A Prototype Photovoltaic/thermal System Integrated With Transpired Collector
A Prototype Photovoltaic/thermal System Integrated With Transpired Collector
The attached
copy is furnished to the author for internal non-commercial research
and education use, including for instruction at the authors institution
and sharing with colleagues.
Other uses, including reproduction and distribution, or selling or
licensing copies, or posting to personal, institutional or third party
websites are prohibited.
In most cases authors are permitted to post their version of the
article (e.g. in Word or Tex form) to their personal website or
institutional repository. Authors requiring further information
regarding Elsevier’s archiving and manuscript policies are
encouraged to visit:
http://www.elsevier.com/copyright
Author's personal copy
Received 30 July 2009; received in revised form 1 March 2010; accepted 18 October 2010
Available online 4 December 2010
Abstract
Building-integrated photovoltaic/thermal (BIPV/T) systems may be utilized to produce useful heat while simultaneously generating
electricity from the same building envelope surface. A well known highly efficient collector is the open-loop unglazed transpired collector
(UTC) which consists of dark porous cladding through which outdoor air is drawn and heated by absorbed solar radiation. Commer-
cially available photovoltaic systems typically produce electricity with efficiencies up to about 18%. Thus, it is beneficial to obtain much
of the normally wasted heat from the systems, possibly by combining UTC with photovoltaics. Combination of BIPV/T and UTC
systems for building facades is considered in this paper – specifically, the design of a prototype facßade-integrated photovoltaic/thermal
system with transpired collector (BIPV/T). A full scale prototype is constructed with 70% of UTC area covered with PV modules spe-
cially designed to enhance heat recovery and compared to a UTC of the same area under outdoor sunny conditions with low wind. The
orientation of the corrugations in the UTC is horizontal and the black-framed modules are attached so as to facilitate flow into the UTC
plenum. While the overall combined thermal efficiency of the UTC is higher than that of the BIPV/T system, the value of the generated
energy – assuming that electricity is at least four times more valuable than heat – is between 7% and 17% higher. Also, the electricity is
always useful while the heat is usually utilized only in the heating season. The BIPV/T concept is applied to a full scale office building
demonstration project in Montreal, Canada. The ratio of photovoltaic area coverage of the UTC may be selected based on the fresh air
heating needs of the building, the value of the electricity generated and the available building surfaces.
Ó 2010 Elsevier Ltd. All rights reserved.
Keywords: Building-integrated photovoltaic/thermal system; Unglazed transpired collector; Air preheating; Equivalent efficiency
0038-092X/$ - see front matter Ó 2010 Elsevier Ltd. All rights reserved.
doi:10.1016/j.solener.2010.10.008
Author's personal copy
Nomenclature
ABIPV/T total surface area of the BIPV/T system (m2) hr1 radiative heat transfer coefficient between the
APV area of the BIPV/T system covered by PV mod- back side surface of the PV module and the
ules (m2) UTC surface of the BIPV/T system that is cov-
AUTC area of the UTC system (m2) ered by the PV (W/m2/°C)
AUTC_exposed exposed UTC area of the BIPV/T system hr2 radiative heat transfer coefficient between the
(m2) UTC surface of the BIPV/T system (that is cov-
AUTC_PV UTC area of the BIPV/T system that is cov- ered by the PV) and the plenum insulated sur-
ered by attached PV modules (m2) face (W/m2/°C)
cp specific heat capacity of air (J/kg/°C) khole thermal conductivity of air evaluated at the
cp_avg specific heat of air evaluated at the average UTC UTC perforation temperature (W/m/°C)
surface temperature and ambient air tempera- mBIPV/T mass flow rate of air through the BIPV/T system
ture (J/kg/°C) (kg/s)
cp_BIPV/T specific heat of air evaluated at the average of mPV mass flow rate of air through the portion of the
the BIPV/T outlet air temperature and ambi- BIPV/T system that is covered by the PV mod-
ent air temperature (J/kg/°C) ules (kg/s)
cp_hole specific heat of air evaluated at the average of msuction mass flow rate of air through one square meter
the UTC pore outlet air temperature and ambi- of transpired collector surface area (kg/h/m2)
ent air temperature (J/kg/°C) mUTC_exposed mass flow rate of air across the exposed
cp_PV specific heat of air for the BIPV/T system UTC area of the BIPV/T system (kg/s)
portion that is covered by the PV modules eval- mUTC mass flow rate of air across the UTC system
uated for the average of outlet air and ambient (kg/s)
air temperatures (J/kg/°C) Nuhole Nusselt number for heat transfer occurring in
cp_UTC specific heat of air evaluated at the average of the front, the sides and the back of the UTC per-
UTC outlet air temperature and ambient air foration.
