RXYTQ-UYF - 50Hz_Data Books_EEDEN24_English
RXYTQ-UYF - 50Hz_Data Books_EEDEN24_English
RXYTQ8U7YF
RXYTQ10U7YF
RXYTQ12U7YF
RXYTQ14U7YF
RXYTQ16U7YF
RXYTQ18U7YF
RXYTQ20U7YF
RXYTQ22U7YF
RXYTQ24U7YF
RXYTQ26U7YF
RXYTQ28U7YF
RXYTQ30U7YF
RXYTQ32U7YF
RXYTQ34U7YF
RXYTQ36U7YF
RXYTQ38U7YF
RXYTQ40U7YF
RXYTQ42U7YF
RXYTQ44U7YF
RXYTQ46U7YF
RXYTQ48U7YF
EEDEN24
TABLE OF CONTENTS
RXYTQ-UYF
1 Features 5
RXYTQ-UYF5
2 Specifications 6
4 Options 13
5 Combination table 14
6 Capacity tables 15
Capacity Table Legend 15
Integrated Heating Capacity Correction Factor 16
Capacity Correction Factor 17
7 Dimensional drawings 22
8 Centre of gravity 23
9 Piping diagrams 24
10 Wiring diagrams 26
Wiring Diagrams - Three Phase 26
12 Sound data 31
Sound Power Spectrum 31
Sound Pressure Spectrum 34
Sound Pressure Spectrum Quiet Mode Level 1 37
Sound Pressure Spectrum Quiet Mode Level 2 39
Sound Pressure Spectrum Quiet Mode Level 3 41
13 Installation 43
Installation Method 43
Fixation and Foundation of Units 44
Refrigerant Pipe Selection 45
14 Operation range 47
3
15 Appropriate Indoors 48
4
VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF
1 Features
1-1 RXYTQ-UYF
› Covers all thermal needs of a building via a single point of contact: › Fits any building as also indoor installation is possible as a result
accurate temperature control, ventilation and air handling units of high external static pressure of up to 78.4 Pa. Indoor installation
› Incorporates VRV IV standards & technologies: Variable Refrigerant leads to less piping length, lower installation costs, increased 1
Temperature, VRV configurator, 7 segment display and full inverter efficiency and better visual aesthetics
compressors, 4-side heat exchanger, refrigerant cooled PCB, new › Wide piping flexibility: 30m indoor height difference, maximum
DC fan motor, ... piping length: 190m, total piping length: 1,000m
› Customize your VRV for best seasonal efficiency & comfort with › The ability to control each conditioned zone individually keeps VRV
the weather dependant Variable Refrigerant Temperature function. system running costs to an absolute minimum
Increased seasonal efficiency with up to 28%. No more cold draft › Spread your installation cost by phased installation
by supply of high outblow temperatures › Keep your system in top condition via the Daikin Cloud Service:
› Free combination of outdoor units to meet installation space or 24/7 monitoring for maximum efficiency, extented lifetime and
efficiency requirements immediate service support thanks to failure prediction
RXYTQ-UYF 5
VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF
2 Specifications
2-1 Specifications
Technical Specifications RXYTQ8UYF RXYTQ10UYF RXYTQ12UYF RXYTQ14UYF RXYTQ16UYF
Cooling capacity MEW R6 48°C ISO kW 16.8 (1) 22.4 (1) 24.0 (1) 25.1 (1) 28.3 (1)
48°C ISO Btu/h 57,350 (1) 76,450 (1) 81,900 (1) 85,650 (1) 96,550 (1)
2 UAE. S 46°C ISO - Full load
46°C ISO - Full load
kW
Btu/h
20.2 (2)
68,950 (2)
25.2 (2)
86,000 (2)
28.5 (2)
97,250 (2)
32.0 (2)
109,200 (2)
35.1 (2)
119,800 (2)
35°C ISO - Full load kW 22.4 (3) 28.0 (3) 33.5 (3) 40.0 (3) 45.0 (3)
35°C ISO - Full load Btu/h 76,450 (3) 95,550 (3) 114,350 (3) 136,500 (3) 153,550 (3)
Heating capacity Nom. 6°CWB Btu/h 76,450 (4) 95,550 (4) 114,350 (4) 136,500 (4) 153,550 (4)
6°CWB kW 22.4 (4) 28.0 (4) 33.5 (4) 40.0 (4) 45.0 (4)
Max. 6°CWB Btu/h 85,350 (4) 107,500 (4) 128,000 (4) 153,550 (4) 170,650 (4)
6°CWB kW 25.0 (4) 31.5 (4) 37.5 (4) 45.0 (4) 50.0 (4)
Power input Cooling MEW R6 48°C ISO kW 5.93 (1) 7.95 (1) 8.71 (1) 9.16 (1) 10.40 (1)
UAE. S 46°C ISO - Full load kW 6.56 (2) 7.95 (2) 8.72 (2) 10.00 (2) 12.10 (2)
- Total
35°C ISO - Full load kW 5.37 (3) 6.81 (3) 8.63 (3) 10.23 (3) 12.64 (3)
- Total
Power input indoor units kW 0.20 0.25 0.29 0.34 0.39
Heating Nom. 6°CWB kW 5.62 (4) 7.20 (4) 9.19 (4) 11.01 (4) 12.92 (4)
Max. 6°CWB kW 6.52 (4) 8.66 (4) 11.06 (4) 12.68 (4) 15.36 (4)
EER MEW R6 48°C ISO kW/kW 2.84 (1) 2.82 (1) 2.75 (1) 2.74 (1) 2.72 (1)
48°C ISO Btu/h/W 9.67 (1) 9.62 (1) 9.40 (1) 9.35 (1) 9.28 (1)
UAE. S 46°C ISO - Full load kW/kW 3.08 (2) 3.17 (2) 3.27 (2) 3.20 (2) 2.90 (2)
46°C ISO - Full load Btu/h/W 10.51 (2) 10.82 (2) 11.16 (2) 10.92 (2) 9.90 (2)
35°C ISO - Full load kW/kW 4.17 (3) 4.11 (3) 3.88 (3) 3.91 (3) 3.56 (3)
35°C ISO - Full load Btu/h/W 14.23 (3) 14.02 (3) 13.24 (3) 13.34 (3) 12.15 (3)
COP at nom. capacity 6°CWB Btu/h/W 13.60 (4) 13.26 (4) 12.44 (4) 12.40 (4) 11.89 (4)
6°CWB kW/kW 3.99 (4) 3.89 (4) 3.64 (4) 3.63 (4) 3.48 (4)
COP at max. capacity 6°CWB Btu/h/W 13.09 (4) 12.42 (4) 11.57 (4) 12.11 (4) 11.10 (4)
6°CWB kW/kW 3.84 (4) 3.64 (4) 3.39 (4) 3.55 (4) 3.25 (4)
CSPF UAE. S 5.81 (5) 6.13 (5) 6.12 (5) 5.66 (5) 5.36 (5)
Capacity range HP 8 10 12 14 16
Maximum number of connectable indoor units 64 (6)
Indoor index connection Min. 100 125 150 175 200
Nom. 200 250 300 350 400
Max. 260 325 390 455 520
Dimensions Unit Height mm 1,685
Width mm 930 1,240
Depth mm 765
Packed unit Height mm 1,820
Width mm 995 1,305
Depth mm 860
Weight Unit kg 198 234 283
Packed unit kg 209 251 300
Packing Material Carton
Weight kg 1.8 2.2
Packing 2 Material Wood
Weight kg 8.9 14.0
Packing 3 Material Plastic
