exceeds the number of run
hours specified, the system will disable all compressors (circuits) and change the unit state to MAX-
IMUM RUN TIME. This test will only be made a midnight when new day logic is being executed. In
this state the Magnum will not enable normal operations and the only screen that will be available
is the Passwords. If the Magnum is reset the chiller state will be MAXIMUM RUN TIME not UNIT
IN POWER UP. Once the system state is MAXIMUM RUN TIME the system can be accessed from
MCS-Connect but the system will not accept changes to the Relay Output states.
If the value of setpoint #60 minus the amount of time that the compressor has been on is greater than the value
in setpoint #59, the compressor will remain in the anti-cycle state for the period of time specified in setpoint #60.
Else the anti-cycle timer will be set to the value in setpoint #59.
For example:
#59 (ANTI-CYC OFF) = 300 seconds
#60 (ANTI-CYC ON) = 600 seconds
If the compressor had been running for 3 minutes (180 seconds)
600 – 180 = 420 this is greater than setpoint #59; therefore, the anti-cycle timer will be set to 600 seconds, the
value of setpoint #63.
If the compressor had been running for 12 minutes (720 seconds)
600 – 720 = -120 this is less than setpoint #59; therefore, the anti-cycle timer will be set to 300 seconds, the
value of setpoint #59.
If the controller loses power, the length of time that the system was down will be taken into consideration when
determining whether the compressor should be in an anti-cycle state and for how long.
32
MCS-REFRIG MANUAL
Warning Relay Output will also be turned on whenever a circuit is placed in a safety state.
Alarm Relay Output will be turned off whenever the system generates an alarm type of message. This indicates
that a safety or lockout condition has occurred.
The adjustment will be made proportional to the positioning of the wanted on of the slide. If the slide is mi- point
between its minimal and maximum, then the adjustment will be one half of the value in set point #89.
The following table is the result of testing this change: Set point #152 = 10.0. Range is 60 (100.0 – 40.0)
Adjusted Adjusted Adjusted Adjusted Adjusted Adjusted
Values Values Values Values Values Values
Voltage 0.3 .7 1.9 2.1 5.0
% Wanted 40 50 83 89 100
% Of range 0 16 71 81 100
Set PT #119 19.0 19.0 17.7 11.8 10.9 9.0
Set PT #122 20.0 20.0 18.2 12.8 11.9 10.0
Set PT #125 14.0 14.0 12.2 6.8 5.9 4.0
Set PT #127 19.0 19.0 17.2 11.8 10.9 9.0
33
MCS-REFRIG MANUAL
This control strategy is based upon developing a control zone and then to step the compressor(s) through their
stages to maintain the control sensor reading within this zone. To accomplish this, the system will constantly
monitor the control value, its rate of change and position in relationship to the control zone and make adjustments
accordingly.
The strategy of a fixed step system, reciprocating compressor, and a variable (slide) step system, screw compressor
or a reciprocating compressor with an inverter, are slightly different. The variable step system allows for infinite
variations of capacity while the fixed step system does not.
This option is active in all software and is specified in the MCS-Config program.
Setpoint
S #3 Low
wer Deadband
d=1
47
7
Temperature
46
6 Upper Lim
mit
Control Zon
ne + 1
45
5 Target Control Zone
Control Zon
ne - 1
44
4 Lower Lim
mit
43
3
Once the control zone has been established, the system will attempt to keep the control sensor reading with in
this range.
34
MCS-REFRIG MANUAL
35
MCS-REFRIG MANUAL
An alternate control strategy is based on a variable voltage input to the Magnum board. This control strategy is based
upon developing a series of cut in (turn on) and cut out (turn off) values for each capacity stage (step) in the system.
When a cut in value has been reached or exceeded and the delay time between stages (steps) has been satisfied, the
Magnum will turn on the next stage (step). Conversely, when a cut out value has been reached and the delay time
between stages (steps) has been satisfied, the Magnum will turn off a stage (step) that was turned on.
36
MCS-REFRIG MANUAL
The system evaporator temperature must be set up in MCS-Config under the MAG REFR button in the Evaporator
Information section, cell EVAP Temp SI:
4. Setpoint #118 ‘TARGET TYPE’ - if setpoint #118 is configured as a “Target” type, then setpoint #118 high
zone column is used as the ambient disable temperature for rotating coil defrost. Otherwise if setpoint #118 is
not configured at “Target” type the old logic of using setpoint #118 value aa the ambient disable point for rotating
coil defrost is used.
5. Set the manual defrost time delay based on the enter temp, high return temp less defrost time required.
If setpoint #120 is setup as “Target” type then manual defrost time delay is based on the enter temp compared
to setpoint #118, 121, and 124 and uses the values in the high zone column from setpoint #120, 123, or 126
as the defrost time delay.
37
MCS-REFRIG MANUAL
When in dehumidification, if the approach value satisfies the approach setpoints, the logic will turn off LLS #1 and
Turn on LLS #2. There, the logic will monitor the approach for the 2nd LLS. Once the 2nd LLS’s approach value
meets the defrost setpoint requirements, a defrost cycle will be initiated.
If not in dehumidification mode, the defrost approach temperature and defrost duration is established by comparing
the systemDefrost Durationtemperature
evaporator = set
to point #120 #118, #121 and #124.
set points
If the system
systemevaporator
evaporatortemperature
temperature is input
greater than #124,
sensor DEF LOW
is greater TEMPDEF
than #121, but less
MED than #121,then
TEMP, DEFthe
MED
approach set
TEMP, then the approach set up will be based
up will be based upon the high temperature values. upon the medium temperature values.
Approach Temperature = set point #122
Approach Temperature = set point #119
Defrost Duration = set point #123
Defrost Duration = set point #120
If the system evaporator temperature is greater than #124, DEF LOW TEMP but less than #121, DEF MED
If not inthen
TEMP, dehumidification
the approachmode,
set up the defrost
will be basedapproach
upon thetemperature and defrost
medium temperature duration is established by comparing
values.
the system evaporator temperature to
Approach Temperature = set point #122set points #118, #121 and #124.
Defrost Duration = set point #123
If the system evaporator temperature is greater than #124, DEF LOW TEMP but less than #121, DEF MED TEMP,
then
If the the approach
system set up
evaporator will be based
temperature upon
is less the
than medium
#124, DEF temperature
LOW TEMP, values.
then the approach set up will be
Approach the low temperature
based uponTemperature values.
= set point #122
Approach Temperature = set point #125
Defrost Duration = set point #123
Defrost Duration = set point #126
If the system evaporator temperature is less than #124, DEF LOW TEMP, then the approach set up will be based
After a defrost cycle, the pre defrost approach values will remain for the time specified in set point #131 then
upon the low temperature values.
they will be reestablished according to the evaporator temp sensor input value.
Approach Temperature = set point #125
If the evaporator
Defrost temp sensor
Duration = setinput value
point #126reads greater than setpoint #118, defrost will be disabled.
Thesecycle,
After a defrost valuesthe
are displayed
pre in both thevalues
defrost approach MCS-Connect program
will remain and on
for the time the Magnum
specified screen
in set point under
#131 status.
then they will be reestab-
lished according to the evaporator temp sensor input value.
MCS-Connect
If the evaporator program
temp sensor under
input thereads
value Status tab: than setpoint #118, defrost will be disabled.
greater
These values are displayed in both the MCS-Connect program and on the Magnum screen under status.
MCS-Connect program under the Status tab:
NOTE:
NOTE:The
Theapproach setpoint
approach set point and
and time
time (duration)
(duration) will bewill be displayed
displayed for eachfor each circuit.
circuit.
11.1.2. Approach type based circuit evaporator temperature
38
The actual circuit approach temperature is the calculated as follows:
MCS-REFRIG MANUAL
The evaporator suction temperature will be the evaporator suction pressure converted to temperature.
If the evaporator suction pressure sensor has not been specified then the evaporator suction temperature will
be the circuit suction pressure plus the value of set point #203, SAT EVAP DIFF which is then converted to
temperature..
This value is displayed for each circuit in MCS-Connect under the Status Tab in the column “Evap.
If theApproach/Time”.
evaporator suction pressure sensor has not been specified then the Circuit Suction Pressures value will be
converted into temperature according to the refrigerants PT Chart. This value is subtracted from the systems
return temperature sensors value. This will be the approach value for that evaporator.
For circuit 1) the 12.4F is the calculated circuit evaporator temperature and time of 00:02:00 is the time that
this temperature must be greater than the Defrost Approach temperature. This time is based upon the value of
This value is displayed
set point #137, DEFfor each
APPRcircuit
TIME.inWhen
MCS-Connect under the
the compressor Status Tab
is running and in
thethe column “Evap.
temperature Approach/Time”.
is greater than the
For circuit 1)defrost
the 12.4F is the calculated circuit evaporator temperature and time of 00:02:00 is the time
approach temperature this counter will be decremented. If the temperature is less then it will that
bethis tempera-
reset to
ture must be greater than the Defrost
the value in set point #137. Approach temperature. This time is based upon the value of set point #137, DEF APPR
TIME. When the compressor is running and the temperature is greater than the defrost approach temperature this counter will
be decremented. If the temperature is less then it will be reset to the value in set point #137.
This value is display locally on the Magnum LCD under “Approach”.
This value is display locally on the Magnum LCD under “Approach”.
MAG REFR software will turn on a relay output when the system is getting ready to enter a defrost cycle. This
must be setup in the cell “Defrost Slave” Indicator in the Evaporator Information section under the MAG REFR
button. If not in defrost this relay output will be off.
12
39
MCS-REFRIG MANUAL
40
MCS-REFRIG MANUAL
Defrost Types are selected in the Evaporator Information Section under the MAG REFR in the MCS-Config
program. If AIR Defrost Type is YES, then the Standard Defrost Type selected will be used as backup.Defrost -
None
No defrost is performed. The defrost approach will indicate NO DEF. One liquid line solenoid is required no other defrost relay
output points are required.
DEF-START
Normal PUMP DOWN DEFROST COILS PUMP DOWN DRIP DOWN
CMP
Comp ON ON ON ON (StPt #166) ON OFF
LLS #1 ON ON OFF OFF OFF OFF
LLS #2 ON ON OFF OFF OFF OFF
REV VALVE OFF OFF OFF ON OFF OFF
The DEF-PUMP DOWN state can be terminated for the following reasons:
• Time in state exceeds the value of set point #141.
• Suction pressure decreases by more than the value of set point #142
The DEFROST COILS state can be terminated for the following reasons:
• Time in state exceeds the time indicated by set point #120 if high temperature, set point #123 if
medium temperature, set point #126 if low temperature, or set point #128 if in dehumidify mode.
• Evaporator temperature is equal to or greater than value of set point #143.
• Discharge pressure is equal to or less than value of set point #144.
41
MCS-REFRIG MANUAL
Normal DEF-START CMP PUMP DOWN DEFROST COILS PUMP DOWN DRIP DOWN
Comp ON ON ON ON ON OFF
LLS #1 ON ON OFF OFF OFF OFF
LLS #2 ON ON OFF OFF OFF OFF
Hot Gas Main OFF OFF OFF ON (StPt #135) OFF OFF
Hot Gas Def 1 OFF OFF OFF ON OFF OFF
Hot Gas Def 2 OFF OFF OFF ON OFF OFF
Hot Gas Bleed OFF OFF OFF ON OFF OFF
The DEF-PUMP DOWN state can be terminated for the following reasons:
• Time in state exceeds the value of set point #141.
• Suction pressure is equal to or less than value of set point #142.
The DEFROST COILS state can be terminated for the following reasons:
• Time in state exceeds the time indicated by set point #120 if high temperature, or set point #123
if medium temperature, or set point #126 if low temperature or set point #128 if in dehumidify
mode.
• Evaporator temperature is equal to or greater than value of set point #143.
• Discharge pressure is equal to or less than value of set point #144.
12.11. Defrost - Hot Gas on the Fly (set point #117 = Inactive)
This type of defrost requires the circuit to consist of two separate evaporators with a liquid line and a hot gas sole-
noid for each. When a defrost cycle is required, the circuit will defrost one evaporator at a time. The circuit states
will indicate which evaporator is in a defrost mode.
42
MCS-REFRIG MANUAL
Following table shows the status of the circuit RO’s when in various defrost states. The compressor states are
not shown. When a defrost cycle begins, the circuit states will move from left to right as indicated below until both
evaporators have been defrosted and then the circuit will return to a normal state.
Normal DEF EVAP #1 DRIP DOWN #1 DEF EVAP #2 DRIP DOWN #2 NORMAL
Comp ON ON ON ON ON ON
LLS #1 ON OFF OFF ON ON ON
LLS #2 ON ON ON OFF OFF ON
HOT GAS MAIN OFF ON (StPt #135) OFF ON (StPt#135) OFF OFF
HOT GAS DEF 1 OFF ON OFF OFF OFF OFF
HOT GAS DEF 2 OFF OFF OFF ON OFF OFF
HOT GAS BLEED OFF ON OFF ON OFF OFF
The DEFROST COILS state can be terminated for the following reasons:
• Time in state exceeds the time indicated by set point #120 if high temperature, set point #123 if
medium temperature, or set point #126 if low temperature.
• Evaporator temperature is equal to or greater than value of set point #143.
• Discharge pressure is equal to or less than value of set point #144.
43
MCS-REFRIG MANUAL
Once this time expires, the compressor will enter the “Off /Ready” state. At this instant, the next compressor in
the sequence will be placed into the “Def – Air Normal” state. The compressor that just finished it’s defrost cycle,
will be started and will run together for the time in setpoint #245. Once this time expires, the compressor slated
for defrost will be cycled OFF.
This procedure will continue for ALL compressors on the unit.
If a Backup Defrost option was selected, the logic will continue to monitor evap approach for running compres-
sors, if any approach values rise above the calculated backup defrost setpoints (Setpoints #118 through #126),
then a backup defrost will be initiated.
• #247, Reheat offset OFF, subtracted from the reheat stage on value, to determine when a heater
will be turned off.
• #248 -253, REHT STAGE #; voltage value: will enable reheat from 1 through 6 (these function like
the STAGE # ON set points.
45
MCS-REFRIG MANUAL
• Unit state will be DEFROST COILS and the circuit state will be DEFROST COILS. In this state all
reheat relays will be on and all other relays will be off, the reheat solenoids are providing the heat
for the defrost cycle and the sensor input allowing reheat and the number are ignore. Circuit will
remain in this state until the defrost time has been reached or the evaporator temperature is equal
to or greater than the value of set point # 143
• Unit state will be DEFROST COILS and the circuit state will be DRIP DOWN. In this state all circuit
relays will be off. The circuit will remain in this state for time in the value cell of set point #132.
• If the return (EVAP temp) temperature is above the HIGH DEFROST TEMPERATURE then all
evaporator relays will be ON and all reheat relays will be OFF.
• If the return (EVAP temp) temperature is less than or equal to the HIGH DEFROST TEMPERA-
TURE then one less than the number of evaporator relays will be ON. The evaporator relays can be
rotated based upon set point #134, this will enable a reheat relay to be turned ON.
• If compressor is on then only one half of the evaporator relays are on others will be off.
• If set point #134 is active and its value is greater than zero; then the evaporator relays will
be rotated based upon the value of this set point. Value is expressed in minutes.
If the sensor allowing reheat is on and the voltage sensor indicating the number of reheat relays
that can be turned will allow up to one half reheat relays to be turned on. If the evaporator relays
are rotated, the reheat relays will also be rotated.
46
MCS-REFRIG MANUAL
MAG REFR software will turn on a relay output when the system is in the dehumidification mode. This must be setup
in the cell “Dehumidify Indicator” in the Evaporator Information section under the MAG REFR button. If not in dehu-
midification mode this relay output will be off.
When the Dehumidification Enable sensor is on, the approach temperature and time will be changed to the values in
set point #127, DEF DEH APPR for temperature, and set point #128, DEF DEH TIME for time. When is indicator is
on, the system will provide only half of its cooling capacity.
When in dehumidification, if the approach value satisfies the approach setpoints, the logic will turn off LLS #1 and
Turn on LLS #2. There, the logic will monitor the approach for the 2nd LLS. Once the 2nd LLS’s approach value meets
the defrost setpoint requirements, a defrost cycle will be initiated.
47
MCS-REFRIG MANUAL
If this temperature is greater than set point #118, DEF HI TEMP, then no defrost is required. Approach will indicate
NO DEF.
If the temperature is less than set point #118 but greater than set point #121, DEF MED TEMP; the approach set point tem-
perature will be set point #119, DEF HI APPR and the time will be set point #120, DEF HI TIME.
If the temperature is less than set point #121 greater than set point #122, DEF LOW TEMP; the approach setpoint tem-
perature will be set point #122, DEF MED APPR and the time will be set point #123, DEF MED TIME.
If the temperature is less than set point #124, DEF LOW TEMP; the approach set point temperature will be set point #125,
DEF LOW APPR and the time will be set point #126, DEF LOW TIME.
48
MCS-REFRIG MANUAL
The evaporator suction temperature will be the evaporator suction pressure converted to temperature.
If the evaporator suction pressure sensor has not been specified then the evaporator suction temperature will be the circuit
suction pressure plus the value of set point #203, SAT EVAP DIFF which is then converted to temperature..
This value is displayed for each circuit in MCS-Connect under the Status Tab in the column “Evap. Approach/Time”.
49
10. Magnum
MCS-REFRIG MANUALDisplays
13. Magnum Displays
13. 10.1.
Magnum Displays
Menu Key
Chapter - 15. Magnum Displays
13.1. Menu Key
Pressing the ‘Menu’ key provides the following: The display shows options available.
13.1. Menu Key
15.1. Menu Key the ‘Menu’ key provides the following: The display shows options available.
Pressing
ACTUAL DISPLAY DESCRIPTION
Pressing the ‘Menu’ key provides the following: The display shows options available.
ACTUAL DISPLAY DESCRIPTION
ACTUAL
09:56 Main Menu DISPLAY HH:MM Screen Title DESCRIPTION
-Status -Setpoints -Control Status Display -Active set pts Display
-Outputs -Serv Tools
09:56 Main Menu -Relay/Analog
HH:MM Display
Screen Title -Service Tools Display
-Inputs
-Status -Lckout RST
-Setpoints
09:56 Main Menu -Sensor
-Control
HH:MM Input Display
Status Display
Screen Title -Lockout Reset
-Active set ptsDisplay
Display
-Alarms
-Outputs
-Status -Lckout
-Serv ALM
Tools
-Setpoints -Alarm Display
-Relay/Analog
-Control StatusDisplay
Display -Lockout
-Service Alarm
Tools
-Active set Display
ptsDisplay
Display
-Graphs
-Inputs
-Outputs -Passwords
-Lckout RST
-Serv Tools -Graphing
-Sensor Display
Input Display
-Relay/Analog Display -Password
-Lockout Display
-Service Reset
Tools Display
Display
Help
-Alarms
-Inputs -Lckout
-Lckout ALM
RST Help
-Alarm
-SensorDisplay
Input Display -Lockout
-Lockout Alarm
Reset Display
Display
-Graphs
-Alarms -Passwords
-Lckout ALM -Graphing Display
-Alarm Display -Password Display
-Lockout Alarm Display
Help
-Graphs -Passwords Help
-Graphing Display -Password Display
Help Help
10.3. Status
15.3. Status DisplayDisplay – Circuit
– Circuit (x) (x)
13.3. Status Display – Circuit (x)
The CURRENT STATE OF A CIRCUIT.
13.3. The
Status Display – Circuit (x)
display shows the current capacity of circuit (x) and how long we have been at this level. By
Thepressing
CURRENT PG youOF
the STATE willAgo back to the Chiller state display OR PG you will get additional
CIRCUIT.
The displayon
Theinformation
CURRENT shows
STATE the current capacity of circuit (x) and how long we have been at this level. By
this circuit. CIRCUIT.
OF A
The display
pressing the shows
PG↑ you thewill
current capacity
go back to theof circuitstate
Chiller (x) and howOR
display longPG
we↓ have been
you will get at this level. By
additional
information
ACTUAL theonPG
pressingDISPLAY ↑ you
this will go back to the Chiller state display
circuit. OR PG↓ you will get additional
DESCRIPTION
information on this circuit.
09:56 ACTUAL
CMP #(x) DISPLAY+5.0v HH:MM DESCRIPTION
CIRCUIT CTL VOLTAGE
CMPACTUAL
OFF/READYDISPLAY CURRENT DESCRIPTION
CONTROL STATE
09:56 000:00;30
CMP #(x) +5.0v HH:MM TIME IN CURRENT
CIRCUIT STATE CTL VOLTAGE
SUCT
09:56 DISC
CMP CMP OPD
OFF/READY
#(x) MOTOR
+5.0v SUCTION
HH:MM DISCHARGE OIL DIFFERENTIAL
CURRENT CONTROL
CIRCUIT STATE CTL MOTOR
VOLTAGE
66P 190P 134P
000:00;30
CMP OFF/READY 0% PRESSURE PRESSURE
TIME IN CURRENT
CURRENT PRESSURE
CONTROL STATE
STATE AMP %
55F
SUCT 177F
DISC ----
OPD
000:00;30 OK
MOTOR TEMPERATURE
SUCTION TEMPERATURE
DISCHARGE ----
OIL DIFFERENTIAL
TIME IN CURRENT STATE STATUS
MOTOR
66P
SUCT DISCPG 134P
190P OPD 0%
PG
MOTOR PRESSURE
SUCTION PAGE OIL
PRESSURE
DISCHARGE UP PRESSURE
DIFFERENTIAL PAGEAMPDN%
MOTOR
55F
66P 177F
190P ----
134P OK
0% TEMPERATURE
PRESSURE TEMPERATURE
PRESSURE ----
PRESSURE STATUS
AMP %
55F 177F PG↑ ---- OK↓
PG TEMPERATURE PAGE UP ----
TEMPERATURE PAGE DN
STATUS
PG↑ PG↓ PAGE UP PAGE DN
09:55 DEFROST
By pressing#(X) the+5.0V
PG you will go HH:MM
back to the DEFROST INFORMATION
previous display OR PG you willCTL get VOLTAGE
information on the
Nxt Air Defr 01:58:23
EVAP next
Triggercircuit. After all
Delay circuit Time when
information is next air
displayed defrost
pressingis scheduled,
the PG willwill decrement
return the user to the chiller
pressing the PG
Bydisplay. ↑ you will go Evap
back to the previous
pressure OR PG↓ youDelay
display pressure
Trigger will getfor
information
triggeron the
41.1 By pressing the PG↑ you will go back
50.0 3:00
PSI to the previous displayPSI OR PG↓ you will getdecrementing
Counter information on the
EVSat next circuit. After
EVSht all circuit information
E Lead is displayed pressing the PG↓ will return the user to the chiller
next circuit. After 1all circuit information is displayed
Evap Sat. SHEATthe PGEvap
pressing
Evap ↓ will return
Lead the user to the chiller
18.1 display.
