FDCI 0223 in po rab
FDCI 0223 in po rab
Legal notice
Technical specifications and availability subject to change without notice.
Issued by:
Siemens Switzerland Ltd.
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41 724-2424
www.siemens.com/buildingtechnologies
Edition: 2016-05-04
Document ID: 009122_h_en_--
2 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Table of contents
3 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
3.4.4.4 Control without confirmation ......................................... 43
3.4.4.5 Control with confirmation .............................................. 44
3.5 Diagnosis levels......................................................................................... 44
3.6 Behavior in degraded mode ....................................................................... 46
3.7 Accessories ............................................................................................... 47
3.7.1 Mounting foot FDCM291 ............................................................. 47
3.7.2 U-rail TS35 ................................................................................. 47
3.7.3 Housing FDCH221 ...................................................................... 47
3.7.4 Connection terminal DBZ1190-AB...............................................48
3.7.5 M20 x 1.5 metal cable gland ....................................................... 48
3.7.6 M20 x 1.5 metal counter nut ........................................................ 48
3.7.7 Cable ties 2.4 x 137 .................................................................... 49
3.7.8 End-of-line EOL22(Ex) ................................................................ 49
3.7.9 Voltage reference diode (transzorb diode) 1.5KE20CA (EOL) ..... 49
4 Planning ............................................................................................50
4.1 Compatibility .............................................................................................. 50
4.2 Defining the mounting site of the module and configuration of the lines ...... 51
4.3 Planning the detector line .......................................................................... 51
4.4 Planning the control line............................................................................. 51
4.5 Planning contact input ............................................................................... 51
4.6 Environmental influences ........................................................................... 51
4.7 Filling out the configuration sheet ............................................................... 51
5 Mounting / Installation ..........................................................................52
5.1 Mounting with housing ............................................................................... 52
5.2 Mounting in a fire control panel .................................................................. 54
5.3 Connecting input/output module................................................................. 55
6 Commissioning ...................................................................................57
6.1 Calibrating the control line ......................................................................... 57
7 Maintenance / Repair ..........................................................................58
7.1 Status query .............................................................................................. 58
7.2 Performance check.................................................................................... 58
8 Specifications .....................................................................................59
8.1 Technical data ........................................................................................... 59
8.2 Dimensions ............................................................................................... 64
8.3 Master gauge for recesses......................................................................... 65
8.4 Environmental compatibility and disposal ................................................... 65
9 Annex ................................................................................................66
9.1 Compatibility .............................................................................................. 66
9.2 Configuration sheets .................................................................................. 68
9.2.1 Planning the type of application, configuration overview .............. 68
9.2.2 Planning the detector line, configuration overview ....................... 68
9.2.3 Configuring the control line, configuration overview ..................... 69
9.2.4 Configuring the contact input, configuration overview .................. 69
Index .........................................................................................................70
4 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
About this document
Applicable documents
1
You can request the data sheet, mounting instructions, and technical manual for
FDCIO223 with a product version ES <50 via the Customer Support Center
(CSC).
Contact the CSC by phone on +49 89 9221-8000.
You will find information on how to ascertain the product version of your device in
chapter 'Product version ES [ 19]' of the technical manual.
Intended use
The input/output module FDCIO223 may only be operated on an FDnet/C-NET
detector line in an AlgoRex, SIGMASYS or FS20/FS720 fire detection system.
5 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
About this document
1 Applicable documents
Target groups
The information in this document is intended for the following target groups:
Document identification
The document ID is structured as follows:
ID code Examples
ID_ModificationIndex_Language_COUNTRY A6V10215123_a_de_DE
-- = multilingual or international A6V10215123_a_en_--
A6V10315123_a_--_--
Date format
The date format in the document corresponds to the recommendation of
international standard ISO 8601 (format YYYY-MM-DD).
6 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
About this document
Applicable documents
1
The 'i' symbol identifies supplementary information and tips for an easier way of
working.