Weight kg 0.5 0.6
Casing Colour Daikin White
Material Painted galvanized steel plate
Heat exchanger Type Cross fin coil
Fan Quantity 1 2
Air flow rate Cooling Nom. m³/min 162 223 260
cfm 5,721 7,875 9,182
External Max. Pa 78
static
pressure
Fan motor Quantity 1 2
Type DC motor
Output W 550 750
Compressor Quantity 1 2
Type Hermetically sealed scroll compressor
Operation range Cooling Min. °CDB -5.0
Max. °CDB 52.0
Heating Min. °CWB -20.0
Max. °CWB 15.5
Sound power level Cooling Nom. dBA 78.0 (7) 79.2 (7) 81.0 (7) 81.6 (7) 86.0 (7)
Sound pressure level Cooling Nom. dBA 57.0 (8) 59.0 (8) 61.0 (8) 64.0 (8)
Refrigerant Type R-410A
GWP 2,087.5
Charge kg 6.7 10.3 10.4 11.7 11.8
Charge tCO2Eq 14.0 21.5 21.7 24.4 24.6
Refrigerant oil Type Synthetic (ether) oil FVC68D
2 Specifications
2-1 Specifications
Technical Specifications RXYTQ8UYF RXYTQ10UYF RXYTQ12UYF RXYTQ14UYF RXYTQ16UYF
Piping connections Liquid Type Braze connection
OD mm 9.52 12.7
Gas Type
OD mm 19.1 22.2
Braze connection
28.6
2
Total piping System Actual m 1,000 (9)
length
Defrost method Reversed cycle
Capacity control Method Inverter controlled
Safety devices Item 01 High pressure switch
02 Fan driver overload protector
03 Inverter overload protector
04 PC board fuse
05 Leakage current detector
Standard accessories: Installation manual;Quantity: 1;
Standard accessories: Operation manual;Quantity: 1;
Standard accessories: Connection pipes;Quantity: 1;
2 Specifications
2-1 Specifications
Technical specifications System RXYTQ18UYF RXYTQ20UYF RXYTQ22UYF RXYTQ24UYF RXYTQ26UYF RXYTQ28UYF RXYTQ30UYF RXYTQ32UYF RXYTQ34UYF RXYTQ36UYF
System Outdoor unit module 1 RXYTQ8U RXYTQ10U RXYTQ8U RXYTQ12U RXYTQ14U RXYTQ16U RXYTQ8U
Outdoor unit module 2 RXYTQ10U RXYTQ12U RXYTQ16U RXYTQ14U RXYTQ16U RXYTQ10U RXYTQ12U
2 Cooling capacity
Outdoor unit module 3
MEW R6 48°C ISO kW 39.2 (1) 40.8 (1) 46.4 (1) 45.1 (1)
-
49.1 (1) 52.3 (1) 53.4 (1) 56.6 (1)
RXYTQ16U
67.5 (1) 69.1 (1)
48°C ISO Btu/h 133,750 (1) 139,200 (1) 158,300 (1) 153,900 (1) 167,550 (1) 178,450 (1) 182,200 (1) 193,150 (1) 230,300 (1) 235,800 (1)
UAE. S 46°C ISO - Full load kW 45.4 (2) 48.7 (2) 53.7 (2) 55.3 (2) 60.5 (2) 63.6 (2) 67.1 (2) 70.2 (2) 80.5 (2) 83.8 (2)
46°C ISO - Full load Btu/h 154,900 (2) 166,150 (2) 183,250 (2) 188,700 (2) 206,450 (2) 217,000 (2) 228,950 (2) 239,550 (2) 274,700 (2) 285,950 (2)
35°C ISO - Full load kW 50.4 (3) 55.9 (3) 61.5 (3) 67.4 (3) 73.5 (3) 78.5 (3) 85.0 (3) 90.0 (3) 95.4 (3) 100.9 (3)
35°C ISO - Full load Btu/h 171,950 (3) 190,750 (3) 209,850 (3) 230,000 (3) 250,800 (3) 267,850 (3) 290,050 (3) 307,100 (3) 325,500 (3) 344,300 (3)
Heating capacity Nom. 6°CWB Btu/h 171,950 (4) 190,750 (4) 209,850 (4) 230,000 (4) 250,800 (4) 267,850 (4) 290,050 (4) 307,100 (4) 325,500 (4) 344,300 (4)
6°CWB kW 50.4 (4) 55.9 (4) 61.5 (4) 67.4 (4) 73.5 (4) 78.5 (4) 85.0 (4) 90.0 (4) 95.4 (4) 100.9 (4)
Max. 6°CWB Btu/h 192,800 (4) 213,250 (4) 235,450 (4) 255,900 (4) 281,500 (4) 298,550 (4) 324,150 (4) 341,200 (4) 363,400 (4) 383,850 (4)
6°CWB kW 56.5 (4) 62.5 (4) 69.0 (4) 75.0 (4) 82.5 (4) 87.5 (4) 95.0 (4) 100.0 (4) 106.5 (4) 112.5 (4)
Power input Cooling MEW R6 48°C ISO kW 13.87 (1) 14.64 (1) 16.66 (1) 16.33 (1) 17.88 (1) 19.12 (1) 19.57 (1) 20.81 (1) 24.28 (1) 25.05 (1)
UAE. S 46°C ISO - Full load kW 14.51 (2) 15.27 (2) 16.67 (2) 18.66 (2) 18.72 (2) 20.82 (2) 22.10 (2) 24.21 (2) 26.61 (2) 27.38 (2)
- Total
35°C ISO - Full load kW 12.18 (3) 14.01 (3) 15.45 (3) 18.01 (3) 18.86 (3) 21.27 (3) 22.87 (3) 25.28 (3) 24.82 (3) 26.65 (3)
- Total
Power input indoor units kW 0.44 0.49 0.54 0.59 0.64 0.68 0.73 0.78 0.83 0.88
Heating Nom. 6°CWB kW 12.82 (4) 14.81 (4) 16.40 (4) 18.54 (4) 20.20 (4) 22.11 (4) 23.92 (4) 25.84 (4) 25.74 (4) 27.73 (4)
Max. 6°CWB kW 15.17 (4) 17.57 (4) 19.71 (4) 21.88 (4) 23.74 (4) 26.42 (4) 28.05 (4) 30.73 (4) 30.54 (4) 32.94 (4)
EER MEW R6 48°C ISO kW/kW 2.83 (1) 2.79 (1) 2.78 (1) 2.76 (1) 2.75 (1) 2.74 (1) 2.73 (1) 2.72 (1) 2.78 (1) 2.76 (1)
48°C ISO Btu/h/W 9.64 (1) 9.51 (1) 9.50 (1) 9.42 (1) 9.37 (1) 9.33 (1) 9.31 (1) 9.28 (1) 9.49 (1) 9.41 (1)
UAE. S 46°C ISO - Full load kW/kW 3.13 (2) 3.19 (2) 3.22 (2) 2.96 (2) 3.23 (2) 3.05 (2) 3.04 (2) 2.90 (2) 3.03 (2) 3.06 (2)
46°C ISO - Full load Btu/h/W 10.68 (2) 10.88 (2) 10.99 (2) 10.11 (2) 11.03 (2) 10.42 (2) 10.36 (2) 9.90 (2) 10.32 (2) 10.44 (2)
35°C ISO - Full load kW/kW 4.14 (3) 3.99 (3) 3.98 (3) 3.74 (3) 3.90 (3) 3.69 (3) 3.72 (3) 3.56 (3) 3.84 (3) 3.79 (3)
35°C ISO - Full load Btu/h/W 14.11 (3) 13.62 (3) 13.59 (3) 12.77 (3) 13.29 (3) 12.59 (3) 12.68 (3) 12.15 (3) 13.11 (3) 12.92 (3)
COP at nom. capacity 6°CWB Btu/h/W 13.41 (4) 12.88 (4) 12.80 (4) 12.41 (4) 12.42 (4) 12.11 (4) 12.12 (4) 11.89 (4) 12.65 (4) 12.42 (4)
6°CWB kW/kW 3.93 (4) 3.77 (4) 3.75 (4) 3.64 (4) 3.55 (4) 3.48 (4) 3.71 (4) 3.64 (4)
COP at max. capacity 6°CWB Btu/h/W 12.71 (4) 12.14 (4) 11.94 (4) 11.70 (4) 11.86 (4) 11.30 (4) 11.56 (4) 11.10 (4) 11.90 (4) 11.65 (4)
6°CWB kW/kW 3.72 (4) 3.56 (4) 3.50 (4) 3.43 (4) 3.48 (4) 3.31 (4) 3.39 (4) 3.25 (4) 3.49 (4) 3.42 (4)
CSPF UAE. S 5.98 (5) 5.97 (5) 6.11 (5) 5.60 (5) 5.92 (5) 5.76 (5) 5.51 (5) 5.36 (5) 5.76 (5) 5.78 (5)
Capacity range HP 18 20 22 24 26 28 30 32 34 36