87.4
display.
PG↑ PG↓
TEMP TEMP #
10.4. Outputs PAGE UP PAGE DN
13.4.Selecting
13.4. Outputs
Outputs the ‘Outputs’ option provides the following:
15.4. Outputs
By
Selectingpressing
ACTUAL
Selecting the PG
the ‘Outputs’
DISPLAY
the ‘Outputs’ ↑ youprovides
option
option will go back
provides to the previous display
the following:
the following: OR PG↓ you will get information on the
DESCRIPTION
Selecting thenext
‘Outputs’
circuit.option provides
After all the following:
circuit information is displayed pressing the PG↓ will return the user to the chiller
display. DISPLAY
ACTUAL DESCRIPTION
ACTUAL DISPLAY DESCRIPTION
09:56 Outputs HH:MM Screen Title Left/Right Arrow
Relays Status RO position & names Current status of RO
13.4.
09:56 Outputs
M-1 COMP1A
Outputs Lck Off HH:MM
HH:MM
Screen Title
Screen
Left/Right Arrow
09:56
Relays Outputs Status
M-2 COMP1B
Lck Off ROUsing Left/Right
position & names arrowTitle
allows
Current Left/Right
user to view
status of ROArrow
all data
Relays
M-3COMP1A
LOAD1 Status
LckOff
Off RO position & namesfor RO’sCurrent status of RO
displayed
M-1 Lck
M-1
M-2 COMP1A
M-4Selecting
COMP1B Lck
LckOff
UNLOAD the ‘Outputs’
Lck Off
Off option provides the following:
Using Left/Right arrow allows user to view all data
M-2 COMP1B PGLck Using Left/Right
Switch to AO’s arrow allows
Page up user to viewPage
all down
data
Anlog
M-3 LOAD1 Lck Off
Off PG for RO’s displayed
for RO’s displayed
M-3 LOAD1
M-4 UNLOAD Lck Off
Lck Off
ACTUAL DISPLAY
M-4 UNLOAD Lck Off Switch to AO’s DESCRIPTION
Page up Page down
Anlog PG↑ PG↓ Switch to AO’s Page up Page down
Anlog PG↑ PG↓
SelectingSelecting
the Pagethe
Down
Pageoption
Down provides the following:
option provides the following:
52
MCS-REFRIG MANUAL
Selecting the Page Down option provides the following:
Selecting the Page Down option provides the following:
Selecting
Selecting the PagetheDown
Page option
Down option provides the following:
ACTUAL DISPLAY provides the following: DESCRIPTION
ACTUAL DISPLAY DESCRIPTION
ACTUAL DISPLAY DESCRIPTION
09:56 Inputs HH:MM Screen Title Left/Right Arrow
09:56
Sensor Inputs
Value HH:MM Screen Title
SI position & names Left/Right
Current status of SIArrow
09:56
Sensor Inputs
M-13RUN/STOP
Value
RUN Man HH:MM Screen
SI position & names Title Left/Right
Current status of SIArrow
Sensor
M-13RUN/STOP Value
RUN SI position
Using & names
Left/Right Current
arrow allows userstatus of all
to view SI data
M-14PHASLOSS NO Man
M-13RUN/STOP
M-14PHASLOSS RUN Man
NO Man Using Left/Right for
arrow allows
SI’s user to view all data
displayed
M-14PHASLOSS NO Man Using Left/Right for
arrow
SI’sallows user to view all data
displayed
Switch to AO’s for SI’s
Page updisplayed Page down
Anlog PG PG Switch to AO’s Page up Page down
Switch to AO’s Page up Page down
Anlog PG PG
Anlog PG PG
53
MCS-REFRIG MANUAL
Selecting
Selectingthethe
Page Down
Page option
Down provides
option thethe
provides following:
following:
ACTUAL
ACTUALDISPLAY
DISPLAY DESCRIPTION
DESCRIPTION
09:56
09:56Setpoints
Setpoints HH:MM
HH:MM Screen
ScreenTitleTitle Left/Right
Left/RightArrow Arrow
Name
Name Value
Value This set point defines the width of each control zone.
This set point defines the width of each control zone. EXVEXV load
loadadjustments
adjustments
1010SPRHT
SPRHTZONE+- 2.5F
1111EXV
ZONE+- 2.5F areare
made
madein response
in responseto to
a load
a loador or
unload
unload slide adjustment.
slide adjustment. EXVEXVfine
fine
EXVLOAD
LOADADJ
ADJ 0.5%
0.5% adjustments are made when in the 1 st
zone
st above or below the control
1212EXV
EXV FINEADJ
FINE ADJ 0.1%
0.1% adjustments are made when in the 1 zone above or below the control
1313EXV
EXVCOURSE
COURSE 0.5%
0.5% zone. The
zone. TheEXVEXVcourse adjustment
course adjustment is made
is madewhen
whenin the 2nd2zone
in the nd above
zone aboveor or
PGPG
PGPG below the control zone. Use left/right arrows to see time and type.
below the control zone. Use left/right arrows to see time and type.
.. Page
Pageupup Page
Pagedown down
Selecting
Selectingthethe
Page Down
Page option
Down provides
option thethe
provides following:
following:
ACTUAL
ACTUALDISPLAY
DISPLAY DESCRIPTION
DESCRIPTION
09:56
09:56Setpoints
Setpoints HH:MM
HH:MM Screen
ScreenTitleTitle Left/Right
Left/RightArrow Arrow
Name
Name Value
Value EXV Load Division: Max slide% – min slide% /
EXV Load Division: Max slide% – min slide% / Max Max vlv%
vlv%- min vlv%)
- min +1.+1.
vlv%)
1414EXV
EXVLOAD
LOADDIV 33
1515EXV
DIV Minimum valve position allowed when modulating the expansion
Minimum valve position allowed when modulating the expansion valve. valve.
EXVMIN
MIN% % 10.0%
10.0%
1616EXV
EXVMAX
MAX% % 50.0%
50.0%
Maximum
Maximum position allowed
position allowedwhen
whenmodulating thethe
modulating expansion
expansion valve.Low
valve. Low
1717LOLOSUPERHEAT
SUPERHEAT 2.0F
2.0F Superheat value before alarm is generated. Use
Superheat value before alarm is generated. Use left/right left/right arrows
arrowsto to
PGPG
PGPG see time and type.
see time and type.
.. Page
Pageupup Page
Pagedowndown
Selecting
Selectingthethe
Page Down
Page option
Down provides
option thethe
provides following:
following:
ACTUAL
ACTUALDISPLAY
DISPLAY DESCRIPTION
DESCRIPTION
09:56
09:56Setpoints
Setpoints HH:MM
HH:MM Screen
ScreenTitle
Title Left/Right
Left/RightArrow
Arrow
Name
Name Value
Value
1818LOSUCTPSIDLY
LOSUCTPSIDLY 30s
30s Delay in seconds
Delay in secondswhen
whenin Low
in LowSuction
SuctionPSI Opening.
PSI Opening.Delay
Delayin seconds
in seconds
1919EXV
EXVDELAY
DELAY 60s
60s between valve adjustments. Time in seconds to to
hold thethe
valve at at
thethe
start
2020EXV between valve adjustments. Time in seconds hold valve start
EXVSTRT
STRTTME
TME 5s5s %%setset
point when the compressor starts. Delay in seconds to power
point when the compressor starts. Delay in seconds to power up. up.
2323POWERUP
POWERUPDLAY 30s
DLAY
PGPG
30s
PGPG Use left/right
Use arrows
left/right to to
arrows see time
see and
time andtype.
type.
Page up
Page up Page
Pagedown down
Selecting
Selectingthethe
Page Down
Page option
Down provides
option thethe
provides following:
following:
ACTUAL
ACTUALDISPLAY
DISPLAY DESCRIPTION
DESCRIPTION
09:56
09:56Setpoints
Setpoints HH:MM
HH:MM Screen
ScreenTitle Title Left/Right
Left/RightArrow Arrow
Name
Name Value
Value This
Thisvalue
valueis used
is usedto to
adjust
adjustthethe
speed
speedof of
responding
responding to to
changes
changes in the
in the
2525STEP
STEPSENSIT
SENSIT 11 control
controlalgorithm.
algorithm. Time
Timedelay
delaybefore increasing
before increasing or or
decreasing
decreasingthethe
number
number
2626STEP
STEPDELAY
DELAY 300s
300s of of
refrigeration steps. Maximum negative Rate OfOf Change allowed before
2727MAX refrigeration steps. Maximum negative Rate Change allowed before
MAXROC-
ROC- -0.6P
-0.6P stopping
stopping thetheunit from
unit loading.
from loading.Maximum
Maximum positive
positiveRate
RateOfOf
Change
Change allowed
allowed
2828MAX ROC+ 0.6p
MAX ROC+
PGPG
0.6p
PGPG before
beforestopping
stopping thethe
unit from
unit fromunloading. Use
unloading. left/right
Use arrows
left/right to to
arrows see time
see time
andandtype.
type. Page
Pageupup Page
Pagedown down
Selecting
Selectingthethe
Page Down
Page option
Down provides
option thethe
provides following:
following:
ACTUAL
ACTUALDISPLAY
DISPLAY DESCRIPTION
DESCRIPTION
09:56
09:56Setpoints HH:MM Screen
Name
Setpoints
Value HH:MM ScreenTitleTitle Left/Right
Left/RightArrow Arrow
Name Value Number of seconds between the samples
Number of seconds between the samples used forused for calculating thethe
calculating actual
actual
2929ROC
ROCINTERVAL
INTERVAL 30s
30s Rate OfOf
Change. Maximum slide or or
speed allowed. Minimum slide or or
3030MAX Rate Change. Maximum slide speed allowed. Minimum slide
MAXSLIDE
SLIDE% % 100.0%
100.0% speed allowed. Maximum percentage adjustment change that can bebe
3131MIN
MINSLIDE
SLIDE% % 55.0% speed allowed. Maximum percentage adjustment change that can
55.0% made. Use 54
left/right arrows to see time and type.
3232MAX
MAXADJUST
ADJUST% % 5.0%
5.0% made. Use left/right arrows to see time and type.
PGPG
PGPG
Page
Pageupup Page
Pagedown
down
25STEP SENSIT 1 control algorithm. Time delay before increasing or decreasing the number
26STEP DELAY 300s of refrigeration steps. Maximum negative Rate Of Change allowed before
27MAX ROC- -0.6P stopping the unit from loading. Maximum positive Rate Of Change allowed
28MAX ROC+ 0.6p
MCS-REFRIG MANUAL PG PG before stopping the unit from unloading. Use left/right arrows to see time
and type. Page up Page down
Selectingthe
Selecting thePage
PageDown
Downoption
option provides
provides thethe following:
following:
Selecting
Selecting thethe Page
Page Down
Down option
option provides
provides thethe following:
following:
ACTUAL
ACTUAL DISPLAY
DISPLAY DESCRIPTION
DESCRIPTION
09:56
09:56 Setpoints
Setpoints HH:MM
HH:MM Screen
Screen Title
Title Left/Right
Left/Right Arrow
Arrow
Name
Name Value
Value System
System checks
checks for for
lowlow suction
suction pressure
pressure for for
eacheach running
running compressor.
compressor.
77 77
LOWLOW SUCTION
SUCTION 20.0P
20.0P Value
Value to take
to take corrective
corrective action
action before
before a low
a low suction
suction pressure
pressure safety
safety occurs.
occurs.
78 78
LO LO SUCT
SUCT UNLD
UNLD 2.0P
2.0P Value
Value to increase
to increase to until
to until thethe compressor
compressor willwill return
return to normal
to normal control.
control.
79 79
LO LO SUCT RELD 4.0P
suction pressure thatthat is unsafe forfor each
SUCT RELD 4.0P System checks
80 80 UNSAFE
UNSAFE SUCT
SUCT 5.0P
5.0P System checks for for
lowlow
suction pressure is unsafe each
PGPG PGPG
running compressor. Use left/right arrows to see
running compressor. Use left/right arrows to see time and type. time and type.
PagePage up up PagePagedowndown
Selecting
Selecting thethe Page
Page Down
Down option
option provides
provides thethe following:
following:
ACTUAL
ACTUAL DISPLAY
DISPLAY DESCRIPTION
DESCRIPTION
09:56
09:56 Setpoints
Setpoints HH:MM
HH:MM Screen
Screen Title
Title Left/Right
Left/Right Arrow
Arrow
Name
Name Value
Value High
High discharge
discharge pressure
pressure condition
condition for for
eacheach running
running compressor.
compressor. Value
Value to to
81 81
HI HI DISC
DISC PSIPSI 350.0P
350.0P take
take corrective
corrective action
action before
before a high
a high discharge
discharge pressure
pressure safety
safety occurs.
occurs.
82 82
HI HI DISC
DISC UNLD
UNLD 10.0P
10.0P Value
Value to reload
to reload highhigh discharge
discharge pressure.
pressure. Low
Low discharge
discharge pressure
pressure
83 83
HI HI DISC
DISC RELD
RELD 30.0P
30.0P compared
compared to the
to the sensor
sensor reading
reading to this
to this value.
value. UseUse left/right
left/right arrows
arrows to see
to see
85 85
LO LO DISC
DISC PSIPSI 120.0P
120.0P time and type.
PGPG PGPG time and type.
PagePage up up Page
Page downdown
Selecting
Selecting thethe Page
Page Down
Down option
option provides
provides thethe following:
following:
ACTUAL
ACTUAL DISPLAY
DISPLAY DESCRIPTION
DESCRIPTION
09:56
09:56 Setpoints
Setpoints HH:MM
HH:MM Screen
Screen Title
Title Left/Right
Left/Right Arrow
Arrow
Name
Name Value
Value High
High discharge
discharge temperature
temperature condition
condition for for
eacheach circuit
circuit thatthat
hashas at least
at least oneone
87 87
HI HI DISCH
DISCH TMPTMP 215.0F
215.0F step
step on.on. Value
Value to take
to take corrective
corrective action
action before
before a high
a high discharge
discharge
88 88
HI HI DISC
DISC UNLD
UNLD 2.0F
2.0F temperature
temperature safety
safety occurs.
occurs. Value
Value to reload
to reload highhigh discharge
discharge temperature.
temperature.
89 89
HI HI DISC RELD 5.0F
. .
DISC RELD 5.0F Low differential oil pressure compared to the calculated differential oil value
91 91
LOWLOW OIL
OIL DIFDIF 70.0P
70.0P Low differential oil pressure compared to the calculated differential oil value
PGPG PGPG UseUse left/right
left/right arrows
arrows to see
to see time
time andand type.
type.
Page
Page up up PagePage downdown
Selecting
Selecting
Selecting thethe
the Page
Page
Page Down
Down
Down option
option
option provides
provides
provides the
thethe following:
following:
following:
ACTUAL
ACTUAL DISPLAY
DISPLAY DESCRIPTION
DESCRIPTION
09:56
09:56 Setpoints
Setpoints HH:MM
HH:MM Screen
Screen Title
Title Left/Right
Left/Right ArrowArrow
Name
Name Value
Value System
System checks
checks for for
lowlow differential
differential oil pressure
oil pressure compared
compared to the
to the calculated
calculated
92 92 UNSAFE
UNSAFE OIL
OIL 20.0P
20.0P differential
differential oil pressure.
oil pressure. System
System checks
checks for for
highhigh motor
motor temperature
temperature
95 95 MOTOR
MOTOR FAULT
FAULT 0 0 compared
compared to the
to the sensor
sensor reading.
reading. Pressure
Pressure indicating
indicating a dirty
a dirty oil filter
oil filter
97 97 DirtyOilFltr
DirtyOilFltr 50.0P
50.0P (discharge
(discharge minus
minus thethe oil filter
oil filter pressure).
pressure). Time
Time (in (in seconds)
seconds) to hold
to hold before
before
101SAFETY
101SAFETY HOLD
HOLD 90s90s
trying to reload when avoiding a safety. Use left/right arrows
trying to reload when avoiding a safety. Use left/right arrows to see time to see time
PGPG PG
PG
andand type.
type. PagePage up up Page Pagedown down
Selecting
Selecting thethe Page
Page Down
Down option
option provides
provides thethe 56
following:
following:
Selecting
Selecting thethe Page
Page Down
Down optionprovides
option providesthe
thefollowing:
following:
57
MCS-REFRIG MANUAL
The status of both the CAPACITY CONTROL STATES and CIRCUIT CONTROL STATES can be viewed from
the MCS-Connect program by accessing the CONTROL STATUS key under status screen. The following will be
displayed:
Use your arrow keys to access all information (Active circuits will be displayed)
58
MCS-REFRIG MANUAL
59
MCS-REFRIG MANUAL
As we review the various states, we must remember that a chiller package consists of a number of dif-
ferent parts or functions: the compressors and their related items such as unloaders hot gas bypasses,
etc.; evaporator; and condensing functions. To control these functions the states will be divided into
three sections:
This information can be viewed form the Magnum’s display, see section Magnum Displays or from MCS-
Connect, see section MCS-Connect Status.
60
MCS-REFRIG MANUAL
61
MCS-REFRIG MANUAL
62
MCS-REFRIG MANUAL
18.21. DEF-STARTING CMP (20) (only used if not Air Normal Defrost)
This state is entered when a capacity steps has indicated a need for defrosting. The system will remain in this
state until the defrosting circuits discharge pressure is less than the value in set point #141, DEF Min PSI or the
time in this state is greater than the value in set point #142.
18.22. DEFROSTING COILS (21) (only used if not Air Normal Defrost)
This state is entered when the defrosting circuits discharge pressure is less than the value in set point #139, DEF
Min PSI. The system will remain in this state until the defrosting function has been completed.
63
MCS-REFRIG MANUAL
The action of the circuit control states actually result in more, less or no change in the amount of cooling capac-
ity. The CAPACITY CONTROL STATES dictate how the individual circuits move within their states.
64
MCS-REFRIG MANUAL
65
MCS-REFRIG MANUAL
66
MCS-REFRIG MANUAL
19.29. DEFROST EVAP1 (28) (not Rotating Coil Air Defrost Only)
The circuit’s first evaporator is being defrosted. Refer to the section on circuit defrost and to the sequence of op-
erations for the various software versions.
19.30. DRIP DOWN #1 (29) (not Rotating Coil Air Defrost Only)
The circuit’s first evaporator has completed its defrost cycle and moisture is allowed to drip off the coils before
cooling begins. Refer to the section on circuit defrost and to the sequence of operations for the various software
versions.
19.31. DEFROSTR EVAP2 (30) (not Rotating Coil Air Defrost Only)
The circuit’s second evaporator is being defrosted. Refer to the section on circuit defrost and to the sequence of
operations for the various software versions.
19.32. DRIP DOWN #2 (31) (not Rotating Coil Air Defrost Only)
The circuit’s second evaporator has completed its defrost cycle and moisture is allowed to drip off the coils before
cooling begins. Refer to the section on circuit defrost and to the sequence of operations for the various software
versions.
19.33. DEF-START CMP (32) (not Rotating Coil Air Defrost Only)
Once one of the circuits is ready for defrost: The circuit that is ready to begin a defrost cycle it will then be placed
in the DEF-PUMP DOWN state. If the circuit is not ready for a defrost cycle it will be turned off.
67
MCS-REFRIG MANUAL
68
MCS-MAGNUM V17 - Condenser Control Logic
■■ RO Step Common
The highest discharge pressure from any compressor on the system will be the controlling pressure.
■■ RO Step Individual
Each compressor will have one or more condenser Relay Outputs associated with it. The discharge pres-
sure on that compressor will be the control pressure for its own condenser.
■■ RO Step Combined
The highest discharge pressure from either of the compressors on the shared circuits will be the control-
ling pressure (circuits 1 and 2 are shared, circuits 3 and 4 are shared, circuits 5 and 6 are shared, and
circuits 7 and 8 are shared).
■■ Modulating Common
The highest discharge pressure from any compressor on the system will be the controlling pressure. The
Analog Output is modulated based on the Rate of Change of the controlling discharge pressure. It can
also be controlled on a selected sensor input.
■■ Modulating Step Common
This type of condenser has a common fan bank for the system. The control will be on the systems highest
discharge pressure. The Relay Outputs are also supported along with an Analog Output.
■■ Modulating Individual
Each compressor will have its own condenser Analog Outputs associated with it. The Analog Output for
each circuit is modulated based on its own discharge pressure Rate of Change. It can also be controlled
on a selected sensor input. You may also select Relay Outputs to be turned ON/OFF while modulating the
Analog Output.
69
MCS-MAGNUM V17 - Condenser Control Logic
■■ RO Shared
This type of condenser will take the highest discharge pressure of circuits 1 and 2, then 2 and 3, then 3
and 4, etc. to use as the control discharge pressure. This condenser type does not have the option to
bypass the startup compressor.
■■ Dual V8
This special type of condenser is a common control air condenser with two stages of fans plus a VFD
Fan. Control of the fan speed will be different depending on whether one or two stages are on. All
compressors are in the same fan bank with the highest discharge pressure being the control.
■■ Common VFD Fan with Bypass
Three consecutive Relay Outputs, an Analog Output, and a VFD fault indicator are required to control this
type of condenser. RO’s needed:
1) VFD LOAD–This relay will be ON indicating the fan can be used.
2) VFD BYPS–This relay will be OFF unless a VFD fault has occurred.
3) VFD ENAB–This relay will be ON unless a VFD fault has occurred.
During normal operation, VFD LOAD will be on, VFD BYPS will be off, and VFD ENAB will be on. The
fan will be modulated as required by the condenser or economizer logic. If a fault occurs, all relays will
be turned off and the VFD will be set to 0. The Magnum will wait for the time specified in Setpoint #90
“COND FAULT” before the fan will be run without VFD control if it is needed by the condenser logic
(economizer logic will not function in this condition). Once this time has passed and the condenser
logic calls for the fan, then VFD BYPS will be turned on thereby turning the fan on, however it will NOT be
modulated.