7 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
About this document
1 Applicable documents
Please also observe the documentation for your fire detection system.
You will also find information about search variants and links to mobile
applications (apps) for various systems on the home page.
8 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
About this document
Technical terms and abbreviations
1
9 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
About this document
1 Revision history
The first edition of a language version or a country variant may, for example, be
version 'd' instead of 'a' if the reference document is already this version.
10 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
About this document
Revision history
1
The table below shows the published language versions with the corresponding
modification index:
X = published
– = no publication with this modification index
11 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Safety
2 Safety instructions
2 Safety
Battery Heat
Signal word
The signal word classifies the danger as defined in the following table:
NOTICE NOTICE identifies possible damage to property that may result from non-
observance.
12 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Safety
Safety instructions
2
WARNING
Nature and origin of the danger
Consequences if the danger occurs
Measures / prohibitions for danger avoidance
NOTICE
Nature and origin of the danger
Consequences if the danger occurs
Measures / prohibitions for danger avoidance
13 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Safety
2 Safety regulations for the method of operation
Electrical installations
WARNING
Electrical voltage
Electric shock
Work on electrical installations may only be carried out by qualified
electricians or by instructed persons working under the guidance and
supervision of a qualified electrician, in accordance with the electrotechnical
regulations.
Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
Lock volt-free areas to prevent them being switched back on again by mistake.
Label the connection terminals with external voltage using a
'DANGER External voltage' sign.
Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
Fit an easily accessible disconnecting device in accordance with IEC 60950-1
outside the installation.
Produce earthing as stated in local safety regulations.
CAUTION
Noncompliance with the following safety regulations
Risk of injury to persons and damage to property
Compliance with the following regulations is required.
14 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Safety
Safety regulations for the method of operation
2
15 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Safety
2 Standards and directives complied with
WARNING
Limited or non-existent fire detection
Personal injury and damage to property in the event of a fire.
Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
NOTICE
Incorrect planning and/or configuration
Important standards and specifications are not satisfied.
Fire detection installation is not accepted for commissioning.
Additional expense resulting from necessary new planning and/or configuration.
Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
16 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Overview
3
3.1 Overview
The input/output module FDCIO223 is operated on the FDnet/C-NET and has two
inputs/outputs. These can be configured as follows:
Collective detector line and conventional detector line
Control line
Contact input
The graphic below shows the integration of the module in the fire detection system.
I/O 1
I/O 2
DC 24 V
Figure 1: Input/output module in the FS20 or FS720 fire detection system
Properties
Connection of two collective detector lines or conventional detector lines to the
FDnet/C-NET
Connection of monitored or non-monitored contacts
Monitored control of equipment
Built-in line separator for the FDnet/C-NET
Compatible with AlgoRex, SIGMASYS, and FS20/FS720 fire detection systems
With safety barrier SB3, it is also possible to connect intrinsically safe collective
detectors (ex-zones 1 and 2)
Electrical isolation of primary and secondary sides:
FDnet/C-NET from I/O 1 and I/O 2
Not all fire detection systems support the functions named above. Please observe
the documentation for your fire detection system accordingly.
17 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Overview
Scope of delivery
1x input/output module FDCIO223
2x resistors 560 , 0.25 W
2x resistors 680 , 0.25 W
2x resistors 2.7 k , 0.25 W
2x resistors 3.3 k , 0.25 W
2x bidirectional voltage reference diodes (transzorb diodes) for terminating the
collective detector lines
2x mounting feet FDCM291 for installing the input/output module on a U-
rail TS35
2x jumpers for bridging the internal fuses
18 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Overview
3
ES
Figure 2: Example of a packaging label with details of the product version
04
ES
Depending on the product and various approvals, the product labels may differ in
terms of the information type and layout.
Look for your device's order number on the product label.
You will find the product version after the order number.