Maximum number of connectable indoor units 64 (6)
Indoor index connection Min. 225 250 275 300 325 350 375 400 425 450
Nom. 450 500 550 600 650 700 750 800 850 900
Max. 585 650 715 780 845 910 975 1,040 1,105 1,170
Sound power level Cooling Nom. dBA 81.7 (7) 82.8 (7) 83.2 (7) 86.6 (7) 84.3 (7) 87.2 (7) 87.3 (7) 89.0 (7) 87.4 (7) 87.7 (7)
Sound pressure level Cooling Nom. dBA 61.1 (8) 62.5 (8) 63.1 (8) 64.8 (8) 64.0 (8) 65.8 (8) 67.0 (8) 65.8 (8) 66.3 (8)
2 Specifications
2-1 Specifications
Technical specifications System RXYTQ38UYF RXYTQ40UYF RXYTQ42UYF RXYTQ44UYF RXYTQ46UYF RXYTQ48UYF
COP at max. capacity 6°CWB Btu/h/W 11.85 (4) 11.76 (4) 11.39 (4) 11.23 (4) 11.40 (4) 11.10 (4)
6°CWB kW/kW 3.47 (4) 3.45 (4) 3.34 (4) 3.29 (4) 3.34 (4) 3.25 (4)
CSPF
Capacity range
UAE.S
HP
5.63 (5)
38
5.72 (5)
40
5.62 (5)
42
5.64 (5)
44
5.46 (5)
46
5.36 (5)
48
2
Maximum number of connectable indoor units 64 (6)
Indoor index connection Min. 475 500 525 550 575 600
Nom. 950 1,000 1,050 1,100 1,150 1,200
Max. 1,235 1,300 1,365 1,430 1,495 1,560
Sound power level Cooling Nom. dBA 87.8 (7) 88.0 (7) 89.4 (7) 89.6 (7) 89.7 (7) 90.8 (7)
Sound pressure level Cooling Nom. dBA 66.3 (8) 66.6 (8) 67.6 (8) 68.0 (8) 68.8 (8)
Electrical specifications System RXYTQ18UYF RXYTQ20UYF RXYTQ22UYF RXYTQ24UYF RXYTQ26UYF RXYTQ28UYF RXYTQ30UYF RXYTQ32UYF RXYTQ34UYF RXYTQ36UYF
Power supply Name YF
Phase 3N~
Frequency Hz 50/60
Voltage V 380-415/400
Power supply intake Both indoor and outdoor unit
Voltage range Min. % -10
Max. % 10
Power Performance Power factor UAE. S 46°C ISO - Full load 0.94 1 0.94 0.93 0.94
Current - 50Hz Nominal MEW R6 Cooling A 18.3 (10) 21.5 (10) 23.9 (10) 27.3 (10) 30.3 (10) 32.9 (10) 36.1 (10) 38.7 (10) 37.6 (10) 40.8 (10)
running UAE. S Cooling A 20.9 (11) 21.9 (11) 23.6 (11) 26.8 (11) 29.5 (11) 31.7 (11) 34.4 (11) 38.1 (11) 39.1 (11)
current
(RLA)
Starting current (MSC) - remark See note 15
Minimum circuit amps (MCA) A 38.1 (12) 40.1 (12) 46.0 (12) 47.1 (12) 51.0 (12) 55.0 (12) 58.0 (12) 62.0 (12) 69.1 (12) 71.1 (12)
Maximum fuse amps (MFA) A 40 (13) 50 (13) 63 (13) 80 (13)
Wiring connections For power Quantity 5G
- 50Hz supply
For connec- Quantity 2
tion with Remark F1,F2
indoor
Cooling Seasonal
Performance Factor
What is CSPFT3?
(Cooling Seasonal Performance Factor for Hot Climate CSPF T3 ) is the testing and rating of air
conditioners as per the ISO 16358 -1 Amendment 1 issued in 2019 for T3 hot climate zones and takes into
consideration the bin hours reflecting high ambient conditions.
Benefits of CSPFT3
The implementation of seasonal efficiency will provide end users with a fair comparison of different equipment
based on realistic year-round efficiency which will lead to:
3
Pioneering in innovation and
environmental responsibility
For Daikin, seasonal efficiency brings together two core ambitions: pushing for innovation and reducing the
environmental footprint of our products. Being the first in the industry to design equipment based on optimal seasonal
efficiency values, Daikin is once again pioneering high-performance cooling products that lower the impact on the
environment and on your wallet.
400 400
350
Weather bin
350
for T3
300 T1 300 Climates as
250 250 per ISO
16358-1
200 200
AMD 1
150 150
100 100
50 50
T3
0 0
20 25 30 35 40 45 50 20 25 30 35 40 45 50
Temperature ° C Temperature ° C
Energy Efficiency Ratio rating is based on one outdoor Cooling Seasonal Performance Factor is based on the Hot Climate
Ambient Temperature condition (T1 or T3) Weather bin as per ISO 16358-1 AMD1
Nominal efficiency gives an indication on how efficient CSPFT3 gives an indication on how efficient an air
an air conditioner operates at nominal conditions. conditioner operates over an entire cooling season.
100% capacity performance is used to measure EER Variable or seasonal performance close to real life is
used and not 100% capacity performance.
For example, 10 HP Daikin VRV IV+Unit (RXYTQ10U7YF) can be evaluated using below mentioned efficiencies:
When the new ISO standard for hot climate was published, Daikin has resolutely chosen for early
implementation of this new legislation and started testing all products for seasonal efficiency. This commitment
to pioneering the implementation of seasonal efficiency is a practice we observe every day.
Today, Daikin leads the way towards more efficient and cost-effective comfort solutions. All Daikin products -
residential, commercial, as well as industrial - are seasonal-efficient, reducing energy and costs the smart way.
4 Options
4-1 Options
RXYTQ-UYF
VRV4
Middle East 4
Option list
Notes
1. All options are kits
2. Only for multi units
3. To operate the cool/heat selector function, options 1a and 1b are both required.
4. To mount option 1a, option 1c is required.
5. To install the demand PCB on the large casing type, the demand PCB mounting plate is required.
Medium casing type VRV4 Middle East heat pump: modules 8HP
Large casing type VRV4 Middle East heat pump: modules 10~16HP
3D119361
5 Combination table
5-1 Combination Table
RXYTQ-UYF
Unit combination restrictions: ·VRV4· outdoor units (all models) + ·15·-class indoor units
Units in scope: ·FXZQ15A· and ·FXAQ15A·.
