SYMBOLS DESCRIPTION

FACP FIRE ALARM CONTROL PANEL


S SMOKE DETECTOR
PLOT LIMIT S SMOKE DETECTOR WITH SOUNDER BASE
H HEAT DETECTOR
E EMERGENCY LIGHT POINT
EXIT EXIT LIGHT POINT
BREAK GLASS POINT (CALL POINT)
FIRE EXTINGUISHER DRY POWDER 10 Lb.
FIRE EXTINGUISHER CO 5 LB.
FOR INSIDE KITCHEN )
15cm FIRE BELL

20cm WATER PROOF FIRE BELL

LANDING VALVE 2 1/2" WITH P.R.V BUILT IN


AIR RELEASE VALVE
PUMP (ELECTRIC) 50 GPM @5 BAR.
100'00"ft (30.48m) LENGTH 1" Dia HOSE REEL
PLOT LIMIT (SWING TYPE)

FD FIRE DOOR 60minuts.


60

FD FIRE DOOR 90minuts.


90

GENERAL NOTES
1. ALL DIMENSIONS ARE IN METERS (m) UNLESS
OTHERWISE SHOWN.
2. DO NOT SCALE DRAWINGS, DIMENSION INDICATED
GOVERN.
3. THE CONTRACTOR IS DEEMED TO HAVE CHECKED
ABOUT THE EXACTNESS OF ALL DIMENSIONS AND
GRID LINES AND SHOULD REPORT IMMEDIATELY IN
WRITING TO THE ARCHITECT BY ANY DISCREPANCIES
BEFORE THE COMMENCEMENT OF ANY WORK.
W.M. COMBINED FIRE FIGHTING PUMP SET
4. THE CONTRACTOR WILL BE RESPONSIBLE FOR
SETTING-OUT.
DUTY : 250GPM @ 8 BAR 5. THE CONTRACTOR IS DEEMED TO HAVE ALLOWED
1 NO. ELECTRIC DRIVEN
1 NO. DIESEL ENGINE DRIVEN RATES FOR ANY ERRORS IN THIS DRAWING.
1 NO. JOCKEY PUMPSET 6. THE CONTRACTOR IS DEEMED TO HAVE CHECKED THE
29.93

UNDER GROUND R.C.C WATER TANK


TOTAL CAPACITY=27,435 UK.GAL.
DOMESTIC WATER CAPACITY=12,435 UK.GAL
DESIGN.
FIRE WATER CAPACITY = 15,000 UK. GAL
PUMP ROOM 7. THE CONTRACTOR SHOULD PROVIDE SHOP DRAWINGS
SIZE = 46.1864 sq.m X 2.70m = 124.703cu.m
DEPTH=3.00= 2.70m WATER DEPTH + 0.30m OF ALL SYSTEMS FOR APPROVAL BY THE CONSULTANT
FREE BOARD BEFORE COMMENCING ANY WORK.
8. ALL EXTERNAL WALLS TO BE 20 cm THERMAL BLOCK.
9. THE COPY RIGHTS OF THIS PLANS AND DRAWINGS
ARE RESERVED FOR ------------
ENG.CONSULTANTS & PROJECT MANAGEMENT.
10. ALL WINDOWS & BALCONY DOORS MUST BE EQUIPPED
WITH WINDOWS OPENING CONTROL DEVICE (W.O.C.D) TO
HAVE MAXIMUM OPENING LIMIT OF 10 CM TO HELP IN THE
PREVENTION OF ACCIDENTAL FALLS FROM WINDOWS &
BALCONIES BY CHILDREN AS PER SHARJAH MUNICIPALITY
PROPOSED G+8 BUILDING REGULATIONS .

NO. MODIFICATION/ REVISION DATE

OWNER

PROJECT

PROPOSED ( G + 8 ) BUILDING

PLOT NO: PLOT AREA: LOCATION: EMARITE:


OWNED GOV.
PLOT LIMIT PLOT LIMIT SHARJAH

20.73 PROJECT NO:

SHEET TITLE
ROAD
SETTING LAYOUT PLAN
DRAWING SET : SHEET NUMBER: SCALE: SIZE:
FF-FA FF-FA 01 / 10 1/100 A2

DESIGNED BY: APPROVED BY:


SETTING LAYOUT PLAN DRAWN BY:
CHECKED BY: DATE: 06 /12 / 2024
SYMBOLS DESCRIPTION
FACP FIRE ALARM CONTROL PANEL
S SMOKE DETECTOR
PLOT LIMIT S SMOKE DETECTOR WITH SOUNDER BASE
H HEAT DETECTOR
E EMERGENCY LIGHT POINT
EXIT EXIT LIGHT POINT
BREAK GLASS POINT (CALL POINT)
FIRE EXTINGUISHER DRY POWDER 10 Lb.
FIRE EXTINGUISHER CO 5 LB.
FOR INSIDE KITCHEN )
15cm FIRE BELL

20cm WATER PROOF FIRE BELL

LANDING VALVE 2 1/2" WITH P.R.V BUILT IN


AIR RELEASE VALVE
PUMP (ELECTRIC) 50 GPM @5 BAR.
100'00"ft (30.48m) LENGTH 1" Dia HOSE REEL
PLOT LIMIT (SWING TYPE)
SHOP - 6
FD FIRE DOOR 60minuts.
60

S E FD
90 FIRE DOOR 90minuts.

