Rac, Module 6-Note
Rac, Module 6-Note
&
AIR
CONDITIONING
MODULE 6
Summer Air-Conditioning
These systems, when properly designed and installed, maintain
the temperature and humidity of indoor air to a level at which
persons feel comfortable during summer. Essentially, it involves
reducing the air temperature and humidity (in humid tropics) by
the processing of cooling and dehumidification.
In most of the places the summer season is hot and humid. Hence,
in order to provide comfortable conditions to the occupants
during summer, it is required to supply cold and dry air to the
occupied space. This requires systems wherein the hot and humid
air can be cooled to temperatures lower than the dew point
temperature, so that the water vapour in air can be removed by
condensation, and the resulting cold and dehumidified air
supplied to the conditioned space in required quantity for
providing thermal comfort. Thus it can be seen that a typical
In some areas such as deserts, the summer is hot and dry. Air
conditioning systems for these hot and dry climates also require
cooling of air below the ambient temperatures, however, in stead
of removing water vapour it may be required to add water to the
air supplied to the conditioned space.
Or
For rooms that do not have external windows or walls, a split type
room air conditioner can be used. In these air conditioners, the
condensing unit comprising of the condenser, compressor and
condenser fan with motor are located outside, while the indoor
unit consisting of the evaporator, evaporator fan with motor,
expansion valve and air filter is located inside the conditioned
room. The indoor and outdoor units are connected by refrigerant
piping. In split type air conditioners, the condensed water has to
be taken away from the conditioned space using separate drain
pipes.
The distance between the indoor and outside units has to be kept
as small as possible. With increase in distance, the pressure drop
in the suction and liquid lines becomes more and that results in a
reduction of the capacity of the unit. The split systems enable
noise, vibration and maintenance to be kept away from the
conditioned space and as such are quite acceptable for office
suite, residences, stores and restaurants.
Central Air-Conditioning
The dual duct systems can provide both cooling and heating
simultaneously. These systems can be further classified into:
1. Dual duct, constant volume systems
2. Dual duct variable volume systems
As shown in the figure, outdoor air (OD air) for ventilation and
recirculated air (RC air) are mixed in the required proportions
using the dampers and the mixed air is made to flow through a
cooling and dehumidifying coil, a heating coil and a humidifier
using a an insulated ducting and a supply fan. As the air flows
through these coils the temperature and moisture content of the
air are brought to the required values. Then this air is supplied to
the conditioned space, where it meets the building cooling or
heating requirements. The return air leaves the conditioned space,
a part of it is recirculated and the remaining part is vented to the
atmosphere.
A thermostat senses the temperature of air in the conditioned
space and controls the amount of cooling or heating provided in
the coils so that the supply air temperature can be controlled as
per requirement. A humidistat measures the humidity ratio in the
conditioned space and controls the amount of water vapour added
in the humidifier and hence the supply air humidity ratio as per
requirement.
As shown in the figure, in a dual duct system the supply air fan
splits the flow into two streams. One stream flow through the
cooling coil and gets cooled and dehumidified to about 13oC,
while the other stream flows the heating coil and is heated to
about 35–45oC. The cold and hot streams flow through separate
ducts. Before each conditioned space or zone, the cold and hot air
streams are mixed in required proportions using a mixing box
arrangement, which is controlled by the zone thermostat. The
total volume of air supplied to each zone remains constant,
however, the supply air temperature varies depending upon load.
The fan coil units are either floor mounted, window mounted or
ceiling mounted. The capacity of a fan coil unit can be controlled
either by controlling the cold water flow rate or by controlling air
flow rate or both. The airflow rate can be controlled either by a
damper arrangement or by varying the fan speed. The control may
be manual or automatic, in which case, a room thermostat
controls the capacity. Since in the fan coil unit there is no
provision for ventilation, a separate arrangement must be made to
take care of ventilation. A fan coil unit with a provision for
introducing treated ventilation air to the conditioned space is
called as unit ventilator
In air-water systems both air and water are used for providing
required conditions in the conditioned space. The air and water
are cooled or heated in a central plant. The air supplied to the
conditioned space from the central plant is called as primary air,
while the water supplied from the plant is called as secondary
water. The complete system consists of a central plant for cooling
or heating of water and air, ducting system with fans for
conveying air, water pipelines and pumps for conveying water
and a room terminal. The room terminal may be in the form of a
fan coil unit, an induction unit or a radiation panel. Figure shows
the schematic of a basic air-water system. Even though only one
conditioned space is shown in the schematic, in actual systems,
the air-water systems can simultaneously serve several
conditioned spaces.