1. In case the system contains these indoor units and the total connection ratio (·CR·) ≤ ·100·%: no special restrictions.
Follow the restrictions that apply to regular ·VRV DX· indoor units.
2. In case the system contains these indoor units and the total connection ratio (·CR·) > ·100·%: special restrictions apply.
A. When the connection ratio (·CR1·) of the sum of all ·FXZQ15A· and/or ·FXAQ15A· units in the system ≤ ·70·%, and ALL other ·VRV DX· indoor units have an
individual capacity class > ·50·: no special restrictions.
B. When the connection ratio (·CR1·) of the sum of all ·FXZQ15A· and/or ·FXAQ15A· units in the system ≤ ·70·%, and NOT ALL other ·VRV DX· indoor units have
an individual capacity class > ·50·: the restrictions below apply.
° 100% < CR ≤ 105% -> ·CR1· of the sum of all ·FXZQ15A· and/or ·FXAQ15A· indoor units in the system must be ≤ ·70·%.
° 105% < CR ≤ 110% -> ·CR1· of the sum of all ·FXZQ15A· and/or ·FXAQ15A· indoor units in the system must be ≤ ·60·%.
° 110% < CR ≤ 115% -> ·CR1· of the sum of all ·FXZQ15A· and/or ·FXAQ15A· indoor units in the system must be ≤ ·40·%.
° 115% < CR ≤ 120% -> ·CR1· of the sum of all ·FXZQ15A· and/or ·FXAQ15A· indoor units in the system must be ≤ ·25·%.
° 120% < CR ≤ 125% -> ·CR1· of the sum of all ·FXZQ15A· and/or ·FXAQ15A· indoor units in the system must be ≤ ·10·%.
° 125% < CR ≤ 130% -> ·FXZQ15A· and ·FXAQ15A· cannot be used.
Remark
Only the ·15·-class indoor units explicitly mentioned on this page are in scope. Other indoor units follow the rules that apply to regular
·VRV DX· indoor units.
3D104665A
RXYTQ-UYF
VRV4
Middle East
Indoor unit combination restrictions
Indoor unit combination pattern ·VRV* DX· indoor unit Air handling unit (AHU) (3)
·VRV* DX· indoor unit O O2
Air handling unit (AHU) (3) O O1
O: Allowed
X: Not allowed
Notes
1. O1
- Combination of ·AHU· only + control box ·EKEQFA· (the combination with ·VRV DX· indoor units is not allowed; maximum ·48·HP for ·3x400· class ·EKEXV· kit)
→ ·X·-control is possible (up to ·3x· [·EKEXV+EKEQFA*· boxes] can be connected to one outdoor unit (system)). No Variable Refrigerant Temperature control possible.
→ ·Y·-control is possible (up to ·3x· [·EKEXV+EKEQFA*· boxes] can be connected to one outdoor unit (system)). No Variable Refrigerant Temperature control possible.
→ ·W·-control is possible (up to ·3x· [·EKEXV+EKEQFA*· boxes] can be connected to one outdoor unit (system)). No Variable Refrigerant Temperature control possible.
- Combination of ·AHU· only + control box ·EKEQMA· (not combined with ·VRV DX· indoor units)
→ Z-control is possible (the allowed number of [·EKEXV + EKEQMA· boxes] is determined by the connection ratio (·90-110%·) and the capacity of the outdoor unit.
2. O2
- Combination of ·AHU· and ·VRV DX· indoor units
→ Z-control is possible (·EKEQMA*· boxes are allowed, but with a limited connection ratio).
3D096860A
6 Capacity tables
6-1 Capacity Table Legend
,QRUGHUWRIXO¿OOPRUH\RXUUHTXLUHPHQWVRQTXLFNDFFHVVRIGDWDLQWKHIRUPDW\RXUHTXLUHZHKDYHGHYHORSHGDWRROWR
FRQVXOWFDSDFLW\WDEOHV
%HORZ\RXFDQ¿QGWKHOLQNWRWKHFDSDFLW\WDEOHGDWDEDVHDQGDQRYHUYLHZRIDOOWKHWRROVZHKDYHWRKHOS\RXVHOHFWWKH 6
FRUUHFWSURGXFW
6 Capacity tables
6-2 Integrated Heating Capacity Correction Factor
RXYTQ‐UYF
The heating capacity tables do not take into account the capacity reduction in case of frost accumulation or defrost operation.
The capacity values that take these factors into account, or in other words, the integrated heating capacity values, can be calculated as follows:
Heating capacity
Inlet air temperature of heat exchanger
[°CDB/°CWB] ‐7/‐7,6 ‐5/‐5,6 ‐3/‐3,7 0/‐0,7 3/2,2 5/4,1 7/6
Integrated correction factor for frost accumulation ∙(C)∙
Time
8HP 0,95 0,93 0,88 0,84 0,85 0,90 1,00
10HP 0,95 0,93 0,87 0,79 0,80 0,88 1,00
12HP 0,95 0,92 0,87 0,75 0,76 0,85 1,00
14HP 0,95 0,92 0,86 0,72 0,73 0,84 1,00
16HP 0,95 0,92 0,86 0,72 0,72 0,83 1,00
∙1∙ cycle
Only free multi‐outdoor‐unit combinations are possible. Respect the following calculation rules:
The total integrated heating capacity of a multi‐outdoor‐unit system = the sum of the integrated heating capacity of each module separately.
Notes
1. The figure shows the integrated heating capacity for a single cycle (from one defrost operation to the next).
2. When there is an accumulation of snow against the outdoor unit heat exchanger, there will always be a temporary reduction in capacity depending on the outdoor temperature (°C DB), relative humidity (RH)
and the amount of frosting which occurs.
3D097510
6 Capacity tables
6-3 Capacity Correction Factor
RXYTQ8UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend
Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit
3D119351
RXYTQ10UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend
Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit
3D119351
6 Capacity tables
6-3 Capacity Correction Factor
RXYTQ12UYF
RXYTQ14UYF Correction ratio for cooling capacity Correction ratio for heating capacity Legend
L
Hm: Maximum level difference (m) between outdoor
L
and indoor units when the outdoor unit is
positioned lower than the indoor units.
Hm Hm
Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit
3D119351
RXYTQ16UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend
Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit
3D119351
6 Capacity tables
6-3 Capacity Correction Factor
RXYTQ18UYF
RXYTQ26-30UYF
RXYTQ38UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend
Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit
For the allowed system setups and the rules for when to increase the main liquid and gas piping diameter, refer to the installation manual.
4. Overall equivalent length
Overall equivalent length = Equivalent length of the main pipe X Correction factor + Equivalent length of the branch pipes
5. Example RXYTQ38-44T
Main gas pipe Equivalent length of the branch pipe of the furthest
Main liquid pipe indoor unit
Overall equivalent length
80 m 40 m
▪ Cooling mode = 80 m x 1,0 + 40 m = 120 m
▪ Heating mode = 80 m x 0,5 + 40 m = 80 m
3D119351
RXYTQ20UYF
RXYTQ32UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend
RXYTQ34UYF
Hp: Maximum level difference (m) between outdoor
and indoor units when the outdoor unit is
Hp Hp positioned higher than the indoor units.
L
Hm: Maximum level difference (m) between outdoor
L
and indoor units when the outdoor unit is
positioned lower than the indoor units.
