Datasheet IPR200 R1.0
Datasheet IPR200 R1.0
www.eaetechnology.com R1.0
• The compact KNX IP Router 200 allows forwarding of telegrams between different lines
through a LAN (IP) as a fast backbone. In addition this device is suited to connect a PC to
the KNX network e.g. for ETS programming.
• The IP address can be obtained by a DHCP server or by manual configuration (ETS)
respectively. This device works according to the KNXnet/IP specification using the core,
the device management, the tunneling and the routing part.
• The KNX IP Router 200 has an extended filter table for main group 0..31 and is able to
buffer up to 150 telegrams. Power is supplied via the KNX bus.
Technical Data
Power supply : - Bus DC 21…30V SELV
- KNX Bus Approx. 15 mA
- IP Line RJ45 socket
Connections - KNX Line Bus connection terminal
- 10BaseT 10Mbit/s
Ethernet - Supported internet protocols ARP, ICMP, IGMP, UDP/IP, DHCP and Auto IP
- Up to 5 KNXnet/IP Tunneling connections simultaneously
- Medium IP/TP
- Extended filter table for main group 0 ..31
KNX - Interface protocols : cEMI
- Max. APDU length: 55
- Device model: 0x091A
- LED KNX (Multicolor)
- LED Mode (Multicolor)
Display elements - LED IP (Multicolor)
- LED RED for program. mode
Operating elements - 2 Function button, programming button
Installation - DIN rail mount
Type of protection - IP 20 EN 60 529
- Operation -5° C + 45° C
Temperature range - Storage -25° C + 70° C
Humidity %5 to 93 % no moisture condensation
Dimensions - Width W in units (18 mm modules)
Weight - 40 g
Box - Housing: plastic (PC)
▪ EMC directive 2014 / 30 / EU ▪ EN 50491-5-1: 2010
▪ RoHS directive 2011 / 65 / EU EN 50491-5-2: 2010
▪ EN 63000: 2018 EN 50491-5-3: 2010
CE ▪ EN 61000-6-2: 2019
EN 63044-3: 2018
EN 61000-6-3: 2007 + A1: 2011
R1.0
©EAE Technology www.eaetechnology.com
Datasheet IPR200
EAE KNX IP Router
Connection Example
Scale Drawing
R1.0
©EAE Technology www.eaetechnology.com