The Magnum can also support a variable speed fan for all three of the air type of condensers. Each
compressor can support a variable speed fan. The variable speed must be on the first Relay Output
associated with that compressor.
Note 1: The discharge temperature must be at least 117° F and the discharge superheat needs to be at
least 20° F to guarantee good oil separation.
Note 2: Condenser staging is critical if the Magnum is to function in different climates. The best option
for air-cooled chillers is to have each fan on its own contactor and a frequency drive on fan 1. This
configuration allows the most optimum control in all weather.
■■ Modulating Step Common
Similar to the Modulating Common type with the addition of relay outputs. The highest discharge pressure
from any compressor on the system will be the controlling pressure. The Analog Output is modulated
based on the Rate of Change of the controlling discharge pressure. It can also be controlled on a selected
sensor input. When the analog output reaches it maximum value and more cooling is required the next
relay will be turned on and the analog output value will be set to its minimum value.
■■ Evap Individual
Evaporative condensers are used to improve the condensers efficiency by spraying water over the
condensing coil from above while air is blown up through the coil from below. Each compressor will have
its own condenser Analog Outputs associated with it. The Analog Output for each circuit is modulated
based on its own discharge pressure Rate of Change. It can also be controlled on a selected sensor
input. You may also select Relay Outputs to be turned ON/OFF while modulating the Analog Output.
■■ Evap Common
Evaporative condensers are used to improve the condensers efficiency by spraying water over the
condensing coil from above while air is blown up through the coil from below .Similar to the Modulating
Common type with the addition of relay outputs. The highest discharge pressure from any compressor on
the system will be the controlling pressure. The Analog Output is modulated based on the Rate of Change
of the controlling discharge pressure. It can also be controlled on a selected sensor input. When the
analog output reaches it maximum value and more cooling is required the next relay will be turned on and
the analog output value will be set to its minimum value.
70
MCS-MAGNUM V17 - Condenser Control Logic
Setpoint #43 “CND DIFF OFF” - Cut Out differential for additional condenser stages (OFF). Setpoint #44
“CND MIN RUN” - Minimum run time for a condenser stage
Condenser Relay Outputs will be turned on based upon the value in setpoint #40 “CND STG1 ON”. When
discharge pressure reaches this value, the first condenser Relay Output is turned on. If additional con-
denser outputs are present, they will be turned on when the pressure exceeds the cut in value plus the
value contained in setpoint #42 “CND DIFF ON“. When discharge pressure falls, the condenser outputs
will be turned off based upon the setpoint #41 “CND STG1 OFF” plus the value contained in setpoint #43
“CND DIFF OFF”. The first step will be turned off when discharge pressure falls below setpoint #41 “CND
STG1 OFF”.
Example:
Setpoint #40 “CND STG1 ON” = 200 psi
Setpoint #41 “CND STG1 OFF” = 170 psi
Setpoint #42 “CND DIFF ON” = 20 psi
Setpoint #43 “CND DIFF OFF” = 5 psi
71
MCS-MAGNUM V17 - Condenser Control Logic
72
MCS-MAGNUM V17 - Condenser Control Logic
This logic will utilize the calculated differential pressure (Discharge Pressure/Suction Pressure) to
control the condenser.
73
MCS-MAGNUM V17 - Condenser Control Logic
All condenser setpoints will remain the same for both modulating and step control.
When Diff PSI is selected the below information will become editable in the config program.
Here you will be able to customize adjustments to the differential target based on discharge superheat
being low or high.
In this config example if discharge superheat falls below 20 degrees for 30 seconds then the differential target
will be increased by 5 psi. If 30 more seconds goes by and the discharge superheat has not increased above
20 degrees then we will do another increase of 5 psi to the target. The adjustments will continue all the way
up to a maximum of 40 psi defined by our “Max Adjustment Allowed” box. Once discharge superheat is
between the high and low settings the adjustment will hold where it’s currently at.
The logic works the same exact way when the discharge superheat rises above 40 degrees only we will
decrease the differential every 30 seconds by 5 psi all the way back down to a 0 psi adjustment. The adjust-
ments cannot go to a negative value.
MCS-CONNECT SCREEN ADJUSTMENT - Diff PSI(Disc-Suct
Other SI - Control logic will be the same as Disc PSI control except the value of the sensor that is
specified will be used as the control. Note changes to related set points will be required. When this
option is selected a “Other Control Sensor” window will enable the sensor to be selected.
The Magnum will not check for the compressor with the highest discharge pressure but will always
use the value of the sensor that is selected as the control.
If Diff PSI(Disc-Suct) is selected as your condenser type in the MCS Config program
you’ll have a “Condenser Adjustment” box in your system status window through
MCS Connect. Here you will see the adjustments made to your condenser target
based on the discharge superheat. If you’re at least “Factory” authorized you can
double click the value in the condenser adjustment box, it will open a window as
you see in the example which will allow you to make changes to how the adjust-
ments are made.
If sensor is specified its value will be added to the condenser control set points #45, #46 and #50.
74
MCS-MAGNUM V17 - Condenser Control Logic
40 CND STG1 ON When the discharge pressure is above this value, turn on the first stage of the condenser
(Air cooled) fans.
‘Time (sec)’ field: (Applies to compressors with shared condensers) If non-zero, then the
compressor in startup state will not be in sole control of the condenser fans, it will control
off of highest discharge pressure. If zero, then compressor in startup will have sole
condenser control for 5 minutes. This option is selected in in the ‘Newly started Comp
Controls Common Fan Bank’ box in the ‘Condenser Information’ section under the MAG
V8 tab.
41 CND STG1 OFF If stage 1 of condenser capacity is on and the discharge pressure drops below this value,
(RO Type) then turn this stage off.
42 CND DIFF ON Differential pressure added to setpoint #45 to set the threshold at which each additional
(RO Type) stage of condenser capacity will turn on.
43 CND DIFF OFF Differential pressure added to setpoint #46 to set the threshold at which each additional
(RO Type) stage of condenser capacity will turn off.
CND DELAY If active, this is the time in seconds between adjustments to the water valve. If inactive,
(Modulating Type) then 30 seconds will be used as the delay.
DUAL PSI DELTA Minimum difference in pressure before the second stage of condenser capacity can be
(Dual V8) started.
44 CND MIN RUN Once a condenser stage has been turned on, it will remain on for at least the amount of
(Modulating Type) minutes specified in this setpoint.
DUAL TIME DELAY Time delay once the pressure difference in setpoint #48 has been reached before the
(Dual V8) second condenser stage can be started.
CND START % If active, then the value is the starting % for the AO when the RO that is tied to it turns
(Modulating Type) on. The value in the “Time (SEC)” cell is the AO starting stage. If no Relays are used
when CMP starts set value.
45 NOT USED
**
46 CND PSI TRGT This is the value that the fans will be modulated to. The High and Low zone cells contain
the respective values to form the deadband around the target.
47 CND ADJ DIV Control scaling of the amount the AO is adjusted. The larger the number, the smaller the
(Modulating Type) AO adjustment as the calculated adjustment will be divided by this value.
CND VFD MIN If there is a VFD associated with the condenser, this is the starting minimum speed.
‘Time (sec)’ field: This field contains the condenser stage that must be on before the VFD
is modulated.
48 CND MIN SPD Minimum AO % allowed.
(Modulating Type) If compressor is off, then check the “Time (SEC)” field:
If 0, then the AO % will be set to the value of this Setpoint. If 2 and the run/stop is set to
run, then set the AO % to 100%, else set the AO % to 0%. This option is se¬lected in the
“Default Valve Opening % when Comp. is OFF” box in the condenser information section
in the MAG HVAC screen.
49 CND ROC - (Modu- Maximum negative rate of change allowed. If the rate of change is less than this Set-
lating Type) point, then stop modulating the AO. The absolute value of this Setpoint also serves as
the maximum positive rate of change allowed. If the rate of change is greater than the
absolute value of this Setpoint, then stop modulating the AO.
50 CND MIN SPD Minimum speed percentage for variable speed condenser control.
(Modulating Type)
CND ADJ MULT Controls scaling of the amount the AO is adjusted. The larger the number the larger the
(Modulating Type) AO adjustment as the adjustment will be multiplied by this value.
75
MCS-MAGNUM V17 - Condenser Control Logic
51 CND MAX SPD Maximum speed percentage for variable speed condenser control.
(RO Type)
CND MIN ADJ The value in this Setpoint is the minimum % the AO will be modulated when a change is
(Modulating Type) made.
52 COND LOW AMB If active, standard condenser control on compressor startup logic will be bypassed when
the ambient temperature is below this value. Normal condenser control will apply, where
the compressor with the highest discharge pressure will control the condenser.
54 COND HI AMB If active, standard condenser control on compressor startup logic will be bypassed when
the ambient temperature is above this value. Normal condenser control will apply, where
the compressor with the highest discharge pressure will control the condenser.
55 COND FAULT If setpoint is active, and an alarm type, if a condenser fault occurs an alarm message will
be generated. If an lockout type, and a condenser fault occurs, then all compressors as-
sociated with this fault will be locked off.
For Common VFD Fan Condensers with Bypass: Time in seconds before the bypass
can be used when a fault has occurred.
56 COND PHASE If this set point is active and a digital input has been selected for the Condenser Phase
FAULT 1 Failure 1 when the compressor is on this digital input will be checked. If the digital input
is on for the Time specified for this set point, the circuit will enter a safety state and an
alarm will be generated indicating which circuit has the failure.
57 COND PHASE If this set point is active and a digital input has been selected for the Condenser Phase
FAULT 2 Failure 2 when the compressor is on this digital input will be checked. If the digital input
is on for the Time specified for this set point, the circuit will enter a safety state and an
alarm will be generated indicating which circuit has the failure.
The RO Step Common of condenser has one bank of fans. Make sure that all compressors in the Circuit
Base point to the same common fan bank. The above example does not have a Fan Analog Output and there
are three stages of fans starting with CND FAN 1 relay. All stages must be consecutive Relay Outputs.
For example:
76
MCS-MAGNUM V17 - Condenser Control Logic
Discharge control pressure is 200.0 P, CND FAN 1, first condenser stage will be turned on.
If control pressure is equal to or greater than 215.0 P then the second stage will be turned on. (200.0 + (15.0 *
1))
If control pressure is equal to or greater than 230.0 P then the third stage will be turned on. (200.0 + (15.0 *
2))
Discharge control pressure is above 230.0 P; all three condenser stages are on.
When the control pressure drops below 180.0P the third condenser stage will be turned off. (170.0 + (5.0 * 2))
When the control pressure drops below 175.0P the second condenser stage will be turned off. (170.0 + (5.0 *
1))
When the control pressure drops below 170.0P the first condenser stage will be turned off. (170.0)
Condenser Faults
This example has no condenser faults. If used, and any one of the digital inputs are ON for the time specified
in Setpoint #90 if active, then the unit will be locked out and an alarm message will be generated.
The above example is the same as the previous example with the addition of a Fan AO and two condenser
faults.
Fan AO Control (same for all types of air condenser control)
Two more Setpoints than the previous example are needed to control the speed of the fan:
77
MCS-MAGNUM V17 - Condenser Control Logic
CND FAN 1 will be turned on when the control pressure is equal to or greater than 200.0, same as in previ-
ous example. At this point the Fan AO speed will be set to its maximum value, Setpoint #55. If the pressure
changes between 170.0 and 214.9 the fan speed will also be modulated proportionally between its maximum
and minimum settings. If the pressure is at 185.0 the fan speed will be set to 61.2%. If the pressure is at
190.0 the fan speed will increase to 75.0%. This will provide precision control in maintaining optimum dis-
charge pressure.
If the pressure increases to 215.0 the condenser’s second stage will be turned on and the fan speed will also
be at 100.0%. If the pressure changes between 175.0 and 229.9 the fan speed will also be modulated propor-
tionally between its maximum and minimum settings.
If the pressure increases to 230.0 the condenser’s third stage will be turned on and the fan speed will also be
at 100.0%. If the pressure changes between 180.0 and 229.9 the fan speed will also be modulated propor-
tionally between its maximum and minimum settings. If the pressure is at 230.0 and above the fan speed will
be at 100.0%.
As the pressure decreases toward the Cut Out point the fan speed will decrease toward its minimum setting.
Once a stage is turned off, the fan speed will be set to 100.0% and again it will be modulated based upon the
pressure.
Condenser Faults
This example has two condenser faults. They must be consecutive digital input types starting with FAN FLT
1. If either of these digital inputs are ON for the time specified in Setpoint #90 if active, then the unit will be
locked out and an alarm message will be generated.
The RO Step Individual has a bank of fans for each compressor. The number and location of the fan are
specified under the Circuit Base screen.
# of Cond ROs –Total number of Relay Outputs of each compressor, in this example there are 3. The number
of fans in each compressor does not have to be the same.
Starting Condenser RO – The starting condenser Relay Output. All the Relay Outputs specified for each cir-
cuit must follow consecutively to this point. In this example CND FAN 1 is the starting Relay Output for circuit
1 and the other 2 fans follow consecutively in the RO screen.
78
MCS-MAGNUM V17 - Condenser Control Logic
Condenser Fan AO–If a condenser fan AO was specified in this cell it would function as described in the
example in section 7.74.3.6 RO Step Common with a Fan AO and Condenser Faults. There is no condenser
fan AO in this example.
Starting Condenser Fault–If there were condenser faults specified in this cell they would function as de-
scribed in the example in section 7.74.3.6 RO Step Common with a Fan AO and Condenser Faults. There are
no condenser faults in this example.
# Cond Faults – Total number of Condenser Faults.
Cond Fan Bank – In this type of condenser all compressors should have a different fan bank.
Each compressor fan bank is controlled individually. The discharge pressure for each compressor is used to
control condenser logic.
The RO Step Combined has a bank of fans that are shared by two consecutive circuits. The number and
location of the fans are specified in the Circuit Base screen. This is similar to the RO Step Individual set up
except only every other compressor has a condenser fans associated with it.
Circuit 1 and 2 will share the same fan bank specified in the ‘Cond Fan Bank’ cell. Circuit 3 and 4 will also
share the same fan bank specified. The highest discharge pressure between the two compressors on each
respective circuit will be used as the control pressure for their fan bank.
Condenser Faults
If any of these digital inputs are ON for the time specified in Setpoint #90 if active, then both compressors
sharing that condenser will we will be locked out and an alarm message will be generated. This example has
no condenser faults.
20.2.6 Modulating
20.2.6.1. Modulating Common
79
MCS-MAGNUM V17 - Condenser Control Logic
This type of condenser uses water for condenser cooling. The AO Modulating Valve will modulate the cold wa-
ter valve based upon the system’s highest discharge pressure.
When the delay counts down to zero, an adjustment will be made based on the equation: (Control dis-
charge pressure – Setpoint #50) × Setpoint #54 ÷ Setpoint #51 = Adjustment Value.
When the control discharge pressure is greater than Setpoint #50 plus the value in the high zone: If
the control discharge pressure rate of change is dropping too fast (more than twice the value of Setpoint #53),
then close the valve by the calculated adjustment. If the control discharge pressure rate of change is drop-
ping too slowly (more than the value of Setpoint #53), then open the valve by the calculated adjustment. Else
make no adjustment.
When the control discharge pressure is less than Setpoint #50 minus the value in the low zone: If the
control discharge pressure rate of change is increasing too fast (more than twice the value of Setpoint #53)
and the control discharge pressure is greater than Setpoint #50 minus 20.0 psi (1.3 bar), then close the valve
by the calculated adjustment. If the control discharge pressure rate of change is increasing too slowly (more
than the value of Setpoint #53), then open the valve by the calculated adjustment. Else make no adjustment.
When the control discharge pressure is within the zone: If the control discharge pressure rate of change
is increasing more than the value of Setpoint #53, then close the valve by 1 percent. If the control discharge
pressure change is decreasing more than the value of Setpoint #53, then open the valve by 1 percent.
Modulating Condenser Type: If heat pump and the mode is HEAT (not in defrost) all condenser relays will
be turned on and the VFD set to 100% when compressor is turned on. If the control pressure is above the
control zone, the condenser will unload; if below the control zone the condenser will load else there will be no
change.
When a RO is being used with an AO the AO will key off the RO turning on. The RO will turn on when the
discharge pressure enters the bottom of the CND HI/LO ZONE (Setpoint #193). At that time the AO will move
to its starting % (Setpoint #49). The AO will stay at its starting % until the discharge pressure gets outside the
top of the CND HI/LO ZONE (Setpoint #193). At that point the AO will modulate based on Setpoints #51, #53-
55. Now if there are 2 RO’s tied to the AO and the “AO Starting Stage” is 1 then once the AO gets to 100%
the 2nd RO will be turned on after a delay (value in the ”MIN VFD Opening“ cell for Setpoint #48) and the AO
will be set back to its minimum % (Setpoint #52) and then modulate as described above. Now if the pressure
begins to fall and goes below the CND HI/LO ZONE (Setpoint #193) the AO will modulate. Once the AO gets
to its minimum % (Setpoint #52) the 2nd RO will be turned off after a delay (value in the “MAX VFD Opening”
cell for Setpoint #48) and the AO will be set back to 100% and continue to modulate as needed.
If the “AO Starting Stage” is 2 then when the discharge pressure enters the bottom of the CND HI/LO ZONE
(Setpoint #193) the 1st RO (stage 1) will be turned on. The 2nd RO will turn on once the discharge pressure
80
MCS-MAGNUM V17 - Condenser Control Logic
gets outside the Heating Info CND HI/LO ZONE (Setpoint #193) and the delay has been met (value in the
“MIN VFD Opening cell” for Setpoint #48) at that time AO will be set to its starting % (Setpoint #49). If the dis-
charge falls below the CND HI/LO ZONE (Setpoint #193) the AO will begin to modulate. Once the AO reaches
its minimum % (Setpoint #52) it will turn off the associated RO after a delay (value in the “MAX VFD Open-
ing” cell for Setpoint #48). The 1st RO will remain on until the discharge pressure falls below the CND HI/LO
ZONE (Setpoint #193) and the delay has been met (value in the “MAX VFD Opening” cell for Setpoint #48).
This type of condenser uses water to provide cooling to the compressors. The AO Modulating Valve will mod-
ulate the cold water based upon this discharge pressure for each circuit. You may also select Relay Outputs
to be turned ON/OFF while modulating the Analog Output.
The individual condensers must be set up in the Circuit Base screen.
The control will be similar to the Modulating Common type, except that the discharge pressure for each circuit
will control its own condenser.
The RO Shared condenser has banks of fans that are shared between two consecutive circuits. The number
and location of the fans are specified under the Circuit Base screen. This is similar to the RO Step Individual
set up.
Circuits 1 and 2 will share the fan bank that is specified in the circuit 1 grid in the Circuit Base screen. The
highest discharge pressure of these two compressors will be used to control this bank of fans. Circuits 2 and
3 will share the fan bank that is specified in the circuit 2 grid in the Circuit Base screen. The highest discharge
pressure of these two compressors will be used to control this bank of fans. In a unit with three circuits, circuit
three will not have a fan bank associated with it. It shares circuit 2’s fan bank.
20.2.10 Dual V8
This is a special type of condenser. It is a common circuit control type with two stages of fans and VFD.
The control of the fan speed will be different depending on whether one or two stages are on. All circuits are
checked to calculate the control discharge pressure, and should be in the same fan bank.
If the control discharge pressure is less than Setpoint #45, then both condenser stages are off and the fan
speed is zero.
If the control discharge pressure is greater than Setpoint #45 and less than Setpoint #46 stage 1 will be on.
The fan speed will be equal the value of (Setpoint #55 minus Setpoint #54) divided by (Setpoint #46 minus
Setpoint #45) and then multiplied by (control discharge pressure minus Setpoint #46) plus Setpoint #54.
81
MCS-MAGNUM V17 - Condenser Control Logic
If the control discharge pressure increases while in stage 1 above the value of Setpoint #46 plus Setpoint #48
for the time contain in Setpoint #49 stage 2 will be entered. Both relays will be on and the fan speed will be
equal the value of (Setpoint #55 minus Setpoint #54) divided by Setpoint #46 and then multiplied by (control
discharge pressure minus Setpoint #46) plus Setpoint #54.
If the speed of the condenser fan is less than Setpoint #54 it will be set to that value or if the speed of the
condenser fan is greater than Setpoint #55 it will be set to that value.
The Common VFD Fan with a Bypass type of condenser has one fan.
All circuits will use this fan; make sure that all circuits in the Circuit
Base point to the same common fan bank. The above setup shows
that there is one condenser stage. However this type requires the
following three consecutive Relay Outputs to be set up. For example:
This type of condenser requires one condenser fault. If the fault occurs then the VFD will be bypassed and the fan will run
at 100% if needed.
40 CND STG1 ON When the discharge pressure is above this value, turn on the first stage of the condenser fans.
(Air cooled) ‘Time (sec)’ field: (Applies to compressors with shared condensers) If non-zero, then the
compressor in startup state will not be in sole control of the condenser fans, it will control off
of highest discharge pressure. If zero, then compressor in startup will have sole condenser
control for 5 minutes. This option is selected in in the ‘Newly started Comp Controls Common
Fan Bank’ box in the ‘Condenser Information’ section under the MAG V8 tab.
41 CND STG1 OFF If stage 1 of condenser capacity is on and the discharge pressure drops below this value, then
(RO Type) turn this stage off.
42 CND DIFF ON Differential pressure added to setpoint #45 to set the threshold at which each additional stage
(RO Type) of condenser capacity will turn on.
43 CND MAX SPD (RO Maximum speed percentage for variable speed condenser control.
Type)
55 COND FAULT If setpoint is active, and an alarm type, if a condenser fault occurs an alarm message will be
generated. If an lockout type, and a condenser fault occurs, then all compressors associated
with this fault will be locked off.
For Common VFD Fan Condensers with Bypass: Time in seconds before the bypass can be
used when a fault has occurred.