EXIT
TOILET

STORE
SHOP - 5 GENERAL NOTES
H 1. ALL DIMENSIONS ARE IN METERS (m) UNLESS
PANTRY S E OTHERWISE SHOWN.
2. DO NOT SCALE DRAWINGS, DIMENSION INDICATED
S E GOVERN.

EXIT
TOILET 3. THE CONTRACTOR IS DEEMED TO HAVE CHECKED
ABOUT THE EXACTNESS OF ALL DIMENSIONS AND
GRID LINES AND SHOULD REPORT IMMEDIATELY IN
WRITING TO THE ARCHITECT BY ANY DISCREPANCIES
TOILET BEFORE THE COMMENCEMENT OF ANY WORK.
TOILET 4. THE CONTRACTOR WILL BE RESPONSIBLE FOR
H SETTING-OUT.
SHOP - 4
PANTRY
5. THE CONTRACTOR IS DEEMED TO HAVE ALLOWED
PUMP ROOM RATES FOR ANY ERRORS IN THIS DRAWING.
6. THE CONTRACTOR IS DEEMED TO HAVE CHECKED THE
S E DESIGN.
E S 7. THE CONTRACTOR SHOULD PROVIDE SHOP DRAWINGS
H E OF ALL SYSTEMS FOR APPROVAL BY THE CONSULTANT
BEFORE COMMENCING ANY WORK.
EXIT

ELECTRICAL
ROOM 8. ALL EXTERNAL WALLS TO BE 20 cm THERMAL BLOCK.
FD
60 9. THE COPY RIGHTS OF THIS PLANS AND DRAWINGS
ARE RESERVED FOR ------------
E
TELECOM.

STAIR CASE
ROOM
S FD
GARBAGE
ROOM
ENG.CONSULTANTS & PROJECT MANAGEMENT.

RAMP
60 H 10. ALL WINDOWS & BALCONY DOORS MUST BE EQUIPPED
E E WITH WINDOWS OPENING CONTROL DEVICE (W.O.C.D) TO
FD
FACP E HAVE MAXIMUM OPENING LIMIT OF 10 CM TO HELP IN THE
90 PREVENTION OF ACCIDENTAL FALLS FROM WINDOWS &
ENERANCE LOBBY
EXIT BALCONIES BY CHILDREN AS PER SHARJAH MUNICIPALITY
FD REGULATIONS .
60
S E
EXIT

ENERANCE
S

PANTRY
NO. MODIFICATION/ REVISION DATE

BATH
RAMP: 10.00% F. F. GUARD ROOM

LIFT LIFT
TOILET TOILET

UNDER GROUND R.C.C WATER TANK


TOTAL CAPACITY=27,435 UK.GAL. OWNER
DOMESTIC WATER CAPACITY=12,435 UK.GAL
FIRE WATER CAPACITY = 15,000 UK. GAL
SIZE = 46.1864 sq.m X 2.70m = 124.703cu.m

S E S E E S
DEPTH=3.00= 2.70m WATER DEPTH + 0.30m
FREE BOARD

SHOP - 1 SHOP - 2 SHOP - 3 PROJECT

PROPOSED ( G + 8 ) BUILDING

EXIT EXIT EXIT PLOT NO: PLOT AREA: LOCATION: EMARITE:


OWNED GOV.
PLOT LIMIT PLOT LIMIT SHARJAH

PROJECT NO:

SHEET TITLE
FIRE FIGHTING
GROUND FLOOR PLAN
DRAWING SET : SHEET NUMBER: SCALE: SIZE:
FF-FA FF-FA 02 / 10 1/100 A2

DESIGNED BY: APPROVED BY:


GROUND FLOOR PLAN DRAWN BY:
CHECKED BY: DATE: 06 /12 / 2024
SYMBOLS DESCRIPTION
FACP FIRE ALARM CONTROL PANEL
S SMOKE DETECTOR
PLOT LIMIT S SMOKE DETECTOR WITH SOUNDER BASE
H HEAT DETECTOR
E EMERGENCY LIGHT POINT
EXIT EXIT LIGHT POINT
BREAK GLASS POINT (CALL POINT)
FIRE EXTINGUISHER DRY POWDER 10 Lb.
FIRE EXTINGUISHER CO 5 LB.
FOR INSIDE KITCHEN )
15cm FIRE BELL

20cm WATER PROOF FIRE BELL

LANDING VALVE 2 1/2" WITH P.R.V BUILT IN


AIR RELEASE VALVE
PUMP (ELECTRIC) 50 GPM @5 BAR.
100'00"ft (30.48m) LENGTH 1" Dia HOSE REEL
PLOT LIMIT (SWING TYPE)

FD FIRE DOOR 60minuts.


60

FD FIRE DOOR 90minuts.


90

S E
OFFICE 4 GENERAL NOTES
OFFICE 3
1. ALL DIMENSIONS ARE IN METERS (m) UNLESS
OTHERWISE SHOWN.
2. DO NOT SCALE DRAWINGS, DIMENSION INDICATED
W.C. O.T.S.
GOVERN.
S E 3. THE CONTRACTOR IS DEEMED TO HAVE CHECKED
ABOUT THE EXACTNESS OF ALL DIMENSIONS AND
H GRID LINES AND SHOULD REPORT IMMEDIATELY IN
PANTRY
W.C. WRITING TO THE ARCHITECT BY ANY DISCREPANCIES
BEFORE THE COMMENCEMENT OF ANY WORK.
4. THE CONTRACTOR WILL BE RESPONSIBLE FOR
H SETTING-OUT.
S E 5. THE CONTRACTOR IS DEEMED TO HAVE ALLOWED
PANTRY
RATES FOR ANY ERRORS IN THIS DRAWING.
6. THE CONTRACTOR IS DEEMED TO HAVE CHECKED THE
DESIGN.
W.M. 7. THE CONTRACTOR SHOULD PROVIDE SHOP DRAWINGS
S E OF ALL SYSTEMS FOR APPROVAL BY THE CONSULTANT
BEFORE COMMENCING ANY WORK.