Hm Hm
Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit
5. Example RXYTQ38-44T
Main gas pipe Equivalent length of the branch pipe of the furthest
Main liquid pipe indoor unit
Overall equivalent length
80 m 40 m
▪ Cooling mode = 80 m x 0,5 + 40 m = 80 m
▪ Heating mode = 80 m x 0,5 + 40 m = 80 m
3D119351
6 Capacity tables
6-3 Capacity Correction Factor
RXYTQ22UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend
Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit
3D119351
RXYTQ46UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend
Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit
3D119351
6 Capacity tables
6-3 Capacity Correction Factor
RXYTQ48UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend
Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit
3D119351
7 Dimensional drawings
7-1 Dimensional Drawings
RXYTQ8UYF Pitch of foundation bolt holes
766
1 2 3
100 07
66
160
106
AB 10
View ·C·
4-15x22.5mm Oblong hole
Detail ·A· Detail ·B· Foundation bolt hole
Notes
1. Detail ·A· and detail ·B· indicate the dimensions after fixing the attached piping.
2D119001B
RXYTQ10-16UYF 1 2 3
Pitch of foundation bolt holes
107㻢
Pitch of foundation bolt holes
393
134
12㻡 8
0 297 7
121 01
1
3 0
1 B
2 A 70
100 71 10
1㻢0 10㻢
AA Oblong hole
4-15x22.5mm - View ·C·
Detail ·A· Detail ·B· Foundation bolt hole
Notes
1.Detail ·A· and detail ·B· indicate the dimensions after fixing the attached piping.
No. Part name Remark 2.Items ·4 - 10:· Knockout hole.
1 Liquid pipe connection port See note ·3·. 3.Gas pipe
2 Gas pipe connection port See note ·3·. RXYTQ10U : Ø ·22.2· brazing connection
Equalising pipe connection port RXYA14-20A REYQ14-20U, REYA14-20A : Ø ·25.4· brazing connection
3 RYYQ14-20U, RYMQ14-20U RXYQ14-20U, RXYQQ14-20U, RXYTQ12-16U : Ø ·28.6· brazing connection
Equalising pipe connection port See note ·3·. RXYA14-20A : Ø ·19.1· brazing connection
High pressure/low pressure gas pipe
Gas pipe connection port RXYA14-20A Liquid pipe
RXYTQ10U : Ø ·9.5· brazing connection
4 Power cord routing hole (side) O65 RYYQ14-16U, RYMQ14-16U, RXYQ14-16U, RXYQQ14-16U, REYQ14-20U, : Ø ·12.7· brazing connection
5 Power cord routing hole (front) O80 REYA14-20A, RXYTQ12-16U, RXYA14-20A
6 Power cord routing hole (front) O65 RYYQ18-20U, RYMQ18-20U, RXYQ18-20U, RXYQQ18-20U : Ø ·15.9· brazing connection
7 Power cord routing hole (front) O27 Equalising pipe
8 O65 RYMQ14-16U : Ø ·22.2· brazing connection
Power cord routing hole (bottom) RYMQ18-20U : Ø ·28.6· brazing connection
9 Pipe routing hole (front) RXYA14-20A : Ø ·25.4· brazing connection
10 Pipe routing hole (bottom) High pressure/low pressure gas pipe
11 Grounding terminal Inside of the switch box (·M8·) REYQ14-20U, REYA14-20A : Ø ·19.1· brazing connection
Model AA AB
RXYQ14-20U, RYYQ14-20U, RXYQQ14-20U, RXY7Q10-16U - -
RYMQ14-16U, REYQ14-20U, REYA14-20A, RXYA14-20A 240 240
RYMQ1-20U 240 12
11
856
1
4
7
221
155
762 95 9
2 7 1
1 13
137 7㻢 7㻢
Detail ·B· Detail ·A· 97 107 5 6 7㻢㻡
272
328
373 C
1240 2D119091B
8 Centre of gravity
8-1 Centre of Gravity
RXYTQ8UYF
Unit AA AB AC
RYYQ8-12U
328 366 565
REMQ5U / REYQ8-12U
RYMQ8-12U 354 443 565
RXYQ8-12U
RXYQQ8-12U 339 448 565
RXYTQ8U
REMA5A / REYA8-12A 353 426 690
RYMA5A / RXYA8-12A 353 426 690
AC
View ·A·
View ·A·
AA AB Foundation bolt hole (slot)
729 766
RXYTQ10-16UYF
Unit AA AB AC
RYYQ14-20U 334 470 610
REYQ14-20U 334 470 610
RYMQ14-20U 360 569 610
RXYQ(Q)14-20U 345 575 610
RXYTQ10-12U 350 610 810
RXYTQ14-16U 351 565 610
REYA14-16A 339 596 758
REYA18-20A 350 587 752
RXYA14-16A 339 596 758
RXYA18-20A 350 587 752
AC
View ·A·
View ·A·
Foundation bolt hole
AA AB (slot)
729 1076
3D119704B
9 Piping diagrams
9-1 Piping Diagrams
RXYQ8-12U
RXYTQ8UYF R1T
9 Y3E
R4T
M
M1F
Thermistor
Heat sink
(PCB)
Y1S
Capillary tube
Expansion valve
S1NPL S1NPH
4-way valve
Propeller fan
R3T
M
R21T Accumulator
Y3S
sv
R8T
M1C
Heat exchanger
sv
Compressor
Y2S
Gas pipe
Double tube heat exchanger
Charge port
Distributor
Solenoid valve
sv
3D118179
RXYQ14-20U
RXYQ14-16UYF
R1T
Y2E
Pressure relief valve
Thermistor
Heat sink
(PCB)
Capillary tube
Expansion valve
Y1S
4-way valve
S1NPL S1NPH
Propeller fan
M
HPS HPS
Accumulator
S1PH S2PH
R21T R22T
Heat exchanger
sv
sv
Y3S Y4S
R8T R9T
M1C M2C Compressor
sv
Oil separator
Y2S
3D118180
9 Piping diagrams
9-1 Piping Diagrams
RXYTQ10-12UYF
R1T
Y3E M M
9
R4T M1F M2F
Charge port / Service port
R5T R6T
Y1E
Stop valve
R7T
Filter
Y2E
Check valve
Propeller fan
M
R3T
Accumulator
R21T
Y3S
sv
M1C
R8T Heat exchanger
sv
Compressor
Y2S
Oil separator
Liquid pipe
Gas pipe Double tube heat exchanger
Charge port Distributor
Solenoid valve
sv
Cooling
Heating
3D119341
10 Wiring diagrams
10 - 1 Wiring Diagrams - Three Phase
RXYQ8-12U
RXYTQ8UYF
10 RYYQ8-12U
RYMQ8-12U
X23A
BLK
BLU
F403U
X37A
X3A HAP (Note 7)
GRN E1 (Note 3) X25A Y4E
Z1F 5 M
S1PH P>
X2A (Note 6)
L1B L2B L3B Z4C N=1 PS
X18A t ゜ R1T
BLK
RED
X28A
WHT
S1NPL
K7R
A3P
K11R
Z7C N=1
K6R
K4R
K5R
K9R
Z5C N=2 X31A
L1B L2B L3B X6A X20A X10A X8A X9A X13A X15A X11A
X40A S1NPH
X4A X32A
HAP
+
V1R
-
P2 Z6C t゜ t゜ t゜ t゜ t゜ t゜ t゜
N=3
V1D +C506 +C503 N32 BLK X3A X50A X19A X30A
GRN
V1R
A5P
U V W X41A (Note 4) (Note 4) (Note 4)
X1A
Z7C N=1 X1M
A4P C/H selector
Z2C N=4 A B C
P1 N1 X5A indoor outdoor outdoor
WHT
WHT
R24
L1R X3A + HAP X4A
-
A1P L1R
A5P
A2P
X3A
X1A X1M A4P
A3P
2D117534
10 Wiring diagrams
10 - 1 Wiring Diagrams - Three Phase
RXYTQ10-12UYF A1P Printed circuit board (main)
A2P Printed circuit board (noise filter)
A3P Printed circuit board (inv)
A4P,A5P Printed circuit board (fan)
10
Y1E
Y2E
Y3E
5 M
5 M
5 M
S1NPH
S1NPL
t ゜ R1T
BS1~3 (A1P) Push button switch (mode,set,return)
C503,C506,C507 (A3P) Capacitor
X21A
X22A
X23A
(note 3) X18A
X32A
DS1,DS2 (A1P) Dip switch
(note 4)
E1HC Crankcase heater
(Q1)(Q2)
outdoor
Q2
1234
SEG3
DS2
BS3
X37A
Q1
(note 4)
F3U Field fuse
SEG2
BS2
(F1)(F2)
F2
outdoor
1234
L1R
DS1
BS1
ON
OFF
F1
(F1)(F2)
F2
indoor
X1M
PS
X6A
A2P
A3P
el.compo.box
K5R (A1P) Magnetic relay (Y2S)
t゜
R7T
A4P
A5P
t゜
S2S heat
cool
fan
X1A
X2A
・
L1R Reactor
t゜
K7R
E1HC
X30A
X11A
R5T
A1P
M1C Motor (compressor)
heat
X1M
cool
A8P
PS (A1P,A3P) Switching power supply
t゜
R3T
cool
terminal of M1C
Y3S
M1C
K5R
X9A
Y2S
U
R8T
A
X19A
K4R
R3T Thermistor (accumulator)
X8A
Y1S
A8P
X1A
el.compo.box
M1C
GRN
(NOTE3)
3)
X20A (note
F1U
(note 6)
M2F
X28A
X2A
X1A
X101A
A1P
RED
BLU
BLK
BLK
P11 RED
BLK
N31 BLK
N32
X6A
X4A
HAP
PS
BLU F601U
Connector for optional accessories
K3R
Z1C
N=5
R300
V1R
X3A
N
U MS W
V1D +C506 +C503
W
L1B L2B L3B
M1C 3~
WHT WHT
V1R
WHT
V
+
NOTES
A2P
E1
X601A
P1
P2
N=2
Z4C
2.