82
MCS-MAGNUM V17 - Condenser Control Logic
When the discharge control pressure is greater than 250 psi the relay VFD ENABLE will be on and the VFD
on the fan will be set to 100%. If the discharge control pressure drops to 210, then the fan speed will be set to
60%. The discharge control pressure is half of its Cut In and Cut Out range (250 – 170 = 80 / 2 = 40= 170 =
210) therefore, the VFD will be positioned to half of its range (100 –20 = 80 / 2 = 40 + 20 = 60). The VFD will
continue to be modulated in this matter until the discharge control pressure drops below 170. Then the VFD
will be at 0% and relay VFD ENABLE will remain on. If the pressure goes above 170 the VFD will be modu-
lated. For example if the discharge control pressure goes to 190.0 the VFD will be set to 50%.
Fan control when a fault occurs:
If a fault occurs, an alarm message will be generated, relay VFD LOAD will Lock off, relay VFD ENABLE will
be off, the VFD speed will be set to 0% and the bypass, VFD BYPASS, will be enabled if needed after waiting
for 30 seconds, Setpoint #90. Once the fan bypass is enabled and the discharge control pressure goes above
250 psi the bypass will be turned on enabling the fan to run at 100% and it will remain on regardless of the
discharge control pressure.
If the fault resets itself, and is no longer on, the state of VFD LOAD will be set to AUTO, the VFD BYPASS
relay will be turned off and VFD will be enabled to control the fan speed if it is needed.
When the discharge control pressure is greater than 250 psi the relay VFD ENABLE will be on and the VFD
on the fan will be set to 100%. If the discharge control pressure drops to 210, then the fan speed will be set to
60%. The discharge control pressure is half of its Cut In and Cut Out range (250 – 170 = 80 / 2 = 40= 170 = 210)
therefore, the VFD will be positioned to half of its range (100 –20 = 80 / 2 = 40 + 20 = 60). The VFD will con-
tinue to be modulated in this matter until the discharge control pressure drops below 170. Then the VFD will
be at 0% and relay VFD ENABLE will remain on. If the pressure goes above 170 the VFD will be modulated.
For example if the discharge control pressure goes to 190.0 the VFD will be set to 50%.
Fan control when a fault occurs:
If a fault occurs, an alarm message will be generated, relay VFD LOAD will Lock off, relay VFD ENABLE will
be off, the VFD speed will be set to 0% and the bypass, VFD BYPASS, will be enabled if needed after waiting
for 30 seconds, Setpoint #90. Once the fan bypass is enabled and the discharge control pressure goes above
250 psi the bypass will be turned on enabling the fan to run at 100% and it will remain on regardless of the
discharge control pressure.
If the fault resets itself, and is no longer on, the state of VFD LOAD will be set to AUTO, the VFD BYPASS
relay will be turned off and VFD will be enabled to control the fan speed if it is needed.
83
MCS-MAGNUM V17 - Condenser Control Logic
- Evap Individual Step, has the same control logic as Modulating Individual.
- Evap Common, has the same control logic as Modulating Common.
In addition to the standard control logic, the evaporative spraying water requires addition input.
Sump Temperature, this sensor will provide the temperature of the sump, area where the spray water is held.
Sump Level Indicator, if set point #249 and a digital input is specified, if it is continually on for the time
greater than the value of the safety time of set point #249 a Sump Low Level alarm will be generated and this
condenser will locked off. If the digital goes to an off state and the condenser is locked off, its state will be
changed to auto and the condenser will be available.
Sump Heater Relay, if this relay and sump temperature sensor is specified and set point #250 is active, this
relay will be turned on and off based upon the values of set point #250.
84
MCS-MAGNUM V17 - Condenser Control Logic
Setpoints used for PID Mod Individual and PID Step Common
40 CND STG1 ON When the discharge pressure is above this value, turn on the first stage of the
(Air cooled) condenser fans.
‘Time (sec)’ field: (Applies to compressors with shared condensers) If non-zero,
then the compressor in startup state will not be in sole control of the condenser
fans, it will control off of highest discharge pressure. If zero, then compressor in
startup will have sole condenser control for 5 minutes. This option is selected in
in the ‘Newly started Comp Controls Common Fan Bank’ box in the ‘Condenser
Information’ section under the MAG V8 tab.
PID MOD Individual If active, multiplier uses PID condenser control KP (Proportional). Setup as set-
PID Step Comm point.
41 CND STG1 OFF If stage 1 of condenser capacity is on and the discharge pressure drops below
(RO Type) this value, then turn this stage off.
PID MOD Individual If active, uses Multiplier for Ki adjustments (Integral Time Delay). Setup as set-
PID Step Common point
85
MCS-MAGNUM V17 - Condenser Control Logic
42 CND DIFF ON Differential pressure added to setpoint #45 to set the threshold at which each ad-
(RO Type) ditional stage of condenser capacity will turn on.
PID MOD Individual If active, uses Multiplier for Kd adjustments, (ROC Time Delay). Setup as Target.
PID Step Common
46 CND PSI TARG Target discharge pressure which the condenser valve will try to maintain by
(Modulating Type) modulating open or closed.
47 CND ADJ DIV Controls scaling of the amount the valve is adjusted (Usually 1). The larger the
(Modulating Type) number the smaller the valve adjustment as the adjustment will be divided by this
value.
CND VFD MIN If there is a VFD associated with the condenser, this is the starting minimum
speed.
‘Time (sec)’ field: This field contains the condenser stage that must be on before
the VFD is modulated.
48 CND MIN SPD Minimum valve opening percentage allowed.
(Modulating Type) If the compressor is off, then check the ‘Time (sec)’ field:
If 0, then set the VFD to the value of this setpoint. If 2 and the run/stop is set
to run, then set the VFD to 100%, else set the VFD to 0%. This option is selected
in in the ‘Default Valve Opening % when Comp. is OFF’ box in the ‘Condenser
Information’ section under the MAG V8 tab.
49 CND ROC- Maximum negative discharge pressure rate of change allowed. If the rate of
(Modulating Type) change is less than this setpoint, then stop opening the valve. The absolute value
of this setpoint also serves as the maximum positive rate of change allowed. If
the rate of change is greater than the absolute value of this setpoint, then stop
closing the valve.
50 CND MIN SPD Minimum speed percentage for variable speed condenser control.
(Modulating Type)
CND ADJ MULT Allows scaling of the amount the valve is adjusted. The larger the number the
(Modulating Type) larger the valve adjustment will be multiplied by this value.
51 CND MAX SPD Maximum speed percentage for variable speed condenser control.
(Modulating Type)
86
MCS-MAGNUM V17 - Condenser Control Logic
PID control will turn an analog output into a stand alone PID controlled output. This output will have a control-
ling sensor that modulates the AO to a maintain target. This logic will run all the time.
87
MCS-MAGNUM V17 - Condenser Control Logic
21.1. Operands
Operands are the building blocks of the Magnum User Logic. An operand consists
of two parts: the top cell provides a drop down list to select the types and then a
drop down list to select the item within that type:
TYPE ITEM
Fixed Value Enter a fixed value with decimal place if required.
SI Select Sensor Input
AO Select Analog Output
RO Select Relay Output
Setpoints Select Setpoint, number is also display for ease of selection. All Setpoints are shown,
both active and inactive.
CLOCK Select system clock. The following can be selected: Hours, Minutes, Seconds, Day
of Month, Day of Week (1 = Sunday–7 = Saturday), Year (2 digits), and Month (1-12).
These are current values from the Magnum.
Unit Chiller The following can be selected: FLA %, Steps wanted, Steps ON, Steps available,
steps allowed on, % Load, STATE, Lead Compressor, Mode (cooling or heating), and
Ice Mode Done (if ice mode option selected).
Compressor #1– The following can be selected for any compressor: Compressor State, Suction
Compressor #20 Pressure, Discharge Pressure, Oil Pressure Differential, Motor Amps, Suction Tem-
perature, Discharge Temperature, Oil Temperature, Motor Temperature, EXV Value
Position, Oil Pressure, Refrigerant Temperature, Flow Indicator, Compressor Proof,
Compressor Speed, Oil Float, Refrigerant Level, Condenser Temperature #1, Con-
denser Temperature #2, Fla %, Saturated Suction Temperature, Suction Superheat,
Saturated Discharge Temperature, and Discharge Superheat.
Note all of the above may not exist for an individual configuration.
88
MCS-MAGNUM V17 - Condenser Control Logic
The value that is passed to the User Logic depends on the item selected. For example:
A Relay Output’s value is 0 if it is off and a 1 if it is on.
A Digital Input’s value is 0 if it is off and a 1 if it is on.
An Analog Input and Analog Output value are the actual values as displayed, includes the decimal place.
The unit, compressor, or loop state is a numeric value that will relate to the state names in this manual.
This value is show as the number in parenthesis following the state name.
21.2. Operators
The action cell is located between the operand cells.
The following actions can be selected from a drop down list this will determine the value of the sensor:
89
MCS-MAGNUM V17 - Condenser Control Logic
First select the display type and then complete the selections. Note operand #1 and #2 are defined in the Oper-
ands section above and the Action Cell is defined in the drop down menu between.
The window below is from MCS-Config is configuring a User Logic type of sensor. It is a digit type of sensor (ON
or OFF) and it is only looking an Operand 1. If the RO Sump and Doors is ON then the value of this sensor will
be ON.
90
MCS-MAGNUM V17 - Condenser Control Logic
The window below is from MCS-Config building a User Logic type of sensor. It is a pressure type of sensor
(display a value with 1 decimal place). The value of this sensor will be result of Operand 1 minus Operand 2.
In this example, if either of the operands become true, then this relay will turn ON, an alarm message will be
generated, and the General alarm relay will also turn ON.
91
MCS-MAGNUM V17 - Condenser Control Logic
92
MCS-MAGNUM-EXV
By clicking on the ‘Type of LLS’ cell under the Circuit Base screen, select either EXV&LLS or EXV Only for
EXV control.
By clicking on the ‘EXV Output cell under the Circuit Base screen, select the analog output for controlling this
circuits EXV.
By clicking on the ‘EXV Control’ cell under the Circuit Base screen, the option will cycle between Suction
Superheat, Discharge Superheat, and Refrigerant Level control. By assigning the 2nd EXV for each circuit in
the “Tandem EXV Circuit#” cell.
93
MCS-MAGNUM-EXV
To view the EXV status through the Keypad LCD, select Status from the Main Menu and then page to the
EXV screen.
EXV States:
94
MCS-MAGNUM-EXV
The logic will work as follows: When the compressor starts the EXV will go to the value in the ‘EXV Start
(when lead)’ column, in this example it is 25%. The EXV will then modulate normally according to the control-
ling superheat or refrigerant level, until the unit is ready to load another step of capacity. Assume the EXV has
stayed at 35% when the second step of capacity is ready to engage (turning off the Hot Gas Bypass). The
EXV adjustment will be 50% (the amount in the ‘EXV Load Adjust’ column of the current EXV position
‘EXV Load Adjust’ column (50%) × current EXV position (35%) = EXV adjustment (17.5%)
50% × 35% = 17.5%
Current EXV position (35%) + EXV adjustment (17.5%) = New EXV position (42.5%)
35% +17.5% = 42.5%
Therefore the final EXV valve position would be 42.5%
This same calculation will be repeated every time a new stage of capacity is turned on. Conversely, when
the unit is unloading, the EXV adjustment will be subtracted from the current EXV position for every step that
turns off. Assume the EXV is at 40% and the compressor is at 100% and is ready to unload a step (turning on
Unload 75% solenoid).
‘EXV Unld Adjust’ column (30%)× current EXV position (40%)= EXV adjustment (12%) 30% × 40% = 12%
Current EXV position (40%)–EXV adjustment (12%) = New EXV position (28%) 40%–12% = 28%
Therefore the final EXV valve position would be 28%
The values given in the example are only start points. You will need to adjust the values for your system.
The idea is to jump the EXV position so that the superheat would still be above the target slightly, and then
the EXV control logic would then adjust the value to achieve the target superheat. We do not want to open
the EXV valve too much when loading or close the valve too much when unloading so we do not cause low
superheat or liquid flooding to the compressor.
95
MCS-MAGNUM-SSH, SSH2, PID
96
MCS-MAGNUM-SSH, SSH2, PID
Next in the Circuit Base screen you need to select ‘Fast SSH‘ or ‘Fast SSH2’ from the Evaporator EXV Control
section drop down menu.
With the release of Fast SSH2 MCS has released a new MCS-Config to support the new functions. The new
MCS-Config provides a new tab, ‘EXV Control’, where you define your system. This then allows MCS-Config
to provide MCS Default Set Point Values for you. The figure below shows the Current ‘Circuit Base’ tab and
the new ‘EXV Control’ tab.
If you enter data in the EXV portion of the Circuit Base tab or in the EXV Control tab it is carried through to the
other tab.
23.4.1 Selecting the ‘EXV Control’ tab you are prompted with the following:
Based on your selections will dictate the set points for compressor control. The subcooler set points are only
displayed if a subcooler id present.
97
MCS-MAGNUM-SSH, SSH2, PID
NOTE: Once you have clicked on the boxes for your setup, be sure to click on ‘Set Values to Default’.
Selection
Option
Compressor
EXV Results
This will set the values to the default for ‘Control Parameter, Heat Exchanger Type and the Control Method.
Make note that clicking in the ‘Target Modifier’ require that some set points must be active.
98
MCS-MAGNUM-SSH, SSH2, PID
99
MCS-MAGNUM-SSH, SSH2, PID
SP # Name Description
9 EXV Target (Value Field) – This is the superheat target the system will make adjustments to the Electronic
Expansion Valve to maintain.
(Time Field) – In Fast SSH when in low suction psi this is the number of seconds the suction psi
must be increasing before the systems stops adjusting the valve.
(Time Field) - In Fast SSH2 it is the number of seconds to calculate the extended slope. When
in low suction, adjustments are stopped when the suction pressure slope is positive for
1 second.
10 EXV Fast Zone ((Value Field) – The system makes adjustments to the EXV Valve percentage to maintain
the superheat within this range.
(Time Field) – The maximum different between two EXV’s on the same circuit allowed
once out of startup and under control.
100
MCS-MAGNUM-SSH, SSH2, PID
13 Rate of Change (Value Field) - This value is used to multiply times the calculated value of current su-
adjust multiplier perheat – the superheat value one second ago. (The slope of the current superheat)
Time Field) – If set point type = ‘Time’ and Time Field is ≥ 2 and ≤ 100 this is the
adjustment multiplier for when the system is in Low Suction. It takes the base valve
adjustment of 0.5% and multiplies it with this value. Adjustments stop when the suc-
tion psi starts too increase. (See set point 9 time field for additional information.) If
the conditions are not met then a value of 0.5 is used. (Delay between adjustments is
specified in the value field of SP 17.)
14 Limit of Adjustment (Value Field) – In FSH this value limits the adjustment while the superheat is < then the
Fast Zone times two. In FSH2 this value is the maximum limit of the adjustment.
(Time Field) - In FSH this value is the limit of adjustment when the superheat > then
two times the Fast Zone. Remember in the value field of this set point you are typically
using a value of 0.2 to 0.5. In the time field a value of 7 is equivalent to 0.7.
(Time Field) - In FSH2 this field is not used.
15 Minimum EXV Valve (Value Field) – The minimum position of the valve. Usually 3%. Will need to be larger if
% hot gas is on system.
(Time Field) - The adjustment multiplier for when the system is in Low Superheat.
16 Maximum EXV Valve (Value Field) – The maximum position of the valve allowed. Usually 100%. Sometimes
% used if valve is oversized.
(Time Field) – This value specifies the number of seconds delay between adjustments,
(for Low Superheat) trying to correct this situation. Adjustments continue until the super-
heat is above the Value Field.
19 EXV Delay (Value field) – The value in this field id decremented by the difference between the absolute
value of the current superheat – superheat target. When the result reaches zero the FSH &
FSH2 make the current calculated adjustment to the current valve percentage.
(Time Field) – The value in the time field determines when control will begin when two EXV’s
are on the same circuit. This value times the value field in the fast zone plus the current tar-
get defines when control is taken, at startup. If this value is 10 and the value in the fast zone
is 2 and the target is 12 the result would be (10 * 2 + 12) = 32%. When both valves are ≤ this
% control is taken and then kept within the value specified in the time field of set point 12.
20 EXV Startup Time (Value Field) – EXV starting time in seconds. The following decisions are made on taking
control:
a). If the current superheat is > target + 5.0 ⁰ & State timer > Startup time / 2 Take
control.
b). If the current superheat is < target – Fast zone & State timer > Startup time / 2
Take Control.
c). If the Suct psi is < Low Suct SP + Low unload & State timer > Startup time / 2 Take
Control.
d). If the EXV startup time ≥ 90 & a) or b) is true adjust the valve start percentage
101
MCS-MAGNUM-SSH, SSH2, PID
102
MCS-MAGNUM-SSH, SSH2, PID
EXV-AA-BB-CCCC
EXV-AA-BB-CCCC
103
MCS-MAGNUM-SSH, SSH2, PID
SLOW
FAST multipliers
multipliers
PID
multipliers
setpoints
Next in the Circuit Base screen you need to select ‘PIP SSH’ from the Evaporator EXV Control section drop
down menu.
NOTE: TANDEM 6 EXV PER CIRCUIT NOT SUPPORTED IN RTU AND CENTRIFUGAL FIRMWARE
105
MCS-MAGNUM-SSH, SSH2, PID
With the release of Fast SSH2 AND PID MCS has released a new MCS-Config to support the new functions.
The new MCS-Config provides a new tab, ‘EXV Control’, where you define your system. This then allows
MCS-Config to provide MCS Default Set Point Values for you. The figure below shows the Current ‘Circuit
Base’ tab and the new ‘EXV Control’ tab.
If you enter data in the EXV portion of the Circuit Base tab or in the EXV Control tab it is carried
through to the other tab.
24.7. Selecting the ‘EXV Control’ tab you are prompted with the following:
Selection
Option
(Evaporator and
condenser Level not
available with Fast
I or Fast II Control
Method)
Compressor
EXV Results
Based on your selections will dictate the set points for compressor control.
106
MCS-MAGNUM-SSH, SSH2, PID
NOTE: Once you have clicked on the boxes for your setup, be sure to click on ‘Set Values to Default’.
This will set the values to the default for ‘Control Parameter, Heat Exchanger Type and the Control Method.
Make note that clicking in the ‘Target Modifier’ require that some set points must be active.
SP # Name Description
9 SPRHT TARGET If EXV control is based upon superheat, this is the Superheat target that the Magnum
or will control from.
LEVEL TARGET If EXV control is based upon refrigerant level, this is the refrigerant level target that the
Magnum will control from.
‘Low Zone’ if nonzero then develop control super heat based upon the lowest superheat
of any compressor that is on with in this suction group else use the superheat of this
compressor.
‘Time (sec)’ field: Seconds between samples used for calculating the Superheat Rate of
Change.
STAGE 7 CUT IN Stage 7 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Control)
10 SPRHT ZONE +- The value in this setpoint is added and subtracted to setpoint #9 to determine the upper
and lower limits of the control zone respectively. Refer to section on EXV control.
‘Time (sec)’ field: If non-zero, skip ROC adjustment logic in the control zone.
STAGE 8 CUT IN Stage 8 cut in, Setpoint value contains the voltage when this stage is turned on.
(Cut In/Out Control)
11 EXV LOAD ADJ The opening adjustment that will be made to the EXV percentage when the circuit
changes to the Loading state or the closing adjustment that will be made when the cir-
cuit changes to the Unloading state. Refer to section on EXV control.
Note: In MOP hold state, only closing adjustments are allowed.
107
MCS-MAGNUM-SSH, SSH2, PID
14 Limit of Adjustment (Value Field) – In FSH this value limits the adjustment while the superheat is < then the
Fast Zone times two. In FSH2 this value is the maximum limit of the adjustment.
(Time Field) - In FSH this value is the limit of adjustment when the superheat > then
two times the Fast Zone. Remember in the value field of this set point you are typically
using a value of 0.2 to 0.5. In the time field a value of 7 is equivalent to 0.7.
(Time Field) - In FSH2 this field is not used.
15 Minimum EXV Valve (Value Field) – The minimum position of the valve. Usually 3%. Will need to be larger if
% hot gas is on system.
(Time Field) - The adjustment multiplier for when the system is in Low Superheat.
16 Maximum EXV Valve (Value Field) – The maximum position of the valve allowed. Usually 100%. Sometimes
% used if valve is oversized.
(Time Field) – This value specifies the number of seconds delay between adjustments,
(for Low Superheat) trying to correct this situation. Adjustments continue until the super-
heat is above the Value Field.
19 EXV Delay (Value field) – The value in this field id decremented by the difference between the absolute
value of the current superheat – superheat target. When the result reaches zero the FSH &
FSH2 make the current calculated adjustment to the current valve percentage.
(Time Field) – The value in the time field determines when control will begin when two EXV’s
are on the same circuit. This value times the value field in the fast zone plus the current tar-
get defines when control is taken, at startup. If this value is 10 and the value in the fast zone
is 2 and the target is 12 the result would be (10 * 2 + 12) = 32%. When both valves are ≤ this
% control is taken and then kept within the value specified in the time field of set point 12.
20 EXV Startup Time (Value Field) – EXV starting time in seconds. The following decisions are made on taking
control:
a). If the current superheat is > target + 5.0 ⁰ & State timer > Startup time / 2 Take
control.
b). If the current superheat is < target – Fast zone & State timer > Startup time / 2
Take Control.
c). If the Suct psi is < Low Suct SP + Low unload & State timer > Startup time / 2 Take
Control.
d). If the EXV startup time ≥ 90 & a) or b) is true adjust the valve start percentage
108
MCS-MAGNUM-SSH, SSH2, PID
Below setpoints are the default Fahrenheit values for Suction Superheat with DX Chiller Barrel.
