DC system design TCE
DC system design TCE
DESIGN GUIDE
FOR
DC SYSTEM
REV.NO R1 R2 R3 R4 ISSUE
REVISION STATUS
R3 99-03-02
ISSUE
R3
CONTENTS
PART-A
LEAD ACID BATTERY
7.0 REFERENCES 13
ISSUE
R3
CONTENTS
PART-B
NICAD BATTERY
SL.NO. TITLE SHEET NO.
1.0 SCOPE 35
8.0 INSTALLATION 42
11.0 REFERENCES 45
PREFERRED DIMENSIONS 47
TEMPERATURE CORRECTION
FACTOR CURVES 64
APPENDIX-2 SAMPLE CELL SIZING CALCULATION 67
CELL SIZING WORK SHEET 69
ISSUE
R3
CONTENTS
PART-C
BATTERY CHARGER
SL.NO. TITLE SHEET NO.
1.0 SCOPE 75
3.0 DISCUSSION 79
4.0 ENCLOSURES
i) FLOAT CUM BOOST
CHARGER WITH TCE.M2-EL-CW-S-2631 R1
2 x 100% BATTERIES
ISSUE
R3
PART-A
LEAD ACID BATTERY
ISSUE
R3
1.0 SCOPE
1.1 This section (Part –A) of this guide pertains to lead acid batteries and
also includes a few recommendations applicable to NiCad batteries
also like selecting voltage levels. The sizing criteria for Nickel
Cadmium batteries are dealt in Part – B of this design guide and
Part – C of this guide covers details about Battery chargers .
2.1 The plante type cells are more rugged, need less maintenance and
have a life expectancy of about 15-18 years, which is 5-7 years longer
than that for tubular type. However, the plante type battery is costlier
than the tubular type. All the manufacturers make tubular cells while
very few manufacturers make plante cell.
2.2 The cells with tubular plate construction are smaller in size than the
plante type for a given AH rating.
2.3 The following types of tubular cells are available in the market in
addition to standard variety :
2.4 The capacity of HDP cells under short duration discharge conditions
are higher than that of normal tubular batteries and are comparable to
that of Plante type batteries. Hence the capacity of battery required
will be smaller than that with the standard performance cells for
applications requiring high discharge currents for short duration.
Hence these cells are preferred for power plant applications.
ISSUE
R3
2.6 The operating experience of the MF-VR and LM type cells for large
capacities is limited and very few manufacturers make the same.
Hence the sizing of these cells is not being discussed in the present
guide and use of these cells may be decided on case to case basis.
2.7 The recommended float voltage for lead acid batteries is between
2.16 V and 2.25V/ cell. The recommended boost charging duration is
10 hours in case of smaller capacity batteries and 14 to 16 hours for
larger capacities (1000 AH and above). The recommended maximum
boost charger voltage is 2.75 V/cell. The recommended equalising
charge voltage is 2.33 VpC.
3.1 The voltage level selection for the plant shall consider the following
aspects :
a) Quantum of power
3.2 For the same power requirement, the battery room size, and battery
cost with higher voltage will be higher than those with lower voltage.
However, the lower voltage requires higher current for the loads and
hence to meet this current and to limit the voltage drop within limits
cable sizes will be higher than those with higher voltage. Considering
all the aspects following voltage levels are recommended.
ISSUE
R3
ISSUE
R3
4.1.2 For large power units (500 MW and above) and nuclear power plants,
for each unit, the 220V DC unit loads shall be divided into two
categories, e.g.
ISSUE
R3
cater power loads and the third one will be catering control loads.
For switchyard , two (2) nos. 100 % batteries shall be provided for
large stations with 220 kV switchyard and for all plants having 400 kV
switchyard. The DCDB shall have two bus sections with bus coupler
open with each section from different source and duplicate outgoing
feeders from two different bus section.
For coal handling plants DC loads – one (1) 100 % battery and a tie
feeder from station DCDB shall be provided. The DCDB shall have
one bus section with two incomers and tie feeder from station DCDB
normally kept open. If distance is large , from voltage drop point of
view, two(2) nos. 100 % batteries shall be provided.
The battery and charging equipment for each gas turbine is supplied
by gas turbine supplier as part of the package.It is recommended to
have each unit battrery rated to cater two gas turbine units.and a tie
feeder is provided between one unit DCDB to another unit DCDB.
4.1.4 Separate batteries with chargers are required to be provided for UPS
for power plants. For details please refer to design guide M6-CL-AU-
G-715-6011 for UPS.
ISSUE
R3
ISSUE
R3
a) Duty cycle
b) End of the duty cycle voltage
c) Temperature correction factor
d) Compensation for ageing
e) Design margin
c) The duration for which each type of D.C. load will have to be
supplied by battery when the normal power supply fails is
different. The same may be continuous or for short time duration
or momentary. In a typical power plant the DC power, control &
protection loads and their classification based on duration for
which they need to be supplied are as follows.
ISSUE
R3
ISSUE
R3
e) I&C battery for power plant application shall be sized to cater the
loads for half hour. The loads to be considered shall be the
maximum load of I&C system at any operating condition viz
starting, running and tripping/stopping.
ISSUE
R3
Correction factor = / K \
for the lowest | 1 + -------- (27-T) |
ISSUE
R3
When the D.C. loads are more or less final at the time of battery
sizing for tender specification purposes and/or the battery sizing is
being done for a similar plant already executed, no design margin is
considered necessary. If the sizing is being done for a new type of
project or with very little confirmed loads, a design margin of 10 to
15% shall be provided over the final capacity arrived.
While sizing the battery for nuclear power plant applications, it shall
be noted that the "margins" required by IEEE STD.323-1273. 6.3.15
& 6.3.3 are to be applied during "Qualification" and are not related to
"design margin".
The plante and tubular high discharge performance cells have better
capacity factors at the short duration discharges (1 hour, 2 hours
etc.). For durations less than one hour, the above types of cells have
higher capacity factor than the tubular standard discharge
performance cell. Hence for power plant application and for
applications where short duration loads are appreciable high
discharge performance cell shall be used.
ISSUE
R3
6.0 INSTALLATION
6.2 The flooring shall be provided with acid resistance tiles, a dished floor
drain and drainage piping for collecting spilled acid. The spilled acid
shall be diluted before discharging to the outside storm water
drainage system.
6.3 Acid proof paint shall be provided on walls upto 2.3m height.
6.4 A wash basin shall be provided for emergency drenching of face and
body.
6.6 Separate cable(s) shall be provided for each polarity of the outgoing
battery leads. If the cables are unarmoured they shall be taken in
separate conduits and the conduits shall be PVC coated for
protection against corrosion. Routing of any cables in cable-trays
through battery room shall be avoided.
6.8 During float or boost charging of the lead acid battery hydrogen gas is
generated. The volume of hydrogen gas generated depends on the
amount of charging current. Also, the float current demand of a fully
charged battery will double approximately for every 10deg.C rise
above the base temperature of 27deg.C. Each fully charged cell
produces 4.5 x 10-4 Cu.m (0.016 Cu.pt) hydrogen gas per hour per
charging amperes in an ambient of 25deg.C to 27deg.C. Hydrogen
explosive concentration is reached if the explosives mixture is three
percent of the volume of room air.
ISSUE
R3
6.10 Lighting fixtures shall be vapour-proof type with reflectors painted with
anticorrosive epoxy-paint. Lighting switch should be outside the
battery room.
7.0 REFERENCES
7.3 IEEE Std 485-1273 : Recommended practice for sizing large lead
acid storage batteries for Generating
Stations and Sub-stations.
ISSUE
R3
APPENDIX-1
STEAM TG
500MW 120MW 210MW
1 a) Bearing oil pump 13kW 15kW 13kW
b) Bearing oil pump for BFPT 2x5.5kW --- ---
c) Bearing oil pump for MBFP 11kW --- ---
ISSUE
R3
APPENDIX-1 (Cont’d)
STEAM TG
500MW 120MW 210MW
Continuous Loads
1 Annunciator window (each) ß---------------------5W -----------------à
2 Indicating lamp (each) ß -----5-10W For filament type ----à
ß ----1 W For cluster LED type type ---à
3 Auxiliary relays (each) <--------------------3W--------------------------à
4 Auxiliary contactors (each) <--------------------10W-----------------------à
5 Semaphore indicator (each) <--------------------3W------------------------à
6 Control room emergency <---------------------1kW---------------------à
lighting
7 FSSS load ß-------------------10kW---------------------à
NOTES:
1. The data for 120MW and 210MW units are taken from the designed
data for GIPCL and Bhatinda units. All DC motor loads,
electromagnetic valve loads, FSSS loads, instrumentation & control,
UPS loads, other turbine generator supervisory loads should be as far
as possible ascertained from the manufacturers.
ISSUE
R3
APPENDIX-2
CELL DATA
RATING AND DESIGNATION
1 Ampere-Hour Rating
2. Designation
Notes:
2.1 The positive plates shall be designated by the letter 'T' for tubular and
'P' for plante.
