VRV IV heat pump,

for high ambient


temperature regions
Air Conditioning
Technical Data
RXYTQ-UYF
50 Hz

RXYTQ8U7YF
RXYTQ10U7YF
RXYTQ12U7YF
RXYTQ14U7YF
RXYTQ16U7YF
RXYTQ18U7YF
RXYTQ20U7YF
RXYTQ22U7YF
RXYTQ24U7YF
RXYTQ26U7YF
RXYTQ28U7YF
RXYTQ30U7YF
RXYTQ32U7YF
RXYTQ34U7YF
RXYTQ36U7YF
RXYTQ38U7YF
RXYTQ40U7YF
RXYTQ42U7YF
RXYTQ44U7YF
RXYTQ46U7YF
RXYTQ48U7YF

EEDEN24
TABLE OF CONTENTS

RXYTQ-UYF
1 Features 5
RXYTQ-UYF5

2 Specifications 6

3 Features and advantages 10

4 Options 13

5 Combination table 14

6 Capacity tables 15
Capacity Table Legend 15
Integrated Heating Capacity Correction Factor 16
Capacity Correction Factor 17

7 Dimensional drawings 22

8 Centre of gravity 23

9 Piping diagrams 24

10 Wiring diagrams 26
Wiring Diagrams - Three Phase 26

11 External connection diagrams 29

12 Sound data 31
Sound Power Spectrum 31
Sound Pressure Spectrum 34
Sound Pressure Spectrum Quiet Mode Level 1 37
Sound Pressure Spectrum Quiet Mode Level 2 39
Sound Pressure Spectrum Quiet Mode Level 3 41

13 Installation 43
Installation Method 43
Fixation and Foundation of Units 44
Refrigerant Pipe Selection 45

14 Operation range 47

3
15 Appropriate Indoors 48

4
VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

1 Features
1-1 RXYTQ-UYF
› Covers all thermal needs of a building via a single point of contact: › Fits any building as also indoor installation is possible as a result
accurate temperature control, ventilation and air handling units of high external static pressure of up to 78.4 Pa. Indoor installation
› Incorporates VRV IV standards & technologies: Variable Refrigerant leads to less piping length, lower installation costs, increased 1
Temperature, VRV configurator, 7 segment display and full inverter efficiency and better visual aesthetics
compressors, 4-side heat exchanger, refrigerant cooled PCB, new › Wide piping flexibility: 30m indoor height difference, maximum
DC fan motor, ... piping length: 190m, total piping length: 1,000m
› Customize your VRV for best seasonal efficiency & comfort with › The ability to control each conditioned zone individually keeps VRV
the weather dependant Variable Refrigerant Temperature function. system running costs to an absolute minimum
Increased seasonal efficiency with up to 28%. No more cold draft › Spread your installation cost by phased installation
by supply of high outblow temperatures › Keep your system in top condition via the Daikin Cloud Service:
› Free combination of outdoor units to meet installation space or 24/7 monitoring for maximum efficiency, extented lifetime and
efficiency requirements immediate service support thanks to failure prediction

Inverter Variable refrig-


erant temper-
ature

RXYTQ-UYF 5
VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

2 Specifications
2-1 Specifications
Technical Specifications RXYTQ8UYF RXYTQ10UYF RXYTQ12UYF RXYTQ14UYF RXYTQ16UYF
Cooling capacity MEW R6 48°C ISO kW 16.8 (1) 22.4 (1) 24.0 (1) 25.1 (1) 28.3 (1)
48°C ISO Btu/h 57,350 (1) 76,450 (1) 81,900 (1) 85,650 (1) 96,550 (1)
2 UAE. S 46°C ISO - Full load
46°C ISO - Full load
kW
Btu/h
20.2 (2)
68,950 (2)
25.2 (2)
86,000 (2)
28.5 (2)
97,250 (2)
32.0 (2)
109,200 (2)
35.1 (2)
119,800 (2)
35°C ISO - Full load kW 22.4 (3) 28.0 (3) 33.5 (3) 40.0 (3) 45.0 (3)
35°C ISO - Full load Btu/h 76,450 (3) 95,550 (3) 114,350 (3) 136,500 (3) 153,550 (3)
Heating capacity Nom. 6°CWB Btu/h 76,450 (4) 95,550 (4) 114,350 (4) 136,500 (4) 153,550 (4)
6°CWB kW 22.4 (4) 28.0 (4) 33.5 (4) 40.0 (4) 45.0 (4)
Max. 6°CWB Btu/h 85,350 (4) 107,500 (4) 128,000 (4) 153,550 (4) 170,650 (4)
6°CWB kW 25.0 (4) 31.5 (4) 37.5 (4) 45.0 (4) 50.0 (4)
Power input Cooling MEW R6 48°C ISO kW 5.93 (1) 7.95 (1) 8.71 (1) 9.16 (1) 10.40 (1)
UAE. S 46°C ISO - Full load kW 6.56 (2) 7.95 (2) 8.72 (2) 10.00 (2) 12.10 (2)
- Total
35°C ISO - Full load kW 5.37 (3) 6.81 (3) 8.63 (3) 10.23 (3) 12.64 (3)
- Total
Power input indoor units kW 0.20 0.25 0.29 0.34 0.39
Heating Nom. 6°CWB kW 5.62 (4) 7.20 (4) 9.19 (4) 11.01 (4) 12.92 (4)
Max. 6°CWB kW 6.52 (4) 8.66 (4) 11.06 (4) 12.68 (4) 15.36 (4)
EER MEW R6 48°C ISO kW/kW 2.84 (1) 2.82 (1) 2.75 (1) 2.74 (1) 2.72 (1)
48°C ISO Btu/h/W 9.67 (1) 9.62 (1) 9.40 (1) 9.35 (1) 9.28 (1)
UAE. S 46°C ISO - Full load kW/kW 3.08 (2) 3.17 (2) 3.27 (2) 3.20 (2) 2.90 (2)
46°C ISO - Full load Btu/h/W 10.51 (2) 10.82 (2) 11.16 (2) 10.92 (2) 9.90 (2)
35°C ISO - Full load kW/kW 4.17 (3) 4.11 (3) 3.88 (3) 3.91 (3) 3.56 (3)
35°C ISO - Full load Btu/h/W 14.23 (3) 14.02 (3) 13.24 (3) 13.34 (3) 12.15 (3)
COP at nom. capacity 6°CWB Btu/h/W 13.60 (4) 13.26 (4) 12.44 (4) 12.40 (4) 11.89 (4)
6°CWB kW/kW 3.99 (4) 3.89 (4) 3.64 (4) 3.63 (4) 3.48 (4)
COP at max. capacity 6°CWB Btu/h/W 13.09 (4) 12.42 (4) 11.57 (4) 12.11 (4) 11.10 (4)
6°CWB kW/kW 3.84 (4) 3.64 (4) 3.39 (4) 3.55 (4) 3.25 (4)
CSPF UAE. S 5.81 (5) 6.13 (5) 6.12 (5) 5.66 (5) 5.36 (5)
Capacity range HP 8 10 12 14 16
Maximum number of connectable indoor units 64 (6)
Indoor index connection Min. 100 125 150 175 200
Nom. 200 250 300 350 400
Max. 260 325 390 455 520
Dimensions Unit Height mm 1,685
Width mm 930 1,240
Depth mm 765
Packed unit Height mm 1,820
Width mm 995 1,305
Depth mm 860
Weight Unit kg 198 234 283
Packed unit kg 209 251 300
Packing Material Carton
Weight kg 1.8 2.2
Packing 2 Material Wood
Weight kg 8.9 14.0
Packing 3 Material Plastic
Weight kg 0.5 0.6
Casing Colour Daikin White
Material Painted galvanized steel plate
Heat exchanger Type Cross fin coil
Fan Quantity 1 2
Air flow rate Cooling Nom. m³/min 162 223 260
cfm 5,721 7,875 9,182
External Max. Pa 78
static
pressure
Fan motor Quantity 1 2
Type DC motor
Output W 550 750
Compressor Quantity 1 2
Type Hermetically sealed scroll compressor
Operation range Cooling Min. °CDB -5.0
Max. °CDB 52.0
Heating Min. °CWB -20.0
Max. °CWB 15.5
Sound power level Cooling Nom. dBA 78.0 (7) 79.2 (7) 81.0 (7) 81.6 (7) 86.0 (7)
Sound pressure level Cooling Nom. dBA 57.0 (8) 59.0 (8) 61.0 (8) 64.0 (8)
Refrigerant Type R-410A
GWP 2,087.5
Charge kg 6.7 10.3 10.4 11.7 11.8
Charge tCO2Eq 14.0 21.5 21.7 24.4 24.6
Refrigerant oil Type Synthetic (ether) oil FVC68D

6 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

2 Specifications
2-1 Specifications
Technical Specifications RXYTQ8UYF RXYTQ10UYF RXYTQ12UYF RXYTQ14UYF RXYTQ16UYF
Piping connections Liquid Type Braze connection
OD mm 9.52 12.7
Gas Type
OD mm 19.1 22.2
Braze connection
28.6
2
Total piping System Actual m 1,000 (9)
length
Defrost method Reversed cycle
Capacity control Method Inverter controlled
Safety devices Item 01 High pressure switch
02 Fan driver overload protector
03 Inverter overload protector
04 PC board fuse
05 Leakage current detector
Standard accessories: Installation manual;Quantity: 1;
Standard accessories: Operation manual;Quantity: 1;
Standard accessories: Connection pipes;Quantity: 1;

Electrical Specifications RXYTQ8UYF RXYTQ10UYF RXYTQ12UYF RXYTQ14UYF RXYTQ16UYF


Power supply Name YF
Phase 3N~
Frequency Hz 50/60
Voltage V 380-415/400
Power supply intake Both indoor and outdoor unit
Voltage range Min. % -10
Max. % 10
Power Performance Power factor UAE. S 46°C ISO - Full load 0.94 0.95 0.93 0.94
Current - 50Hz Nominal MEW R6 Cooling A 7.9 (10) 10.4 (10) 13.6 (10) 16.8 (10) 19.3 (10)
running UAE. S Cooling A 9.6 (11) 11.3 (11) 12.3 (11) 14.5 (11) 17.2 (11)
current
(RLA)
Starting current (MSC) - remark See note 15
Minimum circuit amps (MCA) A 16.1 (12) 22.0 (12) 24.0 (12) 27.0 (12) 31.0 (12)
Maximum fuse amps (MFA) A 20 (13) 25 (13) 32 (13) 40 (13)
Full load Total A 1.2 (14) 1.8 (14) 2.6 (14)
amps (FLA)
Wiring connections For power Quantity 5G
- 50Hz supply
For connec- Quantity 2
tion with Remark F1,F2
indoor
(1) Cooling: T2: indoor temp. 26,6°CDB, 19,4°CWB, outdoor temp. 48°CDB, AHRI 1230:2010, power input indoor units (duct type) included |
(2) Cooling: T3: indoor temp. 29.0°CDB, 19.0°CWB, outdoor temp. 46°CDB, ISO15042:2011 |
(3) Cooling: T1: indoor temp. 27.0°CDB, 19.0°CWB, outdoor temp. 35°CDB, ISO15042:2011 |
(4) Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level differrence: 0m. Power input of indoor units (duct type) included |
(5) Cooling seasonal performance factor for hot climates at T3 condition per ISO 16358-1:2013/AMD 1:2019 |
(6) Actual number of units depends on the indoor unit type (VRV DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤ 130%). |
(7) Sound power level is an absolute value that a sound source generates. |
(8) Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. |
(9) Refer to refrigerant pipe selection or installation manual |
(10) RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB |
(11) RLA is based on following conditions: indoor temp. 29°CDB, 19°CWB; outdoor temp. 46°C |
(12) MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current. |
(13) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). |
(14) FLA means the nominal running current of the fan |
(15) MSC means the maximum current during start up of the compressor. This unit uses only inverter compressors. Starting current is always ≤ max. running current. |
Maximum allowable voltage range variation between phases is 2%. |
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
Sound values are measured in a semi-anechoic room. |
Soundpressure system [dBA] = 10*log[10^(A/10)+10^(B/10)+10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA |
For detailed contents of standard accessories, see installation/operation manual |
Multi combination (18~48HP) data is corresponding with the standard multi combination |