19 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Setup
3.2 Setup
The modules consist of the module carrier, the printed circuit board and the cover
cap. The printed circuit board includes several LEDs. The LEDs indicate the status
of the inputs and outputs and the operating condition of the modules.
The cover cap of the printed circuit board is transparent such that the statuses of
the LEDs are visible even when the housing is closed.
To protect the modules from environmental influences, they can be mounted in
housing FDCH221 (accessories).
3.2.1 Overview
2
3
1
2
4
1
2
Figure 4: Overview
1 Holes for securing the module 3 Push button for calibrating control
lines
2 Holders for cable ties 4 Holes for mounting feet FDCM291
See also
Housing FDCH221 [ 47]
20 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Setup
3
17
17 1
17 1
17
2
16 3a
16 3b
15
4
15
4
5
5
14
6
7
13
13
13 8
13
1 Terminals for ground connection of the module and for shielding of inputs/outputs 'I/O 1' and 'I/O 2' (black)
2 Jumper for ground fault monitoring of inputs/outputs 'I/O 1' and 'I/O 2'
10a LED for indicating the status of input/output 'I/O 1' (green)
10b LED for indicating the status of input/output 'I/O 1' (red)
11a 'PWR SEC' LED for indicating the status of the input/output module's secondary side
11b 'FAULT SEC' LED for indicating the status of the input/output module's secondary side
12a 'PWR PRIM' LED for indicating the status of the input/output module's primary side
12b 'FAULT PRIM' LED for indicating the status of the input/output module's primary side
21 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Setup
'FAULT PRIM'
off t
0 1 2 3 4 5 6 7 8 9 10 11 12 [s]
'FAULT PRIM'
flashes yellow t
every four 0 1 2 3 4 5 6 7 8 9 10 11 12 [s]
seconds
'FAULT PRIM'
flashes yellow t
every second 0 1 2 3 4 5 6 7 8 9 10 11 12 [s]
'FAULT PRIM'
flashes yellow t
every second 0 1 2 3 4 5 6 7 8 9 10 11 12 [s]
and flashes
yellow twice
every four
seconds
¹ The 'PWR PRIM' and 'FAULT PRIM' LEDs do not flash in sync in test mode
22 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Setup
3
'FAULT SEC'
off t
0 1 2 3 4 5 6 7 8 9 10 11 12 [s]
See also
Printed circuit board view [ 21]
23 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Setup
One green (a) and one red (b) LED indicates the status of each input/output (LEDs
with position numbers 9a, 9b and 10a, 10b). Their meaning depends on how the
input/output is configured.
t
0 1 2 3 4 5 6 7 8 9 10 11 12 [s]
LED(b) off
t
0 1 2 3 4 5 6 7 8 9 10 11 12 [s]
24 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Setup
3
LED(b) off
t
0 1 2 3 4 5 6 7 8 9 10 11 12 [s]
25 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Setup
t
0 1 2 3 4 5 6 7 8 9 10 11 12 [s]
LED(b) off
t
0 1 2 3 4 5 6 7 8 9 10 11 12 [s]
See also
Printed circuit board view [ 21]
26 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Setup
3
Invert OFF 2
OFF
Normal ON ON
Adjust I/O 1 I/O 2 Fuse
27 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Setup
Jumper plugged in: The internal fuse of the input/output module is bridged
Jumper not plugged in: The internal fuse is active
28 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Function
3
3.3 Function
3.3.1 Overview
A distinction is made in terms of the function between the primary and secondary
sides of the FDCIO223 input/output module. The primary side represents the
connection to the FDnet/C-NET. Both inputs/outputs are triggered on the
secondary side.
The inputs/outputs can be used as follows:
Collective detector lines
Conventional detector lines
Control lines
Contact inputs
WARNING
The FDCIO223 outputs must not be used for extinguishing equipment.
Line separator
All FDnet/C-NET devices are equipped with a line separator.
