Chapter Four Fault Analysis Using Z Bus Matrix (2)
Chapter Four Fault Analysis Using Z Bus Matrix (2)
Fault Analysis
Using ZBUS
Matrix
Dr. Javed Ahmed Laghari
Associate Professor
PhD, University of Malaya, Malaysia
[email protected]
As already mentioned, short circuit currents are so much larger than the
steady state values that we may neglect the latter.
However, a good approximation is to represent the bus load by a constant
impedance evaluated at the pre-fault bus voltage i.e.
2
Vi (0)
Z iL *
( B)
S L 3
Symmetrical Fault Analysis Using Bus
Impedance Matrix:
The change on the network voltage caused by the fault with impedance Zf
is equivalent to those caused by the added voltage Vk(0) with all other
sources short circuited.
Zeroing all voltage sources & representing all components, loads by their
appropriate impedances. We obtain the thevenin’s circuit shown in Figure.
The bus voltage changes caused by the fault in this circuit are represented
by the column vector:
V1
Vbus Vk (C )
Vn
From thevenin’s theorem bus voltages during the fault are obtained by
superposition of the prefault bus voltages and the changes in the bus
voltages given by: V ( F ) V (0) V ( D)
bus bus bus
4
Fault Analysis Using ZBus Matrix
We have already obtained the node voltage equation for an n-bus network
in admittance matrix derivation. The injected bus currents are expressed in
terms of the bus voltages (with bus 0 as reference) i.e
I bus Ybus Vbus (E )
Where Ibus is the bus current vector entering the bus and Ybus is the bus
admittance matrix. The diagonal element of each bus is the sum of the
admittances connected to it. i.e m
Yii Yij ji (F )
j 0
Where yij (lower case) is the actual admittance of the line i-j.
Writing the above 0 Y11 Y1k Y1n V1
matrix equation in terms
of its elements, we have I k ( F ) Yk1 Ykk Ykn Vk (H )
0 Yn1 Ynk Ynn Vn 5
Fault Analysis Using ZBus Matrix
Or I bus ( F ) Ybus Vbus (I )
1
Solving for ∆Vbus, we have Vbus Ybus I bus ( F ) Zbus I bus ( F ) (J )
Where Zbus = Y -1bus is known as the bus impedance matrix. Substituting this
in equation (D), the bus voltage vector during the fault becomes:
Vbus ( F ) Vbus (0) Z bus I bus ( F ) (K )
In the thevenin’s circuit of Figure, current entering every bus is zero except
at the faulted bus. Since the current at faulted bus is leaving the bus, it is
taken as a negative current entering bus k.
Thus, nodal equation applied to the thevenin’s circuit in Figure becomes:
A three phase fault with a fault impedance Zf = j0.16 per unit occurs at bus
3 in the network given below. Using the bus impedance matrix method,
compute the fault current, the bus voltages and the line currents during the
fault.
Solution:
9
Solution:
In this example the bus impedance
matrix is obtained by finding the
inverse of the bus admittance matrix.
10
Solution:
1 1 1 0 j 0 .4
y13
z13 0 j 0.4 0 j 0.4 0 j 0.4 j 2.5
1 1 1 0 j 0 .4
y23
z23 0 j 0.4
j 2.5
0 j 0.4 0 j 0.4
The generator & transformers impedances are need to be converted in
admittances. 1 1 1 0 j 0 .2
y( G T )1
0 j 0.2 0 j 0.2
j5
Z (G T )1 j 0.1 j 0.1
1 1 1 0 j 0 .4
y ( G T ) 2
Z ( G T ) 2
j 0.2 j 0.2
0 j 0.4 0 j 0.4
j 2.5
Y11 y12 y13 y(G T )1 j1.25 j 2.5 j 5 j8.5
Y22 y12 y23 y(G T ) 2 j1.25 j 2.5 j 2.5 j 6.25
Using MATLAB inverse function inv, the bus impedance matrix is obtained:
j 0.16 j 0.08 j 0.12
Z Bus j 0.08 j 0.24 j 0.16
j 0.12 j 0.16 j 0.34
For a fault at bus 3 with fault impedance Zf =j0.16 per unit, the fault current
is given by:
V3 (0) 1 .0
Ik (F )
Vk (0)
; I3 (F ) j 2.0 p.u
Z kk Z f Z 33 Z f j 0.34 j 0.16
12
Solution:
The bus voltages during the fault are calculated as below:
Vi ( F ) Vi (0) Z ik I k ( F )
V1 ( F ) V1 (0) Z13 I 3 ( F ) 1.0 ( j 0.12) ( j 2.0) 1 0.24 0.76 p.u
V2 ( F ) V2 (0) Z 23 I 3 ( F ) 1.0 ( j 0.16) ( j 2.0) 1.0 0.32 0.68 p.u
V3 ( F ) V3 (0) Z 33 I 3 ( F ) 1.0 ( j 0.34) ( j 2.0) 1.0 0.68 0.32 p.u
Note by J.A.Laghari: It may be noted that according to theory, the voltage at
faulted bus must be zero. However, in the above, voltage at faulted bus V3 is not
zero, but 0.32 p.u. Why?
