Design of Plumbing Analysis Part 1
Design of Plumbing Analysis Part 1
College of Engineering
Mechanical Engineering Department
A.Y. 2022 – 2023
Barcelon, Valyrie A.
Cornelio, Marian A.
Lomerio, Jamaica M.
Malano, Joanna M.
Regoroso, Hannah Olivia
BSME 4A
Floor Plan 1
Tank Sizing 3
Basin 90 23
Sink 90 - 180 23 - 47
Urinal 110 29
WC 180 47
Ground Floor
Lavatory 3 90 270
Second Floor
Lavatory 6 90 540
3
Water Closet 6 180 1080
1252 Gallons
4
2. COLD WATER PIPE SIZING
Cold Water Distribution System and Booster Pump
Pipe Sizing Using WSFU Method
5
Calculations for Pipe Sizes according to Inside Diameter, 𝒅
We use Velocity Formula to find the appropriate PPR pipe sizes through trial and
error. To deduce the appropriate pipe sizes, we use the standard allowable inside pipe
diameter that will give the largest possible optimal velocity for cold water (V ≤ 8fps).
0.4084𝑞
𝑉=
𝑑2
Where 𝑞 = flow rate (gpm)
𝑑 = inside diameter (in)
For Number 1,
0.4084(38.4)
𝑉= = 6.1 𝑓𝑝𝑠
(1.606)2
6.1 fps ≤ 8 fps
For Number 2,
0.4084(23)
𝑉= = 5.7 𝑓𝑝𝑠
(1.283)2
5.7 fps ≤ 8 fps
For Number 3,
0.4084(20)
𝑉= = 7.8 𝑓𝑝𝑠
(1.024)2
6
7.8 fps ≤ 8 fps
For Number 4,
0.4084(16.4)
𝑉= = 6.4 𝑓𝑝𝑠
(1.024)2
6.4 fps ≤ 8 fps
For Number 5,
0.4084(13)
𝑉= = 5.1 𝑓𝑝𝑠
(1.024)2
5.1 fps ≤ 8 fps
For Number 6,
0.4084(9)
𝑉= = 5.7 𝑓𝑝𝑠
(0.803)2
5.7 fps ≤ 8 fps
For Number 7,
0.4084(5)
𝑉= = 5.0 𝑓𝑝𝑠
(0.638)2
5.0 fps ≤ 8 fps
For Number 8,
0.4084(4.5)
𝑉= = 4.5 𝑓𝑝𝑠
(0.638)2
4.5 fps ≤ 8 fps
For Number 9,
0.4084(3)
𝑉= = 3.0 𝑓𝑝𝑠
(0.638)2
3.0 fps ≤ 8 fps
7
Calculations for Pressure Drop per 100 ft, ∆𝑝
∆𝑝 = 0.433𝑓
∆𝑝 = 3.6255 𝑝𝑠𝑖
Use Excel functions to compute for the pressure drop per 100 𝑓𝑡 of number 2 - 9.
At 40 gpm, 27 psi (62.3 ft) = 151.4 L/min and 18.99 m, use 1.5 hp
8
9
10
3. WATER PUMP SIZING DESIGN (PRESSURE TANK AND PUMP)
0.4084(45𝑔𝑝𝑚)
7.1254fps = 1.606²
1
Pipe Size = 1 𝑖𝑛 (1.606 in. inside diameter)
2
11
Computing for the Pressure Drop
100 1.85 𝑞1.85
𝑓 = 0.2083 ( ) × 4.8655 ; 𝐶 = 150
𝐶 𝑑
100 1.85 451.85
𝑓 = 0.2083 ( ) ×
150 1.6064.8655
𝑓 = 11.2282 psi
∆𝑝 = 0.433𝑓
∆𝑝 = 0.433(11.2282)
∆𝑝 = 4.8618 𝑝𝑠𝑖
Pressure drop = 4.8618 𝑝𝑠𝑖 𝑝𝑒𝑟 100 𝑓𝑡
Elbows: 6 elbows × 4 ft = 24 ft
Gate Valves: 4 gate valves × 1.1 ft = 4.4 ft
Check Valve: 15 ft
Strainer: 20 ft
4.8618𝑝𝑠𝑖
𝑇𝐷𝐻 = 19.6850𝑓𝑡 × 0.433 + ( ) (35.7716 𝑓𝑡 + 24𝑓𝑡 + 𝑓𝑡 + 15𝑓𝑡 + 20𝑓𝑡) =
100𝑓𝑡
12
13
14
Pressure Tank
Calculated Tank Volume = 243.24
Drawdown = 90
Residential Tank Recommendation = 2x-WX-302
Volume = 258
Recommended Precharge = 18 psi
15
4. DRAINAGE AND VENT PIPING DESIGN
GROUND FLOOR
Washing Machine 3 2 6
Lavatory 3 1 3
Kitchen Sink 3 2 6
Shower 3 2 6
Water Closet 3 3 9
Laundry Sink 3 3 9
SECOND FLOOR
Lavatory 6 1 6
Shower 6 2 12
Water Closet 6 3 18
TOTAL 75
16
Note: Septic tank sizes include sludge storage capacity as noted in Table B-2.
Inside Dimension with 100 mm wall thickness plus 300 mm free board
𝐻 = 0.3 + 1.8 = 2.1 𝑚
𝑊 = 2.01 𝑚
𝐿 = 2.01 + 0.1 + 2.2 = 4.31 𝑚
Actual Volume of inlet compartment = 2.01 × 2.01 × 1.8 = 7.272 m3
Second compartment = 0.5 × (1.8 − 0.05) × 2.2 × (2.01 − 0.1) = 3.677 m3 > 1.0 m3
Third compartment = 0.5 × (1.8 − 0.05 − 0.05) × 2.2 × (2.01 − 0.1) = 3.572 m3 > 1.0 m3
Actual Capacity = 7.272 + 3.677 = 10.949 m3 > 10.8819 m3
10.949 𝑚3
(1/3) of Actual Capacity = 3
= 3.65 m3 > 3.54 m3 ok.
17
6. STORM DRAINAGE DESIGN
The roof slopes at 2% from the center towards the edges in both directions, creating a
gentle downward gradient. Since the slope divides the roof into two symmetrical halves, we
can calculate the area for each side by dividing the total roof area in half.
Equivalent Roof Area = 10.8 𝑚 × 14.6 𝑚 = 157.68 𝑚2
157.68 𝑚2
Ah = = 78.84 𝑚2
2
Av = 0.02Ah = 1.5768 𝑚2
𝐴𝑣
𝐴 = 𝐴ℎ +
2
1.5768𝑚2
A = 78.84 𝑚2 + = 79.6284 𝑚2
2
𝐴 = 79.6284 𝑚2 = 857.11 𝑓𝑡 2
For Manila, Philippines, a rainfall intensity of 102 mm per hour (4 in per hour) is used.
18
The rate of discharge from any collection area is dependent upon the size of the area and
the maximum rate of rainfall per hour.
Using 4 𝑖𝑛/ℎ𝑟 rate of rainfall it can be shown that 1 𝑔𝑝𝑚 = 24 𝑓𝑡 2 of horizontal surface.
or
2.25 𝐿/𝑠
Use = 1.5 𝑜𝑟 2 minimum Roof Drains/Downspout
1.5 𝐿/𝑠
19