EXIT
FD 4
60 8. ALL EXTERNAL WALLS TO BE 20 cm THERMAL BLOCK.
9. THE COPY RIGHTS OF THIS PLANS AND DRAWINGS
ELE. TEL.
ARE RESERVED FOR ------------
F. F.
S E S E H E ENG.CONSULTANTS & PROJECT MANAGEMENT.
STAIR CASE

GAR.
FD FD 10. ALL WINDOWS & BALCONY DOORS MUST BE EQUIPPED
E E 60 60
WITH WINDOWS OPENING CONTROL DEVICE (W.O.C.D) TO
EXIT

EXIT
FD
90
3 FD HAVE MAXIMUM OPENING LIMIT OF 10 CM TO HELP IN THE
60
PREVENTION OF ACCIDENTAL FALLS FROM WINDOWS &
LOBBY
S E BALCONIES BY CHILDREN AS PER SHARJAH MUNICIPALITY
REGULATIONS .
FD

EXIT
FD
EXIT

60 1 2 60

NO. MODIFICATION/ REVISION DATE

S E LIFT LIFT S E

O.T.S.
W.C. W.C. W.C. W.C. OWNER

H
PANTRY

H
PANTRY

S E S E
PROJECT
OFFICE 2 OFFICE 1
PROPOSED ( G + 8 ) BUILDING

PLOT NO: PLOT AREA: LOCATION: EMARITE:


OWNED GOV.
PLOT LIMIT SHARJAH

PROJECT NO:

SHEET TITLE

FIRE FIGHTING
FIRST FLOOR PLAN
DRAWING SET : SHEET NUMBER: SCALE: SIZE:
FF-FA FF-FA 03 / 10 1/100 A2

DESIGNED BY: APPROVED BY:


FIRST FLOOR PLAN DRAWN BY:
CHECKED BY: DATE: 06 /12 / 2024
SYMBOLS DESCRIPTION
FACP FIRE ALARM CONTROL PANEL
S SMOKE DETECTOR
PLOT LIMIT S SMOKE DETECTOR WITH SOUNDER BASE
H HEAT DETECTOR
E EMERGENCY LIGHT POINT
EXIT EXIT LIGHT POINT
BREAK GLASS POINT (CALL POINT)
FIRE EXTINGUISHER DRY POWDER 10 Lb.
FIRE EXTINGUISHER CO 5 LB.
FOR INSIDE KITCHEN )
15cm FIRE BELL

20cm WATER PROOF FIRE BELL

LANDING VALVE 2 1/2" WITH P.R.V BUILT IN


AIR RELEASE VALVE
PUMP (ELECTRIC) 50 GPM @5 BAR.
BATH 100'00"ft (30.48m) LENGTH 1" Dia HOSE REEL
PLOT LIMIT (SWING TYPE)

FD FIRE DOOR 60minuts.


BED ROOM 60
S
BED ROOM FD FIRE DOOR 90minuts.
BATH 90
S

BED ROOM
BATH GENERAL NOTES
S
1. ALL DIMENSIONS ARE IN METERS (m) UNLESS
S OTHERWISE SHOWN.

O.T.S.
BATH 2. DO NOT SCALE DRAWINGS, DIMENSION INDICATED
BED ROOM
GOVERN.
BATH
3. THE CONTRACTOR IS DEEMED TO HAVE CHECKED
ABOUT THE EXACTNESS OF ALL DIMENSIONS AND
GRID LINES AND SHOULD REPORT IMMEDIATELY IN
FD
WRITING TO THE ARCHITECT BY ANY DISCREPANCIES
60
BEFORE THE COMMENCEMENT OF ANY WORK.
BALCONY TOILET H O.T.S. 4. THE CONTRACTOR WILL BE RESPONSIBLE FOR
KITCHEN S SETTING-OUT.
BED ROOM 5. THE CONTRACTOR IS DEEMED TO HAVE ALLOWED
RATES FOR ANY ERRORS IN THIS DRAWING.
FD
60
6. THE CONTRACTOR IS DEEMED TO HAVE CHECKED THE
S BALCONY
DESIGN.
W.M. H TOILET
7. THE CONTRACTOR SHOULD PROVIDE SHOP DRAWINGS
SITTING AREA
OF ALL SYSTEMS FOR APPROVAL BY THE CONSULTANT
KITCHEN BEFORE COMMENCING ANY WORK.
FD 4
60 8. ALL EXTERNAL WALLS TO BE 20 cm THERMAL BLOCK.
9. THE COPY RIGHTS OF THIS PLANS AND DRAWINGS
ELE. TEL. ARE RESERVED FOR ------------
F. F.
S
E
S
E
H E SITTING AREA ENG.CONSULTANTS & PROJECT MANAGEMENT.
STAIR CASE GAR.
10. ALL WINDOWS & BALCONY DOORS MUST BE EQUIPPED
E E
FD
60
FD
60 S WITH WINDOWS OPENING CONTROL DEVICE (W.O.C.D) TO
EXIT

