Chap 11
Chap 11
ELEVEN
COMPRESSORS
205
206 REFRIGERATION AND AIR CONDITIONING
t
t
The compressor in Fig. 11-1 has 16 cylinders, 2 in each of the heads. During the
suction stroke of the piston, low-pressure refrigerant gas is drawn in through the
suction valve, which may be located in the piston or in the head. During the discharge
stroke the piston compresses the refrigerant and then pushes it out through the dis-
charge valve, which is usually located in the cylinder head.
Following the trend of most rotative machinery, the operating speed of com-
pressors has generally increased in the past 20 years. From the slow speeds of early
compressors of about 2 or 3 r/s, the speeds have increased until compressors today
operate at speeds as high as 60 r/s.
Figure 11-2 Cutaway view of a hermetically sealed compressor. (Carlyle Compressor Company,
Carrier Corporation.)
suction and discharge fittings and electric terminals. Moisture in the system can be
damaging to the motor; therefore dehydration of hermetic units before charging is
essential. On larger hermetically sealed units the cylinder heads are usually removable
'--· .
so that the valves and pistons can be serviced. This type of unit is called semihermetic.
11-3 Condensing units The compressor and the condenser of a system are conve-
niently combined into a condensing unit (Fig. 11-3). The motor, compressor, and con-
denser may be compactly mounted on the same frame and located remotely from the
expansion valve and evaporator.
11-5 Volumetric efficiency Volumetric efficiencies are the bases for predicting per-
formance of reciprocating compressors. Two types of volumetric efficiencies will be
208 REFRIGERATION AND AIR CONDITIONING
Figure 11-3 Compressor and condenser combined into a condensing unit. (The Trane Company.)
considered in this chapter, actual and clearance. The actual volumetric efficiency
11va is defined by
volume flow rate entering compressor, m 3 /s
11 = X 100 (11-1)
va displacement rate of compressor, m3 /s
where the displacement rate is the volume swept through by the pistons in their suction
strokes per unit time.
Clearance volumetric efficiency depends on the reexpansion of gas trapped in the
clearance volume and can be best explained by showing a pressure-volume diagram of a
compressor, as in Fig. 11-4. The maximum volume in the cylinder, which occurs when
the piston is at one end of its stroke, is V 3 . The minimum volume, or clearance volume,
is Ve, which occurs at the other end of the piston stroke. The discharge pressure is Pd·
In the first instance, assume that the suction pressure is p 1 . Gas trapped in the
clearance volume must first expand to volume V 1 before the pressure in the cylinder is
low enough for the suction valves to open and draw in more gas. The volume of gas
drawn into the cylinder will be V 3 - V 1 , and the clearance volumetric efficiency 11vc
for this case is (V3 - V1 ) {100)/(V3 - Ve). When the suction pressure isp 2 , the intake
portion of the stroke is reduced to V 3 - V 2 . In the extreme case where the suction
pressure has dropped to p 3 , the piston uses its entire stroke to reexpand the gas in the
clearance volume and the clearance volumetric efficiency is O percent.
The clearance volumetric efficiency can be expressed in another way, illustrated in
Fig. 11-4 using p 1 as the suction pressure. The percent clearance m, which is constant
for a given compressor, is defined as
m= Ve 100 (11-2)
V3 -VC
COMPRESSORS 209
~.
a..
Q)
---
I-<
;:j
en
en
' (I)
I-< P,
a..
P2
VC
Volume in cylinder, m 3
V-V+V-V
3 V-V
rJ = e e l 100 = 100 + e l 100 (11-3)
ve V - V V - V
3 e 3 C
and
f'/
VC
= 100 - V l - VC 100 = 100 -
V - V
VC
V - V V
_l - 1 100 (V
3 C 3 C C
Therefore Tl
VC
= 100 - m (V V
1- ,
{11-4)
C
V
_1 = sue
V
{11-5)
Ve vdis
where vsue = specific volume of vapor entering compressor
v dis= specific volume of vapor after isentropic compression to pd
Values of the specific volumes are available from the pressure-enthalpy diagram of the
refrigerant or from tables of properties of superheated vapor.