As mentioned the room unit may be in the form of a fan coil unit,
an induction unit or in the form of a radiant panel. In an induction
unit the cooling/heating coil is an integral part of the primary air
system. The primary air supplied at medium to high pressure to
the induction unit, induces flow of secondary air from the
conditioned space. The secondary air is sensibly cooled or heated
as it flows through the cooling/heating coil. The primary and
secondary air are mixed and supplied to the conditioned space.
The fan coil units are similar to the ones used in all water systems.
In winter the outside conditions are cold and dry. As a result, there
will be a continuous transfer of sensible heat as well as moisture
(latent heat) from the buildings to the outside. Hence, in order to
maintain required comfort conditions in the occupied space an air
conditioning system is required which can offset the sensible and
latent heat losses from the building. Air supplied to the
conditioned space is heated and humidified in the winter air
conditioning system to the required level of temperature and
moisture content depending upon the sensible and latent heat
losses from the building.
Humidifiers
Methods of obtaining Humidification
The humidification is achieved either by supplying or spraying
steam or hot water or cold water into the air. The humidification
may be obtained by the following two methods
Direct Method
The water is sprayed in a highly atomised state into the room to
be air-conditioned
Indirect Method
The water is introduced into the air in the air conditioning plant
with the help of an air washer
Adiabatic humidifiers:
Adiabatic humidifiers provide direct evaporation of water into the
air without adding external energy. Because no heat is added to
evaporate the water, there is a cooling effect that is directly
proportional to the amount of water evaporated. This is
sometimes referred to as sensible cooling. Sensible heat is taken
from the surrounding air and thus reducing air temperature.
Adiabatic humidifiers include both atomizing and evaporative
humidifiers
o Atomizing Humidifiers
o Pan Humidifiers
Basic Pan
Electrically heated pan
Pan with wicking plates
o Steam Humidifiers
o Evaporative Humidifiers or Wetted-Element
Humidifiers
Drum Type
Flow Through-type
Spray-type
Compressed air and water are combined inside the nozzle and
discharged onto a resonator to create a fine fog at the nozzle tip
Steam Separator-Type
Steam separator-type humidifiers are comprised of a steam
separator, integral control valve, steam jacketed dispersion
tube(s), and a manifold when there is more than one dispersion
tube. A steam trap and wye-type pipeline strainer are typically
included in the package. Supply steam flows through the strainer
and pre-heats the steam jackets before entering the separator.
Liquid separates and falls with gravity through the separator drain
connection to the steam trap.
High quality steam vapour travels to the control valve and, with
demand for humidity, passes through the dispersion tube(s) into
the airstream.
Infrared-Type Steam
Infrared-type steam humidifiers use one or more radiant heat
bulbs to create heat energy to produce steam. The boiling water
produces steam, which is then removed by air flowing over the
surface of the tank
Atomizing Humidifiers
Atomizing, or spray, humidifiers are similar to evaporative
humidifiers in that they do not heat the water, but unlike their
evaporative counterparts, atomizing humidifiers increase the
moisture in the air by spraying small water droplets into the
central system’s airstream. The air’s ability to absorb moisture
depends on the temperature, flow rate, and moisture content of
the air moving through the system. Small particles of water are
formed and introduced into the airstream in one of the following
ways:
o Spray nozzles rely on water pressure to produce a fine
spray.
o Spray nozzles use compressed air to create a fine mist
o A spinning disk or cone throws a water stream centrifugally
to the rim of the disk and onto deflector plates or a comb,
where it is turned into a fine fog
o Ultrasonic humidifiers, also known as piezoelectric
humidifiers, atomize the water using a vibrating element
that operates at a very high frequency of about 100 kHz
(100,000 cycles per second).
Basic pan
A shallow pan is installed within the furnace plenum. Household
water is supplied to the pan through a control device.
Electrically heated pan
Similar to the basic unit, this type adds an electric heater to
increase water temperature and evaporation rate.
Pan with wicking plates
Similar to the basic unit, this type includes fitted water-absorbent
plates. The increased area of the plates provides greater surface
area for evaporation to take place
Steam Humidifiers
Steam humidifiers heat water to the boiling point, producing
steam. Because steam humidifiers contain their own heat source,
electric heating elements, they are able to add moisture to cooler
airstreams than atomizing or evaporative type humidifiers.
Flow Through-type
Flow through units maintain indoor relative humidity by flowing
fresh water across a porous evaporator pad, where it is exposed
to warm, dry air forced through the humidifier by the furnace
blower or an internal fan.
Drum-type
Drum humidifiers rely on forced air, and are well-suited for
warm-air heating systems. A rotating evaporator pad, or drum,
lifts water from the water pan into the air stream, which is warmed
and circulated by the furnace blower. The pad’s multiple holes
and connecting strands increase the area from which water can
evaporate.
