Chapter 5 Earthing
Chapter 5 Earthing
Important terms
Solid Earth: A conductor is said to be solidly earthed when it is electrically
Earth Wire: A conductor connected to earth and usually situated in proximity to the
2
Cont’d
Earthing conductor: is a conductor which connects part of an electrical installation
to an earthing electrode.
Leakage: The passage of electricity in path, other than that desired, due to imperfect
insulation.
the earthing lead or to each other, those parts of an installation which are required to
be earthed. It may be in whole or in part the metal conduit or metal sheath/the armor
such a conductor.
3
Cont.
• Extraneous conductive part: is a conductive part liable to introduce a potential and
• Exposed Conductive part: a conductive part of equipment which can be touched &
which is not a live part but which may become live under fault condition.
4
Cont.
Protection in electrical installation design means:
Protection of human beings from electric shock and hazards in case of occurrence
Protection of equipment and devices from overcurrents and also some faults.
and devices.
5
Cont.
Electrical protection against the above risks is provided by two methods.
6
5.1. Earthing and Bonding
• Earthing means connection of the neutral point of a supply system or the non-current
frame of every generator and motor etc. to the general mass of earth in such a
manner that at all times immediate discharge of electrical energy takes place
without danger.
7
Cont.
Earthing or grounding is classified as:
Equipment earthing
potential of the general mass of earth to a value consistent with the insulation
level.
electrical equipment.
8
Cont.
Earthing provides protection to personnel and equipment by ensuring operation of
the protective control gear and isolation of the faulty circuit in the following cases:
conductors, as a result of insulation failure, electric current will flow through the
ground path.
transformer
Lightening stroke
9
Cont.
Bonding: is the act of joining two electrical conductors together. These may be two
It has to be done by connecting of all the metal parts that are not supposed to be
carrying current during normal operations to bringing them to the same electrical
potential.
That means we would not get electricity building up in one equipment or between
10
Cont.
No current flow can take place b/n two bonded bodies b/c they have the same
potential.
Bonding itself, does not protect anything. However, if one of those boxes is
earthed there can be no electrical energy build-up. If the grounded box is bonded to
the other box, the other box is also at zero electrical potential.
11
Cont.
Grounding/earthing is done to dissipate the energy into a low impedance
grounding system.
All ground points are bonded together to eliminate ground loops and create an
equipotential plane.
12
Cont.
Grounding reduces the risk of serious electric shock from current leaking into
13
5.2. Grounding/Earthing Electrodes
An earth electrode should be able to resist corrosion for a long time. The
recommended materials are copper, copper-clad iron, cast iron & galvanized
steel.
a) pipe electrodes
b) Rod electrodes
c) Strip electrodes
d) Plate electrodes
14
Cont.
a) Pipe electrodes : is made of cast-iron pipe 2m long and
15
Cont.
c) Strip electrodes: are usually copper strip. They are
most useful in shallow soil overlying rock. It shall not
be smaller in cross-section than 25 mm * 1.60mm of
copper, and 25 mm* 4mm of galvanized iron and steel.
• Ground conductor
• Ground electrode
17
Overall ground system
• Welded, bolted and clamped joints are permissible. All bolted and screwed
corrosion.
• All surfaces where connections are made should be free of grease, paint, dirt or any
19
Cont’d
• Water and gas pipes and members of structural steel-work shall not be used as earth
continuity conductor.
• Flexible conduit shall not be used as E.C.C. A separate earth wire should be
provided either inside or outside the flexible conduit which should be connected by
means of earth clips to the earth system at one end, & to the equipment at the other
end.
20
Cont.
• Earthing of domestic fittings and appliances: Earthing of all domestic appliances
except those provided with double insulation is obligatory. All plugs & sockets shall
be a three-pin type, the earth pins being connected to the earth wire.
– Radio sets should be earthed preferably through an electrode different from that of the
main earth system for better reception. Where it is not possible to have a separate earth
21
Cont.