210 REFRIGERATION AND AIR CONDITIONING
90
80
>-
u
C: 70 f
·c:;
-
Cl)
t.;:
Vl
"
4--,
Cl) 60 00
u
·c
...... 0
i r
Cl)
50 C:
E c...
::i 0
0
>
Cl)
u
C:
40 -""'
er.
V)
Ii
ti:
cO :';I
""' 30 2
,:)
u
20
IO
Figure 11-5 Clearance volumetric efficiency and mass rate of flow of ideal compressor, Refrigerant
22, 4.5 percent clearance, 50 L/s rate of displacement, and 35°C condensing temperature.
11
vc
= 100 - m(vsuc
V
- 1~ (I 1-6)
dis
11-6 Performance of the ideal compressor In the ideal compressor, the compression of
the gas and the reexpansion of gas trapped in the clearance volume are both isentropic.
The reexpansion of the trapped gas is the only factor which influences volumetric ef-
fiency in the ideal compressor.
In the next few pages the effect of suction pressure on the performance of an
ideal compressor will be studied. Figure 11-5 shows the effect of evaporating tempera-
ture on clearance volumetric efficiency. The volumetric efficiencies are calculated from
Eq. (11-6) and apply to a refrigerant 22 compressor with a clearance of 4.5 percent
operating with a condensing temperature of 35°C. The clearance volumetric efficiency
is zero when the evaporating temperature is -61 °C, at which temperature the satura-
tion pressure corresponds to p 3 in Fig. 114. When the suction pressure and discharge
pressure are the same (same evaporating and condensing pressure), the volumetric
efficiency is 100 percent.
The mass rate of flow controls the capacity and power requirement more directly
than the volume rate of flow. The mass rate of flow, w kg/s, through a compressor is
proportional to the displacement rate in liters per second and the volumetric efficiency
and inversely proportional to the specific volume of gas entering the compressor. In
COMPRESSORS 211
'
-
- --·
equation form
- 11 /100
w = displacement rate X _vc_ _ (11-7)
vsuc
Using Eq. {11-7) and an assumed rate of displacement of 50 L/s, the mass rate of
flow can be calculated and plotted as done in Fig. 11-5. As the suction pressure drops,
the specific volume entering the compressor increases, which, together with the·
volumetric efficiency, reduces the mass rate of flow at low evaporating temperatures.
11-7 Power requirement The power required by the ideal compressor is the product
of the mass rate of flow and the increase in enthalpy during the isentropic compression,
P= w !lh.l (11-8)
where P = power, kW
w = mass rate of flow, kg/s
b,.hi = isentropic work of compression, kJ/kg
Figure 11-6 shows the variation in t:Jzi as the evaporating temperature changes. The
20 80
-bl)
...,
cf
0
·-·--J
15 60 ·;;;
Cll
.... I-<
0.
E
0
0 (.)
t.-.
0
10 40 I-<
0
5 20
O'--~L-~..J-~_...~--.~__.~----~--~....._~--~_._--......
-60 -40 -20 0 20 40
Evaporating temperature, °C
Figure 11-6 Work of compression and power required by an ideal compressor, Refrigerant 22, 4.5
percent clearance, 50 L/s displacement rate, and 35°C condensing temperature.
212 REFRIGERATION AND AIR CONDITIONING
value of ~h; is large at low evaporating temperatures and drops to zero when the
suction pressure equals the discharge pressure_ (when the evaporating temperature
equals the condensing pressure). The curve of the power requirement in Fig. 11-6
therefore shows a zero value at two points, where the evaporating temperature equals
the cor.densing tel1' .i:Jerature and where the mass ra~e of flou, is zero. Between the two
extremes the power requirement reaches a peak.
The power curve merits close attention because it has important implications. •
Most refrigeration systems operate on the left side of the peak of the power curve.
During the period of pulldown of temperature following start-up with a warm evapo-
rator, however, the power requirement passes through its peak and may demand more
power than the motor, which is selected for design conditions, is capable of supplying
steadily. Sometimes motors have to be oversized just-to take the system down through
the peak in the power curve. To avoid oversizing the motor, the suction pressure is
sometimes reduced artificially by throttling the suction gas until the evaporator pres-
sure drops below the peak in the power curve.