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 7


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

2 Specifications
2-1 Specifications
Technical specifications System RXYTQ18UYF RXYTQ20UYF RXYTQ22UYF RXYTQ24UYF RXYTQ26UYF RXYTQ28UYF RXYTQ30UYF RXYTQ32UYF RXYTQ34UYF RXYTQ36UYF
System Outdoor unit module 1 RXYTQ8U RXYTQ10U RXYTQ8U RXYTQ12U RXYTQ14U RXYTQ16U RXYTQ8U
Outdoor unit module 2 RXYTQ10U RXYTQ12U RXYTQ16U RXYTQ14U RXYTQ16U RXYTQ10U RXYTQ12U
2 Cooling capacity
Outdoor unit module 3
MEW R6 48°C ISO kW 39.2 (1) 40.8 (1) 46.4 (1) 45.1 (1)
-
49.1 (1) 52.3 (1) 53.4 (1) 56.6 (1)
RXYTQ16U
67.5 (1) 69.1 (1)
48°C ISO Btu/h 133,750 (1) 139,200 (1) 158,300 (1) 153,900 (1) 167,550 (1) 178,450 (1) 182,200 (1) 193,150 (1) 230,300 (1) 235,800 (1)
UAE. S 46°C ISO - Full load kW 45.4 (2) 48.7 (2) 53.7 (2) 55.3 (2) 60.5 (2) 63.6 (2) 67.1 (2) 70.2 (2) 80.5 (2) 83.8 (2)
46°C ISO - Full load Btu/h 154,900 (2) 166,150 (2) 183,250 (2) 188,700 (2) 206,450 (2) 217,000 (2) 228,950 (2) 239,550 (2) 274,700 (2) 285,950 (2)
35°C ISO - Full load kW 50.4 (3) 55.9 (3) 61.5 (3) 67.4 (3) 73.5 (3) 78.5 (3) 85.0 (3) 90.0 (3) 95.4 (3) 100.9 (3)
35°C ISO - Full load Btu/h 171,950 (3) 190,750 (3) 209,850 (3) 230,000 (3) 250,800 (3) 267,850 (3) 290,050 (3) 307,100 (3) 325,500 (3) 344,300 (3)
Heating capacity Nom. 6°CWB Btu/h 171,950 (4) 190,750 (4) 209,850 (4) 230,000 (4) 250,800 (4) 267,850 (4) 290,050 (4) 307,100 (4) 325,500 (4) 344,300 (4)
6°CWB kW 50.4 (4) 55.9 (4) 61.5 (4) 67.4 (4) 73.5 (4) 78.5 (4) 85.0 (4) 90.0 (4) 95.4 (4) 100.9 (4)
Max. 6°CWB Btu/h 192,800 (4) 213,250 (4) 235,450 (4) 255,900 (4) 281,500 (4) 298,550 (4) 324,150 (4) 341,200 (4) 363,400 (4) 383,850 (4)
6°CWB kW 56.5 (4) 62.5 (4) 69.0 (4) 75.0 (4) 82.5 (4) 87.5 (4) 95.0 (4) 100.0 (4) 106.5 (4) 112.5 (4)
Power input Cooling MEW R6 48°C ISO kW 13.87 (1) 14.64 (1) 16.66 (1) 16.33 (1) 17.88 (1) 19.12 (1) 19.57 (1) 20.81 (1) 24.28 (1) 25.05 (1)
UAE. S 46°C ISO - Full load kW 14.51 (2) 15.27 (2) 16.67 (2) 18.66 (2) 18.72 (2) 20.82 (2) 22.10 (2) 24.21 (2) 26.61 (2) 27.38 (2)
- Total
35°C ISO - Full load kW 12.18 (3) 14.01 (3) 15.45 (3) 18.01 (3) 18.86 (3) 21.27 (3) 22.87 (3) 25.28 (3) 24.82 (3) 26.65 (3)
- Total
Power input indoor units kW 0.44 0.49 0.54 0.59 0.64 0.68 0.73 0.78 0.83 0.88
Heating Nom. 6°CWB kW 12.82 (4) 14.81 (4) 16.40 (4) 18.54 (4) 20.20 (4) 22.11 (4) 23.92 (4) 25.84 (4) 25.74 (4) 27.73 (4)
Max. 6°CWB kW 15.17 (4) 17.57 (4) 19.71 (4) 21.88 (4) 23.74 (4) 26.42 (4) 28.05 (4) 30.73 (4) 30.54 (4) 32.94 (4)
EER MEW R6 48°C ISO kW/kW 2.83 (1) 2.79 (1) 2.78 (1) 2.76 (1) 2.75 (1) 2.74 (1) 2.73 (1) 2.72 (1) 2.78 (1) 2.76 (1)
48°C ISO Btu/h/W 9.64 (1) 9.51 (1) 9.50 (1) 9.42 (1) 9.37 (1) 9.33 (1) 9.31 (1) 9.28 (1) 9.49 (1) 9.41 (1)
UAE. S 46°C ISO - Full load kW/kW 3.13 (2) 3.19 (2) 3.22 (2) 2.96 (2) 3.23 (2) 3.05 (2) 3.04 (2) 2.90 (2) 3.03 (2) 3.06 (2)
46°C ISO - Full load Btu/h/W 10.68 (2) 10.88 (2) 10.99 (2) 10.11 (2) 11.03 (2) 10.42 (2) 10.36 (2) 9.90 (2) 10.32 (2) 10.44 (2)
35°C ISO - Full load kW/kW 4.14 (3) 3.99 (3) 3.98 (3) 3.74 (3) 3.90 (3) 3.69 (3) 3.72 (3) 3.56 (3) 3.84 (3) 3.79 (3)
35°C ISO - Full load Btu/h/W 14.11 (3) 13.62 (3) 13.59 (3) 12.77 (3) 13.29 (3) 12.59 (3) 12.68 (3) 12.15 (3) 13.11 (3) 12.92 (3)
COP at nom. capacity 6°CWB Btu/h/W 13.41 (4) 12.88 (4) 12.80 (4) 12.41 (4) 12.42 (4) 12.11 (4) 12.12 (4) 11.89 (4) 12.65 (4) 12.42 (4)
6°CWB kW/kW 3.93 (4) 3.77 (4) 3.75 (4) 3.64 (4) 3.55 (4) 3.48 (4) 3.71 (4) 3.64 (4)
COP at max. capacity 6°CWB Btu/h/W 12.71 (4) 12.14 (4) 11.94 (4) 11.70 (4) 11.86 (4) 11.30 (4) 11.56 (4) 11.10 (4) 11.90 (4) 11.65 (4)
6°CWB kW/kW 3.72 (4) 3.56 (4) 3.50 (4) 3.43 (4) 3.48 (4) 3.31 (4) 3.39 (4) 3.25 (4) 3.49 (4) 3.42 (4)
CSPF UAE. S 5.98 (5) 5.97 (5) 6.11 (5) 5.60 (5) 5.92 (5) 5.76 (5) 5.51 (5) 5.36 (5) 5.76 (5) 5.78 (5)
Capacity range HP 18 20 22 24 26 28 30 32 34 36
Maximum number of connectable indoor units 64 (6)
Indoor index connection Min. 225 250 275 300 325 350 375 400 425 450
Nom. 450 500 550 600 650 700 750 800 850 900
Max. 585 650 715 780 845 910 975 1,040 1,105 1,170
Sound power level Cooling Nom. dBA 81.7 (7) 82.8 (7) 83.2 (7) 86.6 (7) 84.3 (7) 87.2 (7) 87.3 (7) 89.0 (7) 87.4 (7) 87.7 (7)
Sound pressure level Cooling Nom. dBA 61.1 (8) 62.5 (8) 63.1 (8) 64.8 (8) 64.0 (8) 65.8 (8) 67.0 (8) 65.8 (8) 66.3 (8)

Technical specifications System RXYTQ38UYF RXYTQ40UYF RXYTQ42UYF RXYTQ44UYF RXYTQ46UYF RXYTQ48UYF


System Outdoor unit module 1 RXYTQ8U RXYTQ10U RXYTQ12U RXYTQ14U RXYTQ16U
Outdoor unit module 2 RXYTQ14U RXYTQ16U
Outdoor unit module 3 RXYTQ16U
Cooling capacity MEW R6 48°C ISO kW 70.2 (1) 75.8 (1) 79.0 (1) 80.6 (1) 81.7 (1) 84.9 (1)
48°C ISO Btu/h 239,550 (1) 258,650 (1) 269,550 (1) 275,000 (1) 278,750 (1) 289,700 (1)
UAE. S 46°C ISO - Full load kW 87.3 (2) 92.3 (2) 95.4 (2) 98.7 (2) 102.2 (2) 105.3 (2)
46°C ISO - Full load Btu/h 297,900 (2) 314,950 (2) 325,500 (2) 336,800 (2) 348,700 (2) 359,300 (2)
35°C ISO - Full load kW 107.4 (3) 113.0 (3) 118.0 (3) 123.5 (3) 130.0 (3) 135.0 (3)
35°C ISO - Full load Btu/h 366,450 (3) 385,550 (3) 402,650 (3) 421,400 (3) 443,600 (3) 460,650 (3)
Heating capacity Nom. 6°CWB Btu/h 366,450 (4) 385,550 (4) 402,650 (4) 421,400 (4) 443,600 (4) 460,650 (4)
6°CWB kW 107.4 (4) 113.0 (4) 118.0 (4) 123.5 (4) 130.0 (4) 135.0 (4)
Max. 6°CWB Btu/h 409,450 (4) 431,600 (4) 448,700 (4) 469,200 (4) 494,750 (4) 511,850 (4)
6°CWB kW 120.0 (4) 126.5 (4) 131.5 (4) 137.5 (4) 145.0 (4) 150.0 (4)
Power input Cooling MEW R6 48°C ISO kW 25.49 (1) 27.51 (1) 28.76 (1) 29.52 (1) 29.97 (1) 31.21 (1)
UAE. S 46°C ISO - Full load kW 28.66 (2) 30.05 (2) 32.16 (2) 32.92 (2) 34.21 (2) 36.31 (2)
- Total
35°C ISO - Full load kW 28.24 (3) 29.68 (3) 32.09 (3) 33.91 (3) 35.51 (3) 37.92 (3)
- Total
Power input indoor kW 0.93 0.98 1.03 1.08 1.13 1.17
units
Heating Nom. 6°CWB kW 29.54 (4) 31.13 (4) 33.04 (4) 35.03 (4) 36.84 (4) 38.75 (4)
Max. 6°CWB kW 34.56 (4) 36.70 (4) 39.38 (4) 41.79 (4) 43.41 (4) 46.09 (4)
EER MEW R6 48°C ISO kW/kW 2.75 (1) 2.76 (1) 2.75 (1) 2.73 (1) 2.72 (1)
48°C ISO Btu/h/W 9.40 (1) 9.37 (1) 9.32 (1) 9.30 (1) 9.28 (1)
UAE. S 46°C ISO - Full load kW/kW 3.05 (2) 3.07 (2) 2.97 (2) 3.00 (2) 2.99 (2) 2.90 (2)
46°C ISO - Full load Btu/h/W 10.39 (2) 10.48 (2) 10.12 (2) 10.23 (2) 10.19 (2) 9.90 (2)
35°C ISO - Full load kW/kW 3.80 (3) 3.81 (3) 3.68 (3) 3.64 (3) 3.66 (3) 3.56 (3)
35°C ISO - Full load Btu/h/W 12.98 (3) 12.99 (3) 12.55 (3) 12.43 (3) 12.49 (3) 12.15 (3)
COP at nom. capacity 6°CWB Btu/h/W 12.40 (4) 12.39 (4) 12.19 (4) 12.03 (4) 12.04 (4) 11.89 (4)
6°CWB kW/kW 3.64 (4) 3.63 (4) 3.57 (4) 3.53 (4) 3.48 (4)

8 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

2 Specifications
2-1 Specifications
Technical specifications System RXYTQ38UYF RXYTQ40UYF RXYTQ42UYF RXYTQ44UYF RXYTQ46UYF RXYTQ48UYF
COP at max. capacity 6°CWB Btu/h/W 11.85 (4) 11.76 (4) 11.39 (4) 11.23 (4) 11.40 (4) 11.10 (4)
6°CWB kW/kW 3.47 (4) 3.45 (4) 3.34 (4) 3.29 (4) 3.34 (4) 3.25 (4)
CSPF
Capacity range
UAE.S
HP
5.63 (5)
38
5.72 (5)
40
5.62 (5)
42
5.64 (5)
44
5.46 (5)
46
5.36 (5)
48
2
Maximum number of connectable indoor units 64 (6)
Indoor index connection Min. 475 500 525 550 575 600
Nom. 950 1,000 1,050 1,100 1,150 1,200
Max. 1,235 1,300 1,365 1,430 1,495 1,560
Sound power level Cooling Nom. dBA 87.8 (7) 88.0 (7) 89.4 (7) 89.6 (7) 89.7 (7) 90.8 (7)
Sound pressure level Cooling Nom. dBA 66.3 (8) 66.6 (8) 67.6 (8) 68.0 (8) 68.8 (8)

Electrical specifications System RXYTQ18UYF RXYTQ20UYF RXYTQ22UYF RXYTQ24UYF RXYTQ26UYF RXYTQ28UYF RXYTQ30UYF RXYTQ32UYF RXYTQ34UYF RXYTQ36UYF
Power supply Name YF
Phase 3N~
Frequency Hz 50/60
Voltage V 380-415/400
Power supply intake Both indoor and outdoor unit
Voltage range Min. % -10
Max. % 10
Power Performance Power factor UAE. S 46°C ISO - Full load 0.94 1 0.94 0.93 0.94
Current - 50Hz Nominal MEW R6 Cooling A 18.3 (10) 21.5 (10) 23.9 (10) 27.3 (10) 30.3 (10) 32.9 (10) 36.1 (10) 38.7 (10) 37.6 (10) 40.8 (10)
running UAE. S Cooling A 20.9 (11) 21.9 (11) 23.6 (11) 26.8 (11) 29.5 (11) 31.7 (11) 34.4 (11) 38.1 (11) 39.1 (11)
current
(RLA)
Starting current (MSC) - remark See note 15
Minimum circuit amps (MCA) A 38.1 (12) 40.1 (12) 46.0 (12) 47.1 (12) 51.0 (12) 55.0 (12) 58.0 (12) 62.0 (12) 69.1 (12) 71.1 (12)
Maximum fuse amps (MFA) A 40 (13) 50 (13) 63 (13) 80 (13)
Wiring connections For power Quantity 5G
- 50Hz supply
For connec- Quantity 2
tion with Remark F1,F2
indoor

Electrical specifications System RXYTQ38UYF RXYTQ40UYF RXYTQ42UYF RXYTQ44UYF RXYTQ46UYF RXYTQ48UYF


Power supply Name YF
Phase 3N~
Frequency Hz 50/60
Voltage V 380-415/400
Power supply intake Both indoor and outdoor unit
Voltage range Min. % -10
Max. % 10
Power Performance Power factor UAE. S 46°C ISO - Full load 0.93 0.94 0.93 0.94
Current - 50Hz Nominal MEW R6 Cooling A 44.0 (10) 46.5 (10) 49.0 (10) 52.2 (10) 55.4 (10) 58.0 (10)
running UAE. S Cooling A 41.3 (11) 43.0 (11) 45.7 (11) 46.7 (11) 48.9 (11) 51.6 (11)
current
(RLA)
Starting current (MSC) - remark See note 15
Minimum circuit amps (MCA) A 74.1 (12) 80.0 (12) 84.0 (12) 86.0 (12) 89.0 (12) 93.0 (12)
Maximum fuse amps (MFA) A 100 (13) 125 (13)
Wiring connections For power Quantity 5G
- 50Hz supply
For connec- Quantity 2
tion with Remark F1,F2
indoor

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 9


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

3 Features and advantages


3-1 Features and Advantages

Cooling Seasonal
Performance Factor

Nominal Efficiency vs. Seasonal Efficiency


in line with real life performance

Currently, the energy efficiency of cooling conditions. However, these calculation


devices is measured in artificial and methods have not been adopted for high
standardized conditions. For air conditioners, Ambient or hot climates. In order to correct
this is done at a constant temperature of 46 °C this situation, a more realistic calculation
or 35 °C and at full cooling capacity. This results method called Cooling Seasonal Performance
in T1 & T3 energy efficiency (EER), which is Factor for Hot Climate CSPFT3 has been
representing only two points to conclude on developed by the ISO Refrigeration and
Energy performance. Air-Conditioning Subcommittee (SC6) for the
testing and rating of air conditioners and heat
In other markets, like in the US and Europe, pumps. This is the standard ISO 16358 -1
seasonal performance is measured with IPLV, Amendment 1 issued in 2019 for the hot T3
SEER or ESEER calculations based on real-life climate zones.