temperature (J/kg/°C) p UTC perforation pitch (m)
d UTC perforation (pore) diameter (m) QBIPV/T total useful heat transfer from the BIPV/T sys-
EBIPV/T electrical energy produced by the BIPV/T sys- tem
tem (W) QPV total useful heat transfer from the portion of
Thx heat exchange effectiveness of the UTC BIPV/T system that is covered by PV modules
EPV electrical energy produced by the PV modules and which enters the plenum behind the tran-
per unit area of PV module (W/m2) spired collector plate (W)
G total solar irradiance on vertical facade QUTC_exposed total heat transfer from the exposed UTC
(W/m2) area of the BIPV/T system (W)
hc1 convective heat transfer coefficient between the QUTC heat transfer from the UTC system (W)
surface of the PV module and the PV backside Rehole Reynolds number based on the hole(pore) diam-
cavity air (W/m2/°C) eter
hc2 convective heat transfer coefficient between the T temperature used in the air property correla-
PV backside cavity air and the UTC surface of tions (°C)
the BIPV/T system that is covered by the PV Tcavity average air temperature behind the PV modules
(W/m2/°C) (°C)
hc3 convective heat transfer coefficient between the Tins plenum insulated surface temperature (°C)
UTC surface and the air entering the UTC ple- To ambient air temperature (°C)
num of the BIPV/T system (for the section cov- Toutlet_BIPV/T outlet air temperature of the BIPV/T sys-
ered by the PV) (W/m2/°C) tem (°C)
hc4 convective heat transfer coefficient between the Toutlet_PV outlet air temperature of the BIPV/T system
air flowing in the UTC plenum of the BIPV/T that is covered by the PV modules for a con-
system (for section covered by the PV) and the trol volume corresponding to one module (°C)
plenum insulated surface (W/m2/°C) Toutlet_UTC outlet air temperature of the UTC system
hi combined radiative and convective PV module (°C)
backside heat transfer coefficient (W/m2/°C) TPV average PV temperature (°C)
ho combined radiative and convective exterior heat Tstc PV modules cell temperature at standard test
transfer coefficient (W/m2/°C) conditions
Author's personal copy
TUTC_PV average temperature of the UTC surface of the gthermal_BIPV/T equivalent thermal efficiency of the
BIPV/T system for the section that is covered by BIPV/T system
PV modules (°C) mhole kinematic viscosity of air evaluated at the aver-
Vsuction suction velocity (m/s) age UTC perforation outlet air and ambient air
Vwind wind velocity (m/s) temperature (m2/s)
n UTC porosity (%)
Greek symbols q density of air (kg/m3)
aPV average PV module solar absorptance qhole density of air in the UTC holes (evaluated at the
bPV PV module temperature coefficient average of the UTC outlet air temperature and
gstc PV module efficiency at standard conditions ambient air temperature) (kg/m3)
gUTC thermal efficiency of UTC system
gBIPV/T combined thermal and electrical efficiency of the
BIPV/T system
developed correlations for the effectiveness of different UTC 2. Useful heat generation from the PV. In BIPV/T sys-
plates for a number of geometrical patterns of the pores and tems, a cooling fluid, such as water or air, is used to
different porosities and flow rates; the effectiveness is sepa- extract heat from the PV in an open-loop or closed-
rated into three parts: heat transfer from the front of the loop configuration. For example, in an open loop air
plate, in the hole, and at the back of the plate. The UTC system, outdoor air is passed under envelope-integrated
attains its high efficiency by reducing convective heat losses. PV panels, cooling them and recovering useful heat
Both the velocity and thermal boundary layers asymptoti- that would otherwise be lost to the outdoor environ-
cally reach values which remain practically constant over ment. Since PV typically has an electrical efficiency of
most of a large collector surface. Nevertheless, high wind 6–18% – with the remainder 80% or so of incident solar
speeds (higher than about 2 m/s) reduce the efficiency of radiation lost largely as heat, and since it also produces
the UTC by increasing turbulence and convection losses, more electricity when cooled, there is a dual benefit in
particularly for low suction velocities. Gunnewiek et al. cooling the PV modules – increased electricity produc-
(2002) studied the effect of wind flow on UTC performance tion and generation of useful heat. This heat can be
and, to avoid flow reversal, recommend a suction velocity of used for space, ventilation or domestic hot water
0.017 m/s for long buildings and wind normal to the UTC, (DHW) heating either by direct means or through a
0.026 m/s for cubical buildings with normal wind, and heat pump.