G - for glass;
H - for hard-rubber;
P - for plastics;
W - for wood, lead-lined; or
ISSUE
R3
ISSUE
R3
APPENDIX-2 (Cont’d)
CELL DATA
Capacities and Dimensions of
Tubular Cells
-----------------------------------------------------------------------------------------------
Capacity at Maximum Overall Dimensions
10-Hour Rate ----------------------------------------------------------------------
Length Width Height
(1) (2) (3) (4)
Ah mm mm mm
---------------------------------------------------------------------------------------------
20 105 170 365
40 105 170 365
60 140 170 365
80 165 190 365
100 190 190 450
120 190 190 450
150 190 190 550
200 265 215 550
300 320 215 550
400 380 215 550
500 390 235 550
600 390 235 715
800 515 235 715
1000 515 300 750
1500 450 400 865
2000 500 450 865
2500 650 450 865
4000 900 480 1240
5000 900 480 1240
6000 900 500 1240
7000 1100 500 1240
8000 1100 500 1240
---------------------------------------------------------------------------------------------
NOTES :
ISSUE
R3
3. For capacities not covered in this table, the cell dimensions shall
not exceed the dimensions of the cell of next higher size covered
by this table.
APPENDIX - 2 (Cont’d)
Source : IS 1651-1991
ISSUE
R3
APPENDIX - 2 (Cont’d)
CELL DATA
NOTE : The above data is applicable for plante cells also. The capacities for
Type-I HDP cells are same as above for discharge rates of 3 hour, 5
hour and 10 hours (ISS does not specify capacities at other discharge
rates for Type-I cells).
ISSUE
R3
ISSUE
R3
ISSUE
R3
APPENDIX - 2 (Cont’d)
CELL DATA
Capacities and Dimensions: Plante Cells
-----------------------------------------------------------------------------------
Capacity at Maximum Overall Dimensions
10-Hour Rate ----------------------------------------------------------
Length Width Height
(1) (2) (3) (4)
Ah mm mm mm
-----------------------------------------------------------------------------------
2. For capacities not covered in this table, the cell dimensions shall
not exceed the dimensions of the cell of next higher size covered
by this table.
Source : IS 1652-1995
ISSUE
R3
L6 = 84 A
L5 = 186 A
L3 = 46A
L2 = 30A
L1 = 13 A
600
SECTION-1 120
1 60
SECTION-2
SECTION-3
SECTION - 4
DURATION ( MIN )
APPENDIX - 3
ISSUE
R3
LOAD TABULATION
ISSUE
R3
ISSUE
R3
2.3 The cell sizing data that will be useful in filling out the cell sizing work
sheet is derived from the duty cycle diagram and tabulated as below :
1. L1+L2+L3+L4 983 1
2. L1+L2+L3+L5+L6 359 59
3. L1+L2+L6 127 60
4. L1 13 480
--------------------------------------------------------------------------------
2.4 Capacity rating factors (KT) are derived from the table for HDP, Type
II tubular lead acid cells enclosed in Appendix-2. (These can be read
from the curves enclosed in Appendix-2 also).
2.5 Sh.29 &30 shows the way in which the cell sizing work sheet and the
KT rating factor would be used to size the battery for the duty cycle
indicated.
ISSUE
R3
NOTES :
2. If plante cells are being sized, the data on capacities for Type II HDP
cells enclosed in Appendix-2 can be used sizing procedure also
remains same except the value of 'K' in formula for temperature
correction factor (Refer cl.5.2.3).
ISSUE
R3
Project : Date :
Lowest Expected Minimum 1 Min.:1.75V DC Cell Chloride Cell Tubular
Electrolyte Temp : 17oC Cell Voltage : Others: 1.85V DC Mfg. : India Type : HDP, Type-II Sized By : RRN
LOAD DATA :
A1= 983 A, M1= 1 Min; A2 = 359 A, M2 = 59 Min.
A3= 127 A, M3= 60 Min; A4 = 13 A, M4 = 480 Min.
A5= A, M5= Min; A6 = A, M6 = Min.
ISSUE
R3
Section - 6: IF LOAD CYCLE HAS MORE THAN 5 LOAD PERIODS, CONTINUE FURTHER IN SIMILAR MANNER.
Section - 8:
Maximum Section Size = 916
Section - 9:
Random Section Size = -
Section - 10:
Temperature Correction Factor = 1.043
Section - 11:
Design margin = 1.0
Section - 12:
Aging Factor = 1.25
Section - 13:
Uncorrected size = (8) + (9)= 916+ - = 916
Section - 14:
All capacity required = (13) x (10) x (11) x (12) = 916 x 1.043 x 1.0 x 1.25 = 1193 AH
Section - 15:
When AH capacity required is larger than the nearest standard cell, the next larger size cell is required.
Section - 16:
Therefore AH capacity of the cell = 1200 AH
ISSUE
R3
ISSUE
R3
Project : Date :
ISSUE
R3
Section - 6: IF LOAD CYCLE HAS MORE THAN 5 LOAD PERIODS, CONTINUE FURTHER IN SIMILAR MANNER.
Section - 8:
Maximum Section Size =
Section - 9:
Random Section Size =
Section - 10:
Temperature Correction Factor =
Section - 11:
Design margin =
Section - 12:
Aging Factor =
Section - 13:
Uncorrected size = (8) + (9)=
Section - 14:
All capacity required = (13) x (10) x (11) x (12)
Section - 15:
When AH capacity required is larger than the nearest standard cell, the next larger size cell is required.
Section - 16:
Therefore AH capacity of the cell = AH
ISSUE
R3
PART-B
NICAD BATTERY
ISSUE
R3
1.0 SCOPE
2.1 The most common electrode design for the nickel-cadmium batteries
is the pocket plate type designated by 'P' as per IS:10918-1274. The
active constituents are cadmium in the negative plates and nickel in
the positive plates. The active material in each electrode is enclosed
in metal pockets of finely perforated steel strips. Each plate is
insulated from the next by thin plastic separators. The electrolyte is a
solution of potassium hydroxide in de-ionised water. The resulting
electrochemical reaction produces a nominal discharge voltage of 1.2
volts per cell. The electrolyte takes no part in these reactions and acts
only as an ion conductor. The other electrode designs are sintered
plate(s) and tubular plate(T).
2.2 The cells are further classified as H,M,L and X type based on the
discharge performance of individual designs. The plate type, and the
number of such plates employed in a cell indicate the cell type and
determine its discharge characteristics.
ISSUE
R3
3.4 The measure of performance is not the rated Ah capacity but the
battery cell construction. H type cells have thin plates (more plate
area per amount of active material) giving excellent high rate
performance. M and L types have medium thickness plates and thick
plates respectively. For example H-type cell at 15 minutes discharge
can deliver about twice the discharge current compared to an L-type
cell of equal rated capacity.
3.5 The published discharge data for nickel-cadmium cells are most
commonly available in tabular form, in which the current, available
from each cell type, is stated for a given discharge time and end of
discharge voltage. For intermediate times and voltages, it is
necessary to interpolate between the known values (IEEE 1115-
1992).
3.6 There are three manufacturers in India, AMCO (in collaboration with
SAFT,France), SABNIFE POWER SYSTEMS LTD., Hyderabad in
collaboration with M/s Sabnife, Sweden and Punjab Power Packs Ltd.
in collaboration with M/s Alcad Ltd. UK. The available tabulated
discharge performance data from M/s SABNIFE on different types of
cells for varying end cell voltages, is enclosed at Appendix-1.(The cell
designations of Sabnife make cells confirm to IS.S10918-1274). More
details if required, may be obtained from the manufacturers.
Example:
3.7.1 Life of the battery is shortened when temperatures are above the
reference temperature of 25°C. Generally it has been estimated that
Ni-Cd battery loses approximately 15% of its life for every 8°-10°C
electrolyte temperature above 25°C.
To fully charge, a cell will require an Ah input, from the charger to the
battery, of 160% of the capacity. For example a 100Ah cell requires
160 Ah to fully charge it from a fully discharged state. If the charger
can supply 20A then the time for charging will be 160/20 i.e. 8 hours.
3.10 The electrolyte specific gravity (S.G.) is not an indication of the state
of charge in Ni-Cd cells since it does not change appreciably during
charge or discharge. The acceptable limits to be maintained in normal
service (of the electrolyte S.G) are 1.17-1.19 at a reference
temperature of 20° at the specified level line of the cell.
4.2 Applications of High rate (H type) batteries are to deliver high currents
(>3.5C5 A) for very short discharge times of 20 mins and less. Typical
ISSUE
R3
uses are
4.3 Medium rate (M type) applications are load duties having discharge
times between 3 hours to 30 min, for examples:
Example are:-
- Scada/Computer system
ISSUE
R3
d) Gases given off by Ni-Cd batteries are not corrosive and normal
building materials/room can be used and therefore the battery
can be kept in the electrical/mechanical equipment room, if it
becomes necessary to do so. However, adequate ventilation is
necessary as stated under installation (Clause 7.0).
5.1 In the standby battery usage for continuous parallel operation with
rectifier, with occasional battery discharge, the recommended
charging values are as follows:
Charging in service:
ISSUE
R3
5.2 For use of batteries without any boost charge, the float charge voltage
is 1.47-1.5V pC for L type, 1.46-1.49V pC for M type and 1.45-1.47V
pC for H type.
6.1
Nominal System Voltage 24 48 110 220
No. of Cells
For continuous operation with 19 37-38 84-86 168-172
float charging
6.4 Example :
ISSUE
R3
99
Thus permissible cell end voltage =---- = 1.16 volts
85
ISSUE
R3
When the batteries are subjected to discharge and then charge, they
get charged gradually. The state of charge at any point depends on
the initial state of charge, the recharge voltage, the charge current
limit and the charging voltage. The state of charge factor can be
determined by consulting the charging curves provided by Battery
manufacturers and shall be considered if the selected float charge
voltage is 1.47-1.50V (Ref. item 5.2 above).
