Sr.

N
Make Specification Standard Novasys scope vendor scope
o.
A Panel
Novasys Green IEC 61215, IEC 61215 2nd Ed., Supply By
1 PV Module MonoPerc. Bifacial 550 Wp Module
Energy Ltd. IEC 61730, IEC 61701, IEC 62716 Employer Only

B Inverter
IEC 61683, IEC 60068-2 or IEC 62093,IEC 61000
Sungrow / (SG320HX-20 Model) 300KW rated rating at series, 6-2, 6-4, IEC 62109 (1&2), IEEE standard
1 String Inverter yes
WattPower 40degree temp. 929 – 2000 or equivalent,IEC 62116 or equivalent,
IEC 61727

C Cables

I DC-cable
TUV 2PfG 1169/09.07 certified solar cable
1C X 4/6 Sq.mm. , XLPO Copper Cable -1500V, IEC 60228, class 5, UL4703, IEC 60112-1
1 DC-cable Polycab/KEI/RR yes
FRLS (POSITIVE-RED), (NEGATIVE-BLACK) IEC 61034, IEC 60287, IEC 60216, IEC 60754-1, IEC
60811

II AC CABLES

1R x 3C x 300 Sq.mm. (1.9 /3.3 KV) Armoured


1 LT CABLE (INVERTER-ACDB) Polycab/KEI/RR IS 1554, IS 5831-1984, IS 3961, IS 8130, IS 3975 yes
XLPE Al. Cable

LT CABLE (ACDB -
2 Polycab/KEI/RR AC Armoured XLPE Al. Cable (1.9/3.3 KV) IS 1554, IS 5831-1984, IS 3961, IS 8130, IS 3975 yes
TRANSFORMER)

3 LT CABLE (ACDB - Aux. Panel) Polycab/KEI/RR AC Cable Armoured XLPE Al. Cable (1.9/3.3 KV) IS 1554, IS 5831-1984, IS 3961, IS 8130, IS 3975 yes

HT CABLE (Transformer to HT
4 Polycab/KEI/RR AC HT Armoured XLPE Al. Cable (11 KV Earthed) IS 7098-2 (2011) yes
to Metering to Termination)

5 Control cable Polycab/Dlink 18C X 1.5 SQ.MM (copper flexible) IS 1554, IS 5831-1984, IS 3961, IS 8130, IS 3975 yes

Power cable For Aux.


6 Polycab/Dlink AC Cable copper flexibleFRLS 1.1 Kv Grade IS 1554, IS 5831-1984, IS 3961, IS 8130, IS 3975 yes
Component In Plant

1R X 2P X 1/1.5 SQ MM Extruded FRLS PVC (RS-


7 Communication Cable Polycab/Dlink IS 1554, IS 5831-1984, IS 3961, IS 8130, IS 3975 yes
485 COMMUNICATION CABLE)

8 LT Cable ( peripheri Lighting ) Polycab/KEI/RR AC AL. ARM. CABLE 1.1Kv Grade IS 1554, IS 5831-1984, IS 3961, IS 8130, IS 3975 yes

Earthing Cable (Module to 1C x 2.5/4/6 sqmm. CU Flexible Green Cable


Polycab/KEI/RR IS 3043: 2018, IEC 60364
Module) 1.1Kv Grade
Earthing Cable (Inverter 1C x 25/35/75 sq.mm Cu Flexible Green Cable
Polycab/KEI/RR IS 3043: 2018, IEC 60364
Earthing) 1.1Kv Grade
1C x 50/75 sq.mm Cu Flexible Green Cable 1.1Kv
Earthing Cable (LA Earthing) Polycab/KEI/RR IS 3043: 2018, IEC 60364
Grade
ELECTRICAL PANELS AND
D
SWITCH GEARS
Alnico/L&T/Standar Standard As per Requirement As per Approved
1 ACDB Panel IS 8623-part 1:1993 & IEC 439-1:1985 yes
d Drawing and detailing

Auxillary Transformer with Alnico/L&T/Standar


2 As per Requirement IS 8623-part 1:1993 & IEC 439-1:1985 yes
Panel (Inbuilt UPS & Battery) d

0.800/11 KV, (Variable) KVA, with On load tap


changer ± 15%, Z = 5%
Inverter Duty Transformer SNR/DANISH/VOLTA
1 Cooling - ONAN IS 2026, IS 8623-part 1:1993 & IEC 439-1:1985 yes
(Cu. Winding) P/SUPREME/NGG
Vector group: Dyn11, 25kA for 3sec., With RTCC
Panel
Standard As per Requirement As per Approved
1 Main HT Panel L&T /Standard IEC 62271-201 : 2006 yes
Drawing and detailing