0.039 m/s for wind at 45° to UTC on a cubical building.
Another technology that may potentially be combined Various researchers (Bazilian et al., 2001; Charron and
with UTC to produce both useful heat and electricity is a Athienitis, 2006; Guiavarch and Peuportier, 2006; Liao et
building-integrated photovoltaic system. Photovoltaic al., 2007) have studied the energy performance of actively
modules may be integrated as construction elements into cooled PV panels integrated into facßades and roofs.
roofs, walls and windows of buildings. Integration Correlations for convective heat transfer coefficients in
improves the cost effectiveness of PV by providing, in addi- photovoltaic/thermal systems have been developed by Liao
tion to electricity production, one or more of the following et al. (2007) through experiments with a particle image
functions that also define the type of BIPV system: velocimetry system and with computational fluid dynamics
simulations. Charron and Athienitis (2006) performed a
1. Building envelope cladding or outer layer of roof (BIPV) theoretical study of ventilated double-facades with inte-
replacing, for example, roof tiles or asphalt shingles. grated PV to study the effect of different design parameters
Architectural and aesthetic integration is a major require- on thermo-electrical system performance.
ment in this type of BIPV system. BIPV has a significant BIPV/T systems may potentially be made by combining
advantage over modular systems that are an add-on to the UTC with solar cells directly on the collector cladding.
building and often require penetrations of the envelope to Delisle and Collins (2007) investigated such a system
be attached. BIPV orientation may not always be optimal through modelling and a small scale prototype. They
due to other constraints in building design. However, report that the electricity produced may be significantly
building integration of photovoltaic modules results in higher than the reduction in useful thermal energy. How-
a much higher overall performance and enhanced dura- ever, significant technical challenges remain in the develop-
bility of the building envelope when compared with ment of UTC with PV cells directly integrated on it (the
attached PV systems. For example, an IEA report cells would typically cover 20–60% of the available area)
(2002) finds that PV systems can last 50 years while cur- primarily due to the large temperature differentials and
tain wall components such as sealed glazing units may the competing thermal and electrical performance require-
need replacement every 25 years or so. ments. Another option is to integrate specially designed
Author's personal copy
photovoltaic modules onto the UTC using a suitable 2. Design concept and prototype for BIPV/T system
attachment system. In this option, there will be some
uncovered UTC and a larger covered part with PV panels. 2.1. Design concept
This is the option investigated in this paper through the
construction of a prototype and comparison with UTC The combination of UTC and attached PV panels on
under the same conditions. Finally, a full scale demonstra- facades is promising for building applications where there
tion project of the concept is briefly presented. is a significant need to heat ventilation air in winter. Since
Fig. 1. (a) Concept schematic for BIPV/T system and (b) detail showing attachment of PV modules and airflow paths around the bottom frame of a PV
module and into the transpired collector.