10 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

3 Features and advantages


3-1 Features and Advantages
The implementation of the Seasonal Efficiency calculation reflects more realistic energy efficiency
value through the entire cooling season at hot climate conditions compared to currently used EER
value. 3
The calculation follows the below considerations:
The adoption of the CSPFT3
Use of a high ambient climate weather bin for cooling calculation method will result in a
instead of one nominal temperature better estimation of the
Considering operation at partial capacity instead of equipment’s real-life performance
full capacity. over a year.

What is CSPFT3?
(Cooling Seasonal Performance Factor for Hot Climate CSPF T3 ) is the testing and rating of air
conditioners as per the ISO 16358 -1 Amendment 1 issued in 2019 for T3 hot climate zones and takes into
consideration the bin hours reflecting high ambient conditions.

How is CSPFT3 expressed?


It is expressed as the CSPFT3 value (Cooling Seasonal Performance Factor for Hot Climate CSPFT3)
It is defined as the ratio of the total annual amount of heat that the equipment can remove from the
indoor air when operating for cooling in active mode to the total annual amount of energy consumed
by the equipment during the same period.

Cooling Seasonal Total Load


CSPFT3 = @ T3 ISO weather bin

Cooling Seasonal Energy Consumption


@ T3 ISO weather bin

Benefits of CSPFT3
The implementation of seasonal efficiency will provide end users with a fair comparison of different equipment
based on realistic year-round efficiency which will lead to:

Reduced energy Reduced CO2 Reduced


consumption emission electricity bills

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 11


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

3 Features and advantages


3-1 Features and Advantages

3
Pioneering in innovation and
environmental responsibility
For Daikin, seasonal efficiency brings together two core ambitions: pushing for innovation and reducing the
environmental footprint of our products. Being the first in the industry to design equipment based on optimal seasonal
efficiency values, Daikin is once again pioneering high-performance cooling products that lower the impact on the
environment and on your wallet.

Benefits of Seasonal Efficiency vs. Nominal Efficiency

Energy Efficiency Ratio Cooling Seasonal


Performance Factor

400 400

350
Weather bin
350
for T3
300 T1 300 Climates as
250 250 per ISO
16358-1
200 200
AMD 1
150 150

100 100

50 50
T3
0 0
20 25 30 35 40 45 50 20 25 30 35 40 45 50
Temperature ° C Temperature ° C

Energy Efficiency Ratio rating is based on one outdoor Cooling Seasonal Performance Factor is based on the Hot Climate
Ambient Temperature condition (T1 or T3) Weather bin as per ISO 16358-1 AMD1

Cooling Capacity Cooling Seasonal Total Load


@ T1 or T3 @ T3 ISO Weather bin
EER = CSPFT3 =
@ T1 or T3
Power Input Cooling Seasonal Energy Consumption
@ T1 or T3
@ T3 ISO Weather bin

Nominal efficiency gives an indication on how efficient CSPFT3 gives an indication on how efficient an air
an air conditioner operates at nominal conditions. conditioner operates over an entire cooling season.
100% capacity performance is used to measure EER Variable or seasonal performance close to real life is
used and not 100% capacity performance.

For example, 10 HP Daikin VRV IV+Unit (RXYTQ10U7YF) can be evaluated using below mentioned efficiencies:

10.82 (Btu/h)/W CSPFT3: 20.9 (Btu/h)/W


T3 EER : 3.17 W/W 6.13 W/W

When the new ISO standard for hot climate was published, Daikin has resolutely chosen for early
implementation of this new legislation and started testing all products for seasonal efficiency. This commitment
to pioneering the implementation of seasonal efficiency is a practice we observe every day.
Today, Daikin leads the way towards more efficient and cost-effective comfort solutions. All Daikin products -
residential, commercial, as well as industrial - are seasonal-efficient, reducing energy and costs the smart way.

12 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

4 Options
4-1 Options
RXYTQ-UYF

VRV4
Middle East 4
Option list

Nr. Item RXYTQ8U RXYTQ10-12U RXYTQ14-16U RXYTQ18~48U


KHRQ22M29H
I. Refnet header - KHRQ22M64H
- - - KHRQ22M75H
KHRQ22M20T
KHRQ22M29T9
II. Refnet joint
- KHRQ22M64T
- - - KHRQ22M75T
III. Outdoor multi-connection kit (2) - - - BHFQ22P1007
IV. Outdoor multi-connection kit (2) - - - BHFQ22P1517

Nr. Item 8HP 10HP 12HP 14HP 16HP


1a. Cool/heat selector (switch) KRC19-26A
1b. Cool/heat selector (PCB) BRP2A81
1c. Cool/heat selector (fixing box) KJB111A*
2. VRV configurator EKPCCAB
3. Demand PCB (5) DTA104A61/62*
4. Demand PCB mounting plate - KKSB26B1*

Notes
1. All options are kits
2. Only for multi units
3. To operate the cool/heat selector function, options 1a and 1b are both required.
4. To mount option 1a, option 1c is required.
5. To install the demand PCB on the large casing type, the demand PCB mounting plate is required.

Medium casing type VRV4 Middle East heat pump: modules 8HP
Large casing type VRV4 Middle East heat pump: modules 10~16HP
3D119361

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 13


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

5 Combination table
5-1 Combination Table
RXYTQ-UYF

Unit combination restrictions: ·VRV4· outdoor units (all models) + ·15·-class indoor units
Units in scope: ·FXZQ15A· and ·FXAQ15A·.

1. In case the system contains these indoor units and the total connection ratio (·CR·) ≤ ·100·%: no special restrictions.
Follow the restrictions that apply to regular ·VRV DX· indoor units.

2. In case the system contains these indoor units and the total connection ratio (·CR·) > ·100·%: special restrictions apply.
A. When the connection ratio (·CR1·) of the sum of all ·FXZQ15A· and/or ·FXAQ15A· units in the system ≤ ·70·%, and ALL other ·VRV DX· indoor units have an
individual capacity class > ·50·: no special restrictions.

B. When the connection ratio (·CR1·) of the sum of all ·FXZQ15A· and/or ·FXAQ15A· units in the system ≤ ·70·%, and NOT ALL other ·VRV DX· indoor units have
an individual capacity class > ·50·: the restrictions below apply.

° 100% < CR ≤ 105% -> ·CR1· of the sum of all ·FXZQ15A· and/or ·FXAQ15A· indoor units in the system must be ≤ ·70·%.
° 105% < CR ≤ 110% -> ·CR1· of the sum of all ·FXZQ15A· and/or ·FXAQ15A· indoor units in the system must be ≤ ·60·%.
° 110% < CR ≤ 115% -> ·CR1· of the sum of all ·FXZQ15A· and/or ·FXAQ15A· indoor units in the system must be ≤ ·40·%.
° 115% < CR ≤ 120% -> ·CR1· of the sum of all ·FXZQ15A· and/or ·FXAQ15A· indoor units in the system must be ≤ ·25·%.
° 120% < CR ≤ 125% -> ·CR1· of the sum of all ·FXZQ15A· and/or ·FXAQ15A· indoor units in the system must be ≤ ·10·%.
° 125% < CR ≤ 130% -> ·FXZQ15A· and ·FXAQ15A· cannot be used.

Remark

Only the ·15·-class indoor units explicitly mentioned on this page are in scope. Other indoor units follow the rules that apply to regular
·VRV DX· indoor units.

3D104665A
RXYTQ-UYF

VRV4
Middle East
Indoor unit combination restrictions
Indoor unit combination pattern ·VRV* DX· indoor unit Air handling unit (AHU) (3)
·VRV* DX· indoor unit O O2
Air handling unit (AHU) (3) O O1

O: Allowed
X: Not allowed
Notes
1. O1
- Combination of ·AHU· only + control box ·EKEQFA· (the combination with ·VRV DX· indoor units is not allowed; maximum ·48·HP for ·3x400· class ·EKEXV· kit)
→ ·X·-control is possible (up to ·3x· [·EKEXV+EKEQFA*· boxes] can be connected to one outdoor unit (system)). No Variable Refrigerant Temperature control possible.
→ ·Y·-control is possible (up to ·3x· [·EKEXV+EKEQFA*· boxes] can be connected to one outdoor unit (system)). No Variable Refrigerant Temperature control possible.
→ ·W·-control is possible (up to ·3x· [·EKEXV+EKEQFA*· boxes] can be connected to one outdoor unit (system)). No Variable Refrigerant Temperature control possible.

- Combination of ·AHU· only + control box ·EKEQMA· (not combined with ·VRV DX· indoor units)
→ Z-control is possible (the allowed number of [·EKEXV + EKEQMA· boxes] is determined by the connection ratio (·90-110%·) and the capacity of the outdoor unit.

2. O2
- Combination of ·AHU· and ·VRV DX· indoor units
→ Z-control is possible (·EKEQMA*· boxes are allowed, but with a limited connection ratio).

3. (3) The following units are considered AHUs:


→ ·EKEXV + EKEQ(MA/FA) + AHU· coil
→ ·FXMQ_MF· units
Information
- ·VKM· units are considered to be regular ·VRV DX· indoor units.

3D096860A

14 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

6 Capacity tables
6-1 Capacity Table Legend
,QRUGHUWRIXO¿OOPRUH\RXUUHTXLUHPHQWVRQTXLFNDFFHVVRIGDWDLQWKHIRUPDW\RXUHTXLUHZHKDYHGHYHORSHGDWRROWR
FRQVXOWFDSDFLW\WDEOHV

%HORZ\RXFDQ¿QGWKHOLQNWRWKHFDSDFLW\WDEOHGDWDEDVHDQGDQRYHUYLHZRIDOOWKHWRROVZHKDYHWRKHOS\RXVHOHFWWKH 6
FRUUHFWSURGXFW

• Capacity table database:OHWV\RX¿QGEDFNDQGH[SRUWTXLFNO\WKHFDSDFLW\LQIRUPDWLRQ\RXDUHORRNLQJIRUEDVHGXSRQ


XQLWPRGHOUHIULJHUDQWWHPSHUDWXUHDQGFRQQHFWLRQUDWLR
• <RXFDQDFFHVVWKHFDSDFLW\WDEOHYLHZHUKHUH
KWWSVP\GDLNLQHXFRQWHQWGHQYHQB86KRPHDSSOLFDWLRQVVRIWZDUH¿QGHUFDSDFLW\WDEOHYLHZHUKWPO

• $QRYHUYLHZRIall software toolsWKDWZHRႇHUFDQEHIRXQGKHUH


KWWSVP\GDLNLQHXGHQYHQB86KRPHDSSOLFDWLRQVVRIWZDUH¿QGHUKWPO

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 15


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

6 Capacity tables
6-2 Integrated Heating Capacity Correction Factor
RXYTQ‐UYF

6 Integrated heating capacity coefficient

The heating capacity tables do not take into account the capacity reduction in case of frost accumulation or defrost operation.
The capacity values that take these factors into account, or in other words, the integrated heating capacity values, can be calculated as follows:

Formula A=B*C Defrost operation Defrost operation


A= Integrated heating capacity
B= Capacity characteristics value
C= Integrated correction factor for frost accumulation (see table)

Heating capacity
Inlet air temperature of heat exchanger
[°CDB/°CWB] ‐7/‐7,6 ‐5/‐5,6 ‐3/‐3,7 0/‐0,7 3/2,2 5/4,1 7/6
Integrated correction factor for frost accumulation ∙(C)∙
Time
8HP 0,95 0,93 0,88 0,84 0,85 0,90 1,00
10HP 0,95 0,93 0,87 0,79 0,80 0,88 1,00
12HP 0,95 0,92 0,87 0,75 0,76 0,85 1,00
14HP 0,95 0,92 0,86 0,72 0,73 0,84 1,00
16HP 0,95 0,92 0,86 0,72 0,72 0,83 1,00
∙1∙ cycle

Only free multi‐outdoor‐unit combinations are possible. Respect the following calculation rules:
The total integrated heating capacity of a multi‐outdoor‐unit system = the sum of the integrated heating capacity of each module separately.