The FDnet/C-NET device is equipped with electronic switches which isolate the
defective part in case of a short-circuit on the FDnet/C-NET detector line. The rest
of the detector line remains serviceable. On a loop line, all FDnet/C-NET devices
remain fully functional after a single short-circuit.
29 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Function
NOTICE
No fusing of the 24 V power supply on the input/output module
Damage to the device due to nominal currents >2 A
To safeguard the device, the 24 V power supply must be protected with a fuse
of max. 2 AT.
The currents for both control lines are provided by the 24 V supply directly.
The control lines can be operated either with 2x 1 A or 1x 1.5 A. Therefore,
each control line must be protected with a fuse of max.1 AT or 1.5 AT,
depending on its configuration (internal fuses up to max. 0.7 AT).
The external power supply for the input/output module FDCIO223 must be
ungrounded and should feature short-circuit monitoring.
The external power supply must be monitored.
It is not necessary to use electrically isolated power units, as the supply is
already electrically isolated in the input/output module FDCIO223.
The fire control panel's power supply can be used.
Also observe the information in chapter 'Using two detector lines simultaneously
32]'.
Normal operation
The input/output module FDCIO223 is running in intended operation. The inputs
are monitored and evaluated. The outputs can be triggered.
Test/inspection
With test mode/inspection mode, the input/output module functions according to
how the input/output and fire control panel are configured.
Activation of the outputs in test mode/inspection mode will merely be signaled by
means of LEDs on the input/output module.
If the input/output module FDCIO223 is operated with a control panel FC20xx or
FC72x, no control outputs will be triggered in the event of activation of these
control panels in test mode/inspection mode. The input/output module FDCIO223
itself does not switch to test mode/inspection mode in this case. LEDs 12a and 12b
do not indicate any status.
30 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Function
3
Localization
To enable clear identification, the input/output module FDCIO223 can be set to
localization mode from the control panel. Localization mode is signaled by the
yellow LED (12b) for the primary side status display.
See also
Input/output module status display [ 22]
Printed circuit board view [ 21]
NOTICE
Ground fault monitoring is switched off with outputs activated.
See also
Adjustment elements [ 27]
Connection of intrinsically safe detectors in ex-zone 1
36]
31 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Input/output configuration options (secondary side)
You will find information on configuring the input/output module with the software
for the fire detection system in document 009078 for fire control panels FC20xx
and document A6V10210424 for fire control panels FC72x.
You will find more detailed information in the fire detection system documentation.
See also
Applicable documents [ 8]
32 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Input/output configuration options (secondary side)
3
33 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Input/output configuration options (secondary side)
FDM1101A-Rx MT320C
EOL RL
LINE LINE RA
RA
+ +
FDM1101A-Rx
EOL and RL are end-of-lines for a specific control panel.
You will find more specific information on using manual call points FDM1101A-Rx
and MT320 in documents A6V10201154 and 007904.
34 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Input/output configuration options (secondary side)
3
End-of-line (EOL)
One of the following must be used to terminate the detector line:
Bidirectional 20 V voltage reference diode (max. tolerance ±5 %); 1.5 kW pulse
power
EOL22(Ex); absolutely essential with intrinsically safe ex detectors on ex lines
above safety barrier SB3!
Non-assigned inputs/outputs do not require an end-of-line (EOL).
Circuit
A maximum of 32 detectors can be connected (KMK = 32).
FDCIO223 I/O
100 mAT
+
EOL
35 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Input/output configuration options (secondary side)
If two safety barriers SB3 are used, a maximum of 32 devices may be connected
in total.
NOTICE
Activated ground fault monitoring
Input/output module malfunction
If you are using safety barrier SB3, deactivate ground fault monitoring on the
input/output module.
Circuit
FDCIO223 I/O
SB3 EOL22(Ex)
Figure 7: Detector line circuit with intrinsically safe detectors in ex-zone 1+2
Safety barrier SB3 is always required when connecting intrinsically safe ex
detectors for zones 1 and 2.