Author's personal copy
most commercial buildings use heat recovery ventilators to cladding (Fig. 1b). Buoyancy forces due to natural con-
extract as much useful heat as possible from exhaust air, vection act in the opposite direction of mechanically dri-
any excess heat from a BIPV/T system may be utilized ven air flow, thus the attached upper edge encourages air
for space heating or possibly to heat water through a heat flow into the plenum.
pump or air-to-water heat exchanger. A potential advan- 3. The vertical spacing between the modules was chosen
tage of a BIPV/T combination versus simple UTC for a based on the above criterion.
facade is that much of the solar heat generated in summer 4. The value of the electricity produced is assumed here to be
may not be required, so the production of electricity may about four times the value of the heat based on the con-
be an added bonus. This is the case for a new building – cept that with one unit of electricity as input to an air
the John Molson School of Business (JMSB) building – source heat pump, one can produce on average four units
built recently in Montreal at Concordia University. The of heat. In general, the ratio between the relative value of
present study served as a basis for the design of the electricity and heat ranges from 1 for a simple first law
BIPV/T demonstration project of this building and is approach to 17 when a typical exergy analysis is consid-
briefly introduced at the end of the paper. ered (Coventry and Lovegrove (2003)). Others prefer to
The basic concept for the BIPV/T system with tran- use the concept of energy savings efficiency which
spired collector is represented in Fig. 1a and b where the increases the value of BIPV/T electricity based on the elec-
prototype is shown together with a cross section showing tric power generation efficiency of a conventional power
the airflow paths for the heated air. The UTC area without plant (Chow, 2010).Wall (1990) states that electricity is
PV attached is designated as AUTC_exposed while the area of approximately five times as valuable as heat for ordinary
PV is APV. room temperatures. Based on such a concept, we can opti-
This system will generate heat and electricity at a ratio mize the area covered by photovoltaic panels APV versus
that depends on the following factors: the uncovered UTC area AUTC_exposed (the assumed factor
four can change depending on the application).
1. The electrical conversion efficiency of the PV panels and 5. The fan energy consumption needs also to be considered
their temperature coefficient which determines how elec- in designing the system, but this is generally much less (less
trical efficiency is reduced by rising panel temperature. than 5%) than the energy recovered. The outlet air tem-
2. The panel dimensions, framing solar absorptance and perature produced by the system is also important in
thermal properties; these affect the energy balance of deciding flow rate in addition to thermal efficiency, as well
the panels. as electrical efficiency increase due to PV cooling.
3. The array design – non-uniform array temperatures,
caused by vertical stratification, may affect electrical
production depending on the PV array series and paral- 2.2. Prototype development and outdoor experiment
lel interconnections.
4. The porosity of the UTC cladding and how the corruga- A prototype was designed based on the above concept,
tions are oriented – vertical or horizontal. and an experimental facility was built to test and monitor
5. The incidence angle of the solar radiation since at high the performance of the BIPV/T system. Located on the
sun the PV modules will partly shade the area without roof of a building in downtown Montreal at Concordia
PV. University (latitude 45°N), the south-facing facßade of the
6. The flow rate behind the UTC cladding, which generally facility consists of equal areas of UTC and BIPV/T systems
increases heat extraction; however, as it is raised, fric- operating side by side. Since the only difference between the
tion losses and energy consumed by the fan also two setups is the addition of PV modules on the BIPV/T
increase. side, their influence can be directly evaluated. Fig. 2 shows
7. The wind speed which generally affects the exterior con- a schematic of two facßade test sections and the airflow sys-
vective heat loss coefficient. tem. Air is drawn through each test section with a variable
speed fan and airflow is measured by means of a laminar
The design of the system adopted the following impor- flow element with a maximum error of 0.31% at the peak
tant concepts: flow rates.
A Li-Cor weather station was used to measure wind speed
1. The transpired collector cladding was placed with the and direction, as well as ambient air temperature at about
webs horizontal as shown in Fig. 1b, and the PV mod- 10 m high from the local ground (rooftop). Total vertical
ules were sized to minimize the vertical height to hori- irradiance was measured with a Li-Cor Li-200SA pyranom-
zontal length aspect ratio to improve heat removal eter. The local ambient air temperature was measured at one
from the modules. third of the facßade height and at two thirds with shielded
2. The upper edge of the PV modules was mounted directly thermocouples. The temperature distribution along the
against the UTC cladding. This was done to minimize height in various locations was measured with calibrated
the escape of heated air through a potential gap between T-type thermocouples having an accuracy of ±0.3 °C. Ther-
the top frame of the panel and the transpired collector mocouples were placed throughout each facßade test section
Author's personal copy
Fig. 2. Schematic of experimental setup: (a) UTC and BIPV/T test sections and (b) airflow system schematic.