Notes
1. The figure shows the integrated heating capacity for a single cycle (from one defrost operation to the next).
2. When there is an accumulation of snow against the outdoor unit heat exchanger, there will always be a temporary reduction in capacity depending on the outdoor temperature (°C DB), relative humidity (RH)
and the amount of frosting which occurs.

3D097510

16 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

6 Capacity tables
6-3 Capacity Correction Factor
RXYTQ8UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend

Hp: Maximum level difference (m) between outdoor


and indoor units when the outdoor unit is
6
Hp Hp positioned higher than the indoor units.

Hm: Maximum level difference (m) between outdoor


L L
and indoor units when the outdoor unit is
Hm
positioned lower than the indoor units.
Hm

L: Equivalent piping length [m]

Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit

Indoor connection ratio > 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio. X Correction ratio of piping to furthest indoor unit

3. Main liquid and gas pipe size increase


Model Standard liquid side Ø Increased liquid side Ø Standard gas side Ø Increased gas side Ø
8HP 9,5 12,7 19,1 22,2
For the allowed system setups and the rules for when to increase the main liquid and gas piping diameter, refer to the installation manual.
4. Overall equivalent length
Overall equivalent length = Equivalent length of the main pipe X Correction factor + Equivalent length of the branch pipes

Choose the correction factor from the following table.


Correction ratio for cooling capacity Correction ratio for heating capacity
Model
Standard size Size increase Standard size Size increase
8HP 1 0,5 1 0,5
5. Example
Main gas pipe Equivalent length of the branch pipe of the furthest
Main liquid pipe indoor unit
Overall equivalent length
80 m 40 m
▪ Cooling mode = 80 m x 0,5 + 40 m = 80 m
▪ Heating mode = 80 m x 0,5 + 40 m = 80 m

Capacity correction ratio (height difference = 0)


▪ Cooling mode = 0,86
▪ Heating mode = 1,0

3D119351
RXYTQ10UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend

Hp: Maximum level difference (m) between outdoor


and indoor units when the outdoor unit is
Hp Hp positioned higher than the indoor units.

Hm: Maximum level difference (m) between outdoor


L L
and indoor units when the outdoor unit is
Hm
positioned lower than the indoor units.
Hm

L: Equivalent piping length [m]

Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit

Indoor connection ratio > 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio. X Correction ratio of piping to furthest indoor unit

3. Main liquid and gas pipe size increase


Model Standard liquid side Ø Increased liquid side Ø Standard gas side Ø Increased gas side Ø
10HP 9,5 12,7 22,2 25,4
For the allowed system setups and the rules for when to increase the main liquid and gas piping diameter, refer to the installation manual.
4. Overall equivalent length
Overall equivalent length = Equivalent length of the main pipe X Correction factor + Equivalent length of the branch pipes

Choose the correction factor from the following table.


Correction ratio for cooling capacity Correction ratio for heating capacity
Model
Standard size Size increase Standard size Size increase
10HP 1 0,5 1 0,5
5. Example
Main gas pipe Equivalent length of the branch pipe of the furthest
Main liquid pipe indoor unit
Overall equivalent length
80 m 40 m
▪ Cooling mode = 80 m x 0,5 + 40 m = 80 m
▪ Heating mode = 80 m x 0,5 + 40 m = 80 m

Capacity correction ratio (height difference = 0)


▪ Cooling mode = 0,87
▪ Heating mode = 0,90

3D119351

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 17


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

6 Capacity tables
6-3 Capacity Correction Factor
RXYTQ12UYF
RXYTQ14UYF Correction ratio for cooling capacity Correction ratio for heating capacity Legend

RXYTQ24UYF Hp: Maximum level difference (m) between outdoor


6 RXYTQ36UYF Hp Hp
and indoor units when the outdoor unit is
positioned higher than the indoor units.

L
Hm: Maximum level difference (m) between outdoor
L
and indoor units when the outdoor unit is
positioned lower than the indoor units.
Hm Hm

L: Equivalent piping length [m]

Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit

Indoor connection ratio > 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio. X Correction ratio of piping to furthest indoor unit

3. Main liquid and gas pipe size increase


Model Standard liquid side Ø Increased liquid side Ø Standard gas side Ø Increased gas side Ø
12HP 12,7 15,9 28,6 28,6
14HP 12,7 15,9 28,6 28,6
24HP 15,9 19,1 34,9 34,9
36HP 19,1 22,2 41,3 41,3
For the allowed system setups and the rules for when to increase the main liquid and gas piping diameter, refer to the installation manual.
4. Overall equivalent length
Overall equivalent length = Equivalent length of the main pipe X Correction factor + Equivalent length of the branch pipes

Choose the correction factor from the following table.


Correction ratio for cooling capacity Correction ratio for heating capacity
Model
Standard size Size increase Standard size Size increase
12/14/24/36HP 1 / 1 0,5
5. Example
Main gas pipe Equivalent length of the branch pipe of the furthest
Main liquid pipe indoor unit
Overall equivalent length
80 m 40 m
▪ Cooling mode = 80 m x 1,0 + 40 m = 120 m
▪ Heating mode = 80 m x 0,5 + 40 m = 80 m

Capacity correction ratio (height difference = 0)


▪ Cooling mode = 0,89
▪ Heating mode = 1,0

3D119351
RXYTQ16UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend

Hp: Maximum level difference (m) between outdoor


and indoor units when the outdoor unit is
Hp Hp positioned higher than the indoor units.

Hm: Maximum level difference (m) between outdoor


L L
and indoor units when the outdoor unit is
Hm
positioned lower than the indoor units.
Hm

L: Equivalent piping length [m]

Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit

Indoor connection ratio > 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio. X Correction ratio of piping to furthest indoor unit

3. Main liquid and gas pipe size increase


Model Standard liquid side Ø Increased liquid side Ø Standard gas side Ø Increased gas side Ø
16HP 12,7 15,9 28,6 31,8
For the allowed system setups and the rules for when to increase the main liquid and gas piping diameter, refer to the installation manual.
4. Overall equivalent length
Overall equivalent length = Equivalent length of the main pipe X Correction factor + Equivalent length of the branch pipes

Choose the correction factor from the following table.


Correction ratio for cooling capacity Correction ratio for heating capacity
Model
Standard size Size increase Standard size Size increase
16HP 1 0,5 1 0,5
5. Example
Main gas pipe
Equivalent length of the branch pipe of the furthest
Main liquid pipe indoor unit
Overall equivalent length
80 m 40 m
▪ Cooling mode = 80 m x 0,5 + 40 m = 80 m
▪ Heating mode = 80 m x 0,5 + 40 m = 80 m

Capacity correction ratio (height difference = 0)


▪ Cooling mode = 0,88
▪ Heating mode = 0,99

3D119351

18 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

6 Capacity tables
6-3 Capacity Correction Factor
RXYTQ18UYF
RXYTQ26-30UYF
RXYTQ38UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend

Hp: Maximum level difference (m) between outdoor 6


RXYTQ44UYF and indoor units when the outdoor unit is
Hp Hp positioned higher than the indoor units.

Hm: Maximum level difference (m) between outdoor


L L
and indoor units when the outdoor unit is
positioned lower than the indoor units.
Hm Hm

L: Equivalent piping length [m]

Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit

Indoor connection ratio > 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio. X Correction ratio of piping to furthest indoor unit

3. Main liquid and gas pipe size increase


Model Standard liquid side Ø Increased liquid side Ø Standard gas side Ø Increased gas side Ø
18HP 15,9 19,1 28,6 31,8
26-30HP 19,1 22,2 34,9 38,1
38-44HP 19,1 22,2 41,3 41,3

For the allowed system setups and the rules for when to increase the main liquid and gas piping diameter, refer to the installation manual.
4. Overall equivalent length
Overall equivalent length = Equivalent length of the main pipe X Correction factor + Equivalent length of the branch pipes

Choose the correction factor from the following table.


Correction ratio for cooling capacity Correction ratio for heating capacity
Model
Standard size Size increase Standard size Size increase
18/26-30/38-44HP 1 0,5 1 0,5

5. Example RXYTQ38-44T
Main gas pipe Equivalent length of the branch pipe of the furthest
Main liquid pipe indoor unit
Overall equivalent length
80 m 40 m
▪ Cooling mode = 80 m x 1,0 + 40 m = 120 m
▪ Heating mode = 80 m x 0,5 + 40 m = 80 m

Capacity correction ratio (height difference = 0)


▪ Cooling mode = 0,83
▪ Heating mode = 1,0

3D119351
RXYTQ20UYF
RXYTQ32UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend
RXYTQ34UYF
Hp: Maximum level difference (m) between outdoor
and indoor units when the outdoor unit is
Hp Hp positioned higher than the indoor units.

L
Hm: Maximum level difference (m) between outdoor
L
and indoor units when the outdoor unit is
positioned lower than the indoor units.
Hm Hm

L: Equivalent piping length [m]

Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit

Indoor connection ratio > 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio. X Correction ratio of piping to furthest indoor unit

3. Main liquid and gas pipe size increase


Model Standard liquid side Ø Increased liquid side Ø Standard gas side Ø Increased gas side Ø
20HP 15,9 19,1 28,6 31,8
32/34HP 19,1 22,2 34,9 38,1
For the allowed system setups and the rules for when to increase the main liquid and gas piping diameter, refer to the installation manual.
4. Overall equivalent length
Overall equivalent length = Equivalent length of the main pipe X Correction factor + Equivalent length of the branch pipes

Choose the correction factor from the following table.


Correction ratio for cooling capacity Correction ratio for heating capacity
Model
Standard size Size increase Standard size Size increase
20/32/34HP 1 0,5 1 0,5

5. Example RXYTQ38-44T
Main gas pipe Equivalent length of the branch pipe of the furthest
Main liquid pipe indoor unit
Overall equivalent length
80 m 40 m
▪ Cooling mode = 80 m x 0,5 + 40 m = 80 m
▪ Heating mode = 80 m x 0,5 + 40 m = 80 m

Capacity correction ratio (height difference = 0)


▪ Cooling mode = 0,88
▪ Heating mode = 1,0

3D119351

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 19


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

6 Capacity tables
6-3 Capacity Correction Factor
RXYTQ22UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend

6 Hp: Maximum level difference (m) between outdoor


and indoor units when the outdoor unit is
Hp Hp positioned higher than the indoor units.

Hm: Maximum level difference (m) between outdoor


L L
and indoor units when the outdoor unit is
Hm
positioned lower than the indoor units.
Hm

L: Equivalent piping length [m]

Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit

Indoor connection ratio > 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio. X Correction ratio of piping to furthest indoor unit

3. Main liquid and gas pipe size increase


Model Standard liquid side Ø Increased liquid side Ø Standard gas side Ø Increased gas side Ø
22HP 15,9 19,1 28,6 31,8
For the allowed system setups and the rules for when to increase the main liquid and gas piping diameter, refer to the installation manual.
4. Overall equivalent length
Overall equivalent length = Equivalent length of the main pipe X Correction factor + Equivalent length of the branch pipes

Choose the correction factor from the following table.


Correction ratio for cooling capacity Correction ratio for heating capacity
Model
Standard size Size increase Standard size Size increase
22HP 1 0,5 1 0,5
5. Example
Main gas pipe
Equivalent length of the branch pipe of the furthest
Main liquid pipe indoor unit
Overall equivalent length
80 m 40 m
▪ Cooling mode = 80 m x 0,5 + 40 m = 80 m
▪ Heating mode = 80 m x 0,5 + 40 m = 80 m

Capacity correction ratio (height difference = 0)


▪ Cooling mode = 0,88
▪ Heating mode = 1,0

3D119351
RXYTQ46UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend

Hp: Maximum level difference (m) between outdoor


and indoor units when the outdoor unit is
Hp Hp positioned higher than the indoor units.

Hm: Maximum level difference (m) between outdoor


L L
and indoor units when the outdoor unit is
Hm
positioned lower than the indoor units.
Hm

L: Equivalent piping length [m]

Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit

Indoor connection ratio > 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio. X Correction ratio of piping to furthest indoor unit

3. Main liquid and gas pipe size increase


Model Standard liquid side Ø Increased liquid side Ø Standard gas side Ø Increased gas side Ø
46HP 19,1 22,2 41,3 41,3
For the allowed system setups and the rules for when to increase the main liquid and gas piping diameter, refer to the installation manual.
4. Overall equivalent length
Overall equivalent length = Equivalent length of the main pipe X Correction factor + Equivalent length of the branch pipes

Choose the correction factor from the following table.


Correction ratio for cooling capacity Correction ratio for heating capacity
Model
Standard size Size increase Standard size Size increase
46HP 1 / 1 0,5
5. Example
Main gas pipe
Equivalent length of the branch pipe of the furthest
Main liquid pipe indoor unit
Overall equivalent length
80 m 40 m
▪ Cooling mode = 80 m x 1,0 + 40 m = 120 m
▪ Heating mode = 80 m x 0,5 + 40 m = 80 m

Capacity correction ratio (height difference = 0)


▪ Cooling mode = 0,83
▪ Heating mode = 1,0

3D119351

20 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

6 Capacity tables
6-3 Capacity Correction Factor
RXYTQ48UYF
Correction ratio for cooling capacity Correction ratio for heating capacity Legend

Hp: Maximum level difference (m) between outdoor


and indoor units when the outdoor unit is
6
Hp Hp positioned higher than the indoor units.