FD 3 FD HAVE MAXIMUM OPENING LIMIT OF 10 CM TO HELP IN THE


90 60
PREVENTION OF ACCIDENTAL FALLS FROM WINDOWS &
BALCONIES BY CHILDREN AS PER SHARJAH MUNICIPALITY
FD
S E FD REGULATIONS .
60 1 2 60

LOBBY S NO. MODIFICATION/ REVISION DATE


SITTING AREA
SITTING AREA
S

LIFT LIFT

BED ROOM TOILET O.T.S. TOILET S


BED ROOM OWNER
S

FD FD
60 60

H H
KITCHEN KITCHEN PROJECT
BATH BATH
S S
PROPOSED ( G + 8 ) BUILDING
BED ROOM
BED ROOM

BATH PLOT NO: PLOT AREA: LOCATION: EMARITE:


BALCONY BALCONY BATH
OWNED GOV.
PLOT LIMIT SHARJAH

PROJECT NO:

SHEET TITLE
FIRE FIGHTING
TYPICAL FLOOR PLAN
( 2ND FLOOR PLAN )
DRAWING SET : SHEET NUMBER: SCALE: SIZE:
FF-FA FF-FA 04 / 10 1/100 A2

DESIGNED BY: APPROVED BY:


TYPICAL FLOOR PLAN ( 2nd Floor ) DRAWN BY:
CHECKED BY: DATE: 06 /12 / 2024
SYMBOLS DESCRIPTION
FACP FIRE ALARM CONTROL PANEL
S SMOKE DETECTOR
PLOT LIMIT S SMOKE DETECTOR WITH SOUNDER BASE
H HEAT DETECTOR
E EMERGENCY LIGHT POINT
EXIT EXIT LIGHT POINT
BREAK GLASS POINT (CALL POINT)
FIRE EXTINGUISHER DRY POWDER 10 Lb.
FIRE EXTINGUISHER CO 5 LB.
FOR INSIDE KITCHEN )
15cm FIRE BELL

20cm WATER PROOF FIRE BELL

LANDING VALVE 2 1/2" WITH P.R.V BUILT IN


AIR RELEASE VALVE
PUMP (ELECTRIC) 50 GPM @5 BAR.
BATH 100'00"ft (30.48m) LENGTH 1" Dia HOSE REEL
PLOT LIMIT (SWING TYPE)

FD FIRE DOOR 60minuts.


BED ROOM 60
S
BED ROOM FD FIRE DOOR 90minuts.
BATH 90
S

BED ROOM
BATH GENERAL NOTES
S
1. ALL DIMENSIONS ARE IN METERS (m) UNLESS
S OTHERWISE SHOWN.

O.T.S.
BATH 2. DO NOT SCALE DRAWINGS, DIMENSION INDICATED
BED ROOM
GOVERN.
BATH
3. THE CONTRACTOR IS DEEMED TO HAVE CHECKED
ABOUT THE EXACTNESS OF ALL DIMENSIONS AND
GRID LINES AND SHOULD REPORT IMMEDIATELY IN
FD
WRITING TO THE ARCHITECT BY ANY DISCREPANCIES
60
BEFORE THE COMMENCEMENT OF ANY WORK.
BALCONY TOILET H O.T.S. 4. THE CONTRACTOR WILL BE RESPONSIBLE FOR
KITCHEN S SETTING-OUT.
BED ROOM 5. THE CONTRACTOR IS DEEMED TO HAVE ALLOWED
RATES FOR ANY ERRORS IN THIS DRAWING.
FD
60
6. THE CONTRACTOR IS DEEMED TO HAVE CHECKED THE
S BALCONY
DESIGN.
W.M. H TOILET
7. THE CONTRACTOR SHOULD PROVIDE SHOP DRAWINGS
SITTING AREA
OF ALL SYSTEMS FOR APPROVAL BY THE CONSULTANT
KITCHEN BEFORE COMMENCING ANY WORK.
FD 4
60 8. ALL EXTERNAL WALLS TO BE 20 cm THERMAL BLOCK.
9. THE COPY RIGHTS OF THIS PLANS AND DRAWINGS
ELE. TEL. ARE RESERVED FOR ------------
F. F.
S
E
S
E
H E SITTING AREA ENG.CONSULTANTS & PROJECT MANAGEMENT.
STAIR CASE GAR.
10. ALL WINDOWS & BALCONY DOORS MUST BE EQUIPPED
E E
FD
60
FD
60 S WITH WINDOWS OPENING CONTROL DEVICE (W.O.C.D) TO
EXIT

FD 3 FD HAVE MAXIMUM OPENING LIMIT OF 10 CM TO HELP IN THE


90 60
PREVENTION OF ACCIDENTAL FALLS FROM WINDOWS &
BALCONIES BY CHILDREN AS PER SHARJAH MUNICIPALITY
FD
S E FD REGULATIONS .
60 1 2 60

LOBBY S NO. MODIFICATION/ REVISION DATE


SITTING AREA
SITTING AREA
S

LIFT LIFT

BED ROOM TOILET O.T.S. TOILET S


BED ROOM OWNER
S

FD FD
60 60

H H
KITCHEN KITCHEN PROJECT
BATH BATH
S S
PROPOSED ( G + 8 ) BUILDING
BED ROOM
BED ROOM

BATH PLOT NO: PLOT AREA: LOCATION: EMARITE:


BALCONY BALCONY BATH
OWNED GOV.
PLOT LIMIT SHARJAH

PROJECT NO:

SHEET TITLE
FIRE FIGHTING
TYPICAL FLOOR PLAN
( 3RD TO 5TH FLOOR )
DRAWING SET : SHEET NUMBER: SCALE: SIZE:
FF-FA FF-FA 05 / 10 1/100 A2

