1
1
N
Make Specification Standard Novasys scope vendor scope
o.
A Panel
Novasys Green IEC 61215, IEC 61215 2nd Ed., Supply By
1 PV Module MonoPerc. Bifacial 550 Wp Module
Energy Ltd. IEC 61730, IEC 61701, IEC 62716 Employer Only
B Inverter
IEC 61683, IEC 60068-2 or IEC 62093,IEC 61000
Sungrow / (SG320HX-20 Model) 300KW rated rating at series, 6-2, 6-4, IEC 62109 (1&2), IEEE standard
1 String Inverter yes
WattPower 40degree temp. 929 – 2000 or equivalent,IEC 62116 or equivalent,
IEC 61727
C Cables
I DC-cable
TUV 2PfG 1169/09.07 certified solar cable
1C X 4/6 Sq.mm. , XLPO Copper Cable -1500V, IEC 60228, class 5, UL4703, IEC 60112-1
1 DC-cable Polycab/KEI/RR yes
FRLS (POSITIVE-RED), (NEGATIVE-BLACK) IEC 61034, IEC 60287, IEC 60216, IEC 60754-1, IEC
60811
II AC CABLES
LT CABLE (ACDB -
2 Polycab/KEI/RR AC Armoured XLPE Al. Cable (1.9/3.3 KV) IS 1554, IS 5831-1984, IS 3961, IS 8130, IS 3975 yes
TRANSFORMER)
3 LT CABLE (ACDB - Aux. Panel) Polycab/KEI/RR AC Cable Armoured XLPE Al. Cable (1.9/3.3 KV) IS 1554, IS 5831-1984, IS 3961, IS 8130, IS 3975 yes
HT CABLE (Transformer to HT
4 Polycab/KEI/RR AC HT Armoured XLPE Al. Cable (11 KV Earthed) IS 7098-2 (2011) yes
to Metering to Termination)
5 Control cable Polycab/Dlink 18C X 1.5 SQ.MM (copper flexible) IS 1554, IS 5831-1984, IS 3961, IS 8130, IS 3975 yes
8 LT Cable ( peripheri Lighting ) Polycab/KEI/RR AC AL. ARM. CABLE 1.1Kv Grade IS 1554, IS 5831-1984, IS 3961, IS 8130, IS 3975 yes
2 Metering & Check Meter Panel Standard As per MSEDCL Standard yes
I Earthing Strip
3 earthing GI Strip Standard 1R X 100 x 6 mm GI Strip IS 3043: 2018, IEC 60364 yes
II Earthing Pits
5 Earth Board Standard Standard Earthing Specification mentioned IS 3043: 2018, IEC 60364 yes
F LIGHTINING ARRESTER
True
1 PV Field LA 107m radius (ESE type with all accessories) IEC 62305 yes
power/Standard
I LUGS / GLANDS
1 Lugs for Earthing cables Dowell/Comet Ring type copper Lugs IEC 62444, BS 6121, IS-5082: 2003 (19501) yes
2 Alluminium Lugs Dowell/Comet Ring type Alluminium Lugs IEC 62444, BS 6121, IS-5082: 2003 (19501) yes
2 Bimetalic Lugs Dowell/Comet Ring type Bimetalic Lugs IEC 62444, BS 6121, IS-5082: 2003 (19501) yes
6 HT-Termination KIT Standard AC HT Armoured XLPE Al. Cable (11 KV Earthed) IS: 13573 yes
II Termination Accerossies
1 Cable Insulation Sleev Standard As per requirement for Respective AC Cables IEC 60502 yes
IV MISCELLANEOUS
DWC Pipe & There
Accessories For DC Cabling &
1 Plasto/Astral 40mm/32mm OD/ID IS 16098, IS 14930, ISO 21138 yes
Separate Communication
Cabling
As per Required Size GI Perforated cable trey
2 Cable Tray Standards IEC 61537:2023 yes
with cover
3 Flexible Pipe Plasto/Astral PVC -25 mm Dia yes
H Safety Material
1 Fire Extinguisher Standards CO2 type (6 Kg) IS 2190, IS 15683, NFPA yes
2 Sand Bucket Set Standards Sand Bucket Set with Canopy NFPA, IEC 60695-1-10:2016 yes
3 Safety Board Standards Electrical Safety Board NFPA, IEC 60695-1-10:2016 yes
4 Danger Board Standards As per voltage level NFPA, IEC 60695-1-10:2016 yes
5 Insulation Mat Duratuf/Standards (1 Mtr. X 10 Mtr.) Black (As per voltage level) NFPA, IEC 60695-1-10:2016 yes
6 Insulation Glubs Standards As per Voltage Level NFPA, IEC 60695-1-10:2016 yes
2 junction Box Standard IP65 Junction Box IS 1944-1 and 2 (1970), IS 1944-5 (1981) yes
J CCTV