During regular operation heavy refrigeration loads raise the evaporating tempera-
ture, which increases the power requirement of the compressor and may overload the
motor.
b
"
400 200 i/f,
ii'
M-
OJ) •
.....>-
·c:; 300 150
---
,_, •
,ii
.._."
CIS (.)
0.
CIS
(.) t.-.
Q)
OJ)
.s
.....
OJ)
.s
CIS .....
i...
Q)
OJ)
CIS
i...
Q)
..
;E 200 100 OJ)
;E .
,.
Q)
Q)
Refrigerating capacity
100 50
Evaporating temperature, °C
Figure 11-7 Refrigerating effect and capacity of ideal compressor, Refrigerant 22, 4.5 percent
clearance, 50 L/s rate of displacement, and 35°C condensing temperature.
COMPRESSORS 213
11-9 Coefficient of performance and volume flow rate per kilowatt of refrigeration
The coefficient of performance can be derived from the refrigerating capacity of Fig.
11-7 and the power from Fig. 11-6. The result, displayed in Fig.· 11-8, shows a progres-
sive increase as the evaporating temperature increases. The volume flow rate per unit
refrigeration capacity is an indication of the physical size or speed of the compressor
20 4
Volume flow per unit capacity
a:
(I)
u
c::
ro
-"'
,-...l
E .....
·c:;
I-<
0 15 3
'I-<
- ro
0..
---· (I) ro
0.. u
'- .....
0
.....
·2
:l
c::
(I) I-<
·u
;;:: Coefficient of performance
(I)
0..
'- 10 2
(I)
0
0 C
u (I)
E
.2
0
>
5 I.
._____..._____.___~---------'-----...-----------.._-------------0
-60 --40 -20 0 20 40
Evaporating temperature, °C
Figure 11-8 Coefficient of performance and volume flow per kilowatt of refrigeration for ideal
compressor, Refrigerant 22, 4.5 percent clearance, 50 L/s displacement rate, and 35°C condensing
tern per a ture.
214 REFRIGERATION AND AIR CONDI'fIONING
100
90
80
-
>,
u
c::
C1)
70 VJ
·c:; 00
e 60
C1)
u 'i
0
·t:
..... c::
E
(1)
so 0
0
::s ....ro
C1)
,
> 40 I-<
C1) en f
u en
c:: ro
ro
I-<
ro 30
v
20 0.2
IO
0 80 0.1
-20 0 20 40 60
Condensing temperature, °C
Figure 11-9 Volumetric efficiency and mass rate of flow of refrigerant for an ideal Refrigerant 22
compressor, 4.5 percent clearance, 50 L/s displacement rate, and -20°C evaporating temperature.
100 200
>,
.-=!
'J
C'l
c..
:':I
75 150
- 00
......
.....
u
OJ) <+-,
.5
_,
(1)
:-::1 00
I,..
:':)
.5
.....ro
-~ 50 100
...::
(lJ
I-<
(1)
00
0::: J:C1)
0:::
25 50
o--~--~~.__~. . . . ~--.__~--~----..__~--~-----~--~--~---
-20 0 20 40 60 80
Condensing temperature, °C
Figure 11-10 Refrigeration effect and refrigerating capacity for an ideal Refrigerant 22 compres-
sor, 4.5 percent clearance, 50 L/s displacement rate, and -20°C evaporating temperature.
COMPRESSORS 215
11-10 Effect of condensing temperature Most refrigerating systems reject heat to the
atmosphere, and the ambient conditions change throughout the year. Process re-
frigeration plants that operate year round are particularly subject to a wide range of
condensing temperatures. The response of a reciprocating compressor to changes in
condensing temperature can be analyzed similarly to the evaporating temperature.
Figure 11-9 shows the clearance volumetric efficiency as calculated from Eq. (11-6)
for a compressor with an evaporating temperature of -20°C. As the condensing tem-
perature increases, the volumetric efficiency drops off. Because the specific volume
of the refrigerant at the compressor suction remains constant, only the volumetric
efficiency affects the mass rate of flow, which shows a corresponding decrease as the
condensing temperature increases. Figure 11-10 shows such a progressive decrease.