DESIGNED BY: APPROVED BY:


TYPICAL FLOOR PLAN ( 3rd to 5th Floor ) DRAWN BY:
CHECKED BY: DATE: 06 /12 / 2024
SYMBOLS DESCRIPTION
FACP FIRE ALARM CONTROL PANEL
S SMOKE DETECTOR
PLOT LIMIT S SMOKE DETECTOR WITH SOUNDER BASE
H HEAT DETECTOR
E EMERGENCY LIGHT POINT
EXIT EXIT LIGHT POINT
BREAK GLASS POINT (CALL POINT)
FIRE EXTINGUISHER DRY POWDER 10 Lb.
FIRE EXTINGUISHER CO 5 LB.
FOR INSIDE KITCHEN )
15cm FIRE BELL

20cm WATER PROOF FIRE BELL

LANDING VALVE 2 1/2" WITH P.R.V BUILT IN


AIR RELEASE VALVE
PUMP (ELECTRIC) 50 GPM @5 BAR.
BATH 100'00"ft (30.48m) LENGTH 1" Dia HOSE REEL
PLOT LIMIT (SWING TYPE)

FD FIRE DOOR 60minuts.


BED ROOM 60
S
BED ROOM FD FIRE DOOR 90minuts.
BATH 90
S

BED ROOM
S BATH GENERAL NOTES
1. ALL DIMENSIONS ARE IN METERS (m) UNLESS
S OTHERWISE SHOWN.

O.T.S.
BATH 2. DO NOT SCALE DRAWINGS, DIMENSION INDICATED
BED ROOM
GOVERN.
BATH
3. THE CONTRACTOR IS DEEMED TO HAVE CHECKED
ABOUT THE EXACTNESS OF ALL DIMENSIONS AND
GRID LINES AND SHOULD REPORT IMMEDIATELY IN
FD
WRITING TO THE ARCHITECT BY ANY DISCREPANCIES
60
H BEFORE THE COMMENCEMENT OF ANY WORK.
BALCONY TOILET O.T.S. 4. THE CONTRACTOR WILL BE RESPONSIBLE FOR
KITCHEN S
SETTING-OUT.
BED ROOM 5. THE CONTRACTOR IS DEEMED TO HAVE ALLOWED
RATES FOR ANY ERRORS IN THIS DRAWING.
FD
60 6. THE CONTRACTOR IS DEEMED TO HAVE CHECKED THE
S BALCONY
DESIGN.
W.M. H 7. THE CONTRACTOR SHOULD PROVIDE SHOP DRAWINGS
SITTING AREA TOILET
OF ALL SYSTEMS FOR APPROVAL BY THE CONSULTANT
KITCHEN BEFORE COMMENCING ANY WORK.
FD 4
60 8. ALL EXTERNAL WALLS TO BE 20 cm THERMAL BLOCK.
9. THE COPY RIGHTS OF THIS PLANS AND DRAWINGS
ELE. TEL. ARE RESERVED FOR ------------
F. F. S E S E H E
SITTING AREA ENG.CONSULTANTS & PROJECT MANAGEMENT.
STAIR CASE GAR.

S 10. ALL WINDOWS & BALCONY DOORS MUST BE EQUIPPED


E
FD FD

E 60 60
WITH WINDOWS OPENING CONTROL DEVICE (W.O.C.D) TO
EXIT

FD
FD
90
3 60 HAVE MAXIMUM OPENING LIMIT OF 10 CM TO HELP IN THE
PREVENTION OF ACCIDENTAL FALLS FROM WINDOWS &
BALCONIES BY CHILDREN AS PER SHARJAH MUNICIPALITY
S E REGULATIONS .
FD FD
60 1 2 60

LOBBY NO. MODIFICATION/ REVISION DATE


SITTING AREA S
SITTING AREA
S

LIFT LIFT

BED ROOM O.T.S. TOILET S


TOILET
S BED ROOM OWNER

FD FD
60 60

H H
KITCHEN KITCHEN PROJECT
BATH BATH
S S
PROPOSED ( G + 8 ) BUILDING
BED ROOM
BED ROOM

BATH PLOT NO: PLOT AREA: LOCATION: EMARITE:


BALCONY BALCONY BATH
OWNED GOV.
PLOT LIMIT SHARJAH

PROJECT NO:

SHEET TITLE
FIRE FIGHTING
TYPICAL FLOOR PLAN
(6TH TO 8TH FLOOR)
DRAWING SET : SHEET NUMBER: SCALE: SIZE:
FF-FA FF-FA 06 / 10 1/100 A2

DESIGNED BY: APPROVED BY:


TYPICAL FLOOR PLAN ( 6nd to 8th Floor ) DRAWN BY:
CHECKED BY: DATE: 06 /12 / 2024
SYMBOLS DESCRIPTION
FACP FIRE ALARM CONTROL PANEL
S SMOKE DETECTOR
PLOT LIMIT S SMOKE DETECTOR WITH SOUNDER BASE
H HEAT DETECTOR
E EMERGENCY LIGHT POINT
EXIT EXIT LIGHT POINT
BREAK GLASS POINT (CALL POINT)
FIRE EXTINGUISHER DRY POWDER 10 Lb.
FIRE EXTINGUISHER CO 5 LB.
FOR INSIDE KITCHEN )
15cm FIRE BELL

20cm WATER PROOF FIRE BELL

LANDING VALVE 2 1/2" WITH P.R.V BUILT IN


AIR RELEASE VALVE
PUMP (ELECTRIC) 50 GPM @5 BAR.
100'00"ft (30.48m) LENGTH 1" Dia HOSE REEL
PLOT LIMIT (SWING TYPE)

FD FIRE DOOR 60minuts.