109
MCS-MAGNUM-SSH, SSH2, PID
FAST multipliers
Switching
24.12.1.2.to Switching
slow K multipliers
to Slow Kismultipliers
based on: is based on:
b. Distance from target
1. If current superheat is less than (setpoint #9 value field plus setpoint #9 low zone field) but above the
fast multiplier switch of 8 (12 - 4)
Setpoint Value LOW Zone Total
#9 SucSprHtTarg 12.0F + 3.5F = 15.5F
EXV PID algorithm will use the slow multipliers (Setback Value Field)
2. If current superheat is more than (setpoint #9 value field minus setpoint #9 low zone field) and
below the fast multiplier switch of 20 (12 + 4 x 2)
Setpoint Value LOW Zone Total
#9 SucSprHtTarg 12.0F - 3.5F = 8.5
EXV PID algorithm will use the slow multipliers (Setback Value Field)
SLOW multipliers
SLOW multipliers
110
MCS-MAGNUM-SSH, SSH2, PID
1. If current superheat ROC is greater than setpoint #13 (Kd) high zone and current superheat is above target
2. If current superheat ROC is greater than setpoint #13 (Kd) low zone and current superheat is below target
Current Superheat
Current Superheat ROC Setpoint #13 Low Zone
value
-0.3 -0.20 8
EXV PID algorithm will use the fast multipliers (Setpoint Value Field)
FAST
FAST multipliers multipliers
24.12.2 Rate of Change - Moving Slow Enough
If current superheat ROC is less than setpoint #13 (Kd) high zone and current superheat is above target
Current Superheat ROC Setpoint #13 High Zone Current Superheat
0.1 0.20 15F
EXV PID algorithm will use slow multipliers (Setback Field)
If current superheat ROC is less than setpoint #13 (Kd) low zone and current superheat is below target
Current Superheat ROC Setpoint #13 Low Zone Current Superheat
-0.1 -0.20 10
EXV PID algorithm will use slow multipliers (Setback Field)
SLOW multipliers
SLOW multipliers
111
MCS-MAGNUM-SSH, SSH2, PID
Controlling parameter
Integral Adjustment
(Current Superheat minus Superheat
Target setpoint #9 value) x Ki Derivative Adjustment Current K multipliers
Ki = setpoint #10/#66 value(fast) or (Current Superheat minus being used
setback value(slow) Superheat from x seconds ago)
x Kd
Kd = setpoint #13/#68
value(fast) or setback
value(slow)
Ki adjust HiZone
12 plus 2.20 = 14.2
14.20F No
Superheat Target Ki
120F
Ki adjust LOW zone
Adjust in
12 plus -2.20 = 9.8 9.80F this area
112
MCS-MAGNUM-SSH, SSH2, PID
113
MCS-MAGNUM-SSH, SSH2, PID
1.2 0%
3.7 100%
NOTE: If Level Sensor is a 4-20ma output, where at 4ma = 0% level and at 20ma = 100% level,
you would put the designated input jumper on digital and the SI calculation wizard would be
Setup as:
Point #1 .882 vdc = 0% See APP066- 4-20mA Sensor Connection to MCS-Magnum
Point #2 4.41 vdc = 100%
114
MCS-MAGNUM-SSH, SSH2, PID
Make sure the Discharge Pressure and Discharge Temperature are pointing to correct sensors for the
calculation of discharge superheat.
115
MCS-MAGNUM-SSH, SSH2, PID
NOTE: If more than one circuit is available and you want to control two independent circuit target
levels, make setpoint#9 ‘Non-Active’ in the setpoint screen.
Make the used FLA setpoints#171-190 a ‘target’ type and set the level target up in the setback field.
Make setpoint #110 (LoDisSHExvAd) active if you want to dynamically change the EXV target based
on Low Discharge Superheat.
116
MCS-MAGNUM-SSH, SSH2, PID
another adjustment will be made until the max adjust is reached (setpoint #110 setback value) or
the discharge superheat goes above setpoint #110 (#164) low zone value.
b. For Cond Level control method, setpoint #110 (#164) value field is added to the EXV Target and
this value becomes the new EXV Target. The value in the Time (SEC) field will count down again
and another adjustment will be made until the max adjust is reached (setpoint #110 setback val-
ue) or the discharge superheat goes above setpoint #110 (#164) low zone value.
Else if discharge superheat >= setpoint #110 (#164) high zone value and the low discharge superheat
adjusted amount is greater than 0 and the Time (SEC) value has elapsed, then:
a. If Evap Level control, setpoint #110 (#164) value field is added to the EXV Target and this value
becomes the new EXV Target. The value in the Time (SEC) field will count down again and anoth-
er adjustment will be made until the min adjust is reached (0) or the discharge superheat goes
below setpoint #110 (#164) high zone value.
NOTE: The EXV Target adjusted value will not go above the original setpoint Target value.
b. For Cond Level control method, setpoint #110 (#164) value field is subtracted from the EXV Tar-
get and this value becomes the new EXV Target. The value in the Time SEC) field will count down
again and another adjustment will be made until the min adjust is reached (0) or the discharge
superheat goes below setpoint #110 (#164) high zone value.
NOTE: The EXV Target adjusted value will not go below the original setpoint Target value.
Else If Setpoint #110 (#164) is not a “TARGET” type setpoint the following logic occurs (Old Logic):
2. If discharge superheat is < Low discharge superheat safety setpoint #84 value, then:
a. If Evap Level or Cond Level and not level target by compressor circuit, then set EXV target to
setpoint #110 value.
b. Else If Evap Level or Cond Level and EXV target is by compressor circuit, then subtract setpoint
#110 value from the current EXV target.
117
MCS-MAGNUM-SSH, SSH2, PID
PID control will turn an analog output into a stand alone PID controlled output. This output will have a controlling sensor
that modulates the AO to a maintain target. This logic will run all the time.
NOTE
If AO is modulating the wrong direction, simply make all three multipliers negative values to reverse the direction the AO
modulates and vice versa.
If Relay-
If a relay is used and is OFF then associated AO will be set to the defined value and not modulate. If ‘not used’ the logic
is ignored.
Control Sensor
AO or SI point to be used as the controlling sensor for the AO.
118
MCS-MAGNUM-SSH, SSH2, PID
Control Target
SI, AO, or Setpoint used as the target the AO will try to maintain.
AO
Min to Max value the AO can modulate between.
Proportional(Kp)
Multiplier for Kp adjustments.
Integral(Ki)
Multiplier and delay between Ki Adjustments
Derivative(Kd)
Multiplier and time in seconds interval to calculate Kd.
Adjustment Limits
Min and Max adjustments allowed to the AO per adjustment, both negative and positive.
Under the Analog Outputs window in the MCS Connect software. You’ll find an AO PID tab that will show all of the PID
CONTROL AOs and all of the calculated adjustments being made to those Analog Outputs. Here you will be able to see
all three adjustments being made to the PID. This will assist you in any fine tuning required for the given analog output.
119
MCS-REFRIG MANUALVERSION 17
Invalid reading on one sensor This indicates an input problem with 1 sensor.
input. Verify jumper settings correct for that SI.
‘MCS CONTROLLER INITIAL- Indicates Micro in constant reset.
IZATION’ on LCD display. Check incoming power > 105 VAC or 22 VAC
Top row of LCD display all bars Indicates software chip problem possible.
& 2nd row blank. Possible U11 software version incorrect or chip bad.
Possible U13 GAL chip incorrect or chip bad.
Possible bad connection or cable between LCD and MCS8
120
MCS-REFRIG MANUALVERSION 17
121
MCS-REFRIG MANUALVERSION 17
122
MCS-MAGNUM-BMS- Refrig.
Please note the RS485 follows industry standard, two wire twisted pair in shielded cable.
28.1. Setup the Modbus from MCS-Config’s Magnum Setup Screen(see below):
123
MCS-MAGNUM-BMS- Refrig.
124
MCS-MAGNUM-BMS- Refrig.
28.4. In MCS-CONFIG you can see & print a list of the Modbus Registers (see below):
The MCS-Magnum Modbus RTU setting allow you to specify the Modbus Slave address, Modbus
Baud rate (4800, 9600, 19200, 38400, 57600 are supported).
The number data bit is 8, stop bit is 1 and parity is none (these parameter are
not adjustable).
The sensors inputs are 16 bit signed values. (Read input Registers, Function code = 4)
• The analog sensor inputs values typically have 1 assumed decimal place, meaning a value of 12.3
will be transmitted as value 123. The # of decimal point depending on the sensor type define in
the MCS-MAGNUM CONFIG. Most sensor types are 1 decimal place.
But take care there are a few 2 decimal and a few zero decimal place types.
The BMS point list has a column which indicates how many assumed decimal are contained in the
value.
• The digital sensor inputs values will be 0 or 1, 0 = off and 1 = on.
The analog outputs are 16 bit signed values. (Read Input Registers, Function code = 4)
• The analog output have 1 assumed decimal place, meaning a value of 12.3 will be transmitted as value
123.
The relay outputs are 16 bit packed values. (Read Coil Status , Function code = 1)
• Each bit within the 16 bits can contains a relay output. A bit value of 0 = relay off, 1 = relay on.
The number of packed bit depends on the requesting Modbus message.
If only one coil is asked for, then only bit 0 will contains a relay status value and bit 1 thru 7 are do
not care.
If two relays are asked for, then bit 0 and bit 1 will contains values and bit 2 thru 7 are do not care.
The setpoints are 16 bit signed values. (Read Holding Registers, Function code = 3)
• The setpoints values typically have 1 assumed decimal place, meaning a value of 12.3 will be
transmitted as value 123.
The # of decimal point depending on the setpoint type defined in the MCS-MAGNUM CONFIG.
125
MCS-MAGNUM-BMS- Refrig.
126
MCS-MAGNUM-BMS- Refrig.
Sensor M-1 AI: 1 Refer to Config *30001 *AI: 1 Sensor 2-9 AI:41 Refer to Config *30041 *AI: 41
Sensor M-2 AI: 2 Refer to Config *30002 *AI: 2 Sensor 2-10 AI:42 Refer to Config *30042 *AI: 42
Sensor M-3 AI: 3 Refer to Config *30003 *AI: 3 Sensor 2-11 AI:43 Refer to Config *30043 *AI: 43
Sensor M-4 AI: 4 Refer to Config *30004 *AI: 4 Sensor 2-12 AI:44 Refer to Config *30044 *AI: 44
Sensor M-5 AI: 5 Refer to Config *30005 *AI: 5 Sensor 2-13 AI:45 Refer to Config *30045 *AI: 45
Sensor M-6 AI: 6 Refer to Config *30006 *AI: 6 Sensor 2-14 AI:46 Refer to Config *30046 *AI: 46
Sensor M-7 AI: 7 Refer to Config *30007 *AI: 7 Sensor 2-15 AI:47 Refer to Config *30047 *AI: 47
Sensor M-8 AI: 8 Refer to Config *30008 *AI: 8 Sensor 2-16 AI:48 Refer to Config *30048 *AI: 48
Sensor M-9 AI: 9 Refer to Config *30009 *AI: 9 Sensor 3-1 AI:49 Refer to Config *30049 *AI:49
Sensor M-10 AI:10 Refer to Config *30010 *AI: 10 Sensor 3-2 AI:50 Refer to Config *30050 *AI: 50
Sensor M-11 AI:11 Refer to Config *30011 *AI: 11 Sensor 3-3 AI:51 Refer to Config *30051 *AI: 51
Sensor M-12 AI:12 Refer to Config *30012 *AI: 12 Sensor 3-4 AI:52 Refer to Config *30052 *AI: 52
Sensor M-13 AI:13 Refer to Config *30013 *AI: 13 Sensor 3-5 AI:53 Refer to Config *30053 *AI: 53
Sensor M-14 AI:14 Refer to Config *30014 *AI: 14 Sensor 3-6 AI:54 Refer to Config *30054 *AI: 54
Sensor M-15 AI:15 Refer to Config *30015 *AI: 15 Sensor 3-7 AI:55 Refer to Config *30055 *AI: 55
Sensor M-16 AI:16 Refer to Config *30016 *AI: 16 Sensor 3-8 AI:56 Refer to Config *30056 *AI: 56
Sensor 1-1 AI:17 Refer to Config *30017 *AI: 17 Sensor 3-9 AI:57 Refer to Config *30057 *AI: 57
Sensor 1-2 AI:18 Refer to Config *30018 *AI: 18 Sensor 3-10 AI:58 Refer to Config *30058 *AI: 58
Sensor 1-3 AI:19 Refer to Config *30019 *AI: 19 Sensor 3-11 AI:59 Refer to Config *30059 *AI: 59
Sensor 1-4 AI:20 Refer to Config *30020 *AI: 20 Sensor 3-12 AI:60 Refer to Config *30060 *AI: 60
Sensor 1-5 AI:21 Refer to Config *30021 *AI: 21 Sensor 3-13 AI:61 Refer to Config *30061 *AI: 61
Sensor 1-6 AI:22 Refer to Config *30022 *AI: 22 Sensor 3-14 AI:62 Refer to Config *30062 *AI: 62
Sensor 1-7 AI:23 Refer to Config *30023 *AI: 23 Sensor 3-15 AI:63 Refer to Config *30063 *AI: 63
Sensor 1-8 AI:24 Refer to Config *30024 *AI: 24 Sensor 3-16 AI:64 Refer to Config *30064 *AI: 64
Sensor 1-9 AI:25 Refer to Config *30025 *AI: 25 Sensor 4-1 AI:65 Refer to Config *30065 *AI: 65
Sensor 1-10 AI:26 Refer to Config *30026 *AI: 26 Sensor 4-2 AI:66 Refer to Config *30066 *AI: 66
Sensor 1-11 AI:27 Refer to Config *30027 *AI: 27 Sensor 4-3 AI:67 Refer to Config *30067 *AI: 67
Sensor 1-12 AI:28 Refer to Config *30028 *AI: 28 Sensor 4-4 AI:68 Refer to Config *30068 *AI: 68
Sensor 1-13 AI:29 Refer to Config *30029 *AI: 29 Sensor 4-5 AI:69 Refer to Config *30069 *AI: 69
Sensor 1-14 AI:30 Refer to Config *30030 *AI: 30 Sensor 4-6 AI:70 Refer to Config *30070 *AI: 70
Sensor 1-15 AI:31 Refer to Config *30031 *AI: 31 Sensor 4-7 AI:71 Refer to Config *30071 *AI: 71
Sensor 1-16 AI:32 Refer to Config *30032 *AI: 32 Sensor 4-8 AI:72 Refer to Config *30072 *AI: 72
Sensor 2-1 AI:33 Refer to Config *30033 *AI: 33 Sensor 4-9 AI:73 Refer to Config *30073 *AI: 73
Sensor 2-2 AI:34 Refer to Config *30034 *AI: 34 Sensor 4-10 AI:74 Refer to Config *30074 *AI: 74
Sensor 2-3 AI:35 Refer to Config *30035 *AI: 35 Sensor 4-11 AI:75 Refer to Config *30075 *AI: 75
Sensor 2-4 AI:36 Refer to Config *30036 *AI: 36 Sensor 4-12 AI:76 Refer to Config *30076 *AI: 76
Sensor 2-5 AI:37 Refer to Config *30037 *AI: 37 Sensor 4-13 AI:77 Refer to Config *30077 *AI: 77
Sensor 2-6 AI:38 Refer to Config *30038 *AI: 38 Sensor 4-14 AI:78 Refer to Config *30078 *AI: 78
Sensor 2-7 AI:39 Refer to Config *30039 *AI: 39 Sensor 4-15 AI:79 Refer to Config *30079 *AI: 79
Sensor 2-8 AI:40 Refer to Config *30040 *AI: 40 Sensor 4-16 AI:80 Refer to Config *30080 *AI: 80
*- Indicates value multiplied by 10 to include one decimal place. (I.e. BMS value of 500 indicates actual value 50.0)
127
MCS-MAGNUM-BMS- Refrig.
Magnum BACnet ID BACnet Name Modbus N2 Magnum BACnet ID BACnet Name Modbus N2
Relay M–1 BO: 1 Refer to Config 00001 BO: 1 Relay 4–1 BO:41 Refer to Config 00041 BO: 41
Relay M–2 BO: 2 Refer to Config 00002 BO: 2 Relay 4–2 BO:42 Refer to Config 00042 BO: 42
Relay M–3 BO: 3 Refer to Config 00003 BO: 3 Relay 4–3 BO:43 Refer to Config 00043 BO: 43
Relay M–4 BO: 4 Refer to Config 00004 BO: 4 Relay 4–4 BO:44 Refer to Config 00044 BO: 44
Relay M–5 BO: 5 Refer to Config 00005 BO: 5 Relay 4–5 BO:45 Refer to Config 00045 BO: 45
Relay M–6 BO: 6 Refer to Config 00006 BO: 6 Relay 4–6 BO:46 Refer to Config 00046 BO: 46
Relay M–7 BO: 7 Refer to Config 00007 BO: 7 Relay 4–7 BO:47 Refer to Config 00047 BO: 47
Relay M–8 BO: 8 Refer to Config 00008 BO: 8 Relay 4–8 BO:48 Refer to Config 00048 BO: 48
Relay M–9 BO: 9 Refer to Config 00009 BO: 9 Relay 4–9 BO:49 Refer to Config 00049 BO: 49
Relay M-10 BO:10 Refer to Config 00010 BO: 10 Relay 4 -10 BO:50 Refer to Config 00050 BO: 50
Relay 1–1 BO:11 Refer to Config 00011 BO: 11 Relay 5–1 BO:51 Refer to Config 00051 BO: 51
Relay 1–2 BO:12 Refer to Config 00012 BO: 12 Relay 5–2 BO:52 Refer to Config 00052 BO: 52
Relay 1–3 BO:13 Refer to Config 00013 BO: 13 Relay 5–3 BO:53 Refer to Config 00053 BO: 53
Relay 1–4 BO:14 Refer to Config 00014 BO: 14 Relay 5–4 BO:54 Refer to Config 00054 BO: 54
Relay 1–5 BO:15 Refer to Config 00015 BO: 15 Relay 5–5 BO:55 Refer to Config 00055 BO: 55
Relay 1–6 BO:16 Refer to Config 00016 BO: 16 Relay 5–6 BO:56 Refer to Config 00056 BO: 56
Relay 1–7 BO:17 Refer to Config 00017 BO: 17 Relay 5–7 BO:57 Refer to Config 00057 BO: 57
Relay 1–8 BO:18 Refer to Config 00018 BO: 18 Relay 5–8 BO:58 Refer to Config 00058 BO: 58
Relay 1–9 BO:19 Refer to Config 00019 BO: 19 Relay 5–9 BO:59 Refer to Config 00059 BO: 59
Relay 1- 10 BO:20 Refer to Config 00020 BO: 20 Relay 5 -10 BO:60 Refer to Config 00060 BO: 60
Relay 2–1 BO:21 Refer to Config 00021 BO: 21 Relay 6–1 BO:61 Refer to Config 00061 BO: 61
Relay 2–2 BO:22 Refer to Config 00022 BO: 22 Relay 6–2 BO:62 Refer to Config 00062 BO: 62
Relay 2–3 BO:23 Refer to Config 00023 BO: 23 Relay 6–3 BO:63 Refer to Config 00063 BO: 63
Relay 2–4 BO:24 Refer to Config 00024 BO: 24 Relay 6–4 BO:64 Refer to Config 00064 BO: 64
Relay 2–5 BO:25 Refer to Config 00025 BO: 25 Relay 6–5 BO:65 Refer to Config 00065 BO: 65
Relay 2–6 BO:26 Refer to Config 00026 BO: 26 Relay 6- 6 BO:66 Refer to Config 00066 BO: 66
Relay 2–7 BO:27 Refer to Config 00027 BO: 27 Relay 6–7 BO:67 Refer to Config 00067 BO: 67
Relay 2–8 BO:28 Refer to Config 00028 BO: 28 Relay 6–8 BO:68 Refer to Config 00068 BO: 68
Relay 2–9 BO:29 Refer to Config 00029 BO: 29 Relay 6–9 BO:69 Refer to Config 00069 BO: 69
Relay 2 -10 BO:30 Refer to Config 00030 BO: 30 Relay 6–10 BO:70 Refer to Config 00760 BO: 70
Relay 3–1 BO:31 Refer to Config 00031 BO: 31 Relay 7–1 BO:71 Refer to Config 00071 BO: 71
Relay 3–2 BO:32 Refer to Config 00032 BO: 32 Relay 7–2 BO:72 Refer to Config 00072 BO: 72
Relay 3–3 BO:33 Refer to Config 00033 BO: 33 Relay 7–3 BO:73 Refer to Config 00073 BO: 73
Relay 3–4 BO:34 Refer to Config 00034 BO: 34 Relay 7–4 BO:74 Refer to Config 00074 BO: 74
Relay 3–5 BO:35 Refer to Config 00035 BO: 35 Relay 7–5 BO:75 Refer to Config 00075 BO: 75
Relay 3- 6 BO:36 Refer to Config 00036 BO: 36 Relay 7–6 BO:76 Refer to Config 00076 BO: 76
Relay 3–7 BO:37 Refer to Config 00037 BO: 37 Relay 7–7 BO:77 Refer to Config 00077 BO: 77
Relay 3–8 BO:38 Refer to Config 00038 BO: 38 Relay 7–8 BO:78 Refer to Config 00078 BO: 78
Relay 3–9 BO:39 Refer to Config 00039 BO: 39 Relay 7–9 BO:79 Refer to Config 00079 BO: 79
Relay 3–10 BO:40 Refer to Config 00040 BO: 40 Relay 7–10 BO:80 Refer to Config 00070 BO: 80
*- Indicates value multiplied by 10 to include one decimal place. (I.e. BMS value of 500 indicates actual value 50.0)
128
MCS-MAGNUM-BMS- Refrig.
Analog Output PointsAnalog Output points are read-only. Sensor numbering is based upon SI16-AO4 hardware type
board. Notable BACnet properties available: Units
*- Indicates value multiplied by 10 to include one decimal place. (I.e. BMS value of 500 indicates actual value 50.0)
29.4. Setpoints
Setpoints are read-only. Notable BACnet properties available: Units
Magnum BACnet ID BACnet Name Modbus N2
Setpoint #1 AV:0 STP# 1-<Setpoint name> 40301 ADF:1
Setpoint #21 AV:88 STP# 21-<Setpoint name> 40321 ADF:89
STP# 163-<Setpoint
Setpoint #163 AV:230 40463 ADF:231
name>
*- Indicates value multiplied by 10 to include one decimal place. (I.e. BMS value of 500 indicates actual value 50.0)
129
MCS-MAGNUM-BMS- Refrig.
132
MCS-MAGNUM-BMS- Refrig.
The MCS-Magnum must be setup to accept these inputs. The configuration file must contain a Network Run/Stop,
Network Target, Network Demand FLA, and Network Demand Steps sensors.