An EOL22(Ex) end-of-line must always be used to terminate detector lines in
ex-zones 1 and 2.
You will find more information in document 001204.
See also
Applicable documents [ 8]
36 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Input/output configuration options (secondary side)
3
UL tR
tV
1 2 3 4
Figure 8: Alarm verification
The input/output module supports alarm response times (tR) of 0…255 seconds.
To avoid false alarms, transfer to the control panel can be delayed by means of a
setting. In theory, a delay time of 10…250 seconds can be set. However, in
practice the actual setting range will depend on the control panel and the alarm
response time. The permissible combinations should be selected when configuring
the system.
37 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Input/output configuration options (secondary side)
3.4.2.6 Monitoring
The input/output module monitors the detector line for the following criteria:
Alarm
Open line
Short-circuit
Ground fault (only both inputs/outputs jointly, no line-specific fault message)
Status inputs
Status inputs trigger a status change as soon as they are activated.
Danger inputs
Danger inputs trigger an alarm as soon as the input is activated.
Filter time
The statuses of the inputs are polled several times a second. The following
conditions apply to detecting a change in status:
The activation signal must be present for at least as long as the filter time (can
be set from 0.5…240 seconds).
The deactivation signal must be present for at least as long as the filter time but
for no more than 5 seconds.
The filter time is used to suppress interfering pulses.
Line monitoring
The input lines can be monitored for the following criteria:
Open line
Open line and short circuit
No monitoring
To facilitate this, resistors must be connected to the lines of the inputs. When a
short-circuit or open line occurs on one of the input lines, a fault message is
transmitted to the control panel.
38 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Input/output configuration options (secondary side)
3
Circuit
The graphic below shows the various circuit options available for contact inputs:
1 2 3 4
FDCIO223 I/O 40 mAT 2.7 k 560
+
2.7 k
3.3 k
3.3 k
680
560
Figure 9: Circuit for contact inputs
1…3 Monitoring for open line and 4 Monitoring for open line only
short circuit
39 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Input/output configuration options (secondary side)
3.4.4.1 Overview
Current limiting
Within the context of control, the secondary side external supply voltage (DC 24 V)
is applied directly to the relevant output for the control lines via a relay. In the
input/output module FDCIO223, internal fuses (0.7 AT self-resetting fuses: PTCs)
are present on the control lines.
Protect the contacts either with the internal fuses (max. 0.7 AT) or with fuses
provided by the customer (1 AT or 1.5 AT), coupled with bridging the internal fuses
to jumper 3 (see chapter 'Printed circuit board view [ 21]'). The jumper
configuration is described in chapter 'Adjustment elements [ 27]'.
The maximum current load of the outputs is 1 A if two outputs are used (2x 1 A) or
1.5 A (1x 1.5 A) if one output is used. These values apply to a maximum operating
temperature of 60 °C.
Monitoring
You have the option of monitoring the control line. Monitored control lines are
monitored for the following criteria:
Open line
Short-circuit
Ground fault (only both inputs/outputs jointly, no line-specific fault message)
To avoid false alarms, transfer to the control panel can be delayed by means of a
setting. In theory, a delay time of 0.5…240 seconds can be set. However, in
practice the actual setting range will depend on the control panel.
Control
Control is possible with or without confirmation. The various configuration options
are described in the next two sections.
See also
Calibrating the control line [ 57]
Control without confirmation [ 43]
Control with confirmation [ 44]
40 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Input/output configuration options (secondary side)
3
1 +
4V
0V R L = 30...3,3 k
0V
See also
Calibrating the control line [ 57]
Control without confirmation [ 43]
Control with confirmation [ 44]
Printed circuit board view [ 21]
Adjustment elements [ 27]
41 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Input/output configuration options (secondary side)
1 +
0V
10 V 3.3 k
0V
The figure shows the relay in the dropped-out state, i.e., the monitored state.