60

FD FIRE DOOR 90minuts.


90

GENERAL NOTES
1. ALL DIMENSIONS ARE IN METERS (m) UNLESS
OTHERWISE SHOWN.

O.T.S.
2. DO NOT SCALE DRAWINGS, DIMENSION INDICATED
GOVERN.
3. THE CONTRACTOR IS DEEMED TO HAVE CHECKED
ABOUT THE EXACTNESS OF ALL DIMENSIONS AND
GRID LINES AND SHOULD REPORT IMMEDIATELY IN
WRITING TO THE ARCHITECT BY ANY DISCREPANCIES
BEFORE THE COMMENCEMENT OF ANY WORK.
O.T.S. 4. THE CONTRACTOR WILL BE RESPONSIBLE FOR
SETTING-OUT.
5. THE CONTRACTOR IS DEEMED TO HAVE ALLOWED
RATES FOR ANY ERRORS IN THIS DRAWING.
6. THE CONTRACTOR IS DEEMED TO HAVE CHECKED THE
ROOF DESIGN.
7. THE CONTRACTOR SHOULD PROVIDE SHOP DRAWINGS
OF ALL SYSTEMS FOR APPROVAL BY THE CONSULTANT
air lease valve BEFORE COMMENCING ANY WORK.
8. ALL EXTERNAL WALLS TO BE 20 cm THERMAL BLOCK.
9. THE COPY RIGHTS OF THIS PLANS AND DRAWINGS
ARE RESERVED FOR ------------
ENG.CONSULTANTS & PROJECT MANAGEMENT.
STAIR CASE
10. ALL WINDOWS & BALCONY DOORS MUST BE EQUIPPED
E E WITH WINDOWS OPENING CONTROL DEVICE (W.O.C.D) TO
EXIT

FD HAVE MAXIMUM OPENING LIMIT OF 10 CM TO HELP IN THE


90
PREVENTION OF ACCIDENTAL FALLS FROM WINDOWS &
BALCONIES BY CHILDREN AS PER SHARJAH MUNICIPALITY
REGULATIONS .

NO. MODIFICATION/ REVISION DATE

EXIT
FD
60

MACHINE ROOM
E S E
ROOF ROOF

O.T.S.
OWNER

PROJECT

PROPOSED ( G + 8 ) BUILDING

PLOT NO: PLOT AREA: LOCATION: EMARITE:


OWNED GOV.
PLOT LIMIT SHARJAH

PROJECT NO:

SHEET TITLE
FIRE FIGHTING
ROOF FLOOR PLAN
DRAWING SET : SHEET NUMBER: SCALE: SIZE:
FF-FA FF-FA 07 / 10 1/100 A2

DESIGNED BY: APPROVED BY:


ROOF FLOOR PLAN DRAWN BY:
CHECKED BY: DATE: 06 /12 / 2024
SYMBOLS DESCRIPTION
FACP FIRE ALARM CONTROL PANEL
S SMOKE DETECTOR
PLOT LIMIT S SMOKE DETECTOR WITH SOUNDER BASE
H HEAT DETECTOR
E EMERGENCY LIGHT POINT
EXIT EXIT LIGHT POINT
BREAK GLASS POINT (CALL POINT)
FIRE EXTINGUISHER DRY POWDER 10 Lb.
FIRE EXTINGUISHER CO 5 LB.
FOR INSIDE KITCHEN )
15cm FIRE BELL

20cm WATER PROOF FIRE BELL

LANDING VALVE 2 1/2" WITH P.R.V BUILT IN


AIR RELEASE VALVE
PUMP (ELECTRIC) 50 GPM @5 BAR.
100'00"ft (30.48m) LENGTH 1" Dia HOSE REEL
PLOT LIMIT (SWING TYPE)

FD FIRE DOOR 60minuts.


60

FD FIRE DOOR 90minuts.


90

GENERAL NOTES
1. ALL DIMENSIONS ARE IN METERS (m) UNLESS
OTHERWISE SHOWN.

O.T.S.
2. DO NOT SCALE DRAWINGS, DIMENSION INDICATED
GOVERN.
3. THE CONTRACTOR IS DEEMED TO HAVE CHECKED
ABOUT THE EXACTNESS OF ALL DIMENSIONS AND
GRID LINES AND SHOULD REPORT IMMEDIATELY IN
ROOF WRITING TO THE ARCHITECT BY ANY DISCREPANCIES
BEFORE THE COMMENCEMENT OF ANY WORK.
O.T.S. 4. THE CONTRACTOR WILL BE RESPONSIBLE FOR
SETTING-OUT.
5. THE CONTRACTOR IS DEEMED TO HAVE ALLOWED
RATES FOR ANY ERRORS IN THIS DRAWING.
6. THE CONTRACTOR IS DEEMED TO HAVE CHECKED THE
DESIGN.
7. THE CONTRACTOR SHOULD PROVIDE SHOP DRAWINGS
OF ALL SYSTEMS FOR APPROVAL BY THE CONSULTANT
BEFORE COMMENCING ANY WORK.
8. ALL EXTERNAL WALLS TO BE 20 cm THERMAL BLOCK.
9. THE COPY RIGHTS OF THIS PLANS AND DRAWINGS
ARE RESERVED FOR ------------
ENG.CONSULTANTS & PROJECT MANAGEMENT.
TOP ROOF 10. ALL WINDOWS & BALCONY DOORS MUST BE EQUIPPED
WITH WINDOWS OPENING CONTROL DEVICE (W.O.C.D) TO
HAVE MAXIMUM OPENING LIMIT OF 10 CM TO HELP IN THE
PREVENTION OF ACCIDENTAL FALLS FROM WINDOWS &
BALCONIES BY CHILDREN AS PER SHARJAH MUNICIPALITY
REGULATIONS .