Thermostat
It is a temperature control device fitted on a wall in home to
control the cooling (or heating) system. A thermostat is
something that tries to maintain the temperature.
Thermostat senses the temperature inside the room and causes the
electrical contact switch to the compressor ON or OFF depending
on the temperature inside title room. The most commonly used
Thermostat is the bimetallic type. It comprises of two metals
which at particular temperature are of same length, but when their
temperature is increased, one metal increases in length more
while the other increases less due to their different coefficients of
thermal expansions. Hence it gets bent so that this bending action
swithes on or off the ac compressor.
Bimetallic strips
A thermostat has two pieces of different metals joined together to
form a bimetallic strip (or bimetal strip). The strip works as a
bridge in an electrical circuit connected to the cooling system.
When the room becomes hot, bimetallic strip gets hot. When the
strip gets hot, one of the metals expands more than the other so
the whole strip bends so that it connects the circuit and starts the
compressor, and the room starts to cool.
As the room cools, the strip cools too and bends back to its
original shape. Eventually, it detaches the circuit and makes the
electricity stops, so the compressor stops. By adjusting the
temperature settings, one can change the temperature at which the
circuit switches on and off.
Gas-filled bellows
The disadvantage of bimetallic strips is that they take a long time
to heat up or cool down, so they don’t react quickly to temperature
changes. Hence to sense temperature changes more quickly gas-
filled bellows are used for operation of thermostat
Working Principle
A humidistat includes a sensing element, made of a material that
is sensitive to air moisture, and a relay amplifier. Increasing
humidity, strengthens the electrical resistance between the metal
conductors of the sensing element. Similarly decreasing
humidity, weakens the electrical resistance between the metal
conductors of the sensing element. These variations are in turn
amplified by the relay amplifier.
Hair Hygrometer
The length of the element increases or decreases as relative
humidity surrounding it changes, and this change in length
actuates the making and breaking mechanism of the electrical
contact points for the cycling of the humidifying or
dehumidifying equipment’s
Resistive Hygrometer
Electrical resistance of hygroscopic salts like calcium chloride,
lithium chloride, etc. varies with changes in humidity and this
property makes them suitable to be used for humidity control and
measurement
Capacitive Hygrometer
Capacitive hygrometer sensors use a capacitor that is sensitive to
the amount of water vapour in the air to measure humidity. It
consists of a hygroscopic dielectric material placed between a pair
of electrodes. In capacitive hygrometer sensors, changes in the
amount of water vapor in the air alter the capacitance. This
change in capacitance is proportional to a change in relative
humidity.
The air enters from inlet and reaches the fan section and during
this journey the pressure of air drops. The fan raises the pressure
which again drops when the air is released into the system.
Primary, secondary and total air: Primary air is the air that
comes out of the outlet. The room air picked up by the primary
air by entrainment is called secondary air. The sum of primary air
and secondary air is called the total air. The induction ratio is
defined as the ratio of total air to primary air.
Blow depends on the initial supply air velocity, temperature
difference between the supply and room air and induction ratio.
System A: The supply and return grilles are located on the same
wall. The system is simple and cheap to construct and is used
mostly for cooling (summer air-conditioning) rather than heating.
System E: The system has two supply registers and two return
grilles and these provide a cross draft. The system is preferred for
heating, i.e., for winter air-conditioning.
Ejection system: The inlet grille ejects the air into the room and
induces sufficient velocity for circulation.
Upward flow system: The supply air enters the space through
openings near the floor. The return air outlets are provided either
in the ceiling or at walls near the ceiling height. The system helps
the return air to carry with it the vitiating products from the bodies
of the occupants and some other objectionable odour. The air
velocity in the system, however, needs to be properly controlled
so that the occupant’s do not face draft.
Classification of Ducts
The ducts may be classified as follows:
Supply air duct. The duct which supplies the conditioned air
from the air conditioning equipment to the space to be
conditioned is called supply air duct.
Return air duct. The duct which carries the recirculating air from
the conditioned space back to the air conditioning equipment is
called return air duct.
Fresh air duct. The duct which carries the outside air is called
fresh air duct.
Low pressure duct. When the static pressure in the duct is less
than 50 mm of water gauge, the duct is said to be a low pressure
duct.
High velocity duct. When the velocity of air in the duct is more
than 600 m/min, the duct is said to be a high velocity duct.
Duct Shape
The ducts may be made in circular, rectangular or square shapes.