Hm: Maximum level difference (m) between outdoor


L L
and indoor units when the outdoor unit is
Hm
positioned lower than the indoor units.
Hm

L: Equivalent piping length [m]

Notes
1. These figures illustrate the capacity correction factor due to the piping length for a standard indoor unit system at maximum load (with the thermostat set to maximum), under standard conditions.
Moreover, under partial load conditions, there is only a minor deviation for the capacity correction ratio, as shown it the above figures.
2. Method of calculating the capacity of the outdoor units.
The maximum capacity of the system will be either the total capacity of the indoor units or the maximum capacity of the outdoor units as mentioned below, whichever is less.
Indoor connection ratio ≤ 100%.
Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at 100% connection ratio. X Correction ratio of piping to furthest indoor unit

Indoor connection ratio > 100%.


Maximum capacity of outdoor units = Capacity of outdoor units from capacity table at installed connection ratio. X Correction ratio of piping to furthest indoor unit

3. Main liquid and gas pipe size increase


Model Standard liquid side Ø Increased liquid side Ø Standard gas side Ø Increased gas side Ø
48HP 19,1 22,2 41,3 41,3
For the allowed system setups and the rules for when to increase the main liquid and gas piping diameter, refer to the installation manual.
4. Overall equivalent length
Overall equivalent length = Equivalent length of the main pipe X Correction factor + Equivalent length of the branch pipes

Choose the correction factor from the following table.


Correction ratio for cooling capacity Correction ratio for heating capacity
Model
Standard size Size increase Standard size Size increase
48HP 1 / 1 0,5
5. Example
Main gas pipe
Equivalent length of the branch pipe of the furthest
Main liquid pipe indoor unit
Overall equivalent length
80 m 40 m
▪ Cooling mode = 80 m x 1,0 + 40 m = 120 m
▪ Heating mode = 80 m x 0,5 + 40 m = 80 m

Capacity correction ratio (height difference = 0)


▪ Cooling mode = 0,83
▪ Heating mode = 0,97

3D119351

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 21


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

7 Dimensional drawings
7-1 Dimensional Drawings
RXYTQ8UYF Pitch of foundation bolt holes
766
1 2 3

Pitch of foundation bolt holes


7 13㻠
3㻡3
8
12㻡
5
3 92
3 A 0 7 21 70
A 1 1 1
2

100 07
66
160
106
AB 10
View ·C·
4-15x22.5mm Oblong hole
Detail ·A· Detail ·B· Foundation bolt hole

Notes
1. Detail ·A· and detail ·B· indicate the dimensions after fixing the attached piping.

2. Items ·4 - 10:· Knockout hole.


3.Gas pipe
RYYQ8U, RYMQ8U, RXYQ8U, RXYQQ8U, : Ø ·19.1· brazing connection
11 RXYTQ8U
RYMA5A, RXYA8-12A
RYYQ10U, RYMQ10U, RXYQ10U, : Ø ·22.2· brazing connection
RXYQQ10U
REMQ5U, REMA5A, REYQ8-12U, : Ø ·25.4· brazing connection
REYA8-12A
856 RYYQ12U, RYMQ12U, RXYQ12U, : Ø ·28.6· brazing connection
1 RXYQQ12U
4 Liquid pipe
7 RYYQ8-10U, RYMQ8-10U, RXYQ8-10U, RXYQQ8-10U, : Ø ·9.5· brazing connection
REMQ5U, REMA5A, REYQ8-12U, REYA8-12A, RXYTQ8U
9 RYMA5A, RXYA8-12A
RYYQ12U, RYMQ12U, RXYQ12U, : Ø ·12.7· brazing connection
22 RXYQQ12U
5 1 Equalising pipe
1
5 RYMQ8-10U : Ø ·19.1· brazing connection
RYMQ12U : Ø ·22.2· brazing connection
762 95 9 RYMA5A, RXYA8-12A
: Ø ·25.4· brazing connection
2 7 1
1 13 High pressure/low pressure gas pipe
97 107 76 76 REMQ5U, REMA5A, REYQ8-12U, : Ø ·19.1· brazing connection
137 Detail ·A·
Detail ·B· 272 5 6 REYA8-12A
76㻡
328
373 C
930 No. Part name Remark
1 Liquid pipe connection port See note ·3·.
2 Gas pipe connection port See note ·3·.
Equalising pipe connection port RYMA5A, RXYA8-12A
3 Equalising pipe connection port See note ·3·.
High pressure/low pressure gas pipe
Gas pipe connection port RYMA5A, RXYA8-12A
4 Power cord routing hole (side) O65
5 Power cord routing hole (front) O80
6 Power cord routing hole (front) O65
7 Power cord routing hole (front) O27
8
Model Power cord routing hole (bottom) O65
AA AB 9 Pipe routing hole (front)
RYYQ8-12U, RXYQ8-12U, RXYQQ8-12U,RXYTQ8U - - 10 Pipe routing hole (bottom)
11 Grounding terminal Inside of the switch box (·M8·)
REMQ5U,RYMQ8-12U,REYQ8-12U, REMA5A,REYA8A-12A, RYMA5A, RXYA8-12A 240 240

2D119001B

RXYTQ10-16UYF 1 2 3
Pitch of foundation bolt holes
107㻢
Pitch of foundation bolt holes

393
134
12㻡 8

0 297 7
121 01
1
3 0
1 B
2 A 70
100 71 10
1㻢0 10㻢
AA Oblong hole
4-15x22.5mm - View ·C·
Detail ·A· Detail ·B· Foundation bolt hole
Notes
1.Detail ·A· and detail ·B· indicate the dimensions after fixing the attached piping.
No. Part name Remark 2.Items ·4 - 10:· Knockout hole.
1 Liquid pipe connection port See note ·3·. 3.Gas pipe
2 Gas pipe connection port See note ·3·. RXYTQ10U : Ø ·22.2· brazing connection
Equalising pipe connection port RXYA14-20A REYQ14-20U, REYA14-20A : Ø ·25.4· brazing connection
3 RYYQ14-20U, RYMQ14-20U RXYQ14-20U, RXYQQ14-20U, RXYTQ12-16U : Ø ·28.6· brazing connection
Equalising pipe connection port See note ·3·. RXYA14-20A : Ø ·19.1· brazing connection
High pressure/low pressure gas pipe
Gas pipe connection port RXYA14-20A Liquid pipe
RXYTQ10U : Ø ·9.5· brazing connection
4 Power cord routing hole (side) O65 RYYQ14-16U, RYMQ14-16U, RXYQ14-16U, RXYQQ14-16U, REYQ14-20U, : Ø ·12.7· brazing connection
5 Power cord routing hole (front) O80 REYA14-20A, RXYTQ12-16U, RXYA14-20A
6 Power cord routing hole (front) O65 RYYQ18-20U, RYMQ18-20U, RXYQ18-20U, RXYQQ18-20U : Ø ·15.9· brazing connection
7 Power cord routing hole (front) O27 Equalising pipe
8 O65 RYMQ14-16U : Ø ·22.2· brazing connection
Power cord routing hole (bottom) RYMQ18-20U : Ø ·28.6· brazing connection
9 Pipe routing hole (front) RXYA14-20A : Ø ·25.4· brazing connection
10 Pipe routing hole (bottom) High pressure/low pressure gas pipe
11 Grounding terminal Inside of the switch box (·M8·) REYQ14-20U, REYA14-20A : Ø ·19.1· brazing connection

Model AA AB
RXYQ14-20U, RYYQ14-20U, RXYQQ14-20U, RXY7Q10-16U - -
RYMQ14-16U, REYQ14-20U, REYA14-20A, RXYA14-20A 240 240
RYMQ1-20U 240 12
11

856
1
4
7

221
155
762 95 9
2 7 1
1 13
137 7㻢 7㻢
Detail ·B· Detail ·A· 97 107 5 6 7㻢㻡
272
328
373 C
1240 2D119091B

22 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

8 Centre of gravity
8-1 Centre of Gravity
RXYTQ8UYF

Unit AA AB AC

RYYQ8-12U
328 366 565
REMQ5U / REYQ8-12U
RYMQ8-12U 354 443 565
RXYQ8-12U
RXYQQ8-12U 339 448 565
RXYTQ8U
REMA5A / REYA8-12A 353 426 690
RYMA5A / RXYA8-12A 353 426 690

AC
View ·A·
View ·A·
AA AB Foundation bolt hole (slot)
729 766

Foundation bolt hole


Foundation bolt hole Foundation bolt hole
3D119703B

RXYTQ10-16UYF

Unit AA AB AC
RYYQ14-20U 334 470 610
REYQ14-20U 334 470 610
RYMQ14-20U 360 569 610
RXYQ(Q)14-20U 345 575 610
RXYTQ10-12U 350 610 810
RXYTQ14-16U 351 565 610
REYA14-16A 339 596 758
REYA18-20A 350 587 752
RXYA14-16A 339 596 758
RXYA18-20A 350 587 752
AC

View ·A·
View ·A·
Foundation bolt hole
AA AB (slot)
729 1076

Foundation bolt hole


Foundation bolt hole Foundation bolt hole

3D119704B

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 23


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

9 Piping diagrams
9-1 Piping Diagrams
RXYQ8-12U
RXYTQ8UYF R1T

9 Y3E
R4T
M
M1F

Y1E Charge port / Service port


R5T R6T R7T
Stop valve
Filter
Y2E
Check valve

Pressure relief valve

Thermistor
Heat sink
(PCB)
Y1S
Capillary tube
Expansion valve
S1NPL S1NPH
4-way valve

Propeller fan
R3T
M

HPS High pressure switch


Low pressure sensor
HPS High pressure sensor
S1PH

R21T Accumulator
Y3S
sv

R8T
M1C
Heat exchanger

sv
Compressor
Y2S

Liquid pipe Oil separator

Gas pipe
Double tube heat exchanger
Charge port
Distributor

Solenoid valve
sv

3D118179
RXYQ14-20U
RXYQ14-16UYF

R1T

Charge port / Service port


Y3E M M
R4T M1F M2F Stop valve
Y1E
Filter
R5T R6T R7T Check valve

Y2E
Pressure relief valve
Thermistor
Heat sink
(PCB)

Capillary tube
Expansion valve
Y1S
4-way valve

S1NPL S1NPH
Propeller fan
M

HPS High pressure switch


R3T
Low pressure sensor
High pressure sensor

HPS HPS
Accumulator
S1PH S2PH

R21T R22T
Heat exchanger
sv

sv

Y3S Y4S
R8T R9T
M1C M2C Compressor

sv
Oil separator
Y2S

Liquid pipe Double tube heat exchanger

Gas pipe Distributor


Charge port Solenoid valve
sv

3D118180

24 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

9 Piping diagrams
9-1 Piping Diagrams
RXYTQ10-12UYF

R1T

Y3E M M
9
R4T M1F M2F
Charge port / Service port
R5T R6T
Y1E
Stop valve
R7T
Filter
Y2E
Check valve

Pressure relief valve


Thermistor
Heat sink
(PCB)

Y1S Capillary tube


Expansion valve
S1NPL S1NPH 4-way valve

Propeller fan
M
R3T

HPS High pressure switch


Low pressure sensor
HPS High pressure sensor
S1PH

Accumulator
R21T

Y3S
sv

M1C
R8T Heat exchanger

sv
Compressor
Y2S

Oil separator
Liquid pipe
Gas pipe Double tube heat exchanger
Charge port Distributor

Solenoid valve
sv

Cooling
Heating
3D119341

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 25


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

10 Wiring diagrams
10 - 1 Wiring Diagrams - Three Phase
RXYQ8-12U
RXYTQ8UYF
10 RYYQ8-12U
RYMQ8-12U

Power supply 3N~ 380-415V 50Hz


3N~ 380V 60Hz
Wiring diagram
X1M T1A A1P
Q1DI F3U N=1 X1A F1U
L1 L1 RED RED
BLU X21A
L2 L2 WHT BLK F2U Y1E
6 M
L3 L3 BLK Z8C N=3
BLU SEG1 SEG2 SEG3
N N X101A
X22A Y2E
Q1LD 6 M
Z9C N=1 BS1 BS2 BS3
DS1 DS2
X5A ON ON
WHT
RED

X23A
BLK
BLU

A2P Z3C N=1 OFF OFF Y3E


1234 1234 5 M
L1A L2A L3A N X4A
F401U

F403U

X37A
X3A HAP (Note 7)
GRN E1 (Note 3) X25A Y4E
Z1F 5 M
S1PH P>
X2A (Note 6)
L1B L2B L3B Z4C N=1 PS
X18A t ゜ R1T
BLK
RED

X28A
WHT

S1NPL

K7R
A3P

K11R
Z7C N=1
K6R

K4R

K5R

K9R
Z5C N=2 X31A
L1B L2B L3B X6A X20A X10A X8A X9A X13A X15A X11A
X40A S1NPH
X4A X32A
HAP
+

V1R
-

PS X63A E3H Y1S Y2S Y3S Y5S E1HC


P1 (Note 8)
C507 K3R
+ X601A R21T R8T R3T R4T R5T R6T R7T
F601U

P2 Z6C t゜ t゜ t゜ t゜ t゜ t゜ t゜
N=3
V1D +C506 +C503 N32 BLK X3A X50A X19A X30A
GRN

P12 RED X1M


X66A to in/d unit to out/d unit to multi unit
N31 BLK F1 F2 F1 F2 Q1 Q2
(Note 3)
R300 P11 RED
+

V1R
A5P
U V W X41A (Note 4) (Note 4) (Note 4)
X1A
Z7C N=1 X1M
A4P C/H selector
Z2C N=4 A B C
P1 N1 X5A indoor outdoor outdoor
WHT
WHT

(F1)(F2) (F1)(F2) (Q1)(Q2)