The cells float charged at 1.4-1.42V pC (Ref item 5.1 of above) are
not expected to lose much charge if the schedule for equalising
charges is adhered to. Hence no provision is made for float charge
factor in cell sizing calculations.
8.0 INSTALLATION
8.1 Ni-Cd battery can be installed in a separate room or in the same room
as the electrical/mechanical equipment since the gases given off are
not corrosive. However, a separate room specially for large size
batteries would be preferable. The typical battery room layout is
enclosed in Part – A of this design guide for information.
ISSUE
R3
8.3 Hydrogen and oxygen evolved from a battery during charge can form
an explosive mixture. For this reason adequate ventilation is to be
provided to keep the hydrogen content to a low value. The maximum
gas evolution occurs at end of charge or on overcharge. Since
hydrogen is lighter than air, openings/grilles to take away the gas
mixture should be located as high as possible in the room.
9.1 The duty cycle profile (the load currents and the durations for which
the battery is to be sized) shall be prepared.
9.2 The factor KT related to the specified end cell voltage and load
duration is readily available for lead-acid cells. But for Ni-Cd cells, this
shall be computed from the discharge data tables (enclosed at
Appendix-1). Wherever the required data is not available, it can be
interpolated/extrapolated from the known values (Refer item 3.5
above).
Select the cell type most suited to the duty profile required (Ref. item
4.0).
ISSUE
R3
9.5 Select the cell size, looking at the discharge tables, that can meet the
short duration load current requirements.
Crated
9.6 Calculate the capacity rating factors ( KT = ------- ; t = duration )
It
for different load currents & corresponding durations as above, from
the discharge tables.
10.1 Load profile, required end cell voltage, factors to be considered and
other data shall be provided to the bidder and the bidder is allowed to
offer cell size other than the one indicated (determined by TCE
through cell sizing calculations as above) providing the supporting
calculations.
10.2 Bidder may be allowed to offer cell type other than the one indicated,
if the offered cell type & size meets the load cycle duty requirements
satisfactorily (bidder to establish the same through supporting
calculations). This is being recommended as many a time the load
profile consists of mixed type of loads (ie. of different durations) and
thus more than one type (but with different ratings) can meet the
requirements satisfactorily.
11.0 REFERENCES
11.6 IEEE : 323-1273 IEEE Standard for qualifying class IE equipment for
Nuclear Power Generating Stations.
ISSUE
R3
APPENDIX-1
CELL DESIGNATION
Source : IS:10918-1274
ISSUE
R3
APPENDIX-1 (contd)
PREFERRED DIMENSIONS
NOTE 2 -- The widths relate to the overall width dimension of the cell
excluding the thickness of the lug flanges.
NOTE 3 -- The maximum height relates to the total height dimensions over
terminals or closed cell valves. The data for heights given in
table are maximum values, no lower limits being stated.
Source : IS:10918-1274
ISSUE
R3
KPL RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 1.00 VOLT PER CELL
KPL580P 580 1030 914 768 644 596 490 400 319 261 186 116 74 59.7
KPL655P 655 1150 1020 860 722 678 552 448 360 295 210 131 83.5 67.5
KPL730P 730 1270 1120 955 801 743 612 494 402 329 234 146 93.1 75.2
KPL810P 810 1390 1230 1050 880 808 672 540 446 365 259 162 103 83.4
KPL885P 885 1500 1330 1140 966 886 736 594 487 398 283 177 113 91.2
KPL960P 960 1610 1420 1230 1050 964 800 646 528 432 307 192 122 98.9
KPL1100P 1100 1900 1690 1430 1200 1090 912 729 605 495 352 220 140 113
KPL1210P 1210 2080 1840 1570 1320 1210 1010 810 666 545 387 242 154 125
KPL1320P 1320 2250 1992 1710 1450 1330 1100 891 726 594 422 254 168 136
KPL1440P 1440 2410 2140 1840 1570 1440 1190 969 792 648 461 288 184 148
ISSUE
R3
KPL RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 1.02 VOLT PER CELL
KPL580P 580 979 862 724 603 554 462 382 311 257 183 115 73.5 59.5
KPL655P 655 1086 964 810 675 627 519 426 349 290 206 130 83.1 67.1
KPL730P 730 1198 1060 899 750 693 581 474 391 323 230 145 92.5 74.8
KPL810P 810 1310 1162 988 826 760 642 522 435 359 255 160 103 83
KPL885P 885 1412 1254 1073 904 832 702 576 474 391 279 175 112 90.7
KPL960P 960 1514 1344 1158 982 904 759 621 513 424 302 190 122 98.4
KPL1100P 1100 1792 1594 1346 1124 1030 872 709 591 487 347 218 140 113
KPL1210P 1210 1960 1740 1478 1236 1138 963 784 649 536 381 240 154 124
KPL1320P 1320 2118 1883 1610 1354 1246 1050 859 708 584 416 261 163 135
KPL1440P 1440 2266 2020 1735 1470 1352 1134 932 771 638 454 285 183 143
ISSUE
R3
KPL RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 1.02 VOLT PER CELL
KPL580P 580 979 862 724 603 554 462 382 311 257 183 115 73.5 59.5
KPL655P 655 1086 964 810 675 627 519 426 349 290 206 130 83.1 67.1
KPL730P 730 1198 1060 899 750 693 581 474 391 323 230 145 92.5 74.8
KPL810P 810 1310 1162 988 826 760 642 522 435 359 255 160 103 83
KPL885P 885 1412 1254 1073 904 832 702 576 474 391 279 175 112 90.7
KPL960P 960 1514 1344 1158 982 904 759 621 513 424 302 190 122 98.4
KPL1100P 1100 1792 1594 1346 1124 1030 872 709 591 487 347 218 140 113
KPL1210P 1210 1960 1740 1478 1236 1138 963 784 649 536 381 240 154 124
KPL1320P 1320 2118 1883 1610 1354 1246 1050 859 708 584 416 261 163 135
KPL1440P 1440 2266 2020 1735 1470 1352 1134 932 771 638 454 285 183 143
ISSUE
R3
KPL RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 1.05V PER CELL
KPL5P 5 10.1 8.3 6.8 5.5 5 4.2 3.3 2.7 2.2 1.5 1 0.6 0.5
KPL11P 11 22.2 18.4 15 12.2 11 9.2 7.3 5.8 4.8 3.4 2.2 1.4 1.1
KPL19P 19 38.3 31.7 25.9 21 18.9 15.9 12.5 10.1 8.3 6.9 3.7 2.4 1.9
KPL29P 29 58.4 48.4 39.5 32.1 28.9 24.3 19.1 15.4 12.6 9 5.7 3.6 2.9
KPL39P 39 79.6 65.4 52.8 44 40.2 33.1 25.7 20.7 17 12.2 7.6 4.8 3.9
KPL49P 49 102 82.7 67.9 57.3 51.5 42.2 32.3 26 21.3 15.3 9.5 6.1 4.9
KPL60P 60 118 97.9 81.5 69 61.5 51 39.6 31.8 26.1 18.7 11.8 7.4 6
KPL70P 70 133 113 94 76.1 66.9 56 45.5 36.6 30 20.5 13.7 8.6 6.9
KPL75P 75 151 125 102 79.6 69.6 58.5 47.1 39.5 33.1 23.7 14.7 9.4 7.6
KPL90P 90 175 143 114 90.2 77.7 66 55.2 46.3 38.7 27.8 17.6 11 8.9
KPL100P 100 199 162 129 102 89 76 63.2 53 44.4 31.7 19.6 12.5 10.1
KPL130P 130 244 201 166 123 108 94.5 79.4 66.6 55.7 39.9 25.5 15.9 12.7
KPL155P 155 289 238 193 149 130 112 97.3 81.6 68.3 49.8 30.4 19.5 15.6
KPL190 190 335 277 225 175 153 133 115 98.3 82.2 59.8 37.2 23.4 18.8