The refrigerating capacity is the product of the refrigerating effect and the mass rate
of flow, both of which decrease with increasing condensing temperature. The result
is that the refrigerating capacity drops rather rapidly on an increase in condensing
temperature.
The remaining important characteristic is the power, shown on Fig. 11-11. The
100 20
-
00
...... 80 16
' - i::
·enen0
(1)
s-
0..
E 60 12 ..:
0 (1)
u
0
0 p..
s-
0
40 8
Work of compression
20 4
0
-20 0 20 40 60
Condensing temperature, °C
Figure 11-11 Work of compression and compressor power for an ideal Refrigerant 22 compressor,
4.5 percent clearance, 50 L/s displacement rate, and -20°C evaporating temperature.
216 REFRIGERATION AND AIR CONDl110NING __ ,
compressor power is the product of the work of compression in kilojoules per kilo-
gram and the mass rate of flow. The work of compression in kilojoules per kilogram
increases and the mass rate of flow decreases as the condensing temperature increases,
so that the power increases to a peak and then begins to drop off, a trend similar to
~he pow~r as a functbn of the evaporating temperat"Jre shown in Fig. 11-6.
A few comments on the significance of the trends in Figs. 11-9 to 11-11 follow.
The peaking of the power can occur in real compressors as well as the ideal ones, but •
only when pumping from low evaporating temperatures. Single-stage compression
from -20°C evaporating temperature to a 60°C condensing temperature, which resulted
in the peak in Fig. 11-11, is not common. With more moderate differences between
the condensing and evaporating temperatures the expectation is that the power re-
quired by the compressor will increase with an increase in condensing temperature,
although the increase may be slight. The refrigerating capacity always decreases with
an increase in condensing temperature. Another important characteristic, not shown
on the graphs, is the coefficient of performance, which decreases monotonically as the
condensing temperature increases.
From the standpoint of power and efficiency, a low condensing temperature is
desirable; thus the condenser should use the coldest air or water available, should
operate with the maximum airflow or water flow that is economical, and should have
its surfaces kept clean. Air or noncondensable gases in the condenser also cause high
condenser pressures.
All the calculations in Figs. 11-9 to 11-11 are based on a clearance volume of
4.5 percent. McGrath 1 pointed out that increasing the percent clearance from about
4 percent, which is customary, to about 15 percent will give a nearly constant power (Ii
90
80
70
»
0
c:: Actual volumetric efficiency
T,
C
G.> 60
<-.-
J V
50
') -~.........
s
V
40
-" ;::::s
0
--o.,,..:
> 30
20
10
0
2 3 4 5 6 7
Discharge-to-suction pressure ratio
Figure 11-12 Clearance and actual volumetric efficiency of a Refrigerant 22 high-speed compres-
sor. The clearance volume assumed for calculating the clearance volumetric efficiency is 4.5 percent.
where the works of compression are referred to the same suction and discharge pres-
sures. The compression efficiencies for open-type reciprocating compressors are usually
in the range of 65 to 70 percent. Some of the processes that reduce the compression
efficiency from its ideal value of I 00 percent are friction of rubbing surfaces and
pressure drop through valves.
Solution The state of the refrigerant leaving the evaporator and entering the com-
pressor is 5°C saturation temperature (pressure of 584 kPa) and a temperature of
13°C. At this state the following properties prevail: h = 413.l kJ/kg; v = 43.2
L/kg; and s = 1.7656 kJ /kg • K. Following an isentropic compression to a satura-
tion temperature of 50°C (pressure = 1942 kPa) the properties of the refrigerant
are h = 444.5 kl /kg and v = 14.13 L/kg. The enthalpy of the liquid leaving the
condenser and entering the evaporator is the enthalpy of liquid at 47°C = 259.1
kl/kg.
(a) The clearance volumetric efficiency is
43.2
100 - 4.8 ( - - - 1 = 90.1%
14.13
(b) The compressor displacement rate is
0.067 2 1T
(6 cyl) (29 r/s) (
4
m 3 /cyl • 'l (0.057) = 0.03497 m 3/s = 34.97 L/s
\
) I
)
COMPRESSORS 219 I
12. Ii
'-~ by the actual work of compression. The latter is
28.9 kW -
- - - = 46.2 kJ/kg
0.6260 kg/s
so that
444.5 - 413.1 kJ/kg
r,c= X 100=68%
46.2 kJ/kg
120
110
100
~-:::::....
u
0 90
....(I)
-e ::s
Q)
0..