2 Metering & Check Meter Panel Standard As per MSEDCL Standard yes

E EARTHING PITS, STRIP

I Earthing Strip

1 earthing GI Strip Standard 1R X 25 x 3 mm GI Strip IS 3043: 2018, IEC 60364 yes

2 earthing GI Strip Standard 1R X 25 x 6 mm GI Strip IS 3043: 2018, IEC 60364 yes

3 earthing GI Strip Standard 1R X 100 x 6 mm GI Strip IS 3043: 2018, IEC 60364 yes

II Earthing Pits

earthing pits (Inverter, DC 17.2 mm copper bonded 3 Mtrs with Earth


1 Truepower/Standard IS 3043: 2018, IEC 60364 yes
Earthing, LA Earthing) enhancing compound and accessories

100 mm CI-Pipe 3 Mtr with all Earthing


4 Chemical Earthing HT Truepower/Standard IS 3043: 2018, IEC 60364 yes
accessories

5 Earth Board Standard Standard Earthing Specification mentioned IS 3043: 2018, IEC 60364 yes

F LIGHTINING ARRESTER
True
1 PV Field LA 107m radius (ESE type with all accessories) IEC 62305 yes
power/Standard

CABLE LUGS AND GLANDS


G
(Termination Material)

I LUGS / GLANDS

1 Lugs for Earthing cables Dowell/Comet Ring type copper Lugs IEC 62444, BS 6121, IS-5082: 2003 (19501) yes

2 Alluminium Lugs Dowell/Comet Ring type Alluminium Lugs IEC 62444, BS 6121, IS-5082: 2003 (19501) yes

2 Bimetalic Lugs Dowell/Comet Ring type Bimetalic Lugs IEC 62444, BS 6121, IS-5082: 2003 (19501) yes

(Aluminium Gland) As per requirement for


3 Alluminium Glands Dowell/Comet IEC 62444, BS 6121, IS-5082: 2003 (19501) yes
Respective AC Cables

6 HT-Termination KIT Standard AC HT Armoured XLPE Al. Cable (11 KV Earthed) IS: 13573 yes

II Termination Accerossies

1 Cable Insulation Sleev Standard As per requirement for Respective AC Cables IEC 60502 yes

IS 2448-1 (1963), ANSI/CAN/UL 510 and/or CSA


2 Insulation Tape LT Standard Red, Yellow, Blue, Black, Green yes
C22.2 No. 197

III DATA LOGGING

Solar Local as well as Remote monitoring system


1 Data logger WMS+Services Suryalog yes
with Weather Monitoring System.

IV MISCELLANEOUS
DWC Pipe & There
Accessories For DC Cabling &
1 Plasto/Astral 40mm/32mm OD/ID IS 16098, IS 14930, ISO 21138 yes
Separate Communication
Cabling
As per Required Size GI Perforated cable trey
2 Cable Tray Standards IEC 61537:2023 yes
with cover
3 Flexible Pipe Plasto/Astral PVC -25 mm Dia yes

4 PU Foam ABRO/Standards 750 ml yes

5 Cable tie (PL) Standards UV Protected Required Length yes

6 Cable tie (SS) Standards Required Length yes

7 Ferrule Standards String Series yes

8 MC4 Connection Stabuli/Elcom/Elmex Male - Felmale Paire yes

H Safety Material

1 Fire Extinguisher Standards CO2 type (6 Kg) IS 2190, IS 15683, NFPA yes

2 Sand Bucket Set Standards Sand Bucket Set with Canopy NFPA, IEC 60695-1-10:2016 yes

3 Safety Board Standards Electrical Safety Board NFPA, IEC 60695-1-10:2016 yes

4 Danger Board Standards As per voltage level NFPA, IEC 60695-1-10:2016 yes

5 Insulation Mat Duratuf/Standards (1 Mtr. X 10 Mtr.) Black (As per voltage level) NFPA, IEC 60695-1-10:2016 yes

6 Insulation Glubs Standards As per Voltage Level NFPA, IEC 60695-1-10:2016 yes

PERIPHERI LIGHTING &


I
ACCESSORIES
1 LED STREET LIGHT Havells/Standard LED street Light with all accessories IS 1944-1 and 2 (1970), IS 1944-5 (1981) yes

2 junction Box Standard IP65 Junction Box IS 1944-1 and 2 (1970), IS 1944-5 (1981) yes