KPL220P 220 378 315 258 201 176 154 134 115 95.1 69 43.1 27.4 22
KPL250P 250 416 351 286 225 198 174 153 131 110 78.5 49 31.2 25.1
KPL280P 280 453 382 313 248 220 195 173 148 124 88.5 54.9 35.2 28.3
KPL320P 320 496 414 343 271 245 217 193 164 137 98.6 62.7 39.2 31.4
KPL350P 350 539 447 373 301 272 242 213 180 151 108 68.6 43 34.5
KPL380P 380 581 478 403 317 294 262 232 197 165 113 74.5 47 37.7
KPL410P 410 624 510 432 342 316 284 251 214 179 123 80.4 51 40.9
KPL440P 440 640 573 487 406 375 325 270 228 191 149 86.2 55.8 45.1
KPL480P 480 685 615 526 440 407 352 292 248 208 152 94.1 60.6 48.9
KPL500P 500 814 692 580 480 434 373 314 262 217 160 98 63.7 51.5
KPL580P 580 902 786 658 542 492 420 354 300 250 183 114 73.2 59.1
KPL655P 655 990 880 736 604 550 470 394 333 282 207 128 82.7 56.8
KPL730P 730 1090 970 806 674 619 534 445 375 315 232 143 92.1 74.4
KPL810P 810 1190 1060 896 744 688 596 496 418 350 256 159 102 82.6
KPL885P 885 1280 1140 974 812 750 650 540 455 380 281 173 112 90.2
KPL960P 960 1370 1230 1050 880 814 697 584 491 412 306 188 121 97.9
KPL1100P 1100 1630 1450 1220 1010 939 813 678 570 475 346 216 139 112
KPL1210P 1210 1780 1590 1340 1110 1030 894 744 625 523 383 237 153 123
KPL1320P 1320 1920 1720 1460 1210 1120 975 810 680 568 418 259 167 135
KPL1440P 1440 2050 1840 1580 1320 1220 1050 876 740 622 456 282 182 147
ISSUE
R3
KPL RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 1.10V PER CELL
KPL5P 5 8.3 6.9 5.6 4.6 4.4 3.8 3.2 2.6 2.1 1.5 1 0.5 0.5
KPL11P 11 18.4 15.2 12.3 10.1 9.6 8.4 6.9 5.6 4.6 3.4 2.1 1.3 1.1
KPL19P 19 31.7 26.3 21.3 17.5 16.1 13.5 11.5 9.5 8 5.8 3.7 2.3 1.9
KPL29P 29 48.4 40.2 32.5 26.7 25.3 22.2 18.3 14.8 12.2 8.9 5.6 3.5 2.8
KPL39P 39 65.1 53.8 43.6 36.3 35 30.4 24.5 19.9 16.4 12 7.5 4.8 3.8
KPL49P 49 82.6 68.1 55.1 47.3 45 39 31 25 20.6 15 9.5 5.9 4.8
KPL60P 60 97.4 81 66.6 57.3 54 46.5 37.5 30.6 25.2 18.4 11.6 7.3 5.9
KPL70P 70 111 93.3 76.6 61.9 58 50.6 41.7 35.2 29 21.2 13.5 8.4 6.8
KPL75P 75 128 106 81.2 64.2 60 52.5 43.8 36.1 30.4 22.3 14.5 9.3 7.4
KPL90P 90 147 119 94.7 71 66 58.8 50 42.3 35.6 26.7 17.4 10.9 8.7
KPL100P 100 166 135 106 82 75 66.9 57 48.5 40.8 30.8 19.3 12.4 10
KPL130P 130 202 166 130 99 92 83.1 71 60.8 51.2 38.4 25.1 15.5 12.5
KPL155P 155 240 199 158 117 110 101 87 74.6 62.8 47.1 29.9 19.2 15.4
KPL190 190 278 231 182 140 133 121 105 89.8 75.6 56.7 36.7 23.1 18.5
KPL220P 220 313 262 206 160 151 140 122 105 88.4 66.3 42.5 27 21.7
KPL250P 250 346 289 230 179 169 158 139 120 101 75.6 48.3 30.7 24.7
KPL280P 280 380 317 254 202 192 177 156 135 114 85.2 54.1 34.5 27.8
KPL320P 320 417 349 281 225 215 197 174 150 126 94.8 61.8 38.6 31
KPL350P 350 455 382 308 253 238 218 192 165 139 104 67.6 41.3 34
KPL380P 380 492 413 334 275 258 238 210 180 152 114 73.4 45.2 37.1
KPL410P 410 529 445 361 298 279 258 225 195 164 123 79.2 49.7 40.3
KPL440P 440 546 476 401 333 309 275 235 203 175 133 85 55.2 44.6
KPL480P 480 582 514 435 360 335 297 255 220 190 144 92.7 61 48.5
KPL500P 500 690 578 472 384 363 321 273 233 199 152 96.6 63.4 51
KPL580P 580 770 654 540 440 410 361 310 267 230 174 112 80 58.5
KPL655P 655 850 730 608 496 455 407 350 303 262 197 126 89 66.1
KPL730P 730 935 803 670 552 510 453 388 335 290 219 141 98 73.7
KPL810P 810 1020 876 732 608 565 506 430 370 320 243 156 109 81.8
KPL885P 885 1090 952 802 665 618 550 470 405 350 266 171 119 89.3
KPL960P 960 1160 1030 870 720 670 594 510 440 380 288 185 128 96.9
KPL1100P 1100 1400 1200 1000 828 765 680 582 503 435 338 212 149 111
KPL1210P 1210 1530 1310 1100 912 848 759 645 555 480 363 234 165 122
KPL1320P 1320 1640 1430 1200 990 927 825 705 608 525 395 255 179 133
KPL1440P 1440 1740 1540 1300 1080 1000 891 765 660 570 432 278 195 145
ISSUE
R3
KPL RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 1.14V PER CELL
KPL5P 5 6.9 5.8 4.6 3.7 3.3 2.8 2.3 2 1.7 1.3 0.9 0.6 0.5
KPL11P 11 15.2 12.8 10.2 8.2 7.2 6.2 5.1 4.3 3.7 2.9 2 1.3 1
KPL19P 19 26.3 22.1 17.6 14.2 12.5 10.7 8.8 7.4 6.3 5.2 3.4 2.2 1.8
KPL29P 29 40.2 33.7 25.9 21.7 19.1 16.3 13.4 11.3 9.7 7.6 5.2 3.4 2.7
KPL39P 39 53.1 44.4 36.7 29.8 25.9 21.7 18 15.2 13 10.2 7 4.5 3.6
KPL49P 49 67.2 56.5 46.4 38.6 33.7 27.8 22.7 19.2 16.3 12.8 8.7 5.7 4.6
KPL60P 60 80.7 67.5 54.7 46.5 40.6 33.6 27.5 23.5 20 15.7 10.7 7 5.6
KPL70P 70 92.6 78.2 63.8 50.6 44.1 35.4 29.3 25.1 23 18.3 12.5 8 6.5
KPL75P 75 107 85.7 66.7 52.7 45.9 36.3 30.2 27 23.2 19.4 13.4 8.8 7.1
KPL90P 90 123 98.1 77 58.8 51.2 38.9 32.9 29.4 27.1 22.7 16.1 10.3 8.3
KPL100P 100 139 111 87.5 66.9 58.2 44.2 37.7 33.7 31.1 25 17.8 11.8 9.5
KPL130P 130 170 136 108 82.8 72.3 55.1 47.4 42.2 39 32.5 23.2 14.8 12
KPL155P 155 200 163 129 100 88.1 66.7 58.1 51.8 47.9 40 27.7 18.2 14.7
KPL190 190 231 189 150 118 103 80.7 69.9 62.4 57.6 48.2 33.9 21.9 17.7
KPL220P 220 260 214 171 135 118 93 81.8 72.9 67.4 56.4 39.3 25.6 20.7
KPL250P 250 288 238 191 151 133 105 93.2 83.2 76.9 64.3 44.6 29.2 23.6
KPL280P 280 312 263 211 168 148 118 105 93.7 86.6 72.4 50 32.9 26.6
KPL320P 320 338 290 233 184 163 130 117 104 95.4 80.5 57.1 36.7 29.5
KPL350P 350 365 311 254 201 178 143 128 115 106 88.5 62.5 40.3 32.4
KPL380P 380 400 343 275 218 193 156 140 125 116 95.5 67.8 44 35.4
KPL410P 410 437 370 297 236 207 169 152 136 125 105 73.2 47.7 38.4
KPL440P 440 460 395 330 273 245 201 172 150 138 118 78.5 54.7 44.2
KPL480P 480 490 428 357 296 265 218 186 162 149 129 85.7 59.4 48
KPL500P 500 594 488 406 316 286 236 198 176 160 135 89.2 62.5 50.5
KPL580P 580 662 544 456 362 328 266 224 200 182 155 103 71.7 57.9
KPL655P 655 730 600 506 408 370 296 250 224 204 175 117 81 65.4
KPL730P 730 795 661 556 452 409 332 282 249 228 196 130 90.3 72.9
KPL810P 810 860 722 606 496 448 368 314 274 252 217 145 100 80.9
KPL885P 885 920 790 660 544 490 402 344 300 276 237 158 109 88.4
KPL960P 960 980 856 714 588 530 436 372 329 298 257 171 119 95.9
KPL1100P 1100 1190 992 834 678 609 501 426 372 342 295 196 136 110
KPL1210P 1210 1290 1080 909 744 672 552 471 411 378 324 216 150 121
KPL1320P 1320 1380 1180 990 815 735 603 516 450 414 354 236 163 132
KPL1440P 1440 1470 1280 1070 890 795 654 558 486 447 356 257 178 144
ISSUE
R3
KPM RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 1.00V PER CELL
KPM 11 P 11 40.5 28.7 24 21.1 18.9 14.9 9.3 6.6 5.1 3.5 2.2 1.4
KPM 18 P 18 69.1 49.4 39.2 34.6 31 24.3 15.3 10.8 8.4 5.8 3.6 2.2
KPM 25 P 25 101 71.5 55.2 48 43 33.8 21.3 15 11.7 8.1 5 3.2
KPM 32 P 32 125 89 69.8 61.4 55 43.2 27.2 19.2 15 10.3 6.4 4.1
KPM 39 P 39 149 106 82.8 73 65.4 51.3 32.3 22.8 17.8 12.3 7.8 4.8