80
70
- E
Q)
Q)
....tlO
ro
60
..c: 50
u {/)
0 40
30
20
10
0 10 20 30 40 50
Condensing temperature, °C
Figure 11-13 Discharge temperatures following isentropic compression from saturated vapor at
0°C.
220 REFRIGERATION AND AIR COND1r10NING
the evaporating temperature and pressure. This change in the evaporator condition re-
sults in reduced compressor capacity, which ultlmately matches the reduced refrigera-
tion load. The reduction in evaporator temperature may be undesirable for several
reasons. In air conditioning, the coil may collect frost and block the airflow, further
reducing the evapor..ltor pressure. Stored fresh food and many other products may be
damaged by low temperatures. If the evaporator chills a liquid, the liquid may freeze
and burst a tube in the evaporator.
Several methods are commonly used to reduce the compressor capacity:
I. In cycling the compressor stops and starts as needed. The method works well in
small systems.
2. Back-pressure regulation throttles the suction gas between the evaporato_r and the
compressor to keep the evaporator pressure constant. This method gives good
control of the evaporator temperature but is inefficient.
3. Bypassing the discharge gas back to the suction line usually affords precise ca-
pacity reduction, but the method is inefficient and the compressor often runs
hot. A preferred bypass circuit delivers the discharge gas that is bypassed back to
the entrance of the evaporator.
4. Another method is cylinder unloading on a multicylinder compressor by au to-
matically holding the suction valve open or diverting the discharge gas from a
cylinder back to the suction line before compression. In the compressor of Fig.
11-1 there are two horizontal lines carrying high-pressure oil from the oil pump
at the right end of the compressor to hold the suction valves open when the un-
loaders are activated. The loss in efficiency with cylinder unloading is moderate.
A step control may be provided which unloads more and more cylinders as the
suction pressure drops.
11-16 How the screw compressor functions A cross-sectional view of the two prin-
cipal rotating elements of the screw compressor is shown in Fig. 11-14. The male
rotor with four lobes, shown on the right, drives the female rotor in a stationary
housing. Figure 11-15 shows an exploded view of the major parts of the complete
0
Q
0
Figure 11-15 Exploded view of main elements of a screw compressor. (Sullair Refrigeration, Inc.)
compressor. The refrigerant vapor enters one end of the compressor at the top and
leaves the other end at the bottom. At the suction position of the compressor a void
is created into which the inlet vapor flows. Just before the point where the interlobe
space leaves the inlet port, the entire length of the cavity or gully is filled with gas. As
the rotation continues, the trapped gas is moved circumferentially around the housing
of the compressor. Further rotation results in meshing of the male lobe with the fe-
male gully, decreasing the volume in the cavity and compressing the gas. At a certain
point into the compression process the discharge port is uncovered and the com-
pressed gas is discharged by further meshing of the lobe and the gully.
The screw compressor was developed in the 1930s and first became popular for
refrigeration .service in Europe in the 1950s and 1960s. On some early compressors the
two rotors were geared to each other and no lubrication was provided between the ro-
tors. Current practice is to drive the female rotor with the male rotor and inject oil
between the two rotors for lubrication and sealing. In the package water chiller shown
in Fig. 11-16 the screw compressor is just to the right of the control panel, showing its
Figure 11-16 A water-chilling package that uses a screw compressor. (Dunham-Bush, Inc.)
222 REFRIGERATION AND AIR CONDITIONING
100
90
80
>-
0
c:: 70
<U
·u
......
I.;: 60
(I.\
c::
0 50
·;;;
en
G)
'"'
0.
40
E
u
0 30
20
10
0
2 3 4 5 6 7 8
Pressure ratio
Figure 11-17 Compression efficiencies of screw compressors of various built-in volume and pres-
sure ratios.
relatively small size compared with the condenser (in back) and the water-chilling
evaporator at the bottom. The vessel below the control panel is the oil separator, a
standard component in a screw-compressor system.