along the central vertical axis. In the BIPV/T section, three The experiment focused on the performance of the two
of the five modules (first, middle and top) were fitted with systems under clear low wind (velocity less than 2 m/s)
six thermocouples each; three distributed along the central quasi-steady state conditions within 1 h from solar noon.
vertical axis, and three along the outer vertical axis. As the A variable speed controller was used to implement four
photovoltaic panels are centrally located with respect to flow rates in the experiment: 50, 80, 115, 150 kg/h/m2 (mass
the test facade, symmetric temperature distribution about flow rate of air per square meter of collector). A 30-min
the vertical central axis can be assumed (this was confirmed interval between flow rates was chosen to ensure that
through infrared thermography). quasi-steady state conditions were achieved (the time
Author's personal copy
constant of each facßade section is about 3 min). The system 2.4. System modelling and analysis
was found to be balanced without any need to adjust the
balancing dampers, which shows that the addition of the The BIPV/T system was separated into two areas for
PV modules in the BIPV/T prototype did not affect the analysis as shown in Fig. 2a. The first part is the fully
pressure drop in the system (the flow rate was equal in both exposed UTC and the second part is the UTC part that
test sections). Electricity produced by the PV modules is covered by PV panels. Due to the small size of the exper-
(operating at their maximum power point) was measured imental setup, the suction across the UTC was assumed to
and stored in a battery through a charge controller. be uniform. The parameters that are of interest include the
outlet air temperatures and the PV and UTC surface tem-
2.3. Photovoltaic module design considerations peratures for both the exposed and covered portions. These
parameters are greatly influenced by the mass flow rate of
The PV modules selected in this experiment have a num- air per unit transpired collector surface area, msuction, which
ber of custom designed features to improve total absorbed is generally chosen at the early stages of design. It should
solar radiation that can be converted to useful heat. First, be noted that in the design of such BIPV/T systems, which
efforts to increase the effective solar absorptance of the generate both electricity and useful heat, the selection of
panel (including the area between cells) were made by the ratio of the two areas is an important decision.
selecting black PV module backsheet. In addition, the alu- Based on the areas of exposed and covered UTC por-
minum frame was selected to be black. Such modifications tions of the BIPV/T system (Fig. 2a) and the assumption
yield an area-weighted (including framing) average module of uniform suction, the total mass flow rate from each area
normal solar absorptance of 92% as compared to 85% for is given by:
their traditional lighter coloured counterpart. As a conse-
mUTC exposed ¼ ðAUTC exposed msuction Þ=3600 ð1Þ
quence, more thermal energy can be recovered from these
panels for ventilation air preheating. Another important mPV ¼ ðAUTC PV msuction Þ=3600 ð2Þ
design parameter was the sizing of the photovoltaic mod-
ule. Although greatly dictated by the cell sizes available where the total mass flow rate of air for the UTC and
in the industry, a long narrow rectangular module was cho- BIPV/T systems is, respectively:
sen to reduce vertical temperature stratification of the air in mUTC ¼ ðAUTC msuction Þ=3600 ð3Þ
the cavity between the PV panel and the UTC. This reduces
the PV operating temperature and facilitates flow of air mBIPV=T ¼ ðABIPV=T msuction Þ=3600 ð4Þ
from behind the PV into the UTC. A custom designed
where
70 W polycrystalline module containing two rows of nine
solar cells and measuring 1465 mm 359 mm 38 mm ABIPV=T ¼ AUTC exposed þ AUTC PV ð5Þ
was used for this application.