• Earthing of machine tools: Irrespective of the size and type of a machine tool, its
bed plate shall be earthed by means of a strip of conductor of not less than 6.5mm2
cross-sectional area of copper, and 16 mm2 of galvanized iron. The strip should be
22
Grounding resistance
• The value of resistance as measured by the conductive earth and the grounding
• While many factors come into play in determining the overall effectiveness of the
grounding system, the resistance of the earth itself (earth resistivity) can
23
Contd
• Several factors, such as moisture content, mineral content, soil type, soil
• In general, the higher the soil moisture content, the lower the soil’s resistivity.
• Systems designed for areas which typically have very dry soil and arid climates may
need to use enhancement materials or other means to achieve lower soil resistivity.
24
Cont.
• Typical values for soil resistivity in ohms are as follows:
25
Earthing systems
• One popular method of providing some measure of protection against such contact
26
Cont.
• All metalwork associated with electrical apparatus and systems, termed as exposed
Conductive parts.
– Examples are gas, oil and water pipes, structural steelwork, radiators, sinks and
baths.
27
5.3. Location of system earthing
The earthing conductor shall be connected to the earthed service conductor at any
accessible point from the load end of service drop or service lateral.
28
Contd
Where the transformer supplying the services is located outside the building, at least
one additional earthing connection shall be made from the earthed service conductor
An earthing connection shall not be made to any earthed circuit conductor on the
29
Cont.
For circuits that are supplied from two sources in a common enclosure or grouped
connection to the tie point of the earthed circuit conductors from each power supply
30
5.4. Grounding Arrangements
There are different types of earthing systems. These systems have been designated in the
IEE Regulations using the letters T, N, C and S. These letters stand for:
N - Neutral
C - Combined
S –Separate
TT
IT and
TN 31
TT System
• A TT system has a direct connection of the supply source to earth and a direct
• An example is an overhead line supply with earth electrodes, and the mass of earth
32
Cont.
TT system
The supply will have the neutral connected to earth at the supply transformer
equipment.
Therefore, the first letter, T, signifies that the supply has been earthed (T = terra
firma = earth). And the second letter, T, indicates that the installation has its own
earth electrode.
This system is commonly met in rural districts where the incoming supply is by
34
Cont.
• In IT systems, the following requirements must be satisfied.
The ground resistance of the exposed conductive parts must be sufficiently low.
visual signal to indicate the first fault b/n a live part and an exposed conductive
Once the first fault has occurred, the requirement for automatic disconnection of
35
TN Systems
TN–S system: has the supply source directly connected to earth, the installation
metalwork connected to the earthed neutral of the supply source via the metal
sheath of the supply cable, and the neutral and protective conductors throughout
36
TN–S Systems
37
TN–C systems
• Again the first letter indicates that the supply is earthed while the second & third
letters N & C show that the supply neutral & protective conductor is combined in
one.
38
TN–C–S System
A TN–C–S system is as the TN–S system but the supply cable sheath is also the
39
TN–C–S system
40
Earth fault loop impedance
The speed of operation of the protection depends on the magnitude of the fault
current, which in turn depends on the impedance of the earth fault loop path.
41
Cont.
42
The simplified version of this path be:
43
Cont.
• Zs = Ze + R1 + R2
Where: Zs- is the actual total loop impendence,
Ze- is the impedance external to the installation,
R1- is the resistance of the phase conductor and
R2- is the resistance of the CPC.
We also have:
I = Uoc /Zs
Where: I- is the fault current and Uoc is the supply transformer open circuit
voltage
(Usually 220 V) and Uoc is the voltage to earth at consumer terminals.
44
5.5. Protection of Buildings & Structures against Lightning
storm clouds.
occurs during thunderstorms, & sometimes during volcanic eruptions or dust storms.
220,000 km/h (140,000 mph), & can reach temperatures approaching 30,000°C.
45
Cont.
Lightening protection is a system designed to protect a structure from damage due to
lightning strikes by intercepting such strikes and safely passing their extremely high
Copper
Aluminum
Class I
Class II
Structural steel 46
Cont.