11-18 Capacity control Many screw compressors are equipped with a sliding valve for
capacity control. It is in the housing of the compressor and can be moved axially. As
the valve is opened, it delays the position at which compression begins. The capacity
can be modulated down to about 10 percent of full capacity, although there is loss of
efficiency in the capacity reduction.
11-19 Vane compressors The lwo basic-types-of vane -compressors are the roller or
single-vane type and the multiple-vane type. Vane compressors are used mostly in do-
,_:,/
:-)
? COMPRESSORS 223
?---
) ..
mestic refrigerators, freezers, and air conditioners, although they can also be used as
booster compressors in the low-pressure portion of large multistage compression sys-
tems. In the roller type (Figs. 11-18 and 11-19) the centerline of the shaft is the same
as the centerline of the cylinder. The centerline of the shaft, however, is located ec-
centrically on the rotor, so that as the rotor revolves it makes contact with the cylin-
der. The roller-type compressor has a spring-loaded divider which separates the suction
and discharge chambers.
(b)
(a)
:).
.:J
::)
0
Figure 11-21 A centrifugal compressor system. The condenser is the top vessel, and the water-
cooling evaporator is at the bottom. The two impellers of the two-stage compressor are driven by
an electric motor in the rear. (The Trane Company.)
11-22 Flash-gas removal A centrifugal compressor with two or more stages invites the
use of flash-gas removal. Flash gas can be removed by partially expanding the liquid
from the condenser, separating the flash gas, and then recompressing the gas instead of
dropping its pressure further. Flash-gas removal, discussed further in Sec. 16-2, in-
creases the efficiency of the cycle and is conveniently achieved when two or more
stages of compression are available.
High
speed
I
High efficiency
Low speed
tedly the air flowing through a fan was treated as an incompressible fluid while in the
centrifugal compre·ssor the refrigerant vapor is clearly compressed. The predominant
characteristic prevails in both machines, however, in that for a constant-speed com-
pressor as the flow rate starts at zero and increases, the pressure buildup developed by
the compressor starts at some nonzero value, increases for a time, and then progres-
sively drops off.
One choice of coordinates for presenting the characteristics is shown in Fig.
11-22: the discharge-to-suction-pressure ratio versus the flow rate. The graph shows ·•
the performance for several different compressor speeds and isoefficiency lines (lines
of constant efficiency). No performance curves are shown to the left of the surge line;
this surge phenomenon will be discussed in Sec. 11-26.
11-24 Tip speed to develop pressure A rough estimate of the tip speed of the impeller
can be made by using several fundamental relationships for turbomachinery. The
torque the impeller ideally imparts to the gas is
(11-11)
where T = torque, N • m
w = mass rate of flow, kg/s
V 2 t = tangential velocity of refrigerant leaving impeller, m/s
=
r 2 radius of exit of impeller, m
Vlt = tangential velocity of refrigerant entering impeller, m/s
r 1 = radius of inlet of impeller, m
If the refrigerant enters the impeller in an essentially radial direction, the tangential
COMPRESSORS 227
T= wVil2 (11-12)
:::- The power required at the shaft is the product of the torque and the rotative speed
(11-13)_
where P = power, W
. w = rotative speed, rad/s
At least at very low refrigerant flow rates the tip speed of the impeller and the tangen-
tial velocity of the refrigerant are nearly identical; therefore
r2w = v2t
and 2
P=wV2t (11-14)
Another expression for ideal power is the product of the mass rate of flow and the
isentropic work of compression,
P = w t::.\ (1 000 J /kJ) (11-15)
Equating the two expressions for power, Eqs. (11-14) and {11-15), yields
V~t = 1OOOt::.hi (11-16)
Although Eq. (11-16) is based on some idealizations, it can provide an order-of-
magnitude estimate of the tip speed and can also show important comparisons, as in
Example 11-2.
Example 11-2 Calculate the speed of the impeller tip in order to compress the
following refrigerants from saturated vapor at 10°C to a pressure corresponding
to a condensing temperature of 30°C when the refrigerant is (a) refrigerant 11 and
(b) ammonia.