Magnum BACnet ID BACnet Name Modbus N2
Network Run/Stop AV:246 Net_R/S 40201 BO:247
Network Target/Reset AV:247 Net_Tar/Res 40202 AO:248
Network Demand/FLA AV:248 Net_Demad_FLA 40204 AO:249
Network Demand/Steps AV:249 Net_Demad_Steps 40205 AO:250
Note the following Information panel has a Network Run/Stop, and /or Network Target Reset sensors inputs indicated.
This is an example of how MCS-Config must be setup in the General Information and Evaporator Information panels.
133
MCS-MAGNUM-BMS- Refrig.
BMS Points Unit State Chart BMS Points RTU Building Mode Chart
State # State # State # State #
MCS & Modbus BACnet State Text/Name MCS & Modbus BACnet State Text/Name
0 1 UNIT IN POWER UP 0 1 LOST IO LOCKED
1 2 POWER LOSS DELAY 1 2 CMP LOCKED OUT
2 3 NO RUN- I/O LOST 2 3 SWITCHED OFF
3 4 UNIT IN LOCKOUT 3 4 UNLD & PMPDWN
4 5 UNIT IS OFF 4 5 CMP ANTICYCLE
5 6 UNIT IS HOLDING 5 6 CMP OFF/READY
6 7 UNIT UNLOADING 6 7 OIL PMP LUBING
7 8 UNIT IS LOADING 7 8 CMP IS RUNNING
8 9 NO RUN - SAFETY 8 9 CMP UNLOADED
9 10 RUN/STOP SW OFF 9 10 CMP UNLD STEP1
10 11 SCHEDULED OFF 10 11 CMP UNLD STEP2
11 12 OFF-NO FLOW(s) 11 12 CMP IS HOLDING
12 13 OFF-NO COND FLOW 12 13 CMP IS LOADING
13 14 AMBIENT OFF 13 14 CMP IS UNLDING
14 15 PROCESS HEAT OFF 14 15 CMP IS RUNNING
15 16 UNIT IS UNLOADED 15 16 FAST UNLOADING
16 17 UNIT IS LOADED 16 17 LO SUCT UNLOAD
17 18 OFF TMP-ICE MADE 17 18 LO SUCT HOLD
18 19 ECONOMIZER ONLY 18 19 HI DISC UNLOAD
19 20 SWITCHING MODES 19 20 HI DISC HOLD
20 21 DEF-STARTING CMP 20 21 SAFETY TRIPPED
21 22 DEFROSTING COILS 21 22 LO TEMP UNLOAD
22 23 HI AMP UNLDING
BMS Points Unit Mode Chart 23 24 HI AMP HOLD
State # State # 24 25 HI DIS TMP HLD
MCS & Modbus BACnet State Text/Name 25 26 CMP IS AT 40%
0 1 CHILLER MODE 26 27 CMP IS AT 70%
1 2 ICE MAKING MODE
27 28 HI WATER HOLD
2 3 HEATING MODE
3 4 DEHUMID MODE 28 29 DEFROST EVAP#1
4 5 VENT ONLY 29 30 DRIP DOWN #1
5 6 DEHUMID MODE 30 31 DEFROST EVAP#2
6 7 OFF
31 32 DRIP DOWN #2
7 8 SWITCHING MODES
8 9 COOLING w/HEAT 32 33 DEF-START COMP
9 10 HEATING w/COOL 33 34 DEF-PUMP DOWN
10 11 DEFROSTING 34 35 DEFROST COILS
35 36 DEF-AIR NORMAL
36 37 DEF-AIR HOTGAS
37 38 CMP OFF/D-DOWN
38 39 CMP OFF/DefAIR
134
MCS-MAGNUM-BMS- Refrig.
135
MCS-MAGNUM-BMS- Refrig.
If you are going to let your network assign the IP Address, Subnet Mask, and Default Gateway:
Press the Menu key, select Serv Tools, and then press the Enter key.
Select Ethernet Network then press Enter.
Set “DYNAMIC IP” to YES.
Connect the MCS-Magnum to the network and power up the board.
136
MCS-MAGNUM-BMS- Refrig.
Over
Ethernet
Over
RS485
Over
LonWorks
Requires MCS-BMS-GATEWAY
137
MCS-MAGNUM-BMS- Refrig.
MCS-MAGNUM
Building
MCS-MAGNUM .. Management
. System
RS485
MCS-MAGNUM
138
MCS-MAGNUM-BMS- Refrig.
139
MCS-MAGNUM-BMS- Refrig.
MCS-Touch (MCS-Connect)
PC (MCS-Connect)
Internet access through router (which allows connection via MCS-Connect from anywhere)
Or
Or
Or
Ethernet
140
MCS-MAGNUM-BMS- Refrig.
Internet Access
RS485 or
LonWorks
Building
Management
System
MCS-BMS-Gateway
Internet
Ethernet
Router
MCS-Touch
141
MCS-MAGNUM-BMS- Refrig.
Rooftop/Chiller #1 Rooftop/Chiller #2
Ethernet
Building
Management Internet
System Router
142
MCS-MAGNUM-BMS- Refrig.
143
MCS-REFRIG MANUALVERSION 17
# (Number)–From 1 to 255 (maximum number of Setpoints supported). Only active Setpoints will be
displayed in
MCS-Connect and on the keypad display.
Value–The value or target of the Setpoint. With proper authorization this value can be changed,
within limits that
have been established in MCS-Config.
Min–The minimum value that can be set. This field is not displayed and cannot be changed in
MCS-Connect or in
the keypad display.
Max–The maximum value that can be set. This field is not displayed and cannot be changed in
MCS-Connect or in
the keypad display.
Adjust Value–The interval that the value field can be changed by. This field is not displayed
and cannot be
changed in MCS-Connect or in the keypad display.
Select Value: # decimals and print char – This indicates the number of decimal places and the
unit character that accompanies the value displayed. The number of decimal places is crucial when the
Value, Minimum, and Maximum data is entered in MCS-Config.
Level of Auth. To Display – This column indicates what authorization level a user must have in order
to view the Setpoint from MCS-Connect or the keypad display.
Comments – This column allows the user to add comments about the function of the Setpoint.
BMS Writeable (Click Here to Disable All) – The Magnum software will enable communica-
tions with an outside source, building management system (BMS), to modify the value of a set point.
Object is to provide maximum flexibility and capability with an BMS.
144
MCS-REFRIG MANUALVERSION 17
145
MCS-REFRIG MANUALVERSION 17
Seconds to ignore – This is the time in seconds to ignore the associated safety at compressor start
up.
The window to extend safety time and safety time extension fields work together.
Window to extend safety – This value in seconds is the time window when the compressor starts
that the safety time extension is added to the safety time(sec) value.
Safety time extension – This value is the time that is added to the time(sec) value during the
window to extend safety time(sec) time.
Example – Unsafe suction setpoint has a 3 second safety trip. So if we add a 120 to our window to extend
safety, we will then be telling the controller at startup we’re going to extend that 3 second safety trip for 120
seconds. This is where the Safety time extension comes into play. If we put a 6 in this field we’re telling the
controller for the first 120 seconds at startup we’re extending the safety trip time to 9 seconds (3 second
trip plus the 6 second extension). Once the 120 seconds expires we will then revert back to a 3 second trip time
for the duration of the compressors run time till the next startup.
146
MCS-REFRIG MANUALVERSION 17
1 CTL TARGET Control target. This value is used as the base to develop the Control Zone. Refer
to setpoints # 2 and #3.
The control target is used with the control zone and rate of change of the control-
ling sensor to determine required action for the system. The controlling sensor is
usually one of the following:
Leaving Temperature – Most common used as a target, fitting for most applica-
tions.
Return Temperature – Used in sites with large air masses, ice rinks, common
areas, etc.
Suction Pressure – Used in continuously running process systems.
2 CTL ZONE + Added to the CTL TARGET to create the upper limit of the control zone.
3 CTL ZONE - Subtracted from the CTL TARGET to create the lower limit of the control zone.
4 HGS TEMP ON This setpoint is used with screw compressors with a hot gas bypass solenoid.
When this setpoint is active and the control temperature is less than the CTL
TARGET plus the value in this setpoint and the FLA % is within 25% of setpoint
#31 “MIN SLIDE%”, the hot gas bypass solenoid for the compressor will be
turned on.
‘Time (sec)’ field: If this field is not zero, it is added to setpoint #31 to determine
when the hot gas solenoid is to be turned on. If zero, then the value of 2.5 is
added.
5 HGS TEMP OFF This setpoint is used with screw compressors with a hot gas bypass solenoid.
When this setpoint is active and the control temperature is greater than the CTL
TARGET plus the value in this setpoint or the FLA % is not within 25% of set-
point #31 “MIN SLIDE%”, the hot gas bypass solenoid for the compressor will be
turned off.
‘Time (sec)’ field: If this field is not zero, it is added to setpoint #31 to determine
when the hot gas solenoid is to be turned off. If zero, then the value of 3.0 is
added.
6 HGS PSI ON This setpoint is used with screw compressors with a hot gas bypass solenoid.
** not used When this setpoint is active and the suction pressure is less than the value of
this setpoint and the FLA % is within 25% of the setpoint #31 “MIN SLIDE%”, the
hot gas bypass solenoid for the compressor will be turned on.
7 HGS PSI OFF This setpoint is used with screw compressors with a hot gas bypass solenoid.
** not used When this setpoint is active and the suction pressure is greater than the value of
this setpoint or the FLA % is not within 25% of the setpoint #31 “MIN SLIDE%”,
the hot gas bypass solenoid for the compressor will be turned off.
8 L.INJECT.ON This setpoint can be used for both liquid injection solenoids.
** not used Value: Liquid injection is turned on when the discharge temperature is greater
than or equal to this setpoint, and is turned off when the discharge temperature
is less than this setpoint minus 10.0°F (5.5°C).
‘Time (sec)’ field: If the first liquid injection solenoid has been on for a time
greater than this value, then turn on the second liquid injection solenoid.
9 SPRHT TARGET If EXV control is based upon superheat, this is the Superheat target that the
or system will control from.
LEVEL TARGET If EXV control is based upon refrigerant level, this is the refrigerant level target
that the system will control from.
‘Low Zone’ if nonzero then develop control super heat based upon the lowest
superheat of any compressor that is on with in this suction group else use the
superheat of this compressor.
‘Time (sec)’ field: Seconds between samples used for calculating the Superheat
Rate of Change.
10 SPRHT ZONE +- The value in this setpoint is added and subtracted to setpoint #9 to determine
the upper and lower limits of the control zone respectively.
‘Time (sec)’ field: If non-zero, skip ROC adjustment logic in the control zone.
147
MCS-REFRIG MANUALVERSION 17
11 EXV LOAD ADJ The opening adjustment that will be made to the EXV percentage when the
circuit changes to the Loading state, or the closing adjustment that will be made
when the circuit changes to the Unloading state.
Note: In MOP hold state, only closing adjustments are allowed.
12 EXV FINE ADJ The adjustment is made when in the 1st zone above or below the control zone.
Refer to section on EXV control.
13 EXV COURSE If a course adjustment to the EXV when in the 2nd zone above or below the
control
zone.
If the type is TIME and the time (SEC) field is greater than 1 and less than 7 then
multiple the value field by the time field else multiple by 2 for adjustment amount.
If a course adjustment to the EXV when in the 3nd zone above or below the
control
zone. Multiple value by the by 2 for adjustment amount.
If a course adjustment to the EXV when above or below the 3nd zone the control
zone.
The value is the adjustment amount.
Refer to section on EXV control. If a course adjustment to the EXV when in the
3nd
zone above or below the control zone. Multiple value by the by 2 for adjustment
amount.
If a course adjustment to the EXV when above or below the 3nd zone the control
zone.
The value is the adjustment amount.
Refer to section on EXV control.
14 EXV LOAD DIV The EXV slide adjustment can be fined tuned by dividing by the value of this set
point.
Note the value of this set point is used regardless if the set point is active or not.
15 EXV MIN % This is the minimum valve position allowed when modulating the expansion
valve. This value should be set so when hot gas is applied the valve opening is
adequate.
Note the value of this set point is used regardless if it is active or not.
Refer to section on EXV control.Note the value of this set point is used regard-
less if it is
active or not.
16 EXV MAX % This is the maximum position allowed when modulating the expansion valve to
maintain the superheat target. This value should be the valve % opening at full
capacity plus a 10 to 15 % margin.
17 LO SUPERHEAT If super heat is less or equal to this value and the control slope is less that the
roc for
zone 3, make a slide adjustment of 3 times the value of set point #13.
If the calculated superheat remains below this value for the time specified in the
Time
(SEC) cell, the Magnum will generate a LOW SUPERHEAT alarm.
Refer to section on EXV control.
18 LOWSUCPSI DLY Delay in seconds when in ‘Low Suction PSI Opening’ between adjustments to
the EXV valve.
19 EXV DELAY Delay in seconds between valve adjustments. Should not be less than 48.
(When adjusting at 4x this will allow 12 seconds for the controller to process the
results of the last action before making the next adjustment)
20 EXV STRT TIME This is the time in seconds to hold the valve at the start % setpoint when the
compressor starts. Since the superheat calculation is not valid when the com-
pressor is not running the EXV logic sets the valve to a given position for a set
time to allow the system to develop a valid superheat.
‘Time (sec)’ field: If zero, then there is no delay when a compressor is ready to
start. If non-zero, this is the time delay in which the EXV valve is allowed to open
before the compressor starts.
148
MCS-REFRIG MANUALVERSION 17
21 MAX TRG RESET This value is used to adjust setpoint #1 “CTL TARGET”. The sensor input value
** not used will vary between 0 and 5 volts and the adjustment to the control target will be
modulated from negative “MAX TRG RESET” to the positive “MAX TRG RESET”
value.
22 LOW AMBIENT If the ambient temperature is below this value the system will be disabled and
the unit state will be AMBIENT OFF. The unit will remain off until the ambient
temperature rises above this setpoint value by 5.0F (2.5C).
23 POWERUP DELAY The time in seconds that the system will remain in the START UP state before
moving to the next state.
24 HI AMBIENT If the ambient temperature is above this value the system will be disabled and
the unit state will be AMBIENT OFF. The unit will remain off until the ambient
temperature drops below this setpoint value by 5.0F (2.5C).
25 STEP SENSTIY This value is used to adjust the rate of response to changes in the control
algorithm. 1 is the fastest response, whereas higher numbers will mean a more
gradual response. Used only with the Magnum Control Zone control method.
26 STEP DELAY Value: This is the time delay before making adjustments to the system capacity.
Used with both the Magnum Control Zone and Voltage Step control method.
‘Time (sec)’ field: If used, this will force a minimum time delay between any two
compressor starts. This time delay is specified in the ‘Minimum Delay Between
Compressor Starts’ box in the ‘Compressor Information’ section under the MAG
REFR tab.
27 MAX ROC - Maximum negative Rate of Change allowed before preventing the unit from load-
ing. If the ROC is less than this value the capacity control state is set to HOLD-
ING. Used only with the Magnum Control Zone control method.
28 MAX ROC + Maximum positive Rate of Change allowed before preventing the unit from un-
loading. If the ROC is greater than this value the capacity control state is set to
HOLDING. Used only with the Magnum Control Zone control method.
29 ROC INTERV Seconds between samples used for calculating the Rate of Change. Used only
with the Magnum Control Zone control method. (Maximum 60 seconds)
30 MAX FLA % Indicates the maximum amp draw or speed allowed. Usually set to 100%, else
or compressors will load to the value of this setpoint until all steps are on, then the
MAX VFD % system will load to 100%.
‘Time (sec)’ field: If non-zero, then force individual compressors to stay at maxi-
mum capacity when another compressor starts. This option is selected in in the
‘Keep Running Comp at 100% when starting next?’ box in the ‘Compressor Infor-
mation’ section under the MAG V8 tab.
31 MIN FLA % Value: Indicates the minimum amp draw or speed allowed (usually 40%). This is
or where the slide valve or VFD will be set when the compressor is turned on. This
MIN VFD % % is a function of actual amp draw relative to the FLA.
‘Time (sec)’ field: If used, this forces a time delay before unloading all running
compressors before the next compressor is started. This time delay is specified
in the ‘Unload Compressor Before Starting Next’ box in the ‘Compressor Infor-
mation’ section under the MAG V8 tab.
‘Target’ field: Adds support to force the digital compressor speed to a different
min value if only the digital compressor is running on the suction group.
In order to use this new logic you must make setpoint #31 “Min Spd%” a “TAR-
GET” type and put in the Low Zone column the min speed value you want to
running the digital compressor when only the digital compressor is running on
the suction group.
32 MAX ADJUST % Indicates the maximum percentage change that can be made to the slide valve
or VFD.
‘Time (sec)’ field: A zero indicates that the calculated FLA will be used, else the
value in setpoint #31 will be used when starting the next compressor. This value
is specified in the ‘Wanted FLA starting next Compressor’ box in the ‘Compres-
sor Information’ section under the MAG V8 tab.
149
MCS-REFRIG MANUALVERSION 17
33 MIN ADJUST % Indicates the minimum percentage change that can be made to the slide valve or
the VFD.
34 SLIDE SENSITY This controls the sensitivity of the adjustment made to the Wanted Percentage
(adjustments are relative to the difference between the current control sensor
and target). The larger the value the larger the adjustment (usually 1).
35 LOAD PULSE Length of time to engage the slide valve load solenoid in tenths of a second
(usually between 1 and 9).
‘Time (sec)’ field: If non-zero, use this value as a multiplier to increase the load
pulse when the compressor’s amp draw is more than twice the value of setpoint
#36 “AMP DB LO”.
36 UNLOAD PULSE Length of time to engage th e slide valve unload solenoid in tenths of a sec-
ond (usually between 1 and 9).
37 LUBE OIL TMP Safety. If oil seal temperature sensor and this set point is active then when the
compressor is running the oil temperature will be checked for a low condition
based on the values in this set point.
38 LUBE OIL PSI The oil must reach this pressure before the circuit will move out of the LUBE
** not used state.
39 LUBE DELAY This is the maximum time that a compressor can be in the LUBE state. When
this time is exceeded, an alarm is generated and the compressor is locked out.
Both the oil temperature and pressure must be satisfied before the LUBE state
will be exited. Refer to the OIL PMP LUBING state.
40 CND STG1 ON When the discharge pressure is above this value, turn on the first stage of the
(Air cooled) condenser fans.
‘Time (sec)’ field: (Applies to compressors with shared condensers) If non-zero,
then the compressor in startup state will not be in sole control of the condenser
fans, it will control off of highest discharge pressure. If zero, then compressor in
startup will have sole condenser control for 5 minutes. This option is selected in
in the ‘Newly started Comp Controls Common Fan Bank’ box in the ‘Condenser
Information’ section under the MAG V8 tab.
PID MOD Individual If active, multiplier uses PID condenser control KP (Proportional). Setup as
PID Step Comm setpoint.
41 CND STG1 OFF If stage 1 of condenser capacity is on and the discharge pressure drops below
(RO Type) this value, then turn this stage off.
PID MOD Individual If active, uses Multiplier for Ki adjustments (Integral Time Delay). Setup as set-
PID Step Common point
42 CND DIFF ON Differential pressure added to setpoint #45 to set the threshold at which each
(RO Type) additional stage of condenser capacity will turn on.
PID MOD Individual If active, uses Multiplier for Kd adjustments, (ROC Time Delay). Setup as Target.
PID Step Common
44 CND MIN RUN Once a condenser stage has been turned on, it will remain on for at least the
(Modulating Type) amount of minutes specified in this setpoint.
DUAL TIME DELAY Time delay once the pressure difference in setpoint #48 has been reached be-
(Dual V8) fore the second condenser stage can be started.
45 LO AMB COND
** OFF
not used
46 CND PSI TARG Target discharge pressure which the condenser valve will try to maintain by
(Modulating Type) modulating open or closed.
150
MCS-REFRIG MANUALVERSION 17
47 CND ADJ DIV Controls scaling of the amount the valve is adjusted (Usually 1). The larger the
(Modulating Type) number the smaller the valve adjustment as the adjustment will be divided by
this value.
CND VFD MIN If there is a VFD associated with the condenser, this is the starting minimum
speed.
‘Time (sec)’ field: This field contains the condenser stage that must be on before
the VFD is modulated.
48 CND MIN SPD Minimum valve opening percentage allowed.
(Modulating Type) If the compressor is off, then check the ‘Time (sec)’ field:
If 0, then set the VFD to the value of this setpoint. If 2 and the run/stop is set
to run, then set the VFD to 100%, else set the VFD to 0%. This option is selected
in in the ‘Default Valve Opening % when Comp. is OFF’ box in the ‘Condenser
Information’ section under the MAG V8 tab.
49 CND ROC- Maximum negative discharge pressure rate of change allowed. If the rate of
(Modulating Type) change is less than this setpoint, then stop opening the valve. The absolute val-
ue of this setpoint also serves as the maximum positive rate of change allowed.
If the rate of change is greater than the absolute value of this setpoint, then stop
closing the valve.
50 CND MIN SPD Minimum speed percentage for variable speed condenser control.
(Modulating Type)
CND ADJ MULT Allows scaling of the amount the valve is adjusted. The larger the number the
(Modulating Type) larger the valve adjustment will be multiplied by this value.
51 CND MAX SPD Maximum speed percentage for variable speed condenser control.
(Modulating Type)
52 COND LOW AMB Standard condenser logic dictates that a newly started compressor will use its
own discharge pressure as the control for the first five minutes. If this setpoint is
active and the ambient temperature sensor is reading less than the value of this
setpoint, then this compressor’s discharge pressure will remain in control for the
additional time in seconds as specified in the ‘Time (sec)’ field.
53 LOW AMBIENT
** OFF
not used
54 COND HI AMB If active, standard condenser control on compressor startup logic will be by-
passed when there is a high ambient temperature. If the condenser type is
common and the ambient temperature is above the value of this setpoint, then
the compressor with the highest discharge pressure will have control of the
condenser.
55 COND FAULT For Condensers with Fault Indicators: If setpoint is active, a condenser fault oc-
curs, and the setpoint type is Alarm, then an alarm message will be generated.
If the type is Lockout, and a condenser fault occurs, then all of the compressors
associated with this fault will be locked off.
For Common VFD Fan Condensers with Bypass: Time in seconds before the
bypass can be used when a fault has occurred.
56 COND PHASE If this set point is active and a digital input has been selected for the Condenser
Fault 1 Phase Failure 1 when the compressor is on this digital input will be checked. If
the digital input is on for the Time specified for this set point, the circuit will enter
a safety state and an alarm will be generated indicating which circuit has the
failure.