F101U
RED
WHT
BLK

R24
L1R X3A + HAP X4A
-

V V1R Terminal of M1C Layout of M1C


U MS W X1A heat
M1C 3~ cool W M1F el. compo.box
Z1C N=2 cool S2S -
heat U
fan V M1C
X1A
S1S
outer shell
MS Cool/heat selector
El. compo.box
3~ (Optional accessory)(Note 3)
M1F

A1P L1R

A5P
A2P
X3A
X1A X1M A4P

A3P

(Front side) (Rear side)

2D117534

26 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

10 Wiring diagrams
10 - 1 Wiring Diagrams - Three Phase
RXYTQ10-12UYF A1P Printed circuit board (main)
A2P Printed circuit board (noise filter)
A3P Printed circuit board (inv)
A4P,A5P Printed circuit board (fan)
10
Y1E

Y2E

Y3E
5 M

5 M

5 M

A8P Printed circuit board (abc i/p)(option)

S1NPH
S1NPL
t ゜ R1T
BS1~3 (A1P) Push button switch (mode,set,return)
C503,C506,C507 (A3P) Capacitor
X21A

X22A

X23A

(note 3) X18A

to out/d unit to multi unit X31A

X32A
DS1,DS2 (A1P) Dip switch

(note 4)
E1HC Crankcase heater

(Q1)(Q2)
outdoor
Q2
1234
SEG3

DS2
BS3

X37A

F1U (A1P) Fuse (T,3,15A,250V)


ON
OFF

Q1

(note 4)
F3U Field fuse
SEG2

BS2

F101U (A4P,A5P) Fuse

(F1)(F2)
F2

outdoor
1234

L1R
DS1

F401U,F403U (A2P) Fuse


HAP
SEG1

BS1
ON
OFF

F1

F601U (A3P) Fuse


(note 4)

HAP (A1P,A3P,A4P,A5P) Pilotlamp (service monitor-green)


to in/d unit

(F1)(F2)
F2

indoor
X1M
PS

K3R (A3P) Magnetic relay


F1

K4R (A1P) Magnetic relay (Y1S)


Wiring diagram

X6A
A2P

A3P
el.compo.box
K5R (A1P) Magnetic relay (Y2S)
t゜
R7T

K7R (A1P) Magnetic relay (E1HC)


S1S
cool/heat selector (optional accessory) (note 3)

A4P
A5P
t゜

K9R (A1P) Magnetic relay (Y3S)


R6T
Z8C

S2S heat
cool

fan

X1A
X2A

L1R Reactor
t゜

K7R
E1HC

X30A
X11A

R5T

A1P
M1C Motor (compressor)
heat

X1M
cool

M1F,M2F Motor (fan)


t゜
R4T

A8P
PS (A1P,A3P) Switching power supply
t゜
R3T

cool

K9R Q1DI Field earth leakage breaker


X13A

terminal of M1C
Y3S

Q1LD (A1P) Field earth current detector


C/H selector

R24 (A4P,A5P) Resistor (current sensor)


C

M1C

K5R
X9A

Y2S

R300 (A3P) Resistor (current sensor)


B
t゜

U
R8T

R1T Thermistor (air)


X1M

A
X19A

K4R
R3T Thermistor (accumulator)
X8A

Y1S

A8P
X1A

el.compo.box

R4T Thermistor (heat exc. Liq. Pipe)


outer shell
t゜

R5T Thermistor (subcool liq. Pipe)


R21T

M1C, M1F, M2F

M1C

R6T Thermistor (heat exc. Gas pipe)


layout of

GRN
(NOTE3)
3)

X4A X5A X50A


X66A

R7T Thermistor (heat exc. Deicer)


Q1LD

X20A (note
F1U

(note 6)

M2F

R8T Thermistor (M1C body)


X41A

X28A
X2A
X1A

X101A
A1P

R21T Thermistor (M1C discharge)


M1F
RED

RED
BLU
BLK

BLK

S1NPH Pressure sensor (high)


S1PH P>

S1NPL Pressure sensor (low)


Z5C

S1PH Pressure switch (discharge)


SEG1~SEG3 (A1P) 7-Segment display
T1A Current sensor
V1D (A3P) Diode
V1R (A3P,A4P,A5P) Power module
X*A Connector
X1M Terminal block
X1M (A1P) Terminal block (control)
X1M (A8P) Terminal block (power supply)
Y1E Electronic expansion valve (main)
Y2E Electronic expansion valve (injection)
Y3E Electronic expansion valve (refrigerant jacket)
X6A

Y1S Solenoid valve (main)


P12 RED

P11 RED
BLK

N31 BLK

Y2S Solenoid valve (accumulator oil return)


Y3S Solenoid valve (oil1)
X63A

N32
X6A
X4A

Z*C Noise filter (ferrite core)


Z*F (A2P) Noise filter (with surge absorber)
N=2
Z3C

HAP

PS

BLU F601U
Connector for optional accessories
K3R

Z1C
N=5
R300

V1R

X3A
N

X37A Connector (power adapter)


BLK F403U BLK - - BLK
L1A L2A L3A

U MS W
V1D +C506 +C503

W
L1B L2B L3B

X41A L1B L2B L3B


Z1F

X66A Connector (remote switching cool/heat selector)


C507

M1C 3~

WHT WHT
V1R

WHT
V
+

RED F401U RED + + RED


U

NOTES
A2P

E1

X601A

1. This wiring diagram applies only to the outdoor unit.


A3P
GRN

P1

P2
N=2
Z4C

2.
WHT
: Field wiring, : terminal block, : connector,
L1R

WHT
:terminal,
: protective earth (screw), : functional earth, : earth wiring,
N=1
T1A

: field supply, : PCB, : switch box,


: option
P11 RED

P11 RED
P12 RED
N11 BLK

N11 BLK
N12 BLK
WHT
RED

BLU
BLK

3. When using the optional adapter, refer to the installation manual of the
X1M
L1
L2
L3
N

X5A

X5A
X3A

optional adapter.
F101U

F101U
R24

R24

4. For connection wiring to indoor-outdoor transmission F1-F2, outdoor-


HAP

HAP
X3A
X4A

X4A

+ +
-

outdoor transmission F1-F2, outdoor-multi transmission Q1-Q2, refer to


V1R

V1R
A5P

A4P
Z2C X1A

X1A

the installation manual.


50Hz
60Hz

5. How to use BS1~3 switch. Refer to “service precaution” label on el.


Compo. Box cover.
Q1DI F3U
3N~ 380-415V

(NOTE7)7)

(note 7)
Power supply

X2A

X1A

6. When operating, don’t shortcircuit the protection devices (S1PH)


(note
3N~ 380V

7. Connector x1a (m1f) is red, connector x2a (m2f) is white.


8. Colors: BLK: black, RED: red, BLU: blue, WHT: white, GRN: green.
M2F

M1F
MS

MS
L1
L2
L3

3~

3~
N

2D120654A

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 27


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

10 Wiring diagrams
10 - 1 Wiring Diagrams - Three Phase
RXYTQ14-16UYF A1P Printed circuit board (main)
A2P, A5P Printed circuit board (noise filter)
A3P, A6P Printed circuit board (inv)
A4P, A7P Printed circuit board (fan)
10 A8P Printed circuit board (ABC I/P)
BS1~3 (A1P) Push button switch (mode, set, return)
C503, C506, C507 (A3P, A6P) Capacitor
(NOTE 7)7)

DS1, DS2 (A1P) Dip switch S1PH,


Y1E

Y2E

Y3E

Y4E
(note
5 M

5 M

5 M

5 M

S1NPH
S1NPL
t ゜ R1T

E1HC, E2HC Crankcase heater


E3H Drainpan heater (option)
F1U, F2U (A1P) Fuse (T, 3, 15A, 250V)
X21A

X22A

X23A

X25A

X18A

to in/d unit to out/d unit to multi unit X31A

X32A

(note 4)
F3U Field fuse

(Q1)(Q2)
F101U (A4P, A7P) Fuse
outdoor
(NOTE3)3)

Q2
1234
SEG3

DS2
BS3

X37A
(note

F401U, F403U (A2P, A5P) Fuse


ON
OFF

Q1

(note 4)

F601U (A3P, A6P) Fuse


SEG2

BS2

HAP (A1P, A3P, A4P, A6P, A7P) Pilotlamp (service monitor-green)


(F1)(F2)
outdoor
F2
1234
DS1

X5A R L2

R L1
HAP

K3R (A3P, A6P) Magnetic relay


SEG1

BS1
ON
OFF

F1

(note 4)

K3R (A1P) Magnetic relay (Y4S)

A2P

A3P
(F1)(F2)

K4R (A1P) Magnetic relay (Y1S)


F2

indoor
X1M
PS

Z8C
N=1

K5R (A1P) Magnetic relay (Y2S)


F1
Wiring diagram

el.compo.box

X6A
A5P

A6P
K6R (A1P) Magnetic relay (E3H)
(note 8)

K11R
X15A

Y5S

K7R (A1P) Magnetic relay (E1HC)


t゜
R7T

cool/heat selector (optional accessory) (note 3)


S1S

K8R (A1P) Magnetic relay (E2HC)


A4P
A7P
K8R
E2HC
X12A

t゜
R6T

K9R (A1P) Magnetic relay (Y3S)


S2S heat
cool

fan

X1A
X2A

K11R (A1P) Magnetic relay (Y5S)


t゜

K7R
E1HC
X11A

X30A
R5T

L1R, L2R Reactor


heat

A1P

X1M
cool
t゜

M1C, M2C Motor (compressor)


R4T

K3R
Y4S
X7A

A8P
M1F, M2F Motor (fan)
t゜
R3T

K9R PS (A1P, A3P, A6P) Switching power supply


X13A

Y3S

Q1DI Field earth leakage breaker


terminal of
M1C,M2C
C/H selector

V
C
t゜

Q1LD (A1P) Field earth current detector


R9T

K5R
X9A

Y2S

R24 (A4P, A7P) Resistor (current sensor)


B
t゜

U
R8T

R300 (A3P, A6P) Resistor (current sensor)


X1M

A
X19A

K4R
X8A

Y1S

R1T Thermistor (air)


t゜
R22T

A8P
X1A

el.compo.box

outer shell

R3T Thermistor (accumulator)


M1C,M2C,M1F,M2F
t゜

K6R
R21T
X10A

E3H

R4T Thermistor (heat exc, liq, pipe)


M1C
M2C

R5T Thermistor (subcool, liq, pipe)


layout of
X20A (note 3)

GRN
X4A X5A X50A
X66A
Q1LD

R6T Thermistor (heat exc, gas pipe)


F2U
F1U

(note 6)

(note 6)

M2F

R7T Thermistor (heat exc, deicer)


X41A

X40A

X28A
X2A

X3A
X1A

X101A
A1P

R8T, R9T Thermistor (M1C, M2C body)


M1F
RED

RED

WHT
BLU
BLK

BLK

BLK

R21T, R22T Thermistor (M1C, M2C discharge)


X5A
S1PH P>

S2PH P>

S1NPH Pressure sensor (high)


P12 RED

P11 RED
BLK

N31 BLK

S1NPL Pressure sensor (low)


N=1
Z5C

N32

S1PH, S2PH Pressure switch (disch)


X63A

X6A

X4A

SEG1~SEG3 (A1P) 7-segment display


Z4C
N=2

HAP

T1A Current sensor


PS

BLU F601U
K3R
Z6C
N=1

Z1C
N=5
V1R
R300

X3A

V1D (A3P, A6P) Diode


N

BLK F403U BLK - - BLK


V1R (A3P, A4P, A6P, A7P) Power module
L1A L2A L3A

U MS W
W
V1D +C506 +C503
L1B L2B L3B

L1B L2B L3B


Z1F

C507

WHT WHT
M1C 3~

X*A Connector
WHT
V1R

V
+

X1M (A1P) Terminal block (control)


RED F401U RED + + RED
U
A2P

X1M (A8P) Terminal block (power supply)


E1

X601A
X61A
X41A

Y1E Electronic expansion valve (main)


A3P
GRN

P1

P2

WHT
L1R

WHT Y2E Electronic expansion valve (injection)


Y3E Electronic expansion valve (refrigerant jacket)
X6A

Y4E Electronic expansion valve (storage vessel (note 7)


P12 RED

P11 RED
BLK

N31 BLK

Y1S Solenoid valve (main)


Y2S Solenoid valve (accumulator oil return)
X63A

N32
X6A
X4A

Y3S Solenoid valve (oil1)


11)
(NOTE11)

Y4S Solenoid valve (oil2)


HAP

PS
Z7C N=1

F601U
(note

BLU
Y5S Solenoid valve (sub) (note 8)
K3R

Z2C
N=5
V1R
R300

X4A
N

-
Z*C Noise filter (ferrite core)
BLK F403U BLK - BLK
L1A L2A L3A

U MS W
W
V1D +C506 +C503
L1B L2B L3B

X41A L1B L2B L3B


Z1F

Z*F (A2P, A5P) Noise filter (with surge absorber)


C507

WHT WHT
M2C 3~

WHT
V1R

V
+

RED F401U RED + + RED


U

Connector for optional accessories


A5P

E1

X601A

X10A Connector (drainpan heater)


A6P
GRN

P1

P2
Z9C
N=2

WHT
X37A Connector (power adapter)
L2R

WHT
X66A Connector (remote switching
Cool/heat selector)
N=1
T1A

NOTES
P11 RED

RED
N11 BLK

BLK
WHT
RED

BLU
BLK

1. This wiring diagram applies only to the outdoor unit.


P11

N11
X1M
L1
L2
L3
N

X5A

X5A

2.
X3A

: Field wiring, : terminal block, : connector, :terminal,


F101U

F101U
R24

R24

: protective earth (screw), : functional earth, : earth wiring,


HAP

HAP
X3A

+ +
X4A

X4A
-

: field supply, : pcb, : switch box, : option


V1R

V1R

3. When using the optional adapter, refer to the installation manual of the optional adapter.
A7P

A4P
X1A

X1A
50Hz
60Hz

4. For connection wiring to indoor-outdoor transmission F1-F2, outdoor-outdoor


Z3C
N=1

transmission F1-F2, outdoor-multi transmission Q1-Q2, refer to the installation manual.