11-25 Choice of impeller and refrigerant Two crucial impeller dimensions are the
wheel diameter and the width between impeller faces. The designer of a centrifugal
228 REFRIGERATION AND AIR CONDITIONING
compressor system must select a combination of these dimensions along with a choice
of refrigerant. The magnitude of the wheel diameter is heavily dictated by the dis-
charge pressure that must be achieved, because for a given rotative speed a large wheel
Jiameter will provide a higher tip speed, which results in a higher pressure ratio. The
results of Example 11-2 provide some insight into the influence of the refrigerant
choice on required tip speed. If a centrifugal compressor is driven by an electric motor
operating at 60 r/s, the wheel diameter needed for the 113.1 m/s tip speed (refrigerant •
11) is 0.6 m, while for the tip speed of 297 m/s with ammonia the wheel diameter
must be 1.58 m. The required wheel diameter for ammonia would probably be imprac-
tical. Furthermore, from the standpoint of strength of the wheel, the tip speed for
ammonia is nearing the usual limitation 3 of 300 m/s. E
The initial conclusion is to choose a refrigerant with properties similar to refriger- h
L
ant 11 in preference to ammonia. Centrifugal compressors could and do handle am- I
monia, but additional stages of compression might be required. For example, if the
compression in Example 11-2 were executed in two stages, the t::..hi could be cut in half
and the tip speeds of both wheels would be 210 m/s.
Another decision of the designer is the width of passage in the impeller. To in-
crease the capacity, increase the width between the faces of the impeller, which, of
course, also increases the power requirement. Centrifugal-compressor designers con- A
stantly struggle to maintain high efficiencies with machines of small capacity. One ,l
reason for the dropoff of efficiency with low capacities is that the impeller width !
1
becomes narrow and the friction of the gas on the impeller faces becomes large relative l
to the flow rate through the impeller. The choice of a low-density refrigerant allows
one to maintain a wide impeller width for a given capacity.
,3
Refrigerants 11 and 113 especially meet the requirements described above and are
1
the popular refrigerants used in water-chilling systems with centrifugal compressors.
But ammonia, refrigerant 12, and other refrigerants are used successfully with cen- t
_f'c•\
,:-
11-26 Surging Figure 11-22 shows no performance data to the left of the surge
envelope, although the classic performance of a backward-curved-blade pump, fan, and
compressor would be shown by the dashed line in Fig. 11-23. As the refrigeration load
drops off and the flow rate decreases from point A, the performance rides up the
pressure-flow characteristic to point B. Further decrease in flow rate sends the opera-
tion to point C where the pressure-ratio capability of the compressor drops. The drop
in pressure ratio is due both to the inherent characteristics of backward.-curved-blade
turbomachines and to the fact that flow separation begins occurring at the blades.
Although the compressor capacity drops significantly when operation moves to
point C the heat load on the evaporator continues to boil off refrigerant, building up
the evaporator pressure and decreasing the pressure ratio. The compressor is then
momentarily able to shift operation back to point A where the cycle begins to repeat
'··
itself. This sequence, called surging, is characterized by objectionable noise and wide
fluctuations_ of load on the compressor and motor. The period of the cycle is usually
2 to 5 s, depending upon the size of the installation.
One reason for not showing data to the left of the surge envelope is that steady-
<'t~tp readings cannot be obtained. Centrifugal fans (Chap. 6) have the same pressure-
--~
COMPRESSORS 229
-.
-..
.
flow characteristics as the compressor shown in Fig. 11-23 and are thus subject to the
same surge phenomenon. Many fans operate from time to time in the surge region,
however, and the only undesirable result is a low rumbling sound. In the case of cen-
trifugal compressors, however, operating in the surge region is definitely objectionable
and should be avoided. Some compressors are equipped with a discharge-gas bypass
that at low refrigeration loads throttles discharge gas back to the suction line in order
to provide a false load on the compressor.
11-27 Capacity control The two most efficient and most widely used methods of
capacity control are (1) adjusting prerotation vanes at the impeller inlet and (2) vary-
ing the speed. Two methods that are not efficient and not widely used are varying
the condenser pressure and bypassing the discharge gas. The latter was mentioned as
a means of preventing surge and is sometimes combined with prerotation vanes.