NO. MODIFICATION/ REVISION DATE

TOP ROOF

ROOF
O.T.S. ROOF
OWNER

PROJECT

PROPOSED ( G + 8 ) BUILDING

PLOT NO: PLOT AREA: LOCATION: EMARITE:


OWNED GOV.
PLOT LIMIT SHARJAH

PROJECT NO:

SHEET TITLE

WATER SUPPLY FOR


TOP ROOF PLAN
DRAWING SET : SHEET NUMBER: SCALE: SIZE:
FF-FA FF-FA 08 / 10 1/100 A2

DESIGNED BY: APPROVED BY:


TOP ROOF PLAN DRAWN BY:
CHECKED BY: DATE: 06 /12 / 2024
SYMBOLS DESCRIPTION
FACP FIRE ALARM CONTROL PANEL
S SMOKE DETECTOR
ARV
S SMOKE DETECTOR WITH SOUNDER BASE
H HEAT DETECTOR
E EMERGENCY LIGHT POINT
50 0/ 50 0/
EXIT EXIT LIGHT POINT
BREAK GLASS POINT (CALL POINT)

25 0/

HOSE REEL
FIRE EXTINGUISHER DRY POWDER 10 Lb.
FIRE EXTINGUISHER CO 5 LB.
FOR INSIDE KITCHEN )
50 0/ 50 0/ 15cm FIRE BELL

25 0/

HOSE REEL
20cm WATER PROOF FIRE BELL

LANDING VALVE 2 1/2" WITH P.R.V BUILT IN

50 0/ AIR RELEASE VALVE


50 0/
PUMP (ELECTRIC) 50 GPM @5 BAR.

25 0/

HOSE REEL
100'00"ft (30.48m) LENGTH 1" Dia HOSE REEL
(SWING TYPE)
L:VALVE
FD FIRE DOOR 60minuts.
60
50 0/
FD FIRE DOOR 90minuts.

25 0/
90

HOSE REEL
PLAN

L:VALVE

50 0/ 50mmØ HOSE REEL GENERAL NOTES


RISER
1. ALL DIMENSIONS ARE IN METERS (m) UNLESS

25 0/

HOSE REEL
OTHERWISE SHOWN.
2. DO NOT SCALE DRAWINGS, DIMENSION INDICATED
GOVERN.
L:VALVE
3. THE CONTRACTOR IS DEEMED TO HAVE CHECKED
ABOUT THE EXACTNESS OF ALL DIMENSIONS AND
50 0/ GRID LINES AND SHOULD REPORT IMMEDIATELY IN
25 0/ WRITING TO THE ARCHITECT BY ANY DISCREPANCIES

HOSE REEL
DRY POWDER EXTINGUISHERS
& CO EXTINGUISHER BEFORE THE COMMENCEMENT OF ANY WORK.
4. THE CONTRACTOR WILL BE RESPONSIBLE FOR
L:VALVE
SETTING-OUT.
5. THE CONTRACTOR IS DEEMED TO HAVE ALLOWED
RATES FOR ANY ERRORS IN THIS DRAWING.
50 0/
6. THE CONTRACTOR IS DEEMED TO HAVE CHECKED THE
25 0/

DESIGN.
HOSE REEL

7. THE CONTRACTOR SHOULD PROVIDE SHOP DRAWINGS


OF ALL SYSTEMS FOR APPROVAL BY THE CONSULTANT
L:VALVE BEFORE COMMENCING ANY WORK.
8. ALL EXTERNAL WALLS TO BE 20 cm THERMAL BLOCK.
50 0/ 50 0/
9. THE COPY RIGHTS OF THIS PLANS AND DRAWINGS
ARE RESERVED FOR ------------
25 0/

HOSE REEL

ENG.CONSULTANTS & PROJECT MANAGEMENT.


10. ALL WINDOWS & BALCONY DOORS MUST BE EQUIPPED
L:VALVE 2 WAY WITH WINDOWS OPENING CONTROL DEVICE (W.O.C.D) TO
BREACHING
CONNECTION HAVE MAXIMUM OPENING LIMIT OF 10 CM TO HELP IN THE
2"Ø PIPE FOR HOSE REEL
FOR PREVENTION OF ACCIDENTAL FALLS FROM WINDOWS &
SPRINKLER
BALCONIES BY CHILDREN AS PER SHARJAH MUNICIPALITY
REGULATIONS .
100 0/

NO. MODIFICATION/ REVISION DATE


FC

GV
PG
GV

GV

GV

TEST LINE
NRV
PV
TEST LINE

100 0/

CONTROL
PANEL
OWNER
NRV

FIRE PUMP SET E J D


DIESEL+JACK+ELECTRIC
FC PROJECT
CAP:250 USGPM @ 8 BAR
NON UL LISTED
UNDER GROUND R.C.C WATER TANK PROPOSED ( G + 8 ) BUILDING
100 0/ DOMESTIC
SUCTION PIPE

SUCTION PIPE

SUCTION PIPE

TEST LINE FROM FEWA PUMP TOTAL CAPACITY=27,435 UK.GAL.