WHT
: Field wiring, : terminal block, : connector,
L1R
WHT
:terminal,
: protective earth (screw), : functional earth, : earth wiring,
N=1
T1A
P11 RED
P12 RED
N11 BLK
N11 BLK
N12 BLK
WHT
RED
BLU
BLK
3. When using the optional adapter, refer to the installation manual of the
X1M
L1
L2
L3
N
X5A
X5A
X3A
optional adapter.
F101U
F101U
R24
R24
HAP
X3A
X4A
X4A
+ +
-
V1R
A5P
A4P
Z2C X1A
X1A
(NOTE7)7)
(note 7)
Power supply
X2A
X1A
M1F
MS
MS
L1
L2
L3
3~
3~
N
2D120654A
10 Wiring diagrams
10 - 1 Wiring Diagrams - Three Phase
RXYTQ14-16UYF A1P Printed circuit board (main)
A2P, A5P Printed circuit board (noise filter)
A3P, A6P Printed circuit board (inv)
A4P, A7P Printed circuit board (fan)
10 A8P Printed circuit board (ABC I/P)
BS1~3 (A1P) Push button switch (mode, set, return)
C503, C506, C507 (A3P, A6P) Capacitor
(NOTE 7)7)
Y2E
Y3E
Y4E
(note
5 M
5 M
5 M
5 M
S1NPH
S1NPL
t ゜ R1T
X22A
X23A
X25A
X18A
X32A
(note 4)
F3U Field fuse
(Q1)(Q2)
F101U (A4P, A7P) Fuse
outdoor
(NOTE3)3)
Q2
1234
SEG3
DS2
BS3
X37A
(note
Q1
(note 4)
BS2
X5A R L2
R L1
HAP
BS1
ON
OFF
F1
(note 4)
A2P
A3P
(F1)(F2)
indoor
X1M
PS
Z8C
N=1
el.compo.box
X6A
A5P
A6P
K6R (A1P) Magnetic relay (E3H)
(note 8)
K11R
X15A
Y5S
t゜
R6T
fan
X1A
X2A
・
K7R
E1HC
X11A
X30A
R5T
A1P
X1M
cool
t゜
K3R
Y4S
X7A
A8P
M1F, M2F Motor (fan)
t゜
R3T
Y3S
V
C
t゜
K5R
X9A
Y2S
U
R8T
A
X19A
K4R
X8A
Y1S
A8P
X1A
el.compo.box
outer shell
K6R
R21T
X10A
E3H
GRN
X4A X5A X50A
X66A
Q1LD
(note 6)
(note 6)
M2F
X40A
X28A
X2A
X3A
X1A
X101A
A1P
RED
WHT
BLU
BLK
BLK
BLK
S2PH P>
P11 RED
BLK
N31 BLK
N32
X6A
X4A
HAP
BLU F601U
K3R
Z6C
N=1
Z1C
N=5
V1R
R300
X3A
U MS W
W
V1D +C506 +C503
L1B L2B L3B
C507
WHT WHT
M1C 3~
X*A Connector
WHT
V1R
V
+
X601A
X61A
X41A
P1
P2
WHT
L1R
P11 RED
BLK
N31 BLK
N32
X6A
X4A
PS
Z7C N=1
F601U
(note
BLU
Y5S Solenoid valve (sub) (note 8)
K3R
Z2C
N=5
V1R
R300
X4A
N
-
Z*C Noise filter (ferrite core)
BLK F403U BLK - BLK
L1A L2A L3A
U MS W
W
V1D +C506 +C503
L1B L2B L3B
WHT WHT
M2C 3~
WHT
V1R
V
+
E1
X601A
P1
P2
Z9C
N=2
WHT
X37A Connector (power adapter)
L2R
WHT
X66A Connector (remote switching
Cool/heat selector)
N=1
T1A
NOTES
P11 RED
RED
N11 BLK
BLK
WHT
RED
BLU
BLK
N11
X1M
L1
L2
L3
N
X5A
X5A
2.
X3A
F101U
R24
R24
HAP
X3A
+ +
X4A
X4A
-
V1R
3. When using the optional adapter, refer to the installation manual of the optional adapter.
A7P
A4P
X1A
X1A
50Hz
60Hz
5. How to use BS1~3 switch. Refer to “service precaution” label on el. Compo. Box cover.
(note 9)
(note 9)
Power supply
X2A
X1A
M1F
MS
MS
L1
L2
L3
3~
3~
N
2D117536C
RYYQ8-20U 3. For details, refer to the wiring diagram attached to the outdoor unit.
11
RYMQ8-20U
4. Install a circuit breaker for safety.
5. All field wiring and components must be provided by an authorised electrician.
6. Unit has to be grounded in compliance with the applicable legislation.
7. The wiring shown is a general points-of-connection guide and is not intended to include all details for a specific installation.
8. Make sure to install the switch and the fuse to the power line of each equipement.
9. Install a main switch to control the multiple power sources that the various components of the system make use of.
10. The capacity of UNIT1 must be larger than that of UNIT2 when the power source is connected in series between the units.
The capacity of UNIT 2 must be larger than that of UNIT3 when the power source is connected in series between the units.