Answer:- In the example, ground impedance is provided, therefore, there exists
some voltage due to ground impedance. If ground impedance is zero, then voltage
at bus 3 will be zero as proved below.
Proof By J.A.Laghari:
Vk (0) 1.0
Ik (F ) ; I 3 ( F ) V3 (0) j 2.941 p.u
Z kk Z f Z 33 Z f j 0.34 0
V3 ( F ) V3 (0) Z 33 I 3 ( F ) 1.0 ( j 0.34) ( j 2.941) 1.0 1.0 0 p.u
13
Solution: For current, actual impedance
The short circuit currents in the lines are: is used denoted by small z as
written in the formula.
Vi ( F ) V j ( F )
I ij ( F ) ;
zij
V1 ( F ) V2 ( F ) 0.76 0.68 0.08
I12 ( F ) j 0.1 p.u
z12 j 0.8 j 0.8
V1 ( F ) V3 ( F ) 0.76 0.32 0.44
I13 ( F ) j1.1 p.u
z13 j 0.4 j 0.4
V2 ( F ) V3 ( F ) 0.68 0.32 0.36 j 0.9 p.u
I 23 ( F )
z23 j 0.4 j 0.4 Answer
If Fault Occurred at Bus 2:
For a fault at bus 2 with fault impedance Zf =j0.16 per unit, the fault current
is given by:
Vk (0) V2 (0) 1.0 1.0
Ik (F ) ; I2 (F ) j 2.5 p.u
Z kk Z f Z 22 Z f j 0.24 j 0.16 j 0.4
14
Solution:
The bus voltages during the fault are calculated as below:
Vi ( F ) Vi (0) Z ik I k ( F )
V1 ( F ) V1 (0) Z12 I 2 ( F ) 1.0 ( j 0.08) ( j 2.5) 1 0.2 0.8 p.u
V2 ( F ) V2 (0) Z 22 I 2 ( F ) 1.0 ( j 0.24) ( j 2.5) 1.0 0.6 0.4 p.u
V3 ( F ) V3 (0) Z 32 I 2 ( F ) 1.0 ( j 0.16) ( j 2.5) 1.0 0.4 0.6 p.u
The short circuit currents in the lines are:
Vi ( F ) V j ( F )
I ij ( F ) ;
zij
V1 ( F ) V2 ( F ) 0.8 0.4 0.4
I12 ( F ) j 0.5 p.u
z12 j 0.8 j 0.8
V1 ( F ) V3 ( F ) 0.8 0.6 0.2
I13 ( F ) j 0.5 p.u
z13 j 0.4 j 0.4
15
Solution:
V3 ( F ) V2 ( F ) 0.6 0.4 0.2
I 32 ( F ) j 0.5 p.u
z32 j 0.4 j 0.4
If Fault Occurred at Bus 1:
For a fault at bus 1 with fault impedance Zf = j0.16 per unit, the fault current
is given by: Vk (0)
Ik (F ) ;
Z kk Z f
V1 (0) 1.0 1.0
I1 ( F ) j 3.125 p.u
Z11 Z f j 0.16 j 0.16 j 0.32
The bus voltages during the fault are calculated as below:
Vi ( F ) Vi (0) Z ik I k ( F )
V1 ( F ) V1 (0) Z11 I1 ( F ) 1.0 ( j 0.16) ( j 3.125) 1 0.5 0.5 p.u
V2 ( F ) V2 (0) Z 21 I1 ( F ) 1.0 ( j 0.08) ( j 3.125) 1.0 0.25 0.75 p.u
V3 ( F ) V3 (0) Z 31 I1 ( F ) 1.0 ( j 0.12) ( j 3.125) 1.0 0.375 0.625 p.u
16
Solution:
The short circuit currents in the lines are:
Vi ( F ) V j ( F )
I ij ( F ) ;
zij
V2 ( F ) V1 ( F )
I 21 ( F )
z 21
0.75 0.5 0.25
I 21 ( F ) j 0.3125 p.u
j 0.8 j 0.8
V3 ( F ) V1 ( F )
I 31 ( F )
z31
0.625 0.5 0.125
I 31 ( F ) j 0.3125 p.u
j 0.4 j 0.4
V2 ( F ) V3 ( F ) 0.75 0.625 0.125
I 23 ( F ) j 0.3125 p.u
z23 j 0.4 j 0.4
Answer 17
This example is taken from Book Modern Power
Example System Analysis by D.P.Kothari, Chapter 9, Example 9.6.
Solution:
In this example the bus
impedance matrix is obtained
by finding the inverse of the
bus admittance matrix.
Ik (F )
Vk (0) V (0) 1.0
; I4 (F ) 4 j 7.37463 p.u
Z kk Z f Z 44 Z f j 0.1356 0
The bus voltages during the fault are calculated as below:
Vi ( F ) Vi (0) Z ik I k ( F )
V1 ( F ) V1 (0) Z14 I 4 ( F ) 1.0 ( j 0.0780) ( j 7.37463)
V1 ( F ) 1 0.57522 0.4248 p.u
V2 ( F ) V2 (0) Z 24 I 4 ( F ) 1.0 ( j 0.0719) ( j 7.37463)
Thank You
24