The vertical and horizontal spacing between the panels The procedure to analyze the system is presented below
is both an application decision and a spatial configuration by using the experimental results.
constraint. For the prototype system, a major objective was The electricity produced by the PV modules (per unit
to facilitate optimization of the value of the generated area) as a function of their temperature TPV and total solar
energy, assuming that electricity is about four times as irradiance G is given by Skoplaki and Palyvos (2009) and
valuable as heat. Thus, a major purpose of the UTC is to Whitaker et al. (1991)
recover the heat produced by the PV modules while serving EPV ¼ G ½gstc ð1 bPV ðT PV T stc Þ ð6Þ
as a support system. In an effort to match the corrugations
of commercially available UTC, a vertical spacing of where bPV = 0.0046 (PV module temperature coefficient),
90 mm between the PV modules was selected. gstc = 0.125 (PV module efficiency at standard test condi-
The transpired collector used in the prototype is black tions (STC)), Tstc = 25 °C (PV module cell temperature at
galvanized steel (26 gauge) with a porosity of 0.6%. The STC).
plenum depth (distance between UTC and insulation) The total electricity produced by the BIPV/T system is:
was 0.15 m. The transpired collector sheets were installed EBIPV=T ¼ APV EPV ð7Þ
with the corrugations running horizontally to facilitate
closing of a gap between the upper frame of the PV panel The thermal energy produced by the UTC and BIPV/T
(Fig. 1b) and the UTC, so as to reduce heat losses by nat- systems can be calculated as follows:
ural convection, while inducing turbulence behind the pan-
els and increasing mixing in comparison to vertically QUTC ¼ mUTC cp UTC ðT outlet UTC T oÞ ð8Þ
oriented corrugations. Thus, airflow behind the PV mod- QBIPV=T ¼ mBIPV=T cp BIPV=T ðT outlet BIPV=T T oÞ ð9Þ
ules is possible through the bottom and the sides. Finally,
a portion of the UTC was left uncovered at the top to pro- where the specific heat of air is given by (ASHRAE, 2009).
mote buoyancy driven cooling of both the plenum and the
modules in summer. cp ¼ 1005:7 0:066 ðT 27Þ ð10Þ
Author's personal copy
3. Experimental results
As explained above, two identical size systems, a UTC Fig. 4. Comparison of UTC efficiency using two different ambient air
and a BIPV/T system, were installed side by side and temperature sensor locations and the manufacturer’s published data.
Table 3
Dates and average environmental conditions selected for analysis.
Date Local time Mass flow rate per unit surface Incident total solar Wind speed Ambient
area (kg/h/m2) irradiance (W/m2) (m/s) temperature (°C)
April 15th (2009) 1:03 PM–1:28 PM 50 585 2.0 16.6
April 16th (2009) 11:32 AM–11:57 AM 80 570 1.7 15.8
April 16th (2009) 12:05 PM–12:30 PM 115 588 1.0 16.8
April 16th (2009) 12:37 PM–1:02 PM 150 587 1.9 16.3
July 15th (2009) 12:20 PM–12:45 PM 0 430 0.4 25.6
February 9th (2010) 11:27 AM–11:52 AM 50 930 0.5 4.2
February 11th (2010) 12:42 PM–1:07 PM 150 877 0.8 4.4
February 7th (2010) 11:33 AM–11:58 AM 0 926 1.5 2.7
Author's personal copy
where the ambient air temperature was found to be up to conditions and have an accuracy of ±3% based on the
6 °C warmer at the base of the BIPV/T installation than accuracy of the sensors used in the measurements.
at the weather station located about 10 m above. The effect The concept of equivalent thermal efficiency (Eq. (16))
of both of these ambient temperature sensors on the calcu- was introduced to compare the BIPV/T and UTC systems
lated UTC efficiency is demonstrated in Fig. 4. An effi- based on the quality of energy produced. This approach
ciency curve from the UTC manufacturer’s published assumes that one unit of electricity produced by the PV
data (SOLARWALL, 2009) is shown as a reference. For modules can be used to produce four units of thermal
the experimental results presented further in this paper, energy through a heat pump with a coefficient of perfor-
the ambient air temperature recorded at the BIPV/T base, mance (COP) equal to four – a reasonable estimate for
near the roof surface, was selected. This is the most conser- commercially available air source heat pumps (ASHRAE,
vative approach resulting in the lowest calculated efficiency 2009) at source temperatures above 0 °C. Fig. 6 compares
since it is the warmest ambient air temperature representing the measured UTC thermal efficiency, combined BIPV/T
air actually entering the collector. This does not affect the
main objective of the experiment which is relative compar-
ison of UTC and BIPV/T systems.