57 COND PHASE If this set point is active and a digital input has been selected for the Condenser
Fault 2 Phase Failure 2 when the compressor is on this digital input will be checked. If
the digital input is on for the Time specified for this set point, the circuit will enter
a safety state and an alarm will be generated indicating which circuit has the
failure.
151
MCS-REFRIG MANUALVERSION 17
58 CFG TESTING This must be setup as ‘Non-Active. If active the system will not lockout when an
I/O communications signal is lost. This setpoint should NOT be active in a live
unit.
59 ACYC OFF->ON This is the anti-cycle time delay (in seconds) from when the compressor was
turned off. The compressor must wait the time frame (in seconds) in this set-
point, from last shutting off, before being allowed to start again.
60 ACYC ON->ON This is the anti-cycle time delay (in seconds) from when the compressor was
turned on. The compressor must wait the time (in seconds) in this setpoint, from
last start, before being allowed to start again.
61 PMP CUT IN
** not used
62 PMP DWN OFF This is the suction pressure value for turning off the compressor when in the
PUMP DOWN or for opening the liquid line solenoid during the PRE-PUMP
down state.
‘Time (sec)’ field: If non-zero, then the system will bypass the pre-pump down
state. This option is selected in the ‘Pre-Pump Out’ box in the ‘Compressor In-
formation’ section under the MAG V8 tab.
63 PMP DWN DELY Maximum time delay (in seconds) that a compressor can remain in the PUMP
DOWN or PRE-PUMP down states.
64 COMP MIN RUN This is the minimum run time (in minutes) for a compressor once it is turned on.
This minimum run time can be overridden by a safety condition, however.
65 STARTER DLAY This setpoint controls the start of a compressor’s second relay.
If the ‘Select Value: # decimals & print char’ cell is set to ‘HUMD or %’ then logic
is:
If the slide amp percentage is less than the value of this setpoint and the first
relay has been on for 2 seconds or it has been on longer than the value in the
safety time of this setpoint, then turn on the second relay. Else it is off.
If the ‘Select Value: # decimals & print char’ cell is set to ‘Seconds’ then the set-
point’s value is a time delay between the first and second relay’s starts. Used for
part wind (typical value of 1) and star delta (typical value of 5) starter.
66 OIL PUMP OFF If oil pump is set up to cycle and discharge psi minus, etc.(specified in MCS-
** not used Config), this Setpoint is not used.
If Discharge PSI minus Suction PSI is less than Setpoint #74 minus 10
PSI than turn on the oil pump RO.
If Discharge PSI minus Suction PSI is greater than Setpoint #74, turn off the oil
pump RO.
67 HI AMPS This setpoint is a percentage of the FLA; it is used to create the high amp draw
limit. The value of this setpoint is multiplied by the respective compressor’s full
load amps setpoint (#171 through #190) to obtain its upper limit. If the compres-
sor’s amps exceed this value for the time specified in this setpoint, then a safety
trip occurs.
68 LO AMPS This setpoint is a percentage of the FLA; it is used to create the low amp draw
limit. The value of this setpoint is multiplied by the respective compressor’s full
load amps setpoint (#171 through #190) to obtain its lower limit. If the compres-
sor’s amps fall below this value for the time specified in this setpoint, then a
safety trip occurs.
69 LOW SUCTION If active, the system checks for low suction pressure for each running compres-
sor. If suction pressure is less than this value for the specified period of time, a
safety trip occurs.
Refers to ‘Suction Pressure’ column in the Circuit SI screen.
152
MCS-REFRIG MANUALVERSION 17
70 LO SUCT UNLD The purpose of this setpoint is to take corrective action to prevent a low suc-
tion pressure safety trip. For fixed step compressors: If a compressor has more
than one step, is fully loaded, and if the suction pressure is less than the value
of setpoint #77 “LOW SUCTION” plus the value of this setpoint, then one step
of capacity will be turned off. For infinite step compressors: If a compressor has
a suction pressure less than the value of setpoint #69 “LOW SUCTION” plus
the value of this setpoint, then the compressor will be forced to unload. The
circuit state will be changed to LO SUCT HOLD, and will remain in this state for
a minimum of the time in setpoint #90 “SAFETY HOLD DELAY”. At that time, if
the suction pressure has increased greater than the value of setpoint #69 “LOW
SUCTION” plus the value of setpoint #79 “LOW SUCT RELD” the compressor
will return to normal control.
71 LOW SUCT RELD Refer to setpoint #78 description.
72 UNSAFE SUCT If active, the system checks for unsafely low suction pressure for each running
compressor. If suction pressure is less than this value for the specified period of
time a lockout occurs. NOTE: The time period specified should be very short (2-5
seconds). If this setpoint trips, the compressor will be sent straight to the Lockout
state.
Refers to ‘Suction Pressure’ column in the Circuit SI screen.
73 HI DISCH PSI If active, the system checks for high discharge pressure for each running com-
pressor. If the discharge pressure sensor reads greater than this setpoint for the
specified period of time, a safety trip will occur.
Refers to ‘Discharge Pressure’ column in the Circuit SI screen.
74 HI DISC UNLD The purpose of this setpoint is to take corrective action to prevent a high dis-
charge pressure safety trip. For fixed step compressors: If a compressor has
more than one step, is fully loaded, and if the discharge pressure is more than
the value of setpoint #73 “HI DISCH PSI” minus the value of this setpoint,
then one step of capacity will be turned off. For infinite step compressors: If a
compressor has a discharge pressure more than the value of setpoint #73 “HI
DISCH PSI” minus the value of this setpoint, then the compressor will be forced
to unload. The circuit state will be changed to HI DISC HOLD, and will remain
in this state for a minimum of the time in setpoint #90 “SAFETY HOLD DELAY”.
At that time, if the discharge pressure has decreased below than the value of
setpoint #73 “HI DISCH PSI” minus the value of setpoint #75 “HI DISC RELD”
the compressor will return to normal control.
75 HI DISC RELD Refer to setpoint #74 description.
76 LO DISC SHEAT If the calculated discharge superheat is less than this value for the specified
period of time, a safety trip will occur. Also, there is an option in the Circuit Base
screen to tie a Relay Output to this setpoint that will activate whenever a low
discharge superheat condition occurs.
77 LO DISC PSI If active, the system checks for low discharge pressure. If the discharge sensor
reading is less than this value for the specified period of time, a safety trip oc-
curs.
78 HI RETURN TEMP Only active in Mistubishi compressors. If active the system will check for high
** Not used entering liquid temperature. If this temperature is greater than the value in this
setpoint, the circuit state will be HI WATER HOLD.
79 HI DISCH TMP If active, the system checks for high discharge temperature for each compressor.
If the discharge temperature sensor reading is greater than this setpoint for the
specified period of time, a safety trip will occur.
Refers to ‘Discharge Temperature’ column in the Circuit SI screen.
153
MCS-REFRIG MANUALVERSION 17
80 DIS TMP UNLD The purpose of this setpoint is to take corrective action to prevent a high dis-
charge temperature safety trip. For fixed step compressors: If a compressor has
more than one step, is fully loaded, and if the discharge temperature is more
than the value of setpoint #79 “HI DISCH TMP” minus the value of this setpoint,
then one step of capacity will be turned off. For infinite step compressors: If a
compressor has a discharge temperature more than the value of setpoint #79
“HI DISCH TMP” minus the value of this setpoint, then the compressor will be
forced to unload. The circuit state will be changed to HI DISC HOLD, and will
remain in this state for a minimum of the time in setpoint #90 “SAFETY HOLD
DELAY”. At that time, if the discharge temperature has decreased below than
the value of setpoint #79 “HI DISCH TMP” minus the value of setpoint #81 “DIS
TMP RELD” the compressor will return to normal control.
81 DIS TMP RELD Refer to setpoint #80 description.
82 LOW OIL DIF If active, the system checks for low differential oil pressure. If the calculated
differential oil pressure is less than this value for the specified period of time, a
safety trip occurs.
Refers to ‘Oil Pressure’ column in the Circuit SI screen.
83 UNSAFE OIL If active, the system checks for unsafe differential oil pressure. If the calculated
differential oil pressure is less than this value for the specified period of time,
a lockout occurs. NOTE: The time period specified should be very short (2-5
seconds). If this setpoint trips, the compressor will be sent straight to the Lockout
state.
Refers to ‘Oil Pressure’ column in the Circuit SI screen.
84 HI OIL SEAL If the oil seal or oil cooler temperature exceeds the value of this setpoint for the
time specified, a safety trip occurs.
Refers to ‘Oil Seal Temp’ column in Circuit SI screen.
85 HI OIL TEMP If active, the system checks for high oil temperature. The sensor can be either
an analog or digital input. If the oil temperature sensor reading is ON (Digital) or
exceeding the temperature value of this setpoint (Analog) for the specified period
of time, a safety trip occurs.
Refers to ‘Oil Temp’ column in the Circuit SI screen.
86 MOTOR FAULT If active, the system checks for high motor temperature. The sensor can be
either an analog or digital input. If the motor temperature sensor reading is ON
(Digital) or exceeding the temperature value of this setpoint (Analog) for the
specified period of time, a safety trip occurs.
Refers to ‘Motor Temp’ column in the Circuit SI screen.
87 NO CMP PROOF If active, when the compressor is called to be on by the controller, the system will
check for a digital input to indicate that the compressor is indeed running. If the
controller calls for a compressor to turn on and no proof is given in the specified
period of time, a safety trip occurs.
Refers to ‘Comp Proof’ column in the Circuit Base screen
88 DIRTY FILTER If discharge pressure minus oil filter pressure is greater than this value for the
time specified, a safety trip occurs.
89 HIGH SUMP TEMP If active, and sump temperature is above the value of this setpoint for the time
** not used specified, a HIGH SUMP TEMP alarm is generated and the unit is locked out.
90 SAFETY HOLD Time in seconds that the circuit will remain in a hold state after the condition that
DELAY caused it has returned to normal. The circuit can be holding for the following
(only used with vari- reasons:
able type of com- Low suction pressure
pressors) Low refrigerant temperature
High discharge pressure
High discharge temperature
High amperage
91 PUMP FREEZE
** PROTECTION
not used
154
MCS-REFRIG MANUALVERSION 17
92 LEAD COMP Enables the user to specify the lead compressor. The value of this setpoint will
indicate the lead compressor. If zero, then auto rotation is enabled.
If the ‘Time (sec)’ field is non-zero the compressor with the least amount of run
time will become the lead compressor upon rotation.
93 COMP ROTATION Specifies the number of days between rotations (setpoint #92 must be set to
zero to enable auto rotation). If zero, then rotation will occur with every cycle.
94 LLS#2 ON This setpoint is used to control a second liquid line solenoid. When the capacity
** not used wanted is greater than this value (can either be number of steps for Fixed Step
compressors, or percentage of full load amps for Infinite Step compressors) for
the number of seconds in the ‘Time (sec)’ field, the second liquid line solenoid
will open. When the compressor capacity below this value for the number of sec-
onds in Delay Between Trips Field the second liquid line will be turned off.
‘Time (sec)’ field: The delay in seconds before the solenoid will be turned on. If
zero, then there will be no delay.
Delay Between Trips Field: The delay in seconds before turning this solenoid off.
If zero, then an offset of 20 seconds will be used.
95 LLS#3 ON This setpoint is used to control a third liquid line solenoid. When the capacity
** not used wanted is greater than this value (can either be number of steps for Fixed Step
compressors, or percentage of full load amps for Infinite Step compressors) for
the number of seconds in the ‘Time (sec)’ field, the third liquid line solenoid will
open. When the compressor capacity below this value for the number of sec-
onds in Delay Between Trips Field the third liquid line will be turned off.
‘Time (sec)’ field: The delay in seconds before the solenoid will be turned on. If
zero, then there will be no delay.
Delay Between Trips Field: The delay in seconds before turning this solenoid off.
If zero, then an offset of 20 seconds will be used.
96 FREEZE If active, the system will compare the leaving temperature to this setpoint. If it is
less than this value for the specified period of time, a safety trip occurs.
97 NO STOP This setpoint is used to ensure that a compressor is actually off when the con-
troller calls for it to be off. This setpoint contains a percentage of the FLA for set-
points #171-#190. If the compressor amperage is greater than this percentage of
the FLA setpoint for the specified period of time, signaling that the compressor is
still running, then the entire system is locked out and a NO STOP alarm is gener-
ated. If a Control Power relay is specified, then it will be turned off when this
safety trips.
98 OIL INJ TEMP DIFF This is a temperature differential subtracted from setpoint #8 to control the oil
** not used injection relay. When discharge temperature is above this differential, then oil
injection is turned on. If inactive then value will be 5.6° F (2.8° C).
99 OIL TEMP DIFF This is a temperature differential used in controlling the oil heater and second
** not used liquid line solenoid. If inactive then value will be set to 5° F.
100 OIL FLOAT If active, the system checks for an oil float digital input. It must be ON for the
period of time specified in the setpoint before this setpoint will trip.
101 Lost Leg Alm If active, a check for a lost leg (lost current flow) on a part winding starter is
added. A current sensor will be placed on only one of the legs; it must be set up
to be multiplied by 2 in MCS-Config (select CT-### x2 as the sensor in the SI
screen). If current flow to the leg with the sensor is lost, a low amp alarm will be
generated. If the sensor is reading more than the wanted FLA times the value of
this setpoint for the specified period of time, then a high amp alarm is generated.
102 LOW AMBIENT Compressors with a low SI Off sensor will be disabled when the sensor is below
** OFF this setpoint.
not used
103 HI AMBIENT OFF Compressors with a high SI Off sensor will be disabled when the sensor is above
** not used this setpoint.
104 UNLOADED % Used if a slide open percentage sensor is present. When this sensor is reading
** not used less than the value of this setpoint, then the slide is considered closed.
155
MCS-REFRIG MANUALVERSION 17
105 OIL HEATER ON The oil heater will be turned on if the oil temperature is less than the value of this
** not used setpoint. It will be turned off if the oil temperature is greater than the value of this
setpoint plus 5.0° Fahrenheit.
‘Time (sec)’ field: If zero, then the calculated oil temp will be the saturated suc-
tion temperature plus the value of the setpoint. Else it will be the value of this
setpoint.
106 OIL COOLER ON The oil cooler will be turned on if the oil seal temperature is greater than the
** not used value of this setpoint. It will be turned off if the oil seal temperature is less than
the value of this setpoint minus 5.0° Fahrenheit.
107 UNLOADED OFF If active, the system is fully unloaded, and the control temperature is greater
** not used than this value, then the capacity state will be set to holding.
108 HP OVERHEAT This setpoint is only used when the heat pump option has been selected in the
‘Unit Type’ box in the ‘General Information’ section under the MAG V8 tab. It is
used to protect against a heat pump with unloaders (or variable speed) from
overheating. When this setpoint is active and the leaving temperature sensor is
greater than this setpoint minus 3.0° Fahrenheit, then the compressor will enter
HIGH TEMP UNLOAD state. The temperature must drop to less than this set-
point minus 4.5° Fahrenheit before the system will move to the holding state.
109 SftyUnld Del The time delay in seconds between compressor capacity adjustments when
safety unloading.
110 VFD Sfty Adj The VFD percentage adjustment to be made after every amount of time in set-
point #153 “SftyUnld Del” when safety unloading.
111 LO REF TMP If active, the system checks for low refrigerant temperature. If the refrigerant
temperature is less than the value of this setpoint for the specified period of time,
a safety trip occurs.
112 LO REF UNLD The purpose of this setpoint is to take preventative action before a low refriger-
ant temperature safety trip. The compressor will unload when the refrigerant
temperature is less than the value of the setpoint #111 “LO REF TMP” plus
this setpoint. The compressor state will be changed to LO TMP UNLOAD. The
compressor will remain in this state until the refrigerant temperature is above the
value of setpoint #111 “LO REF TMP” plus twice the value of this setpoint. The
compressor state change to LO TMP HOLD.
113 CRANK CASE If active and a crank case heater proof has been specified for a circuit, if the
HEAT digital input, crank case heater proof , is on for the time specified a compressor
safety will be generated.
114 DHH WAIT The system will wait the number of seconds contained in this set point if the
compressor is in dehumidification heat mode and the compressor is ready to be
defrosted before the defrost cycle begins.
115 ROTATE EVAP If active, then the Relay Outputs must have a second liquid line solenoid and 2
** hot gas solenoids. Not used with Reverse Cycle type of defrost. Must be active
and a value = 1
If active and the value is 0 then when the system is in the dehumidification mode
the evaporators will be rotated during the defrost cycle. Refer to dehumidification
defrost with rotation.
116 MAX IN DEHUM This is the maximum number of evaporator solenoids that can be on when the
** not used system is in the dehumidify mode.
117 DefConvType Indicates the types of defrost. If active and value is a 1 then conventional defrost
will be used . Else Defrost on the Fly type of defrost will be used.
118 DEF HI TEMP Set points #118, #119 & #120 work as a group. If the entering temperature is
less than set point #118 but greater than set point #121, the values in #118, #119
& #120 will be used to determine if a defrost cycle is required.
‘Target’ - then setpoint high zone column is used as the ambient disable temper-
ature for rotating coil defrost. Otherwise if is not configured as “Target” type the
old logic value as the ambient disable point for rotating coil defrost is used.
156
MCS-REFRIG MANUALVERSION 17
119 DEF HI APPR The calculated defrost approach temperature must be greater than the value of
this set point for the system to enter a high defrost cycle.
120 DEF HI TIME This set point contains the time expressed in minutes that a compressor will
remain in a high defrost cycle. Expressed as minutes.
‘Target’ - then manual defrost time delay is based on the enter temp compared to
setpoint #118, 121, and 124 and uses the values in the high zone column from
setpoint #120, 123, or 126 as the defrost time delay.
121 DEF MED TEMP Set points #121, #122 & #123 work as a group. If the entering temperature is
less than set point #121 but greater than set point #123, the values in #121,
#122 & #123 will be used to determine if a defrost cycle is required.
122 DEF MED APPR The calculated defrost approach temperature must be greater than the value of
this set point for the system to enter a medium defrost cycle.
123 DEF MED TIME This set point contains the time expressed in minutes that a compressor will
remain in a medium defrost cycle. Expressed as minutes.
124 DEF LO TEMP Set points #124, #125 & #126 work as a group. If the entering temperature is
less than set point #121, the values in #124, #125 & #126 will be used to deter-
mine if a defrost cycle is required..
125 DEF LO APPR The calculated defrost approach temperature must be greater than the value of
this set point for the system to enter a low defrost cycle.
126 DEF LO TIME This set point contains the time expressed in minutes that a compressor will
remain in a low defrost cycle. Expressed as minutes.
127 DEF DEH APPR If the dehumidification enable indicator is on, the calculated defrost approach
temperature must greater than the value of this set point for the system to enter
a defrost cycle.
128 DEF DEH TIME This set point contains the time expressed in minutes that a compressor will
remain in a dehumidification enable defrost cycle. Expressed as minutes.
129 DEF DEH 2ND This set point contains the percent of the time that a compressor will remain in a
dehumidification enable defrost cycle for the second evaporator if set point 115,
ROTATE EVAP, is active and equal to 0.
130 DefMinAccTime This is the minimum accumulated run that a compressor must be on before a
defrost cycle can be initiated. Expressed as minutes.
131 AprTypAdjDly Time in minutes that the system waits, after a defrost, before determining what
defrost valves to use.
132 DEFDRIP DWN This setpoint contains the time expressed in minutes, that the system will remain
in a drip down state for each evaporator defrost. For reverse cycle defrost types,
this setpoint must be active and a value of zero.
133 DEF MAX EVAP This set point contains the maximum number of circuits that can be in defrost at
any one time.
134 EVAP Rotation If this set point is active and its value is greater than zero then the evaporators
will be rotated when the number of evaporator relays that are ON is less than the
number available. The value which is expressed in minutes is the time between
rotations
135 HTGDTD MAIN When the circuit is in a defrost cycle and the time has not exceeded the value
of this set point, the hot gas main is turned off and the hot gas bypass is turned
on. When the time exceeds this value, the hot gas main is turned on; refer to set
point #136 to determine the status of the hot gas bypass.
136 HGDBP&BLEED When the circuit is in a defrost cycle and the time has exceeded the value in set
point #135, HTGDTD MAIN; if this set point contains a zero the hot gas bypass
will be turned off, else it will be turned on.
137 ApprONdly This is the time expressed in seconds that the evaporator temperature must
be greater than the defrost trigger temperature before a defrost cycle will be
checked to determine if a defrost cycle is required.
157
MCS-REFRIG MANUALVERSION 17
138 DEF CMP RTIM This is the minimum time that a compressor must be on before a defrost cycle
can be initiated. Expressed as minutes. Note, time in set point #130, accumu-
lated run must be meet and the compressor must be on for the time specified in
this set point before a defrost cycle is initiated.
139 DEF Min PSI When a compressor is in a defrost start state the defrost cycle will not begin until
the discharge pressure is less or equal to the value in this set point.
140 DEF COND ADJ When a compress is in defrost, the value of this set point is added to the con-
denser set points.
141 DEF PDWN TIM This is the maximum time that a compressor will remain in the defrost pump
down state. Expressed in seconds.
142 DEF PDWN PSI A compressor will remain in the defrost pump down state until the suction pres-
sure decreases by the value of this set point. Also refer to set point #143
143 DEF TERMIN T When a compressor is in a defrost mode and the evaporator suction temperature
rises above the value in this set point, the defrost cycle will be terminated.
144 DEF TERMIN P When a compressor is in a defrost mode and the discharge pressure drops be-
low the value in this set point, the defrost cycle will be terminated.
145 DEF TIME DLY This is the time delay between defrost cycles expressed as minutes. Note this
was a fixed time. Not used if set point #120, #123, #126 high zone has values.
146 DEF AIR HGAS Set point is used to indicate when the defrost air option is used and a hot gas
** not used defrost as backup is required. If this set point is active a message will be gener-
ated indicating which circuit required the hot gas defrost.
147 DEF AIR TIME Value expressed in minutes is the maximum time that a circuit will be in air de-
** not used frosts cycle.
148 DEF AIR BLEED Time expressed in minutes that the bleed solenoid will be on when a normal air
** not used defrost cycle begins. During this time the hot gas main solenoid will be off. Once
this time as pasted the bleed solenoid will be turned off and hot gas main sole-
noid will be turned on.
