Flashing_Firmware_Procedure_S100_Rev_A
Flashing_Firmware_Procedure_S100_Rev_A
S100
Purpose
This document provides the step by step procedure for flashing firmware on an LSIS S100 VFD using the Smart Copier.
This procedure should be followed whenever an application demands custom application specific firmware or an update to
the latest factory firmware.
For questions or assistance with this procedure please contact LSIS Technical Support.
Phone: 800-891-2941 Email: [email protected]
1. Necessary Items
Smart Copier (the below items are included with purchase) LSIS Order Code: 64090112
o 4 qty AA Batteries
o SD Card
Smart Copier Gender (order both this and the Smart Copier!) LSIS Order Code: 64090124
o 10-pin cable
o Gender Connectors for S100, H100, and iS7
Computer with SD card slot
Flash File
No file extension
LSIS S100 VFD
1
Figure 2
LSIS S100 Firmware Flash Procedure
Rev A_12-13-2016
LSIS VFD Firmware Flash Procedure
S100
10-pin
Gender ribbon cable
Smart
Copier
Figure 3
e. Power down the VFD. The VFD must be powered down when flashing the firmware.
f. Slide the Gender housing back to expose the pins which will be connected to the drives flash port. See
Figure 4.
Plastic housing
slides back
Figure 4
Figure 5 Figure 6
h. Connect the “S100 Main” Gender to the VFD flash port. Take note that the Gender connection direction
changes depending on the drive capacity. This is printed on the Gender board and also explained in
Figures 7 and 8 below.
Top of drive
Top of drive Top
portion of
connector
is not
used
Ground
pin is UP
Ground
pin is
DOWN
Figure 7 Figure 8
3