A major design goal of the BIPV/T system is to maxi-
mize the heat recovered from the PV modules using the
techniques discussed earlier in this paper. Two types of
PV modules, covering approximately the same area, were
tested under four flow rates and the total thermal energy
recovery of the system was calculated (Fig. 5). The large
PV modules have an aluminum frame with a white module
backsheet, whereas their smaller counterparts made for this
project have a black frame and backsheet. The experiments
were conducted between 12:00 h and 13:00 h on April 17th
2008 for the large modules and April 16th 2009 with the
small modules, under similar environmental conditions.
Fig. 5 shows that a 33% increase in thermal energy at the
high flow rate is achieved by using the small darker mod-
ules (PV covered UTC area is decreased by 2.5% and the Fig. 6. UTC thermal efficiency, combined BIPV/T efficiency (thermal plus
overall solar absorptance of the PV modules is increased electrical) and equivalent thermal BIPV/T efficiency (Eq. (16)) as a
by 7%).The results presented are taken under low wind function of mass flow rate.
BIP
PV/T WIT
TH L
LAR
RGE M
MOD
DUL
LES BIPV
V/T WIT
TH SM
MAL
LL C
CUST
TOM
M MO
ODU
ULES
S
Maass Floow B
BIPPV/T
T B
BIPV V/T
T
Raate Therrmaal E
T Enerrgyy [W
W] Thherrmaal Enerrgy [W
W]
[kgg/hrr/m
m²] Largge M
(L Moddulees) (Smmalll M
Moddulees)
1115 8660 11337
1550 8666 11551
Fig. 5. Comparison of the BIPV/T system thermal energy production using PV modules with an aluminum frame and white backsheet (left) to that with
specially designed PV modules with a black frame and back sheet (right).
Author's personal copy
Fig. 9. Comparison of photovoltaic electricity production increase due to cooling with fan energy consumption (all parameters are per square meter of the
total area) for two solar irradiance levels (500 and 900 W/m2).
Author's personal copy
20
17
hi [W/m²/ C]
14
11
5
40 60 80 100 120 140 160
heat ventilation air in winter. A building-integrated photo- modules. Luis Candanedo, Jose Candanedo and Sam Sad-
voltaic/thermal system and unglazed transpired collector ighi also contributed to the experiments.
combination may be utilized to produce useful heat while
generating simultaneously electricity from the same sur- Appendix A. (equations used in Table 2 effectiveness
face. Based on this idea, this paper presents a design con- calculation)
cept and a prototype facßade-integrated photovoltaic/
thermal system with transpired collector (BIPV/T) tested Correlations developed by Dymond and Kutscher
in an outdoor experimental facility. The experimental pro- (1997) may be used to calculate the thermal energy transfer
totype was constructed with 70% of UTC area covered to the air flowing through the UTC.
with black-framed PV modules specially designed to The suction velocity is given by:
enhance solar energy absorption and heat recovery and msuction
was compared side by side with a UTC of the same area V suction ¼ ðA:1Þ
q 3600 hrs
under outdoor sunny conditions with low wind.
The orientation of the corrugations in the UTC is hori- where the density of air is calculated by ASHRAE (2009).
zontal and the PV modules are attached so as to hinder air q ¼ 1:1774 0:00359 ðT 27Þ ðA:2Þ
from escaping from the cavity formed by the panels and the
UTC, and instead flow into the UTC plenum. While ther- The Reynolds number based on the hole diameter is given
mal efficiency of the UTC system is higher than the BIPV/T by:
combined thermal plus electrical efficiency, the equivalent V suction d
thermal efficiency of the BIPV/T system (assuming that Rehole ¼ ðA:3Þ
mhole n
electricity can be converted to four times as much heat) is
7–17% higher. The assumption that electricity is worth The following empirical correlation was determined by
about four times the useful heat produced is based on typ- Dymond and Kutscher (1997) to predict the Nusselt num-
ical coefficients of performance of commercially available ber for heat transfer occurring on the front, the sides and
air source heat pumps which are at least equal to four the back of the UTC and is valid for porosities of 0.5–
for the range of temperatures considered. Connection of 5% and Rehole in the range 100–2000.