All buildings and structures, which are susceptible for lightning strokes by virtue of
their height or location in an exposed situation and the important buildings like
This is done by installing lightning arrestors at the top of the structures and
connecting the same to the general mass of earth through a system of connecting
conductors and earth electrodes so that the structure is not subjected to dangerously
The projecting wire which is intended to collect the lightning discharge from the
It should project at least 30cm above the object on which it is fixed. In case of more
than one termination, the same should be fixed 15-23m apart. relevant points, even if
they are less than 15m apart, should be provided with separate air terminations.
All metallic finals, chimneys, ducts, vent pipes, railing, gutters and the like on or
above the main surface of the roof of a structure should be bonded, and form part of
48
the air termination network.
Cont.
Roof conductors: are conductors laid around a building near the top to interconnect
Down conductors: are conductors which connect the air termination with earth.
They should follow shortest routes to earth without any sharp bends, and should not
Zone of protection: of a single vertical conductor is taken as the cone with its apex
at the highest point of the conductor and with a base of radius equal to the height.
Conductor materials: copper is the most preferred material for use in the lightning
on low earth resistance. For this, it is essential to fix electrodes in ground with
The earth resistance, in no case, shall exceed 5 ohms and in case of rocky soils 8
ohms. More than one electrode may be used if the required earth resistance is not
50
51
5.6. Testing of Electrical Installation
Every installation shall, during erection and/or on completion before being put into
The method of test shall be such that no danger to persons, livestock/ property or
charts & similar information related to the installation must be available for the
verifier.
These are:
installation available?
53
Cont.
Identification of conductors: Are conductors correctly identified in accordance
Labeling: are all protective devices, switches (where necessary) and terminals of
Routing of cables: are cables installed in such a way that account is taken of
Conductor Selection: are conductors selected for current carrying capacity and
Protection against shock: what methods have been used to provide protection
Isolation and Switching: are there correctly located and installed appropriate
Protective Devices: are protective devices, monitoring devices, and meters correctly
chosen and set to ensure fault protection against indirect contact and/or overcurrent?
55
Cont.
Access: are all means of access to switches, switchgears and equipment adequate?
Thermal effect: are fire barriers present where required, and protection against
56
Testing of Electrical Installation
a. Insulation Resistance
The insulation resistance b/n the wiring and earth with all fuses (breakers) and
The insulation resistance b/n the conductors with all lamps out & all switches
‘ON’
Test is performed by a DC source not less than twice of working voltage but not
exceeding 500V.
Since installation circuits are wired in parallel, one can see that for a very large
installations an insulation resistance test at the intake position may show a low
In order to overcome this problem, installations should be broken down into smaller
58
Testing of Insulation Resistance b/n the Wiring & the
Earth
The resistance offered to leakage from conductors to earth is known as insulation
resistance test between the wiring and earth.
d. All the lamps are in their positions or the holders are short-circuited.
e. Link all the poles of the supply together i.e. line and neutral terminals are
shorted on the installation side.
59
Cont.
60
Cont.
The line terminal of the Megger (marked as L) is connected to the point where the
conductors have been shorted at the main switch and the E terminal is connected to
the earth.
The handle of the tester is turned, then it begins to slip & the reading on the dial
The insulation resistance to earth measured should not be less than 0.5 Mega ohm.
61
The insulation resistance b/n the conductors
The objective of this test is to ensure that the insulation is sound b/n the conductors
In this test the circuit diagram is the same except that all of the lamps and all
metallic connections b/n the two wires of the installation are removed from the
holders.
62
Cont.
each pole in turn to N). The reading should not be less than 1 Mega ohm.
63
Cont.
64
2. Polarity check
A verification of polarity shall be made & ensured that all fuses & all single pole
control devices are connected in the live conductor only, that the outer contacts lamp
holders are connected to the neutral or earthed conductor, & the wiring has been
An alternative method is using a test lamp. In this method one end of the test lamp is
connected to earth & the other end is tapped to each contact of the switch in turn. If
the test lamp is in the live wire, it gives light, otherwise the installation is wrong.
65
Cont.
66
Reading Assignment:
67
68