149 DEF AIR ALARM If this set point is active, a defrost alarm messages will be generated.
** not used
150 EVAP FAN WAIT After defrost time to keep the system off.
** not used
151 LIQUID LINE CTL Only used with a variable type of compressor to control the liquid injection sole-
noid.
152 ADJUST AP- If this set point is active and the number of steps on is greater than the minimum,
PROACH then all approach defrost set points will be adjusted by this set point. This set
point is expressed as a percentage The amount of adjustment is calculated by
taking the number of steps that are on greater than the minimum number and
dividing this by the number of available steps. This is then multiplied by the value
of this set point and it is subtracted from the approach set points. The actual
value of the set point will be changed.
153 HOT GAS ON If there is a modulating hot gas valve, this valve will be modulated when the
control voltage or temperature is below this value.
154 PUMP DELAY Time in seconds to keep the chilled water pump running after the last compres-
** not used sor has been turned off to ensure the chiller barrel does not freeze.
155 HI SI OFF If active, and a High SI OFF sensor is specified (sensor can be an analog or
digital input, and is specified in the Circuit SI screen for each compressor). If
the High SI Off sensor reading ON (Digital) or the temperature rises above the
value of this setpoint (Analog) for the specified period of time, the circuit will be
disabled. If a digital input, the circuit will be enabled once the sensor is off. If an
analog input, the circuit will be enabled once the sensor is less than the value of
this setpoint minus the value in the ‘Time (sec)’ field.
158
MCS-REFRIG MANUALVERSION 17
156 LOW SI OFF If active, and a LOW SI OFF sensor is specified (sensor can be an analog or
digital input, and is specified in the Circuit SI screen for each compressor). If the
LOW SI Off sensor reading ON (Digital) or temperature drops below the value of
this setpoint (Analog) for the specified period of time, the circuit will be disabled.
If a digital input, the circuit will be enabled once the sensor is off. If an analog
input, the circuit will be enabled once the sensor is rises above the value of this
setpoint plus the value in the ‘Time (sec)’ field.
157 COND COMP HIGH If active, this set point contains the pressure difference that will be used to deter-
** not used mine if a compressor has reached a critical condition when another compressor
is in a start up. If inactive, a value of 50.0 PSI will be used. A critical condition
is determined by subtracting this value from set point #70, HI DISCH PSI. If the
discharge pressure is greater then this pressure will be used to control the fans.
158 PHASE LOSS If active and the phase loss digital input is ON for the specified period of time, a
safety trip occurs. The system will attempt to restart after waiting the number of
minutes contained in the ‘Safety Down Time’ field of this setpoint.
159 PWR OFF TIME If the system is off for a time greater than 2 hours then the system state will
be ‘POWER LOSS DELAY’ for the time contained in this setpoint , the time is
expressed in hours.
160 LO SHT DXcoil If the calculated superheat remains below this value for the time specified, the
system will generate a LOW SHT DX alarm. This is the superheat calculated at
the dx coil.
161 HI SHT DXcoil If the calculated superheat remains above this value for the time specified, the
system will generate a HIGH SHT DX alarm. This is the superheat calculated at
the dx coil.
162 LHI SUPERHEAT If the calculated superheat remains above this value for the time specified, the
system will generate a HIGH SUPERHEAT alarm. This is the superheat calcu-
lated at the compressor.
163 HiRefLevel This setpoint has two functions.
If active, the system checks for high refrigeration level. If the refrigeration level
sensor is greater than this value for the specified period of time, a safety trip oc-
curs.
If active, system has EXV valve control based on refrigerant level, and the refrig-
erant level is greater than this value, then the EXV valve adjustment will be set
to the value in setpoint #13 “EXV COURSE” * ( –3).
Refers to ‘Refirg Level’ column in the Circuit SI screen
164 LoRefLvlTarg If setpoint #76 “LO DiscSPRHT” is active and it has reached one third of its safe-
ty time, then setpoint #9 “REF LVL TARG” will be set to the value of this setpoint,
165 PULSE DELAY Used with infinite capacity screws. The number of seconds between load or un-
load pulses (Usually between 3 and 5. Allows load change to be checked before
next pulse and eliminates oil foaming when unloading too fast).
‘Time (sec)’ field: If used, this is the fast unloading state time delay. This option is
selected in in the ‘Fast Unload Delay’ box in the ‘Compressor Information’ sec-
tion under the MAG V8 tab.If non-zero, and when the compressor’s amp draw is
more than twice the value of setpoint #192 “AMP DB LO” away from the wanted
FLA, then set the delay between pulses to zero.
166 REVERSE CYCLE Add logic for Reverse Cycle defrost to have adjustable time delay for turning off
COMP OFF TIME the compressors when first entering into, and coming out of, the defrosting coil
WHEN DEFROST state. If this setpoint is active its value is used as the delay, otherwise 5 seconds
START is still used. This change was made to help the reversing valve to switch posi-
tions before and after defrost was completed. The scroll compressors do not
need this extra time but reciprocating compressors do need it.
159
MCS-REFRIG MANUALVERSION 17
167 PUMP FAILURE If active, flow is lost, and only one pump is present, then the system will be
(NO FLOW) locked out. If the system has two pumps and flow is lost, then the backup pump
will start and the lead pump will be locked out. If the second pump is running and
flow is lost again then the entire system will be locked out. A lock out reset will be
required to restart the system or to reactivate a locked out pump.
If inactive, and the flow is lost, the system will move to the OFF- NO EVAP
FLOW state. When flow is returned the system will automatically restart.
168 UNLOAD DELAY This is the time delay before the system will begin to unload a circuit due to a
pending safety condition. This includes: high discharge PSI, high discharge tem-
perature, low or high amps, or low suction PSI.
169 LO SUCT SHEAT This set point contains the value that indicates a low suction SUPERHEAT con-
dition. If the calculated suction SUPERHEAT is less than this value, the low suc-
tion SUPERHEAT timer will be set to 120 seconds. This will keep the low suction
SUPERHEAT RO on for that period of time. (This can be used as a warning only
or the user may wire through the low suction superheat relay to solve the prob-
lem.) . Note, during the first 5 minutes that compressor has been running, the
safety time is increased to 3 times the safety time of this set point.
170 SERVICE MODE If non-zero, then a compressor being disabled by the pump down switch will be
continue to run until its suction pressure is zero. The compressor will be turned
on to perform the pump down the number of times indicated in this setpoint. This
is in preparation for service to be performed on the compressor.
171 FLA COMP#1 Full Load Amps for compressor #1. This is the amps at design suction and dis-
charge pressures referenced in the MCS-Config RO screen. This value is used
to calculate the high and the low amperage safety limits. Refer to setpoints #75
and #76.
For screw compressors: The amp draw when the compressor is fully loaded.
This value is used to calculate the Full Load Amps Percentage (FLA %), which is
used to control loading and unloading the slide valve.
172 FLA COMP#2 Full Load Amps for compressor #2. Refer to setpoint #171.
173 FLA COMP#3 Full Load Amps for compressor #3. Refer to setpoint #171.
174 FLA COMP#4 Full Load Amps for compressor #4. Refer to setpoint #171.
175 FLA COMP#5 Full Load Amps for compressor #5. Refer to setpoint #171.
176 FLA COMP#6 Full Load Amps for compressor #6. Refer to setpoint #171.
177 FLA COMP#7 Full Load Amps for compressor #7. Refer to setpoint #171.
178 FLA COMP#8 Full Load Amps for compressor #8. Refer to setpoint #171.
179 FLA COMP#9 Full Load Amps for compressor #9. Refer to setpoint #171.
180 FLA COMP#10 Full Load Amps for compressor #10. Refer to setpoint #171.
181 FLA COMP#11 Full Load Amps for compressor #11. Refer to setpoint #171.
182 FLA COMP#12 Full Load Amps for compressor #12. Refer to setpoint #171.
183 FLA COMP#13 Full Load Amps for compressor #13. Refer to setpoint #171.
184 FLA COMP#14 Full Load Amps for compressor #14. Refer to setpoint #171.
185 FLA COMP#15 Full Load Amps for compressor #15. Refer to setpoint #171.
186 FLA COMP#16 Full Load Amps for compressor #16. Refer to setpoint #171.
187 FLA COMP#17 Full Load Amps for compressor #17. Refer to setpoint #171.
188 FLA COMP#18 Full Load Amps for compressor #18. Refer to setpoint #171.
189 FLA COMP#19 Full Load Amps for compressor #19. Refer to setpoint #171.
190 FLA COMP#20 Full Load Amps for compressor #20. Refer to setpoint #171.
160
MCS-REFRIG MANUALVERSION 17
191 AMP DB HI Used only with screw and centrifugal compressors. If the set point type is “hu-
midity”
then the upper dead band is value times the FLA for that circuit else the value is
the upper dead band limit of the FLA. If the amps are within the dead band, the
slide valve will not be moved.
If controlled by Slide Position, instead of FLA, this Setpoint will not be used.
192 AMP DB LO Used only with screw and centrifugal compressors. . If the set point type is “hu-
midity”
then the lower dead band is value times the FLA for that circuit else the value is
the lower dead band limit of the FLA. If the amps are within the dead band, the
slide valve will not be moved.
If controlled by Slide Position, instead of FLA, this Setpoint will not be used.
193 MOP TARG PSI If active, maximum operating pressure (MOP) control will be added to the EXV
control logic. This value will be the MOP suction pressure target.
194 MOP PSI ZONE Added to and subtracted from setpoint #199 to develop the upper and lower
limits of the MOP control zone.
193 MOP TARG PSI If active, maximum operating pressure (MOP) control will be added to the EXV
control logic. This value will be the MOP suction pressure target.
194 MOP PSI ZONE Added to and subtracted from setpoint #199 to develop the upper and lower
limits of the MOP control zone.
195 MOP ADJ % TME The adjustment value by which the EXV valve will close each time the MOP logic
calls for it to maintain the suction pressure target. This adjustment will be made
each time after the delay in the ‘Time (sec)’ field has expired.
196 MDP MIN OIL DIFF If active, MDP logic will be added to EXV control. If the oil differential pressure is
less than the value of this setpoint following compressor start up during the time
specified in the Sec to Ignore Safety field, then the MDP function is active and
will close the EXV valve to restore the oil differential pressure. However, the EXV
will not be allowed to go into the MDP logic unless the suction pressure is less
than setpoint #69 “LOW SUCTION” plus twice the value of setpoint #71 “LOW
SUCT RELD”. The MDP logic will be exited and go to EXV HOLDING when the
suction pressure is less than the setpoint #69 “LOW SUCTION” plus the value of
setpoint #71 “LOW SUCT RELD”.
The ‘Sec to Ignore Safety’ cell contains the time that the MDP will be active after
a compressor is started. The ‘‘Time (sec)’ field’ cell contains the offset to exit the
MDP control. The ‘Safety Down Time’ contains the percentage to close the EXV
valve.
197 DELTA TEMP EVP If active, the system will check the temperature differential before additional
** not used capacity is enabled. If the difference between entering and leaving temperature
is greater than the value of this setpoint for the amount of time in the ‘Time (sec)’
field, then no additional capacity will be allowed.
198 HiSuctSheat If active, the system will check for high suction superheat. If the suction super-
heat is greater than the value of this setpoint for the specified period of time, an
alarm will be generated and a safety trip occurs.
199- not used
201
202 NO OIL FLOW If active and there is an Oil Flow sensor specified in the ‘Oil Flow Switch’ cell of
the Circuit SI screen, then the system will test for oil flow. If the No Oil Flow sen-
sor reading is OFF (Digital) or falls below the value of this setpoint (Analog) for
the specified period of time, then a safety trip occurs.
203 SAT EVAP ADJ This set point contains the temperature adjustment that is made to suction tem-
perature (converted from suction PSI) when calculating the evaporator approach
value.
204 SPARE Not used.
161
MCS-REFRIG MANUALVERSION 17
205 STAGE CUT OUT Offset used in calculating the cut out value. Subtracted from the stage cut in set
points #206 through #229
206 STAGE 1 CUT IN STAGE 1 cut in, set point value contains the value when this stage is turned on.
207 STAGE 2 CUT IN STAGE 2 cut in, set point value contains the value when this stage is turned on.
208 STAGE 3 CUT IN STAGE 3 cut in, set point value contains the value when this stage is turned on.
209 STAGE 4 CUT IN STAGE 4 cut in, set point value contains the value when this stage is turned on.
210 STAGE 5 CUT IN STAGE 5 cut in, set point value contains the value when this stage is turned on.
211 STAGE 6 CUT IN STAGE 6 cut in, set point value contains the value when this stage is turned on.
212 STAGE 7 CUT IN STAGE 7 cut in, set point value contains the value when this stage is turned on.
213 STAGE 8 CUT IN STAGE 8 cut in, set point value contains the value when this stage is turned on.
214 STAGE 9 CUT IN STAGE 9 cut in, set point value contains the value when this stage is turned on.
215 STAGE 10 CUT IN STAGE 10 cut in, set point value contains the value when this stage is turned on.
216 STAGE 11 CUT IN STAGE 11 cut in, set point value contains the value when this stage is turned on.
217 STAGE 12 CUT IN STAGE 12 cut in, set point value contains the value when this stage is turned on.
218 STAGE 13 CUT IN STAGE 13 cut in, set point value contains the value when this stage is turned on.
219 STAGE 14 CUT IN STAGE 14 cut in, set point value contains the value when this stage is turned on.
220 STAGE 15 CUT IN STAGE 15 cut in, set point value contains the value when this stage is turned on.
221 STAGE 16 CUT IN STAGE 16 cut in, set point value contains the value when this stage is turned on.
222 STAGE 17 CUT IN STAGE 17 cut in, set point value contains the value when this stage is turned on.
223 STAGE 18 CUT IN STAGE 18 cut in, set point value contains the value when this stage is turned on.
224 STAGE 19 CUT IN STAGE 19 cut in, set point value contains the value when this stage is turned on.
225 STAGE 20 CUT IN STAGE 20 cut in, set point value contains the value when this stage is turned on.
226 STAGE 21 CUT IN STAGE 21 cut in, set point value contains the value when this stage is turned on.
227 STAGE 22 CUT IN STAGE 22 cut in, set point value contains the value when this stage is turned on.
228 STAGE 23 CUT IN STAGE 23 cut in, set point value contains the value when this stage is turned on.
229 STAGE 24 CUT IN STAGE 24 cut in, set point value contains the value when this stage is turned on.
230 Not Available This set point cannot be used it MUST be INACIVE! This forces all EXV fine tune
type set points to be inactive; therefore, the default settings will be used.
231- not used
235
236 AirDefHiTemp Set points #236, #237 & #238 work as a group. If the entering temperature is
less than set point #236 but greater than set point #239, the values in #236,
#237 & #238 will be used to determine if a defrost cycle is required.
If the evaporator entering temp SI is greater than this value, air defrost will be
disabled.
237 AirDefHiAppr The calculated defrost approach temperature must be greater than the value of
this set point for the system to enter a high defrost cycle.
238 AirDefHiTime This set point contains the time expressed in minutes that a compressor will
remain in a high defrost cycle. Expressed as minutes.
239 AirDefMdTemp Set points #239, #240 & #241 work as a group. If the entering temperature is
less than set point #239 but greater than set point #242, the values in #239,
#240 & #241 will be used to determine if a defrost cycle is required.
240 AirDefMdAppr The calculated defrost approach temperature must be greater than the value of
this set point for the system to enter a high defrost cycle.
241 AirDefMdTime This set point contains the time expressed in minutes that a compressor will
remain in a high defrost cycle. Expressed as minutes.
162
MCS-REFRIG MANUALVERSION 17
242 AirDefLoTemp Set points #236, #237 & #238 work as a group. If the entering temperature is
less than set point #242 but greater than the value of set point #242 – the Low
Zone value, the values in #242, #243 & #244 will be used to determine if a de-
frost cycle is required.
Low Zone: Contains the value to be subtracted to the value of this setpoint, if
the evaporator entering temp SI is below this calculation, air defrost is disabled.
243 AirDefLoAppr The calculated defrost approach temperature must be greater than the value of
this set point for the system to enter a high defrost cycle.
244 AirDefLoTime This set point contains the time expressed in minutes that a compressor will
remain in a high defrost cycle. Expressed as minutes.
245 AirDefCmpDly Contains the amount of time, expressed as minutes, that a compressor calling
for defrost, will be delayed from shutting off so that the logic can bring another
compressor up to capacity to ensure refrigeration is maintained.
This still applies, even if all compressors are on and fully loaded.
246 AirDefTrgrDly This is the time expressed in seconds that the evaporator temperature must
be greater than the defrost trigger temperature before a defrost cycle will be
checked to determine if a defrost cycle is required.
247 Reheat Offset Off Voltage must be greater than this value to allow reheat relays to be turned on.
248 Reheat Stage 1 Voltage above this value will allow 1 stage of reheat to be turned on.
249 Reheat Stage 2 Voltage above this value will allow 2 stage of reheat to be turned on.
250 Reheat Stage 3 Voltage above this value will allow 3 stage of reheat to be turned on.
251 Reheat Stage 4 Voltage above this value will allow 4 stage of reheat to be turned on.
252 Reheat Stage 5 Voltage above this value will allow 5 stage of reheat to be turned on.
253 Reheat Stage 6 Voltage above this value will allow 6 stage of reheat to be turned on.
254 Low Suction Un- If active the number of low suction unloads will be tracked. If the number of
loads unloads is greater than the value with in the time specified in the safety time cell
then the circuit will be locked off.
255 Split Scroll Staging If active and compressor type is a scroll with split staging, PETRA special stag-
ing:
Value contains the number of compressor steps available for staging.
Safety Time is the delay between step adjustments.
163
MCS-REFRIG MANUALVERSION 17
POWER FAILED
POWER RETURNED
COMPUTER RESET
LCD FAILURE
HW DATE INVALID
HW TIME INVALID
SW DATE INVALID
SW TIME INVALID
RAM INTEGRITY
WATCHDOG RESET
ALARMS CLEARED
STPT CHANGED
RO MANUAL
AO MANUAL
SI MANUAL
POINT INFO CLEAR
CLOCK SET
CFG DOWNLOADED
ROTATED LEAD
DAYLIGHT SAVINGS
164
MCS-REFRIG MANUALVERSION 17
The following circuit sensors are tested. If they fail that circuit only is locked out.
■■ Suction pressure and temperature
■■ Discharge pressure and temperature
■■ Oil pressure and temperature
■■ Motor temperature (if it is an analog input device)
The time in the safety state and the time between safeties are specified in the individual set points. This enables the
times to be unique for each lock out set point.
165
MCS-REFRIG MANUALVERSION 17
33.4.2 Sensor Inputs used In Conjunction with Magnum Set Point Safeties:
Suction Pressure
Read the suction pressure. (Optional digital input)
Discharge Pressure
Read the discharge pressure. (Optional digital input)
Oil Pressure
Read the oil pressure (optional digital input)
Oil Differential Pressure
Calculated valve of the oil pressure as follows:
Fixed step compressors, oil psi minus suction psi
Screws with oil pump, Oil psi minus discharge psi
Screws without oil pump, discharge psi minus suction psi
Oil Temperature
Indicates that a high oil temperature condition. This can be either a temperature sensor or a digital input.
Discharge Temperature
Indicates that a high discharge temperature condition. This can be either a temperature sensor or a digital
input.
Motor Temperature
Indicates that a high motor temperature condition. This can be either a temperature sensor or a digital input.
Motor Amps
Sensor input that measures AMP draw of the compressor. (Optional digital input)
Motor Fault
If the high motor temperature input rises above the value of the setpoint or the digital input turns ON for the time
specified in the ‘Time (sec)’ field, the circuit will be Locked Out and a HIGH MOTOR TEMPERATURE or MOTOR
FAULT alarm generated. Refer to setpoint #86.
Liquid Temperature
Temperature sensor that can be used to detect a freeze condition
Compress Proof
A digital input that when on indicates that a compressor is running.
Flow Switch
A digital input that indicates that flow through the chiller barrel exists. There can be one switch per chiller or
one for each circuit.
33.4.3 Set Point Safeties
For a safety to be interrogated, both the associated sensor input and the lockout set point must be active. If a safety
trips, the alarm name will consist of the set point name plus additional identification such as point number or circuit
number if applicable.
The system exercises “smart” safety testing in the following manner:
If a safety applies to a circuit and it is an active lockout type of a set point, the first time this safety trips an alarm will
be generated and the circuit will be shut down and placed in a safety state. The system will attempt to reactivate this
circuit after waiting the length of time specified in this set point, safety down time. If successful the system will continue
to run. If the same safety trips the time specified in the lockout delay time, the circuit will be locked off and a manual
intervention is required. If the lockout delay time is set to zero, the system will generate a lockout condition the first time
that the safety occurs.
The time in the safety state and the time between safeties are specified in the individual set points. This enables the
times to be unique for each lock out set point.
166
MCS-REFRIG MANUALVERSION 17
MOST SAFETIES ARE CHECKED ONLY IF THE COMPRESSOR IS RUNNING, IF THE SAFETY IS ALWAYS
CHECKED IT WILL BE SO NOTED.
The following are a list of safeties that are incorporated in the standard chiller algorithm control. These safeties are
checked every second. Note, for a multiple circuit system, each circuit is tested individually. If a safety condition exists,
action will be taken with that circuit only, other circuits will continue to function.
Emergency Stop
Emergency stop, as indicated by the emergency stop switch, will result in the system and all circuits being locked off
and an emergency stop notification alarm will be generated. No set point is required.
Hi Oil Temp
If the oil temperature rises above the value of the set point or the digital input turns ON and it remains there for the time
specified in the safety time of that set point, the compressor will be locked out and a high oil temperature alarm gener-
ated.
Hi Motor Amp
If the ampere analog input rises above the value of the set point or the digital input turns ON and it remains there for the
time specified in the safety time of that set point, the compressor will be locked out and a high motor amp alarm gener-
ated. This safety is bypassed for the first 3 seconds after a compressor has started.
No Compress Proof
If a compressor is called to be on and the compressor proof input is off (this is a digital input), a NO COMP PROOF
alarm will be generated.
168
MCS-REFRIG MANUALVERSION 17
Revision/Disclaimer Page
169
Providing HVAC/R Control Solutions Worldwide