Q1DI F3U
3N~ 380-415V

5. How to use BS1~3 switch. Refer to “service precaution” label on el. Compo. Box cover.
(note 9)

(note 9)
Power supply

X2A

X1A

6. When operating, don’t shortcircuit the protection devices (S1PH,S2PH)


3N~ 380V

7. Only for RYYQ model.


8. Only for RYYQ/RYMQ model.
M2F

M1F
MS

MS
L1
L2
L3

3~

3~
N

9. Connector X1A (M1F) is red, connector X2A (M2F) is white.


10. Colors: BLK:black, RED:red, BLU:blue, WHT:white, GRN:green.
11. Only for 14,16 class

2D117536C

28 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

11 External connection diagrams


11 - 1 External Connection Diagrams
RXYQQ8-20U Notes
RXYQ8-20U 1. All wiring, components and materials to be procured on-site must comply with the applicable legislation.

RXYTQ8-16UYF 2. Use copper conductors only

RYYQ8-20U 3. For details, refer to the wiring diagram attached to the outdoor unit.
11
RYMQ8-20U
4. Install a circuit breaker for safety.
5. All field wiring and components must be provided by an authorised electrician.
6. Unit has to be grounded in compliance with the applicable legislation.
7. The wiring shown is a general points-of-connection guide and is not intended to include all details for a specific installation.
8. Make sure to install the switch and the fuse to the power line of each equipement.
9. Install a main switch to control the multiple power sources that the various components of the system make use of.
10. The capacity of UNIT1 must be larger than that of UNIT2 when the power source is connected in series between the units.
The capacity of UNIT 2 must be larger than that of UNIT3 when the power source is connected in series between the units.
11. If there exists the possibility of reversed phase, loose phase or momentary blackout, or if the power goes on and off while the product is operating, attach a reversed
phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
12. Install an earth leakage circuit breaker.

Power supply
L1 L2 L3 N
< Power source is supplied to each outdoor unit
individually. > Power supply
L1 L2 L3 N
< Power source is connected in series between
the units. >
Main switch Outdoor units Main switch Outdoor units

2-wire cable 2-wire cable 2-wire cable 2-wire cable


Transmission line Transmission line Transmission line Transmission line
Unit 1 Unit 2 Unit 3 Unit 1 Unit 2 Unit 3
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
Switch Switch Switch Switch

Fuse Fuse Fuse Fuse

Power supply Power supply


L N L N

Main switch Main switch

2-wire cable
Transmission line
2-wire cable 2-wire cable 2-wire cable 2-wire cable 2-wire cable
2-wire cable 2-wire cable
2- wire cable Transmission line Transmission line
Transmission line Transmission line Transmission line Transmission line
Transmission line
Power line

2-wire cable L N L N L N L N L N L N L N L N

Power line Switch Switch Switch Switch Switch Switch Switch Switch
Fuse Fuse Fuse Fuse Fuse Fuse Fuse Fuse
2-wire cable
Power line
2-wire cable 2-wire cable
2-wire cable 2-wire cable 2-wire cable 2-wire cable 2-wire cable
Power line Power line
Power line Power line Power line Power line Power line

Indoor units Indoor units

3D 119 200

RXYQQ8-20U Notes

RXYQ8-20U 1. All wiring, components and materials to be procured on-site must comply with the applicable legislation.
2.Use copper conductors only
RXYTQ8-16U 3. For details, refer to the wiring diagram attached to the outdoor unit.

RYYQ8-20U 4. Install a circuit breaker for safety.


5.All field wiring and components must be provided by an authorised electrician.
RYMQ8-26U 6. Unit has to be grounded in compliance with the applicable legislation.
7.The wiring shown is a general points-of-connection guide and is not intended to include all details for a specific installation.
8. Make sure to install the switch and the fuse to the power line of each equipement.
9.Install a main switch to control the multiple power sources that the various components of the system make use of.
10.The capacity of UNIT1 must be larger than that of UNIT2 when the power source is connected in series between the units.
11. If there exists the possibility of reversed phase, loose phase or momentary blackout, or if the power goes on and off while the product is operating, attach a reversed phase
protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
12.Install an earth leakage circuit breaker.

Power supply
< Power source is supplied to each outdoor unit individually.
> Power supply
< Power source is connected in series between the units.
>
L1 L2 L3 N L1 L2 L3 N

Main switch Outdoor units Main switch Outdoor units


·2·-wire cable ·2·-wire cable
Transmission lin Transmission line
Unit ·1· e Unit ·2· Unit ·1· Unit ·2·
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
Switch Switch Switch
Fuse Fuse Fuse

Power supply PowerL Nsupply


L N

Main switch Main switch

·2·-wire cable
·2·-wire cable Transmission line
Transmission line ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable
·2·-wire cable Transmission lin Transmission lin Transmission line Transmission line Transmission line
Power line Transmission line
Power line
e e
L N L N L N L N L N L N L N L N
Switch Switch Switch Switch Switch Switch Switch Switch
Fuse Fuse Fuse Fuse Fuse Fuse Fuse Fuse
·2·-wire cable
Power line
·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable ·2·-wire cable
Power line Power line Power line Power line Power line Power line Power line

Indoor units Indoor units

3D119316

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 29


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

11 External connection diagrams


11 - 1 External Connection Diagrams
RXYQQ8-20U
RXYQ8-20U
RYYQ8-20U Notes

11 RYMQ8-20U 1. All wiring, components and materials to be procured on-site must comply with the applicable le
gislation.
RXYTQ8-16UYF
L1 L2 L3 N Power supply
2. Use copper conductors only
3. For details, refer to the wiring diagram attached to the outdoor unit.
Main switch
4. Install a circuit breaker for safety.
5. All field wiring and components must be provided by an authorised electrician.
6. Unit has to be grounded in compliance with the applicable legislation.
Outdoor unit

Switch 7. The wiring shown is a general points-of-connection guide and is not intended to include all details
for a specific installation.
L1 L2 L3 N
Fuse 8. Make sure to install the switch and the fuse to the power line of each equipement.
9. Install a main switch to control the multiple power sources that the various components of t
he system make use of.

Power supply 10. If there exists the possibility of reversed phase, loose phase or momentary blackout, or if the power g
oes on and off while the product is operating, attach a reversed phase protection circuit locally.

L N
Main switch Running the product in reversed phase may break the compressor and other parts.
11. Install an earth leakage circuit breaker.

2-wire cable
Transmission line

2-wire cable 2-wire cable 2-wire cable


Transmission line Transmission line Transmission line
2-wire cable
Power line

L N L N L N L N
Switch Switch Switch Switch

Fuse Fuse Fuse Fuse

2-wire cable 2-wire cable 2-wire cable 2-wire cable


Power line Power line Power line
Power line

Indoor unit
3D119317

30 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

12 Sound data
12 - 1 Sound Power Spectrum
REMQ5U
REYQ8U
RXYQQ8U
RXYQ8U
12
90 90
RXYTQ8UYF 85 NR90
RYYQ8U 80 NR85 80
RYMQ8U 75 NR80
70 NR75 70

65 NR70
Sound power level [dB]

60 60
NR65
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR10 NR15
NR5
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119528
RXYTQ10UYF

90 90

85 NR90
80 NR85 80

75 NR80
70 NR75 70

65 NR70
Sound power level [dB]

60 60
NR65
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR10 NR15
NR5
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = ·10E-6µW/m²·
Measured according to ISO 3744
3D119342

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 31


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

12 Sound data
12 - 1 Sound Power Spectrum
RXYTQ12UYF

90 90
12 85 NR90
80 NR85 80

75 NR80
70 NR75 70

65 NR70
Sound power level [dB]

60 NR65 60

55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR10 NR15
NR5
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = ·10E-6µW/m²·
Measured according to ISO 3744
3D119343
RXYTQ14YUF
90 90

85 NR90
80 NR85 80

75 NR80
70 NR75 70

65 NR70
Sound power level [dB]

60 60
NR65
55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR10 NR15
NR5
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = 10E-6µW/m²
Measured according to ISO 3744
3D119366

32 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

12 Sound data
12 - 1 Sound Power Spectrum
RXYTQ16UYF

95
12
90 90

85 NR90
80 NR85 80
75 NR80
70 NR75 70

65
Sound power level [dB]

NR70
60 NR65 60

55
NR60
50 50
NR55
45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0
NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
dBA = A-weighted sound power level (A scale according to IEC).
Reference acoustic intensity 0dB = ·10E-6µW/m²·
Measured according to ISO 3744
3D119368

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 33


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

12 Sound data
12 - 2 Sound Pressure Spectrum
REMQ5U
REYQ8U
RXYQQ8U
12 RXYQ8U 70 70
NR75

RXYTQ8UYF 65
NR70
RYYQ8U
60 60
RYMQ8U NR65

55
NR60

50 50
NR55
Sound pressure level [dB]

45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119521
RXYTQ10UYF

70 70
NR75

65
NR70

60 60
NR65

55
NR60

50 50
NR55
Sound pressure level [dB]

45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119344

34 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

12 Sound data
12 - 2 Sound Pressure Spectrum
RXYTQ12UYF

70 70
12
NR75

65
NR70

60 60
NR65

55
NR60

50 50
NR55
Sound pressure level [dB]

45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119345
RXYTQ14UYF

70 NR75 70

65
NR70

60 60
NR65

55
NR60

50 50
NR55
Sound pressure level [dB]

45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119365

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 35


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

12 Sound data
12 - 2 Sound Pressure Spectrum
RXYTQ16UYF
70 NR75 70

12 65
NR70

60 60
NR65

55
NR60

50 50
NR55
Sound pressure level [dB]

45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
3D119367

36 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

12 Sound data
12 - 3 Sound Pressure Spectrum Quiet Mode Level 1
REMQ5U
REYQ8-12U 65
NR70
RXYQQ8-12U
60 60 12
RXYQ8-12U NR65

RXYTQ8UYF 55
NR60

RYY8-12U 50 50
NR55
RYMQ8-12U
Sound pressure level [dB]

45
NR50

40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25

15 NR20
NR0 NR5 NR10 NR15

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119535

RXYTQ10-12UYF
70 NR75 70

65
NR70

60 60
NR65

55
NR60

50 50
NR55
Sound pressure level [dB]

45
NR50
40 40
NR45
35
NR40
30 30
NR35
25
NR30
20 20
NR25
15 NR20
NR0 NR5 NR10 NR15
10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: ·35·°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119346

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 37


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

12 Sound data
12 - 3 Sound Pressure Spectrum Quiet Mode Level 1
REYQ14-16U
RXYQQ14-16U 60
NR65
60

RXYQ14-16U
12 55 55
RXYTQ14-16UYF NR60

RYYQ14-16U 50
NR55
50

RYMQ14-16U 45 45
NR50
Sound pressure level [dB]

40 40
NR45

35 35
NR40

30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR0 NR5 NR10 NR15

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119538

38 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

12 Sound data
12 - 4 Sound Pressure Spectrum Quiet Mode Level 2
REMQ5U
REYQ8-12U 60
NR65
60

RXYQQ8-12U
RXYQ8-12U
55
NR60
55 12
RXYTQ8UYF 50
NR55
50

RYYQ8-12U 45 45
RYMQ8-12U NR50
Sound pressure level [dB]

40 40
NR45

35 35
NR40

30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR0 NR5 NR10 NR15

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119536
RXYTQ10-12UYF
60 60
NR65

55 55
NR60

50 50
NR55

45 45
NR50
Sound pressure level [dB]

40 40
NR45

35 35
NR40

30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR0 NR5 NR10 NR15

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: ·35·°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119347

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 39


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

12 Sound data
12 - 4 Sound Pressure Spectrum Quiet Mode Level 2
REYQ14-16U
RXYQQ14-16U 55 55
RXYQ14-16U NR60
12 RXYTQ14-16UYF 50 50
NR55
RYYQ14-16U
45 45
RYMQ14-16U NR50

40 40
Sound pressure level [dB]

NR45

35 35
NR40

30 30
NR35

25 25
NR30

20 20
NR25
NR20
15 15
NR5 NR10 NR15
NR0

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]

Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119539

40 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

12 Sound data
12 - 5 Sound Pressure Spectrum Quiet Mode Level 3
REMQ5U
REYQ8-12U 55 55
NR60
RXYQQ8-12U
RXYQ8-12U 50 50
12
NR55
RXYTQ8UYF
45 45
RYYQ8-12U NR50

RYMQ8-12U 40 40
Sound pressure level [dB]

NR45

35 35
NR40

30 30
NR35

25 25
NR30

20 20
NR25
NR20
15 15
NR5 NR10 NR15
NR0

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119537
RXYTQ10-12UYF
60 60
NR65

55 55
NR60

50 50
NR55

45 45
NR50
Sound pressure level [dB]

40 40
NR45

35 35
NR40

30 30
NR35
25 25
NR30
20 20
NR25
NR20
15 15
NR0 NR5 NR10 NR15

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: ·35·°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)
3D119348

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 41


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

12 Sound data
12 - 5 Sound Pressure Spectrum Quiet Mode Level 3
REYQ14-16U
RXYQQ14-16U 55 55
NR60
RXYQ14U-16U
12
RXYTQ14-16UYF 50
NR55
50