Equation (11-11) for the torque indicates that if a positive component is provided
.. for Vlt, the torque will be reduced, which also translates into reduced pumping capa-
bility. Pre rotation vanes provide a swirl to the gas entering the impeller so that the
i~let gas has a tangential velocity in the direction the impeller is rotating. Figure 11-24
shows how the position of the prerotation vanes influences the compressor character-
...
.s
ro
....
(I)
....
;:l
en
en
(I)
....
p..
t
s::: Open
...
.s
0
;:l 50°
...
en
0
t
oo 30°
15°
Closed
I
(I)
ro
..c:
0
en
a Figure 11-24 Centrifugal-compressor character-
istics at various settings of the prerotation
Flow rate vanes.
230 REFRIGERATION AND AIR CO~DITIONING
istics. The use of prerotation vanes is an efficient method of control when the vanes
are near their fully open position, but the va11es behave more like a throttling valve as
they approach their nearly closed position. The vanes are visible at the inlet of the im-
peller in the compressor shown in Fig. 11-21.
When a centrifugal compressor is driven by a steam or gas turbine, varying the
speed for capacity control can be achieved readily. Figure 11-22 shows that the ca-
pacity drops off at a given pressure ratio as the speed decreases.
11-28 How the various types of compressors share the field The four types of com-
pressors studied in this chapter, reciprocating, screw, vane, and centrifugal, all have
somewhat different qualities, so that each type has found a sphere of application
where it has advantages over the others. A reasonably accurate statement of where the
compressors are used can be based on their refrigerating capacity. Reciprocating com-
pressors dominate from very small refrigerating capacities to about 300 kW. Centrif-
ugal compressors are most widely used for units having refrigerating capacities of 500
kW and above. The screw compressor has found a niche in the 300-to-500-kW capaci-
ties and competes against large reciprocating compressors and against small centrifugal
compressors. The vane compressor competes against the reciprocating compressor
primarily in the market for domestic refrigerators and air conditioners.
Probably more reciprocating compressors are manufactured than any other type
because they are the choice for smaller refrigeration units in high production. For
high-capacity refrigeration systems, the large physical size ?f the reciprocating com-
pressor shifts the choice in favor of the more compact screw and centrifugal compres-
sors, which battle for the market in the 300- to 500-kW capacities. An uneasy truce
sometimes is arrived at in industrial refrigeration plants, where a combination of screw
and reciprocating compressors is used. The operating strategy is to use the screw com-
pressor for the base load and bring on reciprocating compressors to accommodate the
variations above the base. The reason for this distribution of load is that the screw
compressor is efficient when operating near full load, it has fewer moving parts than
the reciprocating compressor, and is developing a reputation for long operating life.
The reciprocating compressor seems to have better efficiencies at part-load operation
than the screw compressor and can accommodate the varying portion of the load
more efficiently.
The centrifugal compressor is the choice for large-capacity units, particularly
for water-chilling plants used for large air-conditioning installations. A feature of
most such installations is that air is cooled at a large number of locations remote from
the compressor room. Since using water as the heat-conveying agent in these cooling
coils is preferable to the complexities of delivering refrigerant, the .refrigeration unit
for most large air-conditioning plants is a water chiller. This concept coincides with
the characteristics of a centrifugal unit which uses low-density refrigerants. The suc-
tion and discharge pipes needed for the low-density refrigerant are of large diameter,
and it is impractical to run them large distances. Instead, they are closely coupled to
the water-chilling evaporator and the water-cooled condenser.
While it may seem that the market distribution of compressors may now be stable,
engineers should be alert to the potential for new compressor developments. The screw
compressor, for example, which was not a factor in the industry a few decades ago, has
now established itself.
COMPRESSORS 231
PROBLEMS
REFERENCES
Methods of Testing for Rating Positive Displacement Refrigerant Compressors, Standard 23-78,
American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Atlanta, Ga.,
1978.
W. D. Cooper: Refrigeration Compressor Performance as Affected by Suction Vapor Superheating,
ASHRAE Trans., vol. 80, pt. 1, pp.195-204, 1974.
J. Brown and S. F. Pearson: Piston Leakage in Refrigeration Compressors, J. Refrig., vol. 6, no. 5,
p. 104, September-October 1963.
232 REFRIGERATION AND AIR CONDITIONING