From an economical point of view, the circular ducts are preferred
because the circular shape can carry more air in less space. This
means that less duct material, less duct surface, less duct surface
friction and less insulation is needed. From an appearance point
of view, the rectangular duct shape may be preferred because it
presents a flat surface that is sometimes easier to work with in
relation to the finish surface of the room or space. From the
practical point of view, the square duct may be preferred.
Pressure in Ducts
The flow of air within a duct system is produced by the pressure
difference existing between the different locations. The greater
the pressure difference, the faster the air will flow. The following
are the three types of pressures involved in a duct system
Total pressure
The total pressure is the algebraic sum of the static pressure and
dynamic or velocity pressure. Mathematically, total pressure of
air,
PT = Ps + PV
A1V1 = A2V2
Q1 = Q2
m1 = m2
m1 = m2 + m3
Q1 = Q2 + Q3
𝝆𝟏𝑽𝟏𝟐 𝝆𝟐𝑽𝟐𝟐
Ps1 + = Ps2 +
𝟐 𝟐
If the velocity of air (V) flowing through the duct in m/s, then
velocity pressure in the duct,
𝑽
PV = ( )2 mm of water
𝟒.𝟎𝟒
𝐟𝐋
Pf = PV mm of water
𝟐𝐦
𝑽
PV = ( )2 mm of water
𝟒.𝟎𝟒
After the layout of the duct is decided and the requirements of air
quantities at various outlets are known, then the size of the ducts
may be obtained
In case the runs are of different lengths, then the shortest run will
have minimum loss and consequently high pressure at the outlet.
So it is necessary to reduce this high pressure by heavy dampering
or modifying this method to provide higher velocities in shorter
runs
When the velocity of air in the duct reduces, the resulting velocity
pressure difference gets converted to static pressure or a static
regain is obtained. The principle of this method is to size the duct
such that the increase in static pressure (due to static regain) at
each branch offsets the pressure loss in the succeeding section of
the duct. Thus, the static pressure for each branch is the same.
This method involves lengthy and complicated calculations, and
hence is generally not used
Mechanical conditioner
Mechanical conditioner is found out to be a huge application in
the comfortable and technology air conditioning. This mechanical
conditioner is not an autonomous conditioner. Thus, it is
necessary to provide it by the outside cold (supply the cold or
non-freezing liquid), heat (supply the hot water or the steam) and
also by the electricity to drive the fans and some other regulations
devices for air & liquid communications.
When there is a need for both heating and cooling throughout the
year, heat pump air conditioners are installed to provide energy-
efficient heating and cooling from the same units. In addition,
these units provide pleasurable dining experience all year round.
Aesthetics
The air conditioning system should not detract from the aesthetics
of the restaurant environment. Thus, the air conditioning units
should have pleasing appearance aesthetically without occupying
more space within the restaurant.
Energy Efficiency
The energy efficiency of air conditioning system is an important
factor to minimize the overall running costs of the system. Heat
pump air-conditioners are very much economical for heating as
they are able to extract heat from outside air, even at very low
temperatures, with minimum power consumption.
Humidity Control
Bacteriological microorganisms ride on dust particles in low
relative humidity resulting in increased static energy. High
humidity in the hospital enhances the danger of growth of
Pseudomonas Aeruginosa. Humidity contributes to the
prevention of dehydration of exposed tissue. To minimize the
risk, the relative humidity required is 40-65 per cent.
ICU: This unit serves seriously ill patients. Hence need of clean
filtered air without contamination from adjoining areas and
variable temperature range of 24 to 270C are important.
Laboratory & Delivery: The procedures for normal child birth are
considered non invasive and rooms are controlled as similar to
patient’s rooms. Invasive caesarean sections are controlled as
performed in Operation Theatre.
When choosing air conditioning unit for retail outlets, the unit
should be best suited for retail environment’s needs, and cost
effective investment for business. To make decisions, the
advantages and limitations of the various air conditioning units
are listed here:
Advantages:
These types of units are very energy efficient and offer full
control of the surrounding environment, making them an ideal
choice for smaller shops
Wall or floor mounted units are usually smaller than their
alternative counterparts, and hence they have low running
costs, especially if installed in a smaller building.
Cheap installation.
Units can be controlled remotely and hence full control of the
retail environments cooling and heating levels at all times can
be achieved.
Limitations:
Wall units, if not installed correctly, can cause unwanted cold
drafts
These types of units are more obviously seen by occupants,
and could distract from the stylish layout of store.
It creates noise pollution than other types of Air Conditioning
Advantages:
The air conditioning box is kept hidden from sight
Customers cannot see anything other than a small grill
mounted in the ceilings- outlet for introducing conditioned air
Advantages:
Ceiling cassette units have the advantage of being remote
control operated, giving, us the complete control over the
temperature levels of the building.