See also
Calibrating the control line [ 57]
Control without confirmation [ 43]
Control with confirmation [ 44]
Printed circuit board view [ 21]
Adjustment elements [ 27]
42 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Input/output configuration options (secondary side)
3
43 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Diagnosis levels
At one switching cycle per second, 300,000 switching cycles are reached after
approx. 3.5 days.
In the case of the 'Degraded mode horn' function, the input/output module
accepts the 'Sounder ON' command. This function can only be configured on
control panels FC20xx and FC72x.
The monitoring of monitored control systems will only be resumed 30 seconds
after deactivation.
44 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Diagnosis levels
3
45 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Behavior in degraded mode
46 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Accessories
3
3.7 Accessories
47 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
3 Accessories
48 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Structure and function
Accessories
3
49 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Planning
4 Compatibility
4 Planning
When planning a project, proceed as follows:
1. Define the mounting site and configuration of the lines
2. Plan the various line types:
– Collective detector line
– Collective detector line for areas at risk of explosion (zone 1 and zone 2)
– Conventional detector line
– Control lines
– Contact inputs
4.1 Compatibility
The input/output module FDCIO223 is compatible with the following fire detection
systems:
Sinteso FS20
Cerberus PRO FS720
SIGMASYS
AlgoRex
X = compatible
– = not compatible
You will find detailed information in the 'List of compatibility'.
Limitations
Maximum of 32 devices per collective detector line if each device has a KMK =
1
If devices have a KMK >1, the maximum number of devices per collective
detector line decreases accordingly.
See also
Applicable documents [ 8]
50 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Planning
Defining the mounting site of the module and configuration of the lines
4
NOTICE
The input/output module must be mounted either in housing FDCH221 or on a U-
rail TS35 in a cabinet or in a control panel housing; it must not be installed without
protection.
51 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Mounting / Installation
5 Mounting with housing
5 Mounting / Installation
The mounting procedure depends on whether the input/output module FDCIO223
is installed on a U-rail TS35 in a fire control panel or with housing FDCH221.
WARNING
Electrical voltage on output cables!
Mortal danger due to electric shock!
Ensure that the cables are not supplied with voltage during installation.
NOTICE
High temperatures in the module's environment
Module overheating and damage
A minimum clearance of 1 cm must be observed between two modules or
between the module and any other boundary.
52 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Mounting / Installation
Mounting with housing
5
See also
Connection terminal DBZ1190-AB [ 48]
Master gauge for recesses [ 65]
53 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Mounting / Installation
5 Mounting in a fire control panel
To make sure that the LEDs on the module remain visible at all times, the cover
cap is transparent. Pick a suitable mounting position, ensuring that the LEDs will
remain visible at all times during operation.
1 2 3 4
TS35
FDCM291
Figure 13: Installing the module on a DIN rail TS35
54 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Mounting / Installation
Connecting input/output module
5
NOTICE
Incorrectly connected input/output module
Damage to the device
Never connect the external DC 24 V power supply or the FDnet/C-NET
detector line to the green terminals of input/output 'I/O 1' or input/output
'I/O 2'.
Observe the assignment of terminals as per chapter 'Printed circuit board
view [ 21]'.
Do not connect the external DC 24 V power supply until you have configured the
input/output module FDCIO223.
DC 24 V
- + 2
2
1
- +
DC 24 V -
+I/O 2
-
FDnet +I/O 1
C-NET
- +
- +
FDnet
C-NET
55 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Mounting / Installation
5 Connecting input/output module
Note the following with regard to the device connections. You will find an overview
of the terminal assignments in chapter 'Printed circuit board view [ 21]'.
The shielding of the FDnet/C-NET detector line must be connected to terminal
15.
The shielding of the 24 V secondary side power supply must be connected to
terminal 16.
The grounding for the shielding on the secondary side must be connected to
terminal 1, as must the secondary side ground fault monitoring.