KPM 45 P 45 174 124 98.1 86.4 77.4 60.8 38.3 27 21.1 14.5 9 5.9
KPM 55 P 55 199 142 116 102 91.2 71.6 45.1 31.8 24.9 17.1 11 6.7
KPM 60 P 60 229 164 129 113 101 79.7 50.2 35.4 27.7 19.1 12 7.5
KPM 80 P 80 270 204 166 154 141 112 70.6 50.2 38.9 26.8 16 10.5
KPM 100 P 100 325 248 202 187 172 136 85.9 61.1 47.4 32.5 20 12.8
KPM 120 P 120 377 290 236 218 201 159 100 71.4 55.3 38.1 24 15
KPM 145 P 145 457 340 276 254 239 189 120 87 68 46.8 29 18.4
KPM 165 P 165 507 390 320 292 276 217 139 100 78.3 53.9 33 21.2
KPM 190 P 190 556 440 359 331 312 246 157 113 88.6 61 38 24
KPM 210 P 210 594 475 401 369 348 274 175 127 99 68.2 42 26.8
KPM 230 P 230 679 533 441 406 383 302 193 139 109 74.9 46 29.5
KPM 250 P 250 741 590 483 445 419 330 211 152 119 82 50 32.3
KPM 275 P 275 801 635 524 483 455 359 229 166 129 89.1 55 35.1
KPM 300 P 300 843 675 566 522 492 387 247 179 140 96.3 60 37.8
KPM 320 P 320 890 720 606 558 526 415 265 191 150 103 64 40.5
KPM 340 P 340 935 755 648 597 563 443 283 205 160 110 68 43.3
KPM 360 P 360 1060 810 657 607 575 451 295 213 166 116 72 45.3
KPM 380 P 380 1110 853 703 650 616 483 315 228 178 124 76 48.5
KPM 410 P 410 1170 895 749 693 656 514 336 243 190 132 82 51.8
KPM 450 P 450 1450 1050 833 770 729 572 374 270 211 147 90 57.4
KPM 500 P 500 1570 1170 925 855 810 635 415 300 235 164 100 58.8
KPM 555 P 555 1700 1280 1030 949 899 705 461 333 260 181 111 70.8
KPM 600 P 600 1820 1390 1120 1030 980 768 502 363 284 198 120 77.1
KPM 655 P 655 1970 1500 1210 1120 1060 832 544 393 307 214 131 83.5
KPM 710 P 710 2120 1620 1310 1210 1150 902 589 426 333 232 142 90.5
KPM 760 P 760 2230 1700 1410 1300 1230 965 631 456 356 249 152 96.9
KPM 810 P 810 2350 1790 1500 1380 1310 1030 672 486 380 265 162 103
KPM 830 P 830 2550 1920 1540 1420 1350 1060 691 500 390 272 166 106
KPM 910 P 910 2730 2090 1680 1550 1470 1150 753 545 426 297 182 116
KPM 985 P 985 2950 2250 1820 1630 1590 1250 815 590 461 321 197 125
KPM 1060 P 1060 3180 2430 1970 1820 1720 1350 884 639 499 348 212 135
KPM 1140 P 1140 3350 2550 2110 1950 1850 1450 946 684 535 373 228 145
KPM 1220 P 1220 3520 2630 2250 2080 1970 1540 1010 729 570 397 244 156
ISSUE
R3
KPM RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 1.05V PER CELL
KPM 11 P 11 35.2 24.4 19.5 16.8 15.6 13 8.6 6.3 5 3.5 2.2 1.2
KPM 18 P 18 61 41.6 31.9 27.5 25.6 21.2 14.2 10.4 8.2 5.7 3.6 2.2
KPM 25 P 25 87 60 45 38.3 35.5 29.5 19.8 14.5 11.5 7.9 5 3.1
KPM 32 P 32 108 75 56.6 49 45.4 37.8 25.3 18.6 14.7 10.1 6.3 4
KPM 39 P 39 128 89 67.3 58.1 54 44.8 30 22 17.4 12 7.7 4.7
KPM 45 P 45 149 104 79.7 68.9 63.9 53.1 35.6 26.1 20.7 14.4 8.9 5.8
KPM 55 P 55 170 120 93.8 81.1 75.3 62.5 41.9 30.7 24.3 16.8 10.9 6.7
KPM 60 P 60 195 134 104 90.3 83.8 69.6 46.6 34.2 27.1 19 11.9 7.4
KPM 80 P 80 233 171 141 127 118 97.9 65.6 48.1 33.1 26.3 15.8 10.4
KPM 100 P 100 278 210 172 155 143 119 79.8 58.6 45.4 32 19.8 12.7
KPM 120 P 120 322 245 201 181 168 139 93.2 68.4 54.2 37.4 23.8 14.8
KPM 145 P 145 392 294 236 218 202 168 115 84.1 56.6 45.9 28.7 18.2
KPM 165 P 165 438 327 272 251 232 194 132 96.9 76.7 52.9 32.7 21
KPM 190 P 190 476 364 308 284 263 219 149 110 86.8 59.8 37.6 23.8
KPM 210 P 210 515 393 344 317 293 245 167 122 96.5 67 41.6 26.5
KPM 230 P 230 587 450 378 348 322 269 183 135 106 73.4 45.5 29.2
KPM 250 P 250 643 492 414 381 353 295 201 147 117 80.4 49.5 31.9
KPM 275 P 275 694 531 450 414 384 320 218 160 127 87.4 54.5 34.7
KPM 300 P 300 728 563 486 447 414 346 235 173 137 94.3 59.4 37.5
KPM 320 P 320 765 595 520 479 443 370 252 185 146 101 63.4 40.1
KPM 340 P 340 801 625 556 512 474 396 269 198 157 108 67.3 42.9
KPM 360 P 360 931 690 565 522 483 408 280 206 162 112 71.3 44.8
KPM 380 P 380 971 723 595 559 517 437 300 220 174 120 75.2 48
KPM 410 P 410 1010 755 625 595 551 466 320 235 185 128 81.2 51.2
KPM 450 P 450 1260 903 700 662 612 518 356 261 206 142 89.1 56.8
KPM 500 P 500 1370 1000 778 735 680 575 395 290 228 158 99 63.1
KPM 555 P 555 1480 1100 873 816 755 638 438 322 254 175 110 70.1
KPM 600 P 600 1600 1200 968 889 823 696 478 351 276 191 119 76.4
KPM 655 P 655 1730 1290 1040 963 891 753 517 380 299 207 130 82.7
KPM 710 P 710 1860 1380 1130 1040 956 817 561 412 324 224 141 89.6
KPM 760 P 760 1940 1440 1190 1120 1030 874 600 441 347 240 150 95.9
KPM 810 P 810 2020 1510 1250 1190 1100 932 640 470 3B0 256 160 102
KPM 830 P 830 2230 1650 1310 1220 1130 957 658 483 380 263 164 105
KPM 910 P 910 2400 1800 1450 1330 1230 1040 717 526 415 287 180 115
KPM 985 P 985 2590 1930 1560 1440 1340 1130 776 570 449 311 195 124
KPM 1060 P 1060 2790 2070 1690 1570 1450 1220 841 618 486 337 210 134
KPM 1140 P 1140 2910 2160 1780 1680 1550 1310 901 661 531 360 225 144
KPM 1220 P 1220 3030 2260 1870 1790 1650 1400 960 705 555 384 242 154
ISSUE
R3
KPM RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 1.10V PER CELL
KPM 450 P 450 1080 750 562 490 444 390 315 243 196 138 87.3 56.2
KPM 500 P 500 1170 836 638 560 506 450 350 270 218 153 97 62.5
KPM 555 P 555 1270 922 714 630 573 505 389 300 241 170 108 69.3
KPM 600 P 600 1360 1000 790 690 635 560 424 327 263 185 116 75.6
KPM 655 P 655 1450 1070 856 745 695 610 459 354 285 200 127 81.8
KPM 710 P 710 1540 1140 922 810 750 660 497 383 309 217 138 88.7
KPM 760 P 760 1610 1190 969 851 785 690 532 410 331 233 147 95
KPM 810 P 810 1680 1250 1010 892 820 728 567 437 352 248 157 101
KPM 830 P 830 1900 1380 1070 945 860 758 583 450 362 255 161 104
KPM 910 P 910 2040 1510 1180 1030 953 840 635 490 395 278 177 114
KPM 985 P 985 2170 1610 1280 1120 1040 915 688 531 427 301 191 123
KPM 1060 P 1060 2310 1710 1380 1210 1120 990 746 575 463 325 206 132
KPM 1140 P 1140 2410 1790 1450 1280 1180 1030 798 616 496 349 221 142
KPM 1220 P 1220 2520 1870 1510 1340 1230 1090 851 656 529 372 237 152
ISSUE
R3
KPM RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 1.14V PER CELL
CELL TYPE CAP SECONDS MINUTES HOURS
AH 1 60 5 10 15 30 60 90 2 3 5 8
KPM 11 P 11 25.2 16.9 13.2 11.3 10.5 8.4 6.4 5.1 4.2 3.2 2.1 1.3
KPM 18 P 18 45.4 28.7 22.4 19.2 17.1 13.9 10.6 8.4 7 5.5 3.4 2.1
KPM 25 P 25 63 42.2 33 27 23.8 19.3 14.8 11.8 9.7 7.2 4.7 3
KPM 32 P 32 78 54 41.3 34.4 30.4 24.6 18.9 15 12.5 9.3 6 3.8
KPM 39 P 39 90.1 64.5 49.3 41.5 36.1 29.3 22.4 17.9 14.8 11 7.3 4.5
KPM 45 P 45 105 73.7 57 48.4 42.8 34.7 26.6 21.2 17.5 13.1 8.5 5.5
KPM 55 P 55 119 82.8 64.7 55.3 50.4 40.8 31.3 24.9 20.6 15.4 10.3 6.4
KPM 60 P 60 132 92 73.5 63 56.1 45.4 34.8 27.7 23 17.2 11.3 7.1
KPM 80 P 80 166 118 93.3 83 74.7 63.9 49 39 32.3 24.1 15 10
KPM 100 P 100 197 145 114 101 90.9 77.8 59.6 47.5 39.3 29.4 18.8 12.2
KPM 120 P 120 228 172 134 116 106 90.9 69.6 55.5 45.9 34.3 22.6 14.2
KPM 145 P 145 275 210 163 142 130 110 85.6 68.2 56.4 42.2 27.3 17.5
KPM 165 P 165 314 231 183 160 148 127 98.5 78.5 65 48.5 31 20.1
KPM 190 P 190 339 260 203 179 166 144 112 88.8 73.6 54.9 35.7 22.8
KPM 210 P 210 363 280 221 196 186 160 124 99.2 82.1 61.3 39.5 25.5
KPM 230 P 230 426 321 246 218 204 176 137 109 90.3 67.4 43.3 28
KPM 250 P 250 462 350 268 237 224 193 150 119 98.9 73.8 47 30.6
KPM 275 P 275 500 379 290 255 241 210 163 130 107 80.2 51.7 33.3
KPM 300 P 300 523 396 314 277 262 226 176 140 116 86.6 56.4 36
KPM 320 P 320 538 423 335 297 281 242 188 150 124 92.7 60.2 38.5
KPM 340 P 340 552 436 359 321 300 259 201 160 133 99.1 64 41.1
KPM 360 P 360 655 482 370 332 306 264 208 167 138 101 67.7 43.9
KPM 380 P 380 682 501 389 349 321 277 221 179 148 108 71.5 47
KPM 410 P 410 708 519 408 366 339 297 234 190 158 115 77.1 50.2
KPM 450 P 450 943 629 472 404 365 320 263 212 176 128 84.7 55.7
KPM 500 P 500 1020 704 530 460 414 360 292 235 195 142 94.1 61.3
KPM 555 P 555 1090 779 588 516 467 410 321 261 216 158 104 63.6
KPM 600 P 600 1170 854 646 572 520 445 355 284 235 172 113 74.5
KPM 655 P 655 1240 909 693 618 566 485 383 308 255 186 123 81
KPM 710 P 710 1310 964 740 664 612 527 416 334 277 202 134 87.3
KPM 760 P 760 1360 1000 778 698 650 567 442 357 296 216 143 94
KPM 810 P 810 1410 1040 816 722 672 594 468 381 316 230 152 100
KPM 830 P 830 1640 1160 882 774 701 607 482 391 324 236 156 103
KPM 910 P 910 1760 1280 969 858 780 670 530 427 355 258 171 113
KPM 985 P 985 1860 1360 1040 927 849 735 575 462 384 280 185 122
KPM 1060 P 1060 1960 1440 1110 996 918 790 624 501 413 301 199 131
KPM 1140 P 1140 2040 1500 1160 1040 963 840 663 536 445 324 214 141
KPM 1220 P 1220 2120 1550 1220 1090 1020 891 702 571 476 346 229 151
ISSUE
R3
KPH RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 0.65V PER CELL
ISSUE
R3
KPH RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 0.85V PER CELL
ISSUE
R3
KPH RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 1.00V PER CELL
KPH 11 P 11 99.9 88 71.5 65.5 53.2 46 34 27 16.8 9.5 6.6 3.5 2.2
KPH 14 P 14 136 120 97.2 89 71.8 62.5 46.3 36.2 21.8 12 8.4 4.5 2.8
KPH 18 P 18 171 151 123 112 90.7 79 58.5 45.8 27.6 15.5 10.8 5.8 3.6
KPH 22 P 22 215 190 154 141 114 99.5 73.7 57.8 34.8 18.9 13.2 7 4.4
KPH 26 P 26 250 221 180 164 133 116 85.8 67.5 40.6 22.4 15.6 8.3 5.2
KPH 34 P 34 319 282 229 210 170 148 110 86.8 52.2 29.2 20.4 10.9 6.8
KPH 38 P 38 353 312 254 232 188 164 122 96.4 58 32.7 22.8 12.2 7.6
KPH 46 P 46 429 379 309 282 229 200 149 118 71.1 39.6 27.6 14.7 9.2
KPH 50 P 50 471 415 339 310 251 219 164 130 78.3 43 30 16 10
KPH 60 P 60 536 473 387 353 287 249 185 144 88.7 49.9 34.8 18.6 12
KPH 65 P 65 609 537 439 401 327 283 210 165 102 57.6 40.2 21.4 13
KPH 85 P 85 757 669 548 500 408 357 268 210 129 73.1 51 27.2 17
KPH 95 P 95 825 729 598 546 446 390 293 231 142 80 55.8 29.8 19
KPH 100 P 100 892 788 648 591 483 423 319 252 154 87.7 61.2 32.6 20
KPH 110 P 110 958 846 696 635 520 456 344 273 167 95.5 66.6 35.5 22
KPH 130 P 130 1090 965 796 725 596 523 396 317 194 110 76.8 41 26
KPH 140 P 140 1150 1020 842 767 631 554 420 338 207 118 82.2 43.8 28
KPH 150 P 150 1220 1080 897 817 673 588 445 356 222 126 88.2 47 30
KPH 170 P 170 1370 1210 1010 917 759 667 510 408 254 144 101 53.8 34
KPH 190 P 190 1500 1330 1110 1010 838 737 566 453 285 163 114 60.8 38
KPH 210 P 210 1630 1440 1210 1100 916 807 623 497 318 181 127 67.5 42
KPH 245 P 245 1800 1600 1340 1220 1020 906 705 573 366 210 146 78.1 49
KPH 255 P 255 1860 1650 1390 1260 1060 940 733 599 383 218 152 81.3 51
KPH 265 P 265 1910 1700 1430 1300 1090 969 759 624 399 228 159 84.8 53
KPH 290 P 290 1420 1410 1330 1260 1070 991 824 695 450 258 180 95.1 58
KPH 320 P 320 1560 1550 1460 1380 1180 1090 905 764 493 283 197 104 64
KPH 355 P 355 1770 1750 1660 1560 1330 1230 1030 866 552 317 221 117 71
KPH 410 P 410 2040 2020 1910 1800 1540 1430 1190 1000 639 367 255 135 82
KPH 470 P 470 2320 2300 2170 2050 1750 1620 1350 1140 725 417 290 154 94
KPH 525 P 525 2590 2570 2430 2290 1960 1820 1510 1280 814 467 326 172 105
KPH 580 P 580 2870 2840 2690 2530 2170 2010 1670 1410 899 516 360 190 116
KPH 635 P 635 3140 3120 2950 2780 2380 2210 1840 1550 984 565 394 208 127
KPH 700 P 700 3490 3460 3270 3080 2640 2450 2040 1720 1080 623 434 230 140
KPH 785 P 785 3900 3870 3660 3450 2950 2730 2270 1910 1220 699 487 257 157
KPH 870 P 870 4320 4280 4050 3810 3250 3020 2510 2120 1350 774 539 285 174
KPH 955 P 955 4730 4690 4430 4180 3580 3310 2750 2330 1480 850 592 313 191
ISSUE
R3
KPH RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 1.05V PER CELL
KPH 11 P 11 85.7 74.8 61.6 55.8 45.1 39.5 30.5 24.9 15.8 9.1 6.4 3.5 2.2
KPH 14 P 14 116 102 68.7 75.8 61.3 53.5 39.9 31.8 20.2 11.6 8.2 4.4 2.8
KPH 18 P 18 147 128 106 95.7 77.5 67.5 51.2 40.9 25.9 14.9 10.5 5.7 3.6
KPH 22 P 22 185 161 133 120 97.5 83.7 62.4 49.9 31.7 18.3 12.9 5.9 4.4
KPH 26 P 26 215 188 155 140 113 98.6 73.7 59 37.4 21.6 15.2 6.2 5.1
KPH 34 P 34 274 240 198 179 145 126 96 77.2 49 28.2 19.9 10.7 6.7
KPH 38 P 38 303 265 219 198 161 140 107 86.3 54.7 31.5 22.2 12 7.5
KPH 46 P 46 369 323 266 241 196 170 129 104 66.2 38.2 26.9 14.5 9.1
KPH 50 P 50 404 354 292 264 215 187 140 114 72 41.5 29.3 15.8 9.9
KPH 60 P 60 461 404 333 310 245 213 160 129 81.8 48.1 33.9 18.3 11.9
KPH 65 P 65 523 459 379 343 279 243 183 148 94.5 55.6 39.2 21.1 12.9
KPH 85 P 85 651 572 472 427 349 305 232 187 120 70.6 49.7 26.8 16.8
KPH 95 P 95 710 624 516 466 382 337 257 207 131 77.2 54.4 29.3 18.8
KPH 100 P 100 768 675 558 505 414 363 278 226 144 84.7 59.7 32.1 19.8
KPH 110 P 110 825 725 600 543 445 393 304 247 157 92.1 64.9 35 21.8
KPH 130 P 130 940 828 686 620 510 453 348 284 180 106 74.9 40.3 25.7
KPH 140 P 140 994 876 726 656 541 481 371 303 193 114 80.1 43.2 27.7
KPH 150 P 150 1050 933 773 699 577 507 390 318 204 122 86 46.3 29.7
KPH 170 P 170 1180 1040 869 785 650 575 443 360 234 133 98.3 52.9 33.7
KPH 190 P 190 1300 1150 956 863 718 637 497 404 264 158 111 59.9 37.6
KPH 210 P 210 1410 1250 1040 941 786 695 540 445 293 175 123 66.5 41.6
KPH 245 P 245 1560 1390 1160 1050 881 788 628 520 339 203 143 76.9 48.5
KPH 255 P 255 1610 1440 1200 1080 913 817 655 541 353 211 149 80 50.5
KPH 265 P 265 1660 1480 1230 1110 941 845 677 562 368 220 155 83.5 52.5
KPH 290 P 290 1270 1260 1170 1090 921 848 720 631 431 252 177 94 57.4
KPH 320 P 320 1400 1380 1290 1200 1010 931 791 693 472 277 194 103 63.4
KPH 355 P 355 1580 1560 1450 1350 1150 1060 897 787 529 310 217 115 70.3
KPH 410 P 410 1830 1810 1680 1560 1330 1220 1040 911 612 358 251 133 81.2
KPH 470 P 470 2080 2050 1910 1770 1510 1390 1180 1030 695 407 285 152 93.1
KPH 525 P 525 2320 2300 2130 1980 1691 1560 1320 1160 780 457 320 170 104
KPH 580 P 580 2570 2540 2360 2190 1872 1720 1460 1280 861 505 354 188 115
KPH 635 P 635 2820 2780 2590 2400 2054 1890 1600 1410 943 552 387 206 126
KPH 700 P 700 3130 3090 2870 2670 2280 2100 1780 1560 1040 589 427 227 139
KPH 785 P 785 3500 3460 3210 2980 2540 2330 1980 1740 1170 683 479 254 155
KPH 870 P 870 3870 3820 3550 3300 2810 2580 2190 1920 1290 757 531 282 172
KPH 955 P 955 4240 4190 3890 3620 3080 2840 2410 2110 1420 831 583 309 189
ISSUE
R3
KPH RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 1.10V PER CELL
KPH 11 P 11 71 62.7 51.7 45.7 36.3 32.1 25.5 21.5 14.3 8.7 6.2 3.4 2.2
KPH 14 P 14 96.5 85.2 70.3 62.1 49.5 43.5 34.2 28.2 18.5 11.1 7.9 4.4 2.7
KPH 18 P 18 122 108 88.7 78.4 63 55.7 43.9 36.3 23.8 14.2 10.2 5.6 3.5
KPH 22 P 22 153 135 112 98.6 79.2 69.6 53.7 44.3 29 17.4 12.4 6.9 4.3
KPH 26 P 26 178 157 130 115 92.4 81.2 63.4 52.4 34.3 20.5 14.7 8.1 5.1
KPH 34 P 34 228 201 166 147 119 105 83 68.5 44.9 26.9 19.2 10.6 6.7
KPH 38 P 38 252 223 184 162 132 117 93 76.6 50.2 30 21.5 11.9 7.5
KPH 46 P 46 307 271 223 198 162 142 112 92.7 60.7 36.3 26 14.4 9
KPH 50 P 50 337 297 245 217 178 157 122 101 66 39.5 28.3 15.6 9.8
KPH 60 P 60 384 339 280 248 193 169 135 113 76 45.8 32.8 18.1 11.8
KPH 65 P 65 437 386 318 282 220 194 155 131 87.8 52.9 37.9 20.9 12.7
KPH 85 P 85 545 481 397 352 280 248 197 166 111 67.2 48 26.5 16.7
KPH 95 P 95 595 526 433 384 306 270 216 181 122 73.5 52.5 29 18.6
KPH 100 P 100 644 569 469 416 332 295 237 199 134 80.6 57.6 31.8 19.6
KPH 110 P 110 693 612 504 447 361 320 258 216 145 87.7 62.7 34.6 21.6
KPH 130 P 130 792 700 576 512 415 370 297 250 168 101 72.3 39.9 25.5
KPH 140 P 140 838 740 610 542 442 395 318 267 179 108 77.4 42.7 27.5
KPH 150 P 150 893 789 649 578 445 395 320 273 187 116 83.1 45.9 29.4
KPH 170 P 170 1000 887 730 650 501 448 366 312 213 133 94.9 52.4 33.3
KPH 190 P 190 1100 976 803 717 563 503 414 353 241 150 107 59.3 37.3
KPH 210 P 210 1200 1060 876 783 627 560 460 392 268 167 119 65.8 41.2
KPH 245 P 245 1340 1180 977 875 722 645 532 454 310 193 138 76.1 48
KPH 255 P 255 1390 1230 1010 906 756 675 554 472 323 201 144 79.2 50
KPH 265 P 265 1430 1260 1040 933 787 703 578 493 337 209 150 82.7 52
KPH 290 P 290 1130 1120 1020 921 747 699 624 560 406 247 175 93.7 56.9
KPH 320 P 320 1240 1230 1110 1010 821 766 684 614 445 270 192 103 62.7
KPH 355 P 355 1410 1390 1260 1150 931 858 765 687 498 303 215 115 69.6
KPH 410 P 410 1630 1610 1460 1330 1080 993 886 795 577 350 249 133 80.4
KPH 470 P 470 1850 1820 1660 1510 1220 1130 1010 903 655 398 283 151 92.2
KPH 525 P 525 2070 2040 1850 1690 1370 1260 1130 1010 735 446 318 170 103
KPH 580 P 580 2290 2260 2050 1870 1510 1400 1250 1120 812 493 351 187 114
KPH 635 P 635 2510 2470 2250 2040 1660 1530 1360 1230 889 540 384 205 125
KPH 700 P 700 2780 2740 2500 2270 1840 1690 1500 1350 980 595 424 226 137
KPH 785 P 785 3110 3070 2790 2540 2060 1890 1690 1510 1100 667 475 254 154
KPH 870 P 870 3440 3390 3090 2810 2280 2100 1870 1680 1220 740 526 281 171
KPH 955 P 955 3770 3720 3380 3080 2490 2300 2050 1840 1340 812 578 308 187
ISSUE
R3
KPH RANGE
o o
TYPICAL CELL PERFORMANCE DATA ( 20 C + 5 C )
Discharge data is for full charged cells after 1 hour open circuit and allowing for voltage losses associated with connectors.
AMPERES ON DISCHARGE TO 1.14V PER CELL
KPH 11 P 11 59.4 52.3 42.9 37.4 28.6 24.8 19.8 17.1 12.3 8 5.9 3.4 2.1
KPH 14 P 14 80.8 71 58.3 50.9 39 33.8 27 22.8 15.7 10.2 7.6 4.3 2.7
KPH 18 P 18 102 89.7 73.6 64.3 49.4 42.8 34.2 29.3 20.2 13.1 9.7 5.5 3.5
KPH 22 P 22 128 113 92.7 80.9 62.4 54 43.2 35.9 24.6 16 11.9 6.7 4.3
KPH 26 P 26 149 131 108 94.1 72.8 63 50.4 32.4 29.1 18.9 14 7.9 5
KPH 34 P 34 191 168 138 120 93.6 81 64.8 55.4 38.1 24.7 18.4 10.4 6.6
KPH 38 P 38 212 186 153 133 104 90 72 61.9 42.6 27.6 20.5 11.6 7.4
KPH 46 P 46 258 226 186 162 127 110 88.2 75 51.5 33.4 24.8 14 8.9
KPH 50 P 50 283 249 204 178 140 122 97.2 81.5 56 36.3 27 15.3 9.7
KPH 60 P 60 323 284 232 204 154 135 105 88.2 63.8 42.1 31.3 17.7 11.7
KPH 65 P 65 368 323 264 232 177 154 121 102 73.7 48.6 36.2 20.4 12.6
KPH 85 P 85 460 403 330 290 224 195 153 129 93.5 61.6 45.9 25.9 16.5
KPH 95 P 95 503 441 360 317 247 215 168 141 102 67.4 50.2 28.4 18.4
KPH 100 P 100 546 477 390 344 269 234 194 155 112 74 55.1 31.1 19.4
KPH 110 P 110 587 513 420 370 291 254 199 169 122 80.5 59.9 33.9 21.4
KPH 130 P 130 673 588 480 425 339 295 231 195 141 92.8 69.1 39 25.2
KPH 140 P 140 713 623 508 450 361 315 247 208 151 99.3 74 41.8 27.2
KPH 150 P 150 761 664 541 480 367 323 261 222 162 107 79.4 44.8 29.1
KPH 170 P 170 859 748 609 542 421 368 299 254 185 122 90.7 51.2 33
KPH 190 P 190 948 825 671 599 472 416 336 287 209 138 103 58 36.9
KPH 210 P 210 1040 901 732 656 526 464 374 319 232 153 114 64.4 40.8
KPH 245 P 245 1160 1010 817 736 606 534 431 368 268 177 132 74.4 47.5
KPH 255 P 255 1200 1040 846 763 635 559 451 384 279 184 137 77.5 49.5
KPH 265 P 265 1240 1070 871 787 660 582 469 400 292 192 143 80.8 51.5
KPH 290 P 290 1020 1000 854 772 650 576 473 427 334 226 169 92.8 56.3
KPH 320 P 320 1120 1090 938 848 714 633 519 469 366 248 185 102 62.1
KPH 355 P 355 1270 1240 1060 961 809 718 589 532 409 278 208 114 68.9
KPH 410 P 410 1460 1430 1230 1110 937 832 682 616 474 321 240 132 79.6
KPH 470 P 470 1660 1630 1400 1260 1060 945 775 700 538 365 273 150 91.3
KPH 525 P 525 1860 1820 1570 1420 1190 1060 868 784 604 410 306 168 102
KPH 580 P 580 2060 2010 1740 1570 1320 1170 961 868 667 452 338 186 113
KPH 635 P 635 2260 2210 1900 1720 1450 1280 1050 952 730 495 370 203 123
KPH 700 P 700 2500 2450 2110 1910 1610 1430 1170 1060 805 546 408 224 136
KPH 785 P 785 2800 2740 2350 2120 1790 1590 1300 1180 903 612 458 251 152
KPH 870 P 870 3100 3030 2600 2350 1980 1760 1440 1300 1000 679 507 278 169
KPH 955 P 955 3390 3320 2860 2580 2170 1930 1580 1430 1100 745 557 306 185
ISSUE
R3
ISSUE
R3
ISSUE
R3
ISSUE
R3
APPENDIX-2
2.0 Since the battery backup is required for more than 4 hours, the low
rate discharge type (L) cell is to be considered. As per catalog of
Sabnife they do not have any cell which delivers 983 A for one minute
in the KPL type of cells. Hence KPM type cell is considered.
3.0 For temperature derating factors and the discharge data for
calculating the capacity rating factors, the data of M/s SABNIFE (for
KPM type) included in Appendix-1 is considered.
4.0 The end cell voltage selected is 1.16 volts (Ref. item 6.4 of Part – B in
this Design guide).
1 min = 0.96
1 hour = 0.97
2 hours/1 hr. 59 min = 0.98
8-10 hrs = 1.0
983 359
I1 = --------- = 1024A, I2= ------ = 370A
0.96 0.97
127 13
I3 = ------- = 131A, I4 = ------ = 13A
0.97 1.0
6.0 The published discharge data from manufacturers does not indicate
discharge ratings at the required end cell voltage of 1.16 volts. Hence
these need to be extrapolated from the data available.
6.1 As per catalog of Sabnife they do not have any cell which delivers
1024 A for one minute in the KPL type of cells. Hence select KPM
ISSUE
R3
6.2 The extrapolated discharge data for KPM 830P cell comes to,
1 Min. - 1050A
1 hr. - 431.5A
2 hrs. - 305A
8 hrs. - 102.5A
9 hrs. - 91.1A(by interpolation)
10 hrs. - 82A
8.0 The cell sizing worksheet is filled up using the above data and the
required cell size is 898 AH. determined as enclosed.
ISSUE
R3
Project : Date :
Lowest Expected Minimum Cell Cell
Electrolyte Temp : 17oC Cell Voltage : 1.16V DC Mfg. : SAB NIFE Type : KPL 1440P Sized By : RRN
LOAD DATA :
A1= 983 A, M1= 1 Min; A2 = 359 A, M2 = 59 Min.
A3= 127 A, M3= 60 Min; A4 = 13 A, M4 = 480 Min.
A5= A, M5= Min; A6 = A, M6 = Min.
ISSUE
R3
Section - 6: IF LOAD CYCLE HAS MORE THAN 5 LOAD PERIODS, CONTINUE FURTHER IN SIMILAR MANNER.
Section - 8:
Maximum Section Size = 809
Section - 9:
Random Section Size = -
Section - 10:
Design margin Factor = 1.0
Section - 11:
Aging Factor = 1.11
Section - 12:
Uncorrected size = (8) + (9)= 809+ - = 809
Section - 13:
All capacity required = (10) x (11) x (12) = 1.0 x 1.11 x 809 = 898 AH
Section - 14:
Select the next higher standard size of the cell.
Section - 15:
Therefore AH capacity of the cell = 910 AH
ISSUE
R3
APPENDIX-3
Some technical details of lead-acid and Ni-Cd battery cells are compared.
Lead-Acid Ni-Cd
k) Loss of rated capacity For temp below 25°C Approx: For temp below
per oC : 0.43% 20°C 0.5%
ISSUE
R3
Project : Date :
LOAD DATA :
A1= A, M1= Min; A2 = A, M2 = Min.
A3= A, M3= Min; A4 = A, M4 = Min.
A5= A, M5= Min; A6 = A, M6 = Min.
ISSUE
R3
Section - 6: IF LOAD CYCLE HAS MORE THAN 5 LOAD PERIODS, CONTINUE FURTHER IN SIMILAR MANNER.
Section - 8:
Maximum Section Size =
Section - 9:
Random Section Size =
Section - 10:
Design margin =
Section - 11:
Aging Factor =
Section - 12:
Uncorrected size = (8) + (9)=
Section - 13:
All capacity required = (10) x (11) x (12)= AH
Section - 14:
When AH capacity required is larger than the nearest standard cell, the next larger size cell is required.
Section - 15:
Therefore AH capacity of the cell = AH
ISSUE
R3
PART-C
BATTERY CHARGER
ISSUE
R3
1.0 SCOPE
2.1 Type
2.1.2 Silicon Controlled Rectifiers (SCR) type battery chargers are provided
for both float and boost chargers.
2.2 Scheme
2.2.1 The charging equipment shall be suitable for charging each battery in
float as well as in boost mode. The float charger should be provided
with Automatic Voltage Regulator to maintain the output voltage
within +1% of the set value under all load conditions and for an input
voltage variation of +10% and frequency variation of +5%. Boost
charging mode should have current control and limiting facility. The
boost charger shall be provided with automatic constant current
regulator to maintain the current output within +2% of the set value for
AC input voltage and frequency variation of +10% and +5%
respectively. The load limiting feature shall be provided for the
chargers.
2.3.1 Wherever 2x100% capacity batteries are provided for each service,
2x100% combined float cum boost charger shall be provided (For ex.
battery chargers for I&C systems, 220 kV switchyards of large
stations and 400 kV switchyards). Typical scheme of battery and
charger connection is shown in sketch no. TCE.M2-EL-CW-S-2631
R1.
ISSUE
R3
(a) In a multiple unit power stations, coal handling plants above 100
MW when distances are not very large, switchyards for two unit
installation non expandable up to 220 kV switchyard - battery
charger with separate float and boost charging units shall be
provided for each battery. Typical scheme of battery and
charger connection is shown in sketch no. TCE.M2- EL-CW-S-
2633 R1.
(b) For unit loads of each gas turbine, one battery, 2x100%
combined float cum boost charger shall be provided. Typical
scheme of battery and charger connection is shown in sketch
no. TCE.M2-EL-CW-S-2632 R1.
ISSUE
R3
1.2.3 Station loads 1X100% One per Float & Float & Boost- Station loads
battery Boost 1no
1.2.4 Coal handling 1X100% One per Float cum Float cum CHP loads
plant(CHP) battery Boost Boost- 1no
1.2.5 I & C System 2x100% One per Floot cum NIL. I&C system
battery Boost loads
1.2.6 Switchyard 2x100% One per Float cum NIL Swyd. Load-
battery Boost 220 kV &
400 kV
2.0 Gas Turbine
power plant.
2.1 For all unit sizes
2.1.1 Unit loads 1x100% One per Float cum Float cum two unit loads
battery Boost Boost- 1no
2.1.2 STG loads & 2X100% One per Float cum Nil STG loads
Station loads battery Boost +Station loads
2.1.3 I & C System 2x100% One per Float cum NIL. I&C system
battery Boost loads
2.1.4 Switchyard loads 1x100% One per Float & NIL Small stations &
battery Boost upto 220 kV
switchyard
2x100% One per Float cum NIL Large stations
battery Boost with 220 kV
swyd.& for
400 kV swyd.
3.0 DG Plants
3.1 Unit size upto 20
MW
3.1.1 Unit & Station 1X100% One per Float cum Float cum Complete unit
loads battery boost boost- 1no +station loads
3.2 DG Power plant -
Independent
Power Plant (IPP)
3.2.1 Unit loads in one 2X100% One per Float cum Nil Complete DG
block Batteries for battery Boost Set loads in one
a group of block
DG Sets (in
one block)
3.2.2 Station loads 1x100% One per Float cum Float cum Station loads
battery Boost Boost- 1no
4.0 Hydro Power
Plants
4.1 All Unit Sizes 2X100% for One per Float cum Nil Complete Unit
complete battery Boost & Station loads
plant
5.0 Industrial Plants
5.1 All Types of
Plants
ISSUE
R3
5.1.1 Complete Plant 2X100% for One per Float cum Nil Complete Plant
Loads complete battery Boost loads.
plant
2.4 Capacity
2.4.2 The float charger for DC power and control supply system of plant
shall be capable of meeting the following load requirements.
2.4.3 The float charger for I&C system battery shall be capable of meeting
the highest of the I&C system loads which will occur during the
starting or tripping/shut down or running of the unit/plant.
3.0 DISCUSSION
ISSUE
R3
3.1 The spare charger unit wherever provided should have facilities for
connection to the DC distribution board. Drawing no. TCE.M2-EL-
CW-S-2633 R1 shows typical spare charger connection. The design
of the leads from the spare charger should be such that chance of
wrong connection (reversal of polarity) is totally eliminated.
3.3 The cables shall be sized considering the voltage drop within
acceptable limits of 5% from the battery to load terminal.
3.4 The Blocker diodes connected between the end cell Tap and the DC
bus should be rated to carry the 1 min. output of the battery. Two
diodes in series are preferred to safeguard the D.C system against
short circuiting of one diode.
3.5 The ripple content of the DC output nominal voltage of the Float and
Boost charger shall be within +1% of the nominal output voltage when
battery is disconnected.
3.6 The transformer rating of the float & boost charger offered by the
Vendor shall be checked for it's suitability by asking the sizing
calculation from the charger supplier.
4.0 ENCLOSURES
ISSUE
R3