11. If there exists the possibility of reversed phase, loose phase or momentary blackout, or if the power goes on and off while the product is operating, attach a reversed
phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
12. Install an earth leakage circuit breaker.
Power supply
L1 L2 L3 N
< Power source is supplied to each outdoor unit
individually. > Power supply
L1 L2 L3 N
< Power source is connected in series between
the units. >
Main switch Outdoor units Main switch Outdoor units
2-wire cable
Transmission line
2-wire cable 2-wire cable 2-wire cable 2-wire cable 2-wire cable
2-wire cable 2-wire cable
2- wire cable Transmission line Transmission line
Transmission line Transmission line Transmission line Transmission line
Transmission line
Power line
2-wire cable L N L N L N L N L N L N L N L N
Power line Switch Switch Switch Switch Switch Switch Switch Switch
Fuse Fuse Fuse Fuse Fuse Fuse Fuse Fuse
2-wire cable
Power line
2-wire cable 2-wire cable
2-wire cable 2-wire cable 2-wire cable 2-wire cable 2-wire cable
Power line Power line
Power line Power line Power line Power line Power line
3D 119 200
RXYQQ8-20U Notes
RXYQ8-20U 1. All wiring, components and materials to be procured on-site must comply with the applicable legislation.
2.Use copper conductors only
RXYTQ8-16U 3. For details, refer to the wiring diagram attached to the outdoor unit.
Power supply
< Power source is supplied to each outdoor unit individually.
> Power supply
< Power source is connected in series between the units.
>
L1 L2 L3 N L1 L2 L3 N
·2·-wire cable
·2·-wire cable Transmission line
Transmission line ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable
·2·-wire cable Transmission lin Transmission lin Transmission line Transmission line Transmission line
Power line Transmission line
Power line
e e
L N L N L N L N L N L N L N L N
Switch Switch Switch Switch Switch Switch Switch Switch
Fuse Fuse Fuse Fuse Fuse Fuse Fuse Fuse
·2·-wire cable
Power line
·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable
Power line Power line Power line Power line Power line Power line Power line
3D119316
11 RYMQ8-20U 1. All wiring, components and materials to be procured on-site must comply with the applicable le
gislation.
RXYTQ8-16UYF
L1 L2 L3 N Power supply
2. Use copper conductors only
3. For details, refer to the wiring diagram attached to the outdoor unit.
Main switch
4. Install a circuit breaker for safety.
5. All field wiring and components must be provided by an authorised electrician.
6. Unit has to be grounded in compliance with the applicable legislation.
Outdoor unit
Switch 7. The wiring shown is a general points-of-connection guide and is not intended to include all details
for a specific installation.
L1 L2 L3 N
Fuse 8. Make sure to install the switch and the fuse to the power line of each equipement.
9. Install a main switch to control the multiple power sources that the various components of t
he system make use of.
Power supply 10. If there exists the possibility of reversed phase, loose phase or momentary blackout, or if the power g
oes on and off while the product is operating, attach a reversed phase protection circuit locally.
L N
Main switch Running the product in reversed phase may break the compressor and other parts.
11. Install an earth leakage circuit breaker.
2-wire cable
Transmission line
L N L N L N L N
Switch Switch Switch Switch
Indoor unit
3D119317
12 Sound data
12 - 1 Sound Power Spectrum
REMQ5U
REYQ8U
RXYQQ8U
RXYQ8U
12
90 90
RXYTQ8UYF 85 NR90
RYYQ8U 80 NR85 80
RYMQ8U 75 NR80
70 NR75 70
65 NR70
Sound power level [dB]
60 60
NR65
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR10 NR15
NR5
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119528
RXYTQ10UYF
90 90
85 NR90
80 NR85 80
75 NR80
70 NR75 70
65 NR70
Sound power level [dB]
60 60
NR65
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR10 NR15
NR5
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = ·10E-6µW/m²·
Measured according to ISO 3744
3D119342
12 Sound data
12 - 1 Sound Power Spectrum
RXYTQ12UYF
90 90
12 85 NR90
80 NR85 80
75 NR80
70 NR75 70
65 NR70
Sound power level [dB]
60 NR65 60
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR10 NR15
NR5
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = ·10E-6µW/m²·
Measured according to ISO 3744
3D119343
RXYTQ14YUF
90 90
85 NR90
80 NR85 80
75 NR80
70 NR75 70
65 NR70
Sound power level [dB]
60 60
NR65
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR10 NR15
NR5
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119366
12 Sound data
12 - 1 Sound Power Spectrum
RXYTQ16UYF
95
12
90 90
85 NR90
80 NR85 80
75 NR80
70 NR75 70
65
Sound power level [dB]
NR70
60 NR65 60
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0
NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = ·10E-6µW/m²·
Measured according to ISO 3744
3D119368
12 Sound data
12 - 2 Sound Pressure Spectrum
REMQ5U
REYQ8U
RXYQQ8U
12 RXYQ8U 70 70
NR75
RXYTQ8UYF 65
NR70
RYYQ8U
60 60
RYMQ8U NR65
55
NR60
50 50
NR55
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119521
RXYTQ10UYF
70 70
NR75
65
NR70
60 60
NR65
55
NR60
50 50
NR55
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119344
12 Sound data
12 - 2 Sound Pressure Spectrum
RXYTQ12UYF
70 70
12
NR75
65
NR70
60 60
NR65
55
NR60
50 50
NR55
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119345
RXYTQ14UYF
70 NR75 70
65
NR70
60 60
NR65
55
NR60
50 50
NR55
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119365
12 Sound data
12 - 2 Sound Pressure Spectrum
RXYTQ16UYF
70 NR75 70
12 65
NR70
60 60
NR65
55
NR60
50 50
NR55
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119367
12 Sound data
12 - 3 Sound Pressure Spectrum Quiet Mode Level 1
REMQ5U
REYQ8-12U 65
NR70
RXYQQ8-12U
60 60 12
RXYQ8-12U NR65
RXYTQ8UYF 55
NR60
RYY8-12U 50 50
NR55
RYMQ8-12U
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119535
RXYTQ10-12UYF
70 NR75 70
65
NR70
60 60
NR65
55
NR60
50 50
NR55
Sound pressure level [dB]
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: ·35·°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119346
12 Sound data
12 - 3 Sound Pressure Spectrum Quiet Mode Level 1
REYQ14-16U
RXYQQ14-16U 60
NR65
60
RXYQ14-16U
12 55 55
RXYTQ14-16UYF NR60
RYYQ14-16U 50
NR55
50
RYMQ14-16U 45 45
NR50
Sound pressure level [dB]
40 40
NR45
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119538
12 Sound data
12 - 4 Sound Pressure Spectrum Quiet Mode Level 2
REMQ5U
REYQ8-12U 60
NR65
60
RXYQQ8-12U
RXYQ8-12U
55
NR60
55 12
RXYTQ8UYF 50
NR55
50
RYYQ8-12U 45 45
RYMQ8-12U NR50
Sound pressure level [dB]
40 40
NR45
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119536
RXYTQ10-12UYF
60 60
NR65
55 55
NR60
50 50
NR55
45 45
NR50
Sound pressure level [dB]
40 40
NR45
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: ·35·°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119347
12 Sound data
12 - 4 Sound Pressure Spectrum Quiet Mode Level 2
REYQ14-16U
RXYQQ14-16U 55 55
RXYQ14-16U NR60
12 RXYTQ14-16UYF 50 50
NR55
RYYQ14-16U
45 45
RYMQ14-16U NR50
40 40
Sound pressure level [dB]
NR45
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR5 NR10 NR15
NR0
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119539
12 Sound data
12 - 5 Sound Pressure Spectrum Quiet Mode Level 3
REMQ5U
REYQ8-12U 55 55
NR60
RXYQQ8-12U
RXYQ8-12U 50 50
12
NR55
RXYTQ8UYF
45 45
RYYQ8-12U NR50
RYMQ8-12U 40 40
Sound pressure level [dB]
NR45
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR5 NR10 NR15
NR0
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119537
RXYTQ10-12UYF
60 60
NR65
55 55
NR60
50 50
NR55
45 45
NR50
Sound pressure level [dB]
40 40
NR45
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: ·35·°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119348
12 Sound data
12 - 5 Sound Pressure Spectrum Quiet Mode Level 3
REYQ14-16U
RXYQQ14-16U 55 55
NR60
RXYQ14U-16U
12
RXYTQ14-16UYF 50
NR55
50
RYYQ14-16U 45 45
RYMQ14-16U NR50
40 40
Sound pressure level [dB]
NR45
35 35
NR40
30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR5 NR10 NR15
NR0
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119540
13 Installation
13 - 1 Installation Method
RXYTQ-UYF
10 or more Front 10 or more 10 or more 20 or more Front 20 or more 10 or more 10 or more Front 20 or more 10 or more 10 or more Front 20 or more 10 or more 10 or more 20 or more 10 or more
500 or more 500 or more 500 or more Front
600 or more
900 or more
Pattern 2 100 or more Pattern 2 100 or more 10 or more Front 20 or more 10 or more 300 or more
10 or more 20 or more 10 or more
500 or more 10 or more 20 or more 10 or more Front 500 or more
100 or more
50 or more Front 100 or more 50 or more
Front 400 or more Front __________ or more 500 or more 50 or more 100 or more 50 or more 50 or more Front 50 or more
200 or more 200 or more 100 or more 500 or more
Notes Unit mm
2.If the design outdoor air temperature exceeds 46°C, provide a broader suction space than shown on the drawing.