The shielding for the lines on the secondary side should be connected to
terminal 1.
In the case of shielding on the secondary side, the secondary-side grounding
must be connected. If there is no local station ground available, the shielding
for the secondary-side supply can be used as a ground instead.
See also
Configuration as a detector line [ 33]
Configuration as a contact input [ 38]
Configuration as a control line [ 40]
Printed circuit board view [ 21]
56 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Commissioning
Calibrating the control line
6
6 Commissioning
The device is commissioned via the control panel. The exact procedure is
described in the control panel documentation.
NOTICE
Before commissioning the device, check that the configuration of the
inputs/outputs corresponds to the circuit.
The control line will be recalibrated whenever the push button is pressed.
57 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Maintenance / Repair
7 Status query
7 Maintenance / Repair
Recommendation:
Check the devices every year.
Replace heavily soiled or damaged devices.
No other special maintenance work is necessary.
You will find more detailed information in the fire detection system documentation.
58 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Specifications
Technical data
8
8 Specifications
59 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Specifications
8 Technical data
Detector lines at I/O1, I/O2 Can be configured as: Collective detector line
Collective detector line for areas at
risk of explosion
Conventional detector line
Number of detectors per detector line Max. 32
Collective detector key figures KMK 32
Max. number of devices in total when 32
using one or two safety barriers SB3
Operating voltage / quiescent current:
Collective / collective Ex 20 V / 6.25 mA
Conventional 20 V / 17 mA
Line resistance / line capacitance / line
inductance:
Without safety barrier SB3 150 / 4 F / 5 mH
With safety barrier SB3 50 / 83 nF / 1.6 mH
Alarm activation:
Collective / collective Ex Z-diode 5.6 V
Conventional Nominal resistance 450…620
Alarm current / alarm voltage
Collective / collective Ex Min. 4 mA / 4.5...12 V
Conventional Min. 23 mA / 6 V
Reset voltage <1 V
Reset time >3 s
Settling time following a reset 10 s
Flashing current / cycle / duration Approx. 80 mA / every second / 60 ms
End-of-line (EOL) Voltage reference diode (20 V ±5 %;
1.5 kW pulse power)
EOL22(Ex) end-of-line; obligatory for
ex lines
Monitored for: Open line (creeping)
Short circuit (creeping)
Ground fault (both inputs/outputs
jointly)
60 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Specifications
Technical data
8
61 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Specifications
8 Technical data
62 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Specifications
Technical data
8
63 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Specifications
8 Dimensions
8.2 Dimensions
43.5 46.5 24
8.2
A
132
118
102
A = Ø 4.5
5.8
Figure 14: Module dimensions
119 54
207
64 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Specifications
Master gauge for recesses
8
6.4
B
187.2
200
B = Ø 5.0
6.4
65 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Annex
9 Compatibility
9 Annex
9.1 Compatibility
The table below shows the devices which, together with the FDCIO223, are
approved according to EN 54-13. It is possible to connect additional devices as per
the 'List of compatibility'. However, these devices have not been tested according
to EN 54-13.