such heat pumps to solar-heated air as the heat source will " 0:48 #
p 1:21 V wind
enable expanded use of such BIPV/T systems over a wider Nuhole ¼ 2:75 Re0:43 þ 0:011 n Rehole
hole
range of outdoor temperatures for space heating in addi- d V suction
tion to fresh air preheating. ðA:4Þ
Finally, the concept was applied to a full scale office
building demonstration project in Montreal; this project For the present experiment, the hole diameter (d) is
is a near optimal application in an urban location due to 1.8 mm and the pitch (p) is 20.6 mm.
the fact that the mechanical room with the HVAC system In the BIPV/T system, for the area covered by PV, the
was located directly behind the BIPV/T facßade and the ori- velocity Vwind may be assumed to be zero.
entation was in the optimal range. The concept may be uti- The heat exchange effectiveness of the UTC is given by
lized both for retrofit and new buildings. Detailed design Dymond and Kutscher (1997) as follows:
and performance considerations of this project and similar
ðn 1Þ k hole Nuhole
full scale systems will be reported in a future study that will Ehx ¼ 1 exp ðA:5Þ
d qhole cp hole V suction
also consider the various parameters that need to be con-
sidered for such a system; these include instantaneous The more detailed relationships developed by Van
price/value of heat and electricity, need for fresh air pre- Decker et al. (2001) may also be utilized for higher accuracy.
heating, potential use of heated air outside the heating sea-
son and comprehensive optimization considerations. References
Delisle, V., Collins, M.R., 2007. PVT unglazed corrugated transpired solar Liao, L., Athienitis, A.K., Candanedo, L., Park, K.W., 2007. Numerical
collector model. Canadian Solar Buildings Conference, June 2007, and experimental study of heat transfer in a BIPV–thermal system.
Calgary, Canada. ASME Journal of Solar Engineering 129 (4), 423–430.
Dymond, C., Kutscher, C.F., 1997. Development of a flow distribution Skoplaki, E., Palyvos, J.A., 2009. On the temperature dependence of
and design model for transpired solar collectors. Solar Energy 60 (5), photovoltaic module electrical performance. A review of efficiency/
291–300. power correlations. Solar Energy 83 (5), 614–624.
Guiavarch, A., Peuportier, B., 2006. Photovoltaic collectors efficiency SOLARWALL, 2009. The SOLARWALL Solar Heating System. Conser-
according to their integration in buildings. Solar Energy 80 (1), 65–77. val Engineering Inc., Canada. <http://www.solarwall.com/> (accessed
Gunnewiek, L.H., Brundett, E., Hollands, K.G.T., 2002. Effect of wind in July 2009).
flow distribution in unglazed transpired plate collectors. Solar Energy Van Decker, G.W.E., Hollands, K.G.T., Brunger, A.P., 2001. Heat-
72 (4), 317–325. exchange relations for unglazed transpired solar collectors with
IEA, 2002. Reliability study of grid connected PV systems. In: IEA PV circular holes on a square or triangular pitch. Solar Energy 71 (1),
Power Systems Program Report No. PVPS T7-08. Task 7. 33–45.
Kutscher, C.F., 1994. Heat exchanger effectiveness and pressure drop for Wall, G., 1990. Exergy conversion in the Japanese society. Energy 15 (5),
air flow through perforated plates with and without crosswind. Journal 435–444.
of Heat Transfer 116, 391–399. Whitaker, C.M., Townsend, T.U., Wenger, H.J., Iliceto, A., Chimento,
Kutscher, C.F., Christensen, C., Barker, G., 1993. Unglazed transpired G., Paletta, F., 1991. Effects of irradiance and other factors on PV
solar collectors: heat loss theory. ASME Journal of Solar Engineering temperature coefficients. In: Conference Record of the 22nd IEEE
115 (3), 182–188. Photovoltaic Specialists Conference, vol. 1, pp. 608–613.