RYYQ14-16U 45 45
RYMQ14-16U NR50

40 40
Sound pressure level [dB]

NR45

35 35
NR40

30 30
NR35

25 25
NR30

20 20
NR25
NR20
15 15
NR5 NR10 NR15
NR0

10 10
63 125 250 500 1000 2000 4000 8000 dBA
Octave band centre frequency [Hz]
Notes
Data is valid at free field condition.
Data is valid at nominal operation condition.
dBA = A-weighted sound pressure level (A scale according to IEC).
Reference acoustic pressure 0 dB = 20 µPa
Data is valid under the following conditions
Cooling operation
Outdoor Ta: 35°C
Full load (maximum fan rps and maximum compressor rps for the dedicated low noise mode)

3D119540

42 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

13 Installation
13 - 1 Installation Method
RXYTQ-UYF

For single unit installation

For installation in rows For centralised group layout 13


Pattern 1 Pattern 1 Pattern 1
300 or more 300 or more 300 or more 300 or more
Front 500 or more

10 or more Front 10 or more 10 or more 20 or more Front 20 or more 10 or more 10 or more Front 20 or more 10 or more 10 or more Front 20 or more 10 or more 10 or more 20 or more 10 or more
500 or more 500 or more 500 or more Front
600 or more
900 or more

Pattern 2 100 or more Pattern 2 100 or more 10 or more Front 20 or more 10 or more 300 or more
10 or more 20 or more 10 or more
500 or more 10 or more 20 or more 10 or more Front 500 or more

50 or more 50 or more 50 or more


Pattern 2
Front 100 or more Front 100 or more 50 or more
500 or more 500 or more
100 or more Front 500 or more
100 or more

Pattern 3 Pattern 3 Wall height unrestricted


50 or more Front 100 or more 50 or more 50 or more Front 100 or more 50 or more
Wall height unrestricted 500 or more 500 or more Front 50 or more 50 or more
300 or more 300 or more 100 or more
600 or more

100 or more
50 or more Front 100 or more 50 or more
Front 400 or more Front __________ or more 500 or more 50 or more 100 or more 50 or more 50 or more Front 50 or more
200 or more 200 or more 100 or more 500 or more

Notes Unit mm

1. Height of the walls in case of patterns 1 and 2:


Front: 1500mm
Suction side: 500mm
Side: height unrestricted
The installation space shown on this drawing is based on cooling operation at 46°C (outdoor temperature).

2.If the design outdoor air temperature exceeds 46°C, provide a broader suction space than shown on the drawing.
3.When installing the units, select the pattern that best fits the available space.
Always keep in mind to leave sufficient space for a person to pass between unit and wall and for the air to circulate freely.
If more units are to be installed than are foreseen in the above patterns, your layout should take into account the possibility of air short circuits.

4. Provide sufficient space at the front to connect refrigerant piping (comfortably).


h2

Suction side
Front

h1
1500

Unit mm 500
3D096862A

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 43


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

13 Installation
13 - 2 Fixation and Foundation of Units
RXYTQ-UYF
Foundation bolt fixing method

13
Drain ditch
°

80
Smooth downgrade of about 1/50
60

AD AA AD AA
929
729

00 8
O1 0 80
X X When building a foundation on the ground When building a foundation on a concrete floor
Y ditch
100

Y ditch
10050 Drain ditch
Drain ditch

50
Smooth downgrade
of about 1/50

50
Y ditch AC AA Floor

AB
Cross section · X - X·

Nut Foundation bolt type: ·JA · For multi-unit installation


Spring washer Size: ·M12· Model AA AB AC AD
4 holes for anchor bolts RYYQ8-12U
Frame ·3· thread ridges or more RYMQ8-12U
RXYQ8-12U 766 992
RXYQQ8-12U
REMQ5T/REYQ8-12U
RXYTQ8U
REMA5A/REYA8-12A 113 185
75

RYMA5A/RXYA8-12A
RYYQ14-20U
RYMQ14-20U
RXYQ14-20U 1076 1076
RXYQQ14-20U
REYQ14-20U
RXYTQ10-16U
Notes REYA14-20A
RXYA14-20A
1. Provide a drain ditch around the foundation to drain water from the installation area.
2.The surface has to be finished with mortar. The corner edges have to be chamfered.
3. Build the foundation on a concrete floor or, if not possible, make sure the foundation surface has a rough finish.
4. Use a cement/sand/gravel ratio of 1/2/4 for the concrete, and a diameter of 10 mm for the reinforcement bars (approximately, 300mm intervals).
5.When installing the equipment on a roof, make sure to check the strength of the floor and take adequate water proofing
measures.
3D118459B

44 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

13 Installation
13 - 3 Refrigerant Pipe Selection
RXYTQ-UYF
VRV4
Middle East
Piping restrictions ·3/3·
13
System pattern Total Connection ratio
Allowed connection ratio (CR) Maximum allowed amount of connectable indoor
VRV DX Air handling unit
Other combinations are not allowed. Connection ratio units (·VRV,AHU·)
indoor unit (AHU)
Excluding ·EXV· kits
·VRV DX· indoor units only 50~130% Maximum ·64· 50~130% -
·VRV DX· indoor unit + ·AHU· (2) (1)
50~110% Maximum ·64· 50~110% 0~110%
Mix
·AHU· only (3) (2) (1) (4)
90~110% Maximum ·64· - 90~110%
Pair + multi
Notes
1. ·EKEXV· kits are also considered indoor units.
2. Restrictions regarding the air handling unit capacity
3. Pair AHU = system with 1 air handling unit connected to one outdoor unit
Multi AHU = system with multiple air handling units connected to one outdoor unit
4. In case of cooling-only use in the ·DAME· region, the allowed connection ratio is ·75~110·%.

About ventilation applications


I. ·FXMQ_MF· units are considered air handling units, following air handling unit limitations.
- Maximum connection ratio when combined with ·VRV DX· indoor units: ·CR ≤ 30·%.
- Maximum connection ratio when only air handling units are connected: ·CR ≤ 100·%.
For information on the operation range, refer to the documentation of the ·FXMQ_MF· unit.
II. ·Biddle· air curtains are considered air handling units, following air handling unit limitations:
For information on the operation range, refer to the documentation of the ·Biddle· unit.
III. ·EKEXV + EKEQ· units combined with an air handling unit are considered air handling units, following air handling unit limitations.
For information on the operation range, refer to the documentation of the ·EKEXV-EKEQ· unit.
IV. ·VKM· units are considered to be regular ·VRV DX· indoor units.
For information on the operation range, refer to the documentation of the ·VKM· unit.
V. Because there is no refrigerant connection with the outdoor unit (only communication F1/F2), ·VAM· units do not have connection limitations.
However, since there is communication via F1/F2, count them as regular indoor unit when calculating the maximum allowed number of connectable indoor units.

3D096859B
RXYTQ-UYF

VRV4
Middle East
Piping restrictions ·1/3·

Maximum piping length Maximum height difference


After first After first branch (for multi-
For the reference drawing, see Longest pipe Indoor-to-outdoor Indoor-to-indoor Outdoor-to-outdoor Total piping
branch outdoor)
page ·2/3·. length
(A+[B,J]) (B,J) (D) (H1) (2) (H2) (H3)
Actual / (Equivalent) Actual Actual / (Equivalent)
Single unit 165/(190)m 40m (1) 10/(13)m 50/(40)m (2) 30m 5m 1000m
Multi-combination 135/(160)m 40m (1) 10/(13)m 50/(40)m (2) 30m 5m 500m
Air handling Pair (4) 50/(55)m (3) - - 40/(40)m - - -
unit (AHU) Multi (5) 165/(190)m 40m 10/(13)m 40/(40)m 15m 5m 500m
Connection Mix 165/(190)m 40m 10/(13)m 40/(40)m 15m 5m 500m

Notes
1. An extension to up to ·90· m is possible if all of the following conditions are met:
a. The piping length between all indoor units and the nearest branch kit is ≤ 40m.
b. It is necessary to increase the size of the gas and liquid piping.
If the increased pipe size is larger than the pipe size of the main pipe, also increase the size of the main pipe.
c. When the piping size is increased, the piping length has to be counted as double.
The total piping length has to be within limitations.
d. The piping length difference between the nearest indoor unit to the outdoor unit and the farthest indoor unit to the outdoor unit is ≤ ·40·m.
2. An extension to up to ·90· m is possible without an additional option kit. Respect the following conditions:
-> If the outdoor units are positioned higher than the indoor units:
- Size up the liquid piping
For more information, refer to the installation manual.
- A dedicated setting on the outdoor unit is required.
For more information, refer to the installation manual.
-> If the outdoor units are positioned lower than the indoor units:
- 40~60m: Minimum connection ratio: ·80%·
- 60~65m: Minimum connection ratio: ·90%·
- 65~80m: Minimum connection ratio: ·100%·
- 80~90m: Minimum connection ratio: ·110%·
+
- Size up the liquid piping
For more information, refer to the installation manual.
- A dedicated setting on the outdoor unit is required.
For more information, refer to the installation manual.
3. The allowable minimum length is ·5· m.
4. Multiple air handling units (·AHU·)(·EKEXV· + ·EKEQ· kits).
5. Mix of air handling units (·AHU·) and ·VRV DX· indoor units.
6. If the equivalent piping length between is > ·90·m, size up the main liquid and gas piping.

3D096859B

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 45


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

13 Installation
13 - 3 Refrigerant Pipe Selection
RXYTQ-UYF
VRV4
Middle East
13 Piping restrictions ·2/3·
H3

B
A J
D

C
H1

EXV

H4
EXV K
H2

VRV indoor unit Air handling unit (AHU)

Air handling unit (AHU) VRV indoor unit


Notes
1. Schematic indication
Illustrations may differ from the actual appearance of the unit.
2. This is only to illustrate piping length limitations.
Refer to combination table ·3D096860· for details about the allowed combinations.

Allowed piping length Maximum height difference


·EXV· to ·AHU· ·EXV· to ·AHU·
(K) (H4)
Pair (1)
≤5m 5m
Air handling unit (AHU) Multi (2)
≤5m 5m
Connection Mix ≤5m 5m

Notes
1. Multiple air handling units (·AHU·)(·EKEXV· + ·EKEQ· kits).
2. Mix of air handling units (·AHU·) and ·VRV DX· indoor units. 3D096859B

46 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

14 Operation range
14 - 1 Operation Range
RXYTQ-U
UYF
Cooling
55
14
52
50
48
Heating
45
20
40

15 15.5
35

10
Pull-down operation range

30 Outdoor temperature [°C WB]


Outdoor temperature [°C DB]

25 5
Operation range

20

Operation range
Pull-down operation range
0

15
-5

10
-10
5

-15
0

-5 -20
14 28 27
10 15 20 25 30 10 15 20 25 30

Indoor temperature [°C WB] Indoor temperature [°C DB]


Notes
1. These figures assume the following operation conditions
Indoor and outdoor units
Equivalent piping length: 5m
Level difference: 0m

2. Depending on operation and installation conditions, the indoor unit can change over to freeze-up operation (indoor de-icing).

3. To reduce the freeze-up operation (indoor de-icing) frequency, it is recommended to install the outdoor unit in a location not exposed to wind.
4. Operation range is valid in case direct expansion indoor units are used.
If other indoor units are used, refer to the documentation of the respective indoor units.
5. : Unit operation is possible, but no guaranteed capacity

3D096861

VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF 47


VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF

15 Appropriate Indoors
15 - 1 Appropriate Indoors
RXYTQ-UYF

Recommended indoor units for ·RXYTQ*U* · outdoor units


15 ·· HP 8 10 12 14 16
4 x FXMQ50 5 x FXMQ50 6 x FXMQ50 7 x FXMQ50 8 x FXMQ50

For multi outdoor units ·>16HP·, the recommended amount of indoor units is the sum of the indoor units defined for a single
outdoor unit.

Appropriate indoor units for · RXYTQ*U*· outdoor units

Model name Class


FXAQ-A 15-20-25-32-40-50-63
FXAQ-PVER 20-25-32-40-50-63
FXCQ-A 20-25-32-40-50-63-80-125
FXDQ-A3 15-20-25-32-40-50-63
FXFQ-B 20-25-32-40-50-63-80-100-125
FXFSQ-ARVE 25-32-40-50-63-80-100-125-140
FXHQ-A 32-63-100
FXKQ 25-32-40-63
FXLQ 20-25-32-40-50-63
FXMQ-P7 50-63-80-100-125
FXMQ-P7H 50
FXMQ-PVE 140
FXMQ-NVE6 200-250
FXNQ-A 20-25-32-40-50-63
FXSQ-A 15-20-25-32-40-50-63-80-100-125-140
FXUQ-A 71-100
FXZQ-A 15-20-25-32-40-50
VKM-GB 50-80-100
VKM-GBM 50-80-100
FXMQ-MF 125-200-250
EKEXV 50-63-80-100-125-140-200-250-400-500
EKEXVA 50-63-80-100-125-140-200-250-300-350-400-450-500
3D128612B

48 VRV IV heat pump, for high ambient temperature regions • RXYTQ-UYF


Daikin Europe N.V. Naamloze Vennootschap · Zandvoordestraat 300 · 8400 Oostende · Belgium · www.daikin.eu · BE 0412 120 336 · RPR Oostende (Responsible Editor)

The present leaflet is drawn up by way of information only and does not constitute an
offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of
this leaflet to the best of its knowledge. No express or implied warranty is given for the
completeness, accuracy, reliability or fitness for particular purpose of its content and the
products and services presented therein. Specifications are subject to change without prior
notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in
EEDEN24 01/2024