66 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Annex
Compatibility
9
Collective devices and manual call points for potentially explosive atmospheres
Safety barrier SB3 -
DM1101 -
DM1103 G295036
DM1104 G299068
Special detectors
FDF241-9 G204010
FDL241-9 G204063
67 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Annex
9 Configuration sheets
68 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Annex
Configuration sheets
9
69 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Index
Index
A E
Adjustment element End-of-line for ex-zone 1+2
Jumper ........................................................... 28 EOL22(Ex)...................................................... 36
Application area Environmental compatibility ............................... 65
Ambient conditions ......................................... 51 Environmental influences .................................. 51
Approvals........................................................ 59 EOL22(Ex)
End-of-line for ex-zone 1+2............................. 36
C ES
Calibrating the control line Product version............................................... 19
Control............................................................ 57 EU directives ................................................... 59
CE marking ..................................................... 59 External fuse
Collective behavior DC 24 V voltage ............................................. 40
Degraded mode operation .............................. 46 External power supply ...................................... 30
Communication External supply ................................................ 30
Control panel .................................................. 29 Ex-zone 1+2
Communication with the control panel via Intrinsically safe detectors ............................... 36
the detector line
Primary side.................................................... 29 F
Compatibility.................................................... 50 Fault messages ............................................... 44
Configuration ................................................... 29 FDCIO223 inputs/outputs
Software ......................................................... 32 Secondary side ............................................... 29
Configuration overview ..................................... 68 FDCIO223 status display
Configuration sheet .......................................... 51 LED ................................................................ 22
Control Fire Control Group ........................................... 43
Calibrating the control line ............................... 57 Fire control panel failure
Control panel ................................................... 57 Degraded mode operation .............................. 46
Communication ............................................... 29
Status query ................................................... 58 I
Identical polarity
Customer Support Center .................................. 5
Monitoring ...................................................... 41
D Impact
DC 24 V voltage Chemicals....................................................... 51
External fuse................................................... 40 Moisture ......................................................... 51
Degraded mode operation Temperature ................................................... 51
Collective behavior ......................................... 46 Input/output module FDCIO223
Fire control panel failure.................................. 46 Transponder ..................................................... 5
Detector exchanger and tester Intelligent detector tester
Diagnosis levels .............................................. 44 Diagnosis levels .............................................. 44
Detector exchanger and tester FDUD292 Intelligent detector tester FDUD293
MC link ........................................................... 58 MC link ........................................................... 58
Diagnosis levels Intended use .................................................... 5
Detector exchanger and tester ........................ 44 Interface
Intelligent detector tester ................................. 44 MC link ........................................................... 58
Disposal.......................................................... 65 Intrinsically safe detectors
Documentation for fire detection system .............. 8 Ex-zone 1+2 ................................................... 36
Download center
URL .................................................................. 8
70 | 72
Building Technologies 009122_h_en_--
Fire Safety 2016-05-04
Index
J P
Jumper ................................................ 21, 27, 31 Packaging label
Adjustment element ........................................ 28 Product version............................................... 19
Primary side
L Communication with the control panel via
LED the detector line .............................................. 29
FDCIO223 status display ................................ 22 Power supply .................................................. 30
Line status display .......................................... 24 Product label
Line separator Product version............................................... 19
Function.......................................................... 29 Product version ................................................. 5
Line status display
LED ................................................................ 24 R
List of compatibility ................................. 8, 46, 50 Recycling ....................................................... 65
Localization Reverse polarity
Operation mode .............................................. 31 Monitoring....................................................... 42
M S
Maintenance intervals ...................................... 58 Safety barrier
Manual call point SB3 ................................................................ 36
Switching contact ............................................ 34 SB3
MC link ........................................................... 58 Safety barrier .................................................. 36
Detector exchanger and tester FDUD292 ........ 58 Scope of delivery ............................................. 18
Intelligent detector tester FDUD293 ................ 58 Secondary side
Monitoring FDCIO223 inputs/outputs................................ 29
Identical polarity .............................................. 41 Power supply .................................................. 30
Reverse polarity .............................................. 42 Shock ............................................................ 52
Short-circuit
N Line separator................................................. 29
Normal operation Source language ............................................... 6
Operation mode .............................................. 30 Standards ....................................................... 63
Status query
O
Operation mode Control panel .................................................. 58
Localization..................................................... 31 Switching contact
Normal operation ............................................ 30 Manual call point ............................................. 34
Test/inspection................................................ 30
T
Original language .............................................. 6 Test/inspection
Operation mode .............................................. 30
Transponder
Input/output module FDCIO223......................... 5
Type plate
Product version............................................... 19
71 | 72
Building Technologies 009122_h_en_--