Placed in the ceiling, this type of unit blends easily into the
store’s environment, allowing to retain shop’s aesthetics
without sacrificing on customer comfort.
Being ceiling mounted; these units won’t take up any of the
valuable sales floor space.
Limitations:
Installation can be most costly for ceiling mounted units, and
can cause some disruption to the business while being fitted.
Ceiling cassette units have to be accessed from below when
carrying out servicing, which may need to be done only during
shop closing hours.
Textile industry
The air-conditioning plays an important role in textile industry
and is essential for the production of quality textile products in
addition to reduction in wastage. The industries producing cotton,
silk, rayon, wool and nylon require maintenance of specific
relative humidity during manufacturing process. The finished
fabrics are soft and durable when manufactured under proper
humidity conditions. If these are manufactured under dry
humidity conditions, the finished product becomes brittle and
weak.
Photographic industry
In photographic industry, the manufacturing processes require
accurate control of temperature and humidity. The photographic
film is made of cellulose ester, coated with silver salt emulsion.
The photographic paper used for films is manufactured by
applying a coating of emulsion on a particular, highly pure wood
pulp paper. All these processes are carried out under controlled
conditions, as these are sensitive to variations in temperature and
humidity. The dust particles are undesirable during
manufacturing processes in the photographic industry. Special
type of filters are employed to supply clean cool air at the required
humidity. The absolute filters are normally employed as the
filtering media along with pre-filters.
Printing Industry
In printing industry, the required temperature and humidity are in
the range of 23°C to 27°C (296 K to 300 K) and 20% to 50%
relative humidity. In textile printing factory, it is very essential to
maintain correct humidity conditions as low humidity may result
in light prints and high humidity may result in blurring or blots.
Farm Animals
The yield of Jersey cows decreases drastically during summer
months. Low temperature results in more efficient digestion of
food and increase in weight of cow and the milk yield. Animal
barns have to be ventilated in any case since their number density
is usually very large. In many countries evaporative cooling is
used for creating comfort conditions in animal houses
Computer Rooms
These require control of temperature, humidity and cleanliness.
The temperature of around 25 °C and relative humidity of 50% is
maintained in these rooms. The dust spoils the CD drives and
printers etc.; hence the rooms have to be kept clean also by using
micro filters in the air-conditioning system.
Vehicular Air-conditioning
Bus, tram, truck, car. recreational vehicle, crane cabin, aircraft
and ships all require air-conditioning. In bus. tram, aircraft and
ship, the occupancy density is very high and the metabolic heat
and water vapour generated by persons has to be rejected. The
cooling load in these is very high and rapidly changes that
provides a challenge for their design.
Laboratories
This may involve precision measurement to performance testing
of materials, equipment and processes at controlled temperature
and relative humidity. Laboratories carrying out research in
electronics and biotechnology areas require very clean
atmosphere. Many laboratories using high voltage like in
LASERS require very low humidity to avoid the sparking.
Pharmaceutical Industries
In these industries to obtain sterile atmosphere, the airborne
bacteria and dust must be removed in the air-conditioning system
by filters. These industries require clean rooms. If capsules are
made or used in the plant, then air has to be dry otherwise the
gelatin of capsules will become sticky
Marine Air-conditioning
The air-conditioning of the passenger ships as well as cargo ships
is recently developed and is used by many companies of the
world. It may be noted that the general principles of air-
conditioning which apply to land installations are also applicable
to marine, provided all the factors affecting the construction and
operation of a ship are given proper considerations. The system
should be flexible to work under different climates, ranging from
extreme hot to extreme cold as the ship may pass through regions
of different climates. This should be taken into account for
selecting the equipment for outside design conditions.
Comfort Air-Conditioning
Energy of food is converted into chemical energy for functioning
of brain, lungs, heart and other organs and this energy is
ultimately rejected to the surroundings. Also the internal organs
require a temperature close to 35oC for their efficient operation,
and regulatory mechanisms of human body maintain this
Since persons have to spend a major part of their time within the
building, without much exposure to outdoors, the concept of
Indoor .Air Quality (IAQ) has become very important. There are
a large number of pollutants that are emitted by the materials used
in the construction of buildings and brought into the buildings.
IAQ addresses to these issues and gives recommendation for their
reduction to safe limits. Sick building syndrome is very' common
in poorly designed air conditioned buildings due to inadequate
ventilation and use of improper materials. The sick building
syndrome is characterized by the feeling of nausea, headache, eye
and throat irritation and the general feeling of being
uncomfortable with the indoor environment. In developed
countries this is leading to litigation also.