3.When installing the units, select the pattern that best fits the available space.
Always keep in mind to leave sufficient space for a person to pass between unit and wall and for the air to circulate freely.
If more units are to be installed than are foreseen in the above patterns, your layout should take into account the possibility of air short circuits.
Suction side
Front
h1
1500
Unit mm 500
3D096862A
13 Installation
13 - 2 Fixation and Foundation of Units
RXYTQ-UYF
Foundation bolt fixing method
13
Drain ditch
°
80
Smooth downgrade of about 1/50
60
AD AA AD AA
929
729
00 8
O1 0 80
X X When building a foundation on the ground When building a foundation on a concrete floor
Y ditch
100
Y ditch
10050 Drain ditch
Drain ditch
50
Smooth downgrade
of about 1/50
50
Y ditch AC AA Floor
AB
Cross section · X - X·
RYMA5A/RXYA8-12A
RYYQ14-20U
RYMQ14-20U
RXYQ14-20U 1076 1076
RXYQQ14-20U
REYQ14-20U
RXYTQ10-16U
Notes REYA14-20A
RXYA14-20A
1. Provide a drain ditch around the foundation to drain water from the installation area.
2.The surface has to be finished with mortar. The corner edges have to be chamfered.
3. Build the foundation on a concrete floor or, if not possible, make sure the foundation surface has a rough finish.
4. Use a cement/sand/gravel ratio of 1/2/4 for the concrete, and a diameter of 10 mm for the reinforcement bars (approximately, 300mm intervals).
5.When installing the equipment on a roof, make sure to check the strength of the floor and take adequate water proofing
measures.
3D118459B
13 Installation
13 - 3 Refrigerant Pipe Selection
RXYTQ-UYF
VRV4
Middle East
Piping restrictions ·3/3·
13
System pattern Total Connection ratio
Allowed connection ratio (CR) Maximum allowed amount of connectable indoor
VRV DX Air handling unit
Other combinations are not allowed. Connection ratio units (·VRV,AHU·)
indoor unit (AHU)
Excluding ·EXV· kits
·VRV DX· indoor units only 50~130% Maximum ·64· 50~130% -
·VRV DX· indoor unit + ·AHU· (2) (1)
50~110% Maximum ·64· 50~110% 0~110%
Mix
·AHU· only (3) (2) (1) (4)
90~110% Maximum ·64· - 90~110%
Pair + multi
Notes
1. ·EKEXV· kits are also considered indoor units.
2. Restrictions regarding the air handling unit capacity
3. Pair AHU = system with 1 air handling unit connected to one outdoor unit
Multi AHU = system with multiple air handling units connected to one outdoor unit
4. In case of cooling-only use in the ·DAME· region, the allowed connection ratio is ·75~110·%.
3D096859B
RXYTQ-UYF
VRV4
Middle East
Piping restrictions ·1/3·
Notes
1. An extension to up to ·90· m is possible if all of the following conditions are met:
a. The piping length between all indoor units and the nearest branch kit is ≤ 40m.
b. It is necessary to increase the size of the gas and liquid piping.
If the increased pipe size is larger than the pipe size of the main pipe, also increase the size of the main pipe.
c. When the piping size is increased, the piping length has to be counted as double.
The total piping length has to be within limitations.
d. The piping length difference between the nearest indoor unit to the outdoor unit and the farthest indoor unit to the outdoor unit is ≤ ·40·m.
2. An extension to up to ·90· m is possible without an additional option kit. Respect the following conditions:
-> If the outdoor units are positioned higher than the indoor units:
- Size up the liquid piping
For more information, refer to the installation manual.
- A dedicated setting on the outdoor unit is required.
For more information, refer to the installation manual.
-> If the outdoor units are positioned lower than the indoor units:
- 40~60m: Minimum connection ratio: ·80%·
- 60~65m: Minimum connection ratio: ·90%·
- 65~80m: Minimum connection ratio: ·100%·
- 80~90m: Minimum connection ratio: ·110%·
+
- Size up the liquid piping
For more information, refer to the installation manual.
- A dedicated setting on the outdoor unit is required.
For more information, refer to the installation manual.
3. The allowable minimum length is ·5· m.
4. Multiple air handling units (·AHU·)(·EKEXV· + ·EKEQ· kits).
5. Mix of air handling units (·AHU·) and ·VRV DX· indoor units.
6. If the equivalent piping length between is > ·90·m, size up the main liquid and gas piping.
3D096859B
13 Installation
13 - 3 Refrigerant Pipe Selection
RXYTQ-UYF
VRV4
Middle East
13 Piping restrictions ·2/3·
H3
B
A J
D
C
H1
EXV
H4
EXV K
H2
Notes
1. Multiple air handling units (·AHU·)(·EKEXV· + ·EKEQ· kits).
2. Mix of air handling units (·AHU·) and ·VRV DX· indoor units. 3D096859B
14 Operation range
14 - 1 Operation Range
RXYTQ-U
UYF
Cooling
55
14
52
50
48
Heating
45
20
40
15 15.5
35
10
Pull-down operation range
25 5
Operation range
20
Operation range
Pull-down operation range
0
15
-5
10
-10
5
-15
0
-5 -20
14 28 27
10 15 20 25 30 10 15 20 25 30
2. Depending on operation and installation conditions, the indoor unit can change over to freeze-up operation (indoor de-icing).
3. To reduce the freeze-up operation (indoor de-icing) frequency, it is recommended to install the outdoor unit in a location not exposed to wind.
4. Operation range is valid in case direct expansion indoor units are used.
If other indoor units are used, refer to the documentation of the respective indoor units.
5. : Unit operation is possible, but no guaranteed capacity
3D096861
15 Appropriate Indoors
15 - 1 Appropriate Indoors
RXYTQ-UYF
For multi outdoor units ·>16HP·, the recommended amount of indoor units is the sum of the indoor units defined for a single
outdoor unit.
The present leaflet is drawn up by way of information only and does not constitute an
offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of
this leaflet to the best of its knowledge. No express or implied warranty is given for the
completeness, accuracy, reliability or fitness for particular purpose of its content and the
products and services presented therein. Specifications are subject to change without prior
notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in
EEDEN24 01/2024
the broadest sense, arising from or related to the use and/or interpretation of this leaflet.
All content is copyrighted by Daikin Europe N.V.