2"Ø

2"Ø

2"Ø

DOMESTIC WATER CAPACITY=12,435 UK.GAL PLOT NO: PLOT AREA: LOCATION: EMARITE:
DOMESTIC USE FIRE WATER CAPACITY = 15,000 UK. GAL OWNED GOV.
NOTE:WATER STORAGE TANK OF 20000 GAL CAPACITY.
SIZE = 46.1864 sq.m X 2.70m = 124.703cu.m SHARJAH
FIRE WATER RESERVE
DEPTH=3.00= 2.70m WATER DEPTH + 0.30m
PROJECT NO:
FREE BOARD
SHEET TITLE

FIRE FIGTING RISER DIAGRAM

DRAWING SET : SHEET NUMBER: SCALE: SIZE:


FF-FA FF-FA 09 / 10 1/100 A2

DESIGNED BY: APPROVED BY:


DRAWN BY:
CHECKED BY: DATE: 06 /12 / 2024
SYMBOLS DESCRIPTION
FACP FIRE ALARM CONTROL PANEL
S SMOKE DETECTOR
S SMOKE DETECTOR WITH SOUNDER BASE
H HEAT DETECTOR
E EMERGENCY LIGHT POINT
EXIT EXIT LIGHT POINT
BREAK GLASS POINT (CALL POINT)
FIRE EXTINGUISHER DRY POWDER 10 Lb.
FIRE EXTINGUISHER CO 5 LB.
FOR INSIDE KITCHEN )
15cm FIRE BELL

20cm WATER PROOF FIRE BELL

LANDING VALVE 2 1/2" WITH P.R.V BUILT IN


AIR RELEASE VALVE
PUMP (ELECTRIC) 50 GPM @5 BAR.
100'00"ft (30.48m) LENGTH 1" Dia HOSE REEL
(SWING TYPE)

FD FIRE DOOR 60minuts.


60

FD FIRE DOOR 90minuts.


LOOP1 IN 90
H H S
ROOF

S S S S S S S H S S S S H S S S S H S S S H S S S H S S S H S S
GENERAL NOTES
8th FLOOR 1. ALL DIMENSIONS ARE IN METERS (m) UNLESS
OTHERWISE SHOWN.
2. DO NOT SCALE DRAWINGS, DIMENSION INDICATED
GOVERN.
3. THE CONTRACTOR IS DEEMED TO HAVE CHECKED
H H S ABOUT THE EXACTNESS OF ALL DIMENSIONS AND
GRID LINES AND SHOULD REPORT IMMEDIATELY IN
WRITING TO THE ARCHITECT BY ANY DISCREPANCIES
BEFORE THE COMMENCEMENT OF ANY WORK.
S S S S S S S H S S S S H S S S S H S S S H S S S H S S S H S S 4. THE CONTRACTOR WILL BE RESPONSIBLE FOR
SETTING-OUT.
7th FLOOR 5. THE CONTRACTOR IS DEEMED TO HAVE ALLOWED
RATES FOR ANY ERRORS IN THIS DRAWING.
6. THE CONTRACTOR IS DEEMED TO HAVE CHECKED THE
H H S DESIGN.
7. THE CONTRACTOR SHOULD PROVIDE SHOP DRAWINGS
OF ALL SYSTEMS FOR APPROVAL BY THE CONSULTANT
BEFORE COMMENCING ANY WORK.
S S S S S S S H S S S S H S S S S H S S S H S S S H S S S H S S 8. ALL EXTERNAL WALLS TO BE 20 cm THERMAL BLOCK.
9. THE COPY RIGHTS OF THIS PLANS AND DRAWINGS
6th FLOOR ARE RESERVED FOR ------------
ENG.CONSULTANTS & PROJECT MANAGEMENT.
10. ALL WINDOWS & BALCONY DOORS MUST BE EQUIPPED
S S H S S S H S S S H S S S H S S S S H S S S S H S S S S S S S WITH WINDOWS OPENING CONTROL DEVICE (W.O.C.D) TO
HAVE MAXIMUM OPENING LIMIT OF 10 CM TO HELP IN THE
5th FLOOR
PREVENTION OF ACCIDENTAL FALLS FROM WINDOWS &
BALCONIES BY CHILDREN AS PER SHARJAH MUNICIPALITY
REGULATIONS .
S S S S S S S H S S S S H S S S S H S S S H S S S H S S S H S S
1 LOOP ADDRESSIBLE

4th FLOOR NO. MODIFICATION/ REVISION DATE


FACP

S S H S S S H S S S H S S S H S S S S H S S S S H S S S S S S S
3rd FLOOR

S S S S S S S H S S S S H S S S S H S S S H S S H S S H
2nd FLOOR
OWNER

H S S S H S S S H S S S H S S S S H S S S S H S S S S S S S
1st FLOOR

PROJECT

LOOP1 OUT
S S H S S H H S PROPOSED ( G + 8 ) BUILDING

220V POWER SUPPLY GROUND FLOOR


PLOT NO: PLOT AREA: LOCATION: EMARITE:
12V 12V
OWNED GOV.
SHARJAH

PROJECT NO:

SHEET TITLE

FIRE FIGTING RISER DIAGRAM

DRAWING SET : SHEET NUMBER: SCALE: SIZE:

FIRE ALARM CONTROL PANEL FF-FA FF-FA 10 / 10 1/100 A2

DESIGNED BY: APPROVED BY:


DRAWN BY:
CHECKED BY